CA 01

Digital modules - SM 321 digital input

Digital modules - SM 321 digital input

Overview

Digital inputs For connecting standard switches and two-wire proximity switches (BERO)

Application
Digital input modules can be used to connect the PLC to digital process signals. They are suitable for connecting standard switches and two-wire proximity switches (BERO).

Design
Digital input modules are characterized by the following mechanical features:

Compact configuration: The rugged plastic housing contains: Green LEDs to indicate signal states at the inputs Slot for front connector, protected by a front cover Labeling area on the front cover. Easy installation: There are no slot rules; the addresses of the inputs are predetermined by the slot. When they are used in the ET 200M in combination with active bus modules, hot-swapping is possible. User-friendly wiring

Function
Digital input modules convert the levels of the external digital signals from the process into the internal signal level of the PLC.

Technical specifications

Seite 1 von 5

CA 01
6ES7 321-1BH02-0AA0 Voltages and currents Load voltage L+ Rated value (DC) Current consumption from load voltage L+ (no load), max. from backplane bus 5 V DC, max. Power dissipation, typical Connection system Requisite front connector Clock synchronism Clock synchronous operation Digital inputs 16 Number of digital inputs Number of inputs that can be driven in parallel vertical mounting positions up to 40C horizontal mounting positions up to 40C up to 60C Length of cable Length of cable shielded, max Length of cable unshielded, max Input characteristic to comply with IEC 1131, Type 1 Input voltage Rated value, DC for signal "0" for signal "1" Input current for 1 signal, typical Input delay (at rated value of the input voltage) For standard inputs at 0 to 1, min. at 0 to 1, max. Sensor Connectable encoders 2-wire BEROS permissible closed-circuit current (2-wire BEROS), max. Status information/ interrupts/ diagnostics Interrupts Interrupts Diagnostics Diagnostic functions Diagnostic display LED Status display digital input (green) Insulation Insulation tested with Potentials/ electrical isolation Digital input functions between the channels between the channels, in groups of between the channels and the backplane bus Dimensions and weight Width Height Depth Weight, approx. 40 mm 125 mm 120 mm 200 g 40 mm 125 mm 120 mm 200 g 40 mm 125 mm 120 mm 260 g 500 V DC 500 V DC 500 V DC 16 16 32 No No No 20-pin 20-pin 40-pin 25 mA 10 mA 3.5 W 10 mA 3.5 W 15 mA 6.5 W 6ES7 321-1BH50-0AA0

Digital modules - SM 321 digital input


6ES7 321-1BL00-0AA0 6ES7 321-1BH10-0AA0

24 V

24 V

24 V

24 V

110 mA 3.8 W

20-pin

Yes

16

16

32 32 16 1,000 m 600 m Yes

16

16 1,000 m 600 m Yes

16 1,000 m 600 m Yes

16 1,000 m 600 m Yes

24 V -30 V to 5 V 13 to 30 V 7 mA

24 V 30 V to -5 V -13 to -30 V 7 mA

24 V -30 to 5 V 13 to 30 V 7 mA

24 V -30 V to 5 V 13 to 30 V 7 mA

1.2 ms 4.8 ms

1.2 ms 4.8 ms

1.2 ms 4.8 ms

25 s 75 s

Yes 1.5 mA

Yes 1.5 mA

Yes 1.5 mA

Yes 1.5 mA

No No Yes

No No Yes

No No Yes

No No Yes

500 V DC

16 Yes; Optocoupler

16 Yes; Optocoupler

Yes 16 Yes; Optocoupler

16 Yes; Optocoupler

40 mm 125 mm 120 mm 200 g

Seite 2 von 5

CA 01
6ES7 321-7BH01-0AB0 Voltages and currents Load voltage L+ Rated value (DC) Load voltage L1 Rated value (AC) Current consumption from load voltage L+ (no load), max. from backplane bus 5 V DC, max. Power dissipation, typical Connection system Requisite front connector Clock synchronism Clock synchronous operation Digital inputs 16 Number of digital inputs Number of inputs that can be driven in parallel vertical mounting positions up to 40C horizontal mounting positions up to 50C up to 60C Length of cable Length of cable shielded, max Length of cable unshielded, max Input characteristic to comply with IEC 1131, Type 1 Input characteristic to comply with IEC 1131, Type 2 Input voltage Rated value, AC Rated value, DC for signal "0" for signal "1" Frequency range Input current for 1 signal, typical Input delay (at rated value of the input voltage) For standard inputs Parameterizable at 0 to 1, min. at 0 to 1, max. Sensor Connectable encoders 2-wire BEROS permissible closed-circuit current (2-wire BEROS), max. Status information/ interrupts/ diagnostics Interrupts Interrupts Diagnostic interrupt Process interrupt Diagnostics Diagnostic functions Diagnostic display LED Status display digital input (green) Insulation Insulation tested with Potentials/ electrical isolation Digital input functions between the channels between the channels, in groups of between the channels and the backplane bus 500 V DC 1500 V AC 1500 V DC Yes No 16 ms 0.1 ms 3.5 ms Yes 16 16 16 Yes No No 20-pin 40-pin 20-pin 90 mA 130 mA 4W 100 mA 1.5 W 40 mA 4.3 W 6ES7 321-1CH00-0AA0

Digital modules - SM 321 digital input


6ES7 321-1CH20-0AA0 6ES7 321-1FH00-0AA0

24 V

24 V 24 V

48 V 230 V

29 mA 4.9 W

20-pin

No

16

16

8 8 8 1,000 m 600 m Yes

16

16 1,000 m 600 m

16 1,000 m 600 m Yes

16 1,000 m 600 m Yes

24 V -30 to 5 V 13 to 30 V

24 V; 24 or 48 V AC 24 V; 24 to 48 V DC -5 to 5 V AC 14 to 60 V AC 0 to 63 Hz 2.7 mA

230 V; 120/230 V AC 48 V; 48 to 125 V DC -146 V DC to 15 V DC 30 to 146 V DC 0 to 40 V 79 to 264 V 47 to 63 Hz 8 mA; (120 V, 60 Hz), 16mA (230 V, 50 Hz)

7 mA

3.5 mA

No 25 ms

Yes 2 mA

Yes 1 mA

Yes 1 mA

Yes 2 mA

Yes Yes; parameterizable Yes; parameterizable Yes; parameterizable Yes

No No No No Yes

No No No No Yes

No No No No Yes

4000 V DC

16 Yes; Optocoupler

Yes 1 Yes; Optocoupler

Yes 8 Yes; Optocoupler

Yes 4 Yes; Optocoupler

Seite 3 von 5

CA 01
Dimensions and weight Width Height Depth Weight, approx. 40 mm 125 mm 120 mm 200 g 40 mm 125 mm 120 mm 260 g 40 mm 125 mm 120 mm 200 g

Digital modules - SM 321 digital input

40 mm 125 mm 120 mm 240 g

6ES7 321-1EL00-0AA0 Voltages and currents Load voltage L1 Rated value (AC) Current consumption from backplane bus 5 V DC, max. Power dissipation, typical Connection system Requisite front connector Clock synchronism Clock synchronous operation Digital inputs Number of digital inputs Number of inputs that can be driven in parallel vertical mounting positions up to 40C horizontal mounting positions up to 40C up to 60C Length of cable Length of cable shielded, max Length of cable unshielded, max Input characteristic to comply with IEC 1131, Type 1 Input characteristic to comply with IEC 1131, Type 2 Input voltage Rated value, AC for signal "0" for signal "1" Frequency range Input current for 1 signal, typical Input delay (at rated value of the input voltage) For standard inputs Parameterizable at 0 to 1, max. Sensor Connectable encoders 2-wire BEROS permissible closed-circuit current (2wire BEROS), max. Status information/ interrupts/ diagnostics Interrupts Interrupts Diagnostic interrupt Process interrupt Diagnostics Diagnostic functions Diagnostic display LED Status display digital input (green) Insulation Insulation tested with Potentials/ electrical isolation Digital input functions between the channels between the channels, in groups of between the channels and the backplane bus Dimensions and weight Width Height Depth 40 mm 125 mm 120 mm 2500 V DC Yes 32 No 40-pin 16 mA 4W

6ES7 321-1FF01-0AA0

6ES7 321-1FF10-0AA0

120 V

230 V 29 mA 4.9 W

230 V 100 mA 4.9 W

20-pin

40-pin

No

No

32 32 24 1,000 m 600 m

8 1,000 m 600 m Yes

8 1,000 m 600 m Yes

120 V 0 to 20 V 74 to 132 V 47 to 63 Hz 21 mA

230 V; 120/230 V AC 0 to 40 V 79 to 264 V 47 to 63 Hz 6.5 mA; (120 V); 11mA (230 V)

120 V; 120/230 V AC 0 to 40 V 79 to 264 V 47 to 63 Hz 7.5 mA; (120 V); 17.3 mA (230 V)

No 15 ms

No 25 ms

No 25 ms

Yes 4 mA

Yes 2 mA

Yes 2 mA

No No No No Yes

No No No No Yes 4000 V DC

No No No No Yes 1500 V AC

Yes 8 Yes; Optocoupler

Yes 2 Yes; Optocoupler

Yes 1 Yes; Optocoupler

40 mm 125 mm 120 mm

40 mm 125 mm 120 mm

Seite 4 von 5

CA 01
Weight, approx. 300 g 240 g

Digital modules - SM 321 digital input


240 g

Seite 5 von 5