Measurement and control

Analogue instruments

Analogue instruments
Analogue instruments
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Product selection table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

EC / EM / EZC / EC FA / CEC 96
Moving iron ammeters (AC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

EC / EM / EZC / ECF / EC FN / CEC 96


Moving iron voltmeters (AC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

BC / BM / CBC 96
Moving-coil ammeter (DC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

BC / BM / CBC 96
Moving-coil voltmeter (DC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

BC / BM / ZC
Analogue indicator to measure a process signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

MC / MMC / EMC
Power demand meters. Analogue indicator to measure alternating current and its maximeter . . . . . . . . . . . . . . . . . . . . . . . 27

HC / HM / HZC
Pointer Frequency meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

HLC
Reed Frequency meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

WMC / WTC
Wattmeters. Analogue indicator to measure power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

YMC / YTC
Varmeters. Analogue indicator to measure the reactive energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

FEM / FETC / FMZ / FTZ


Electronic phase-meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

PIC A / PIC B / PIC E


Induction phase-meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

PGR
Bidirectional protection wattmeters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

2 EC / 2 HC / 2 HLC
Synchronisation and marine applications equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

SMC / STC / UC / CUC


Synchronisation and marine applications equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Synchro MAX / Synchro MAX PID


Synchronisation and marine applications equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

M1-2

Measurement and control

MEG-1000
Insulation resistance meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

CH
Hours run meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

M1-3

Analogue instruments

Analogue instruments
In many applications, such as control and distribution panels, it is important to control the installation quickly and visually, with no need to interpret data to detect the installation's status. CIRCUTOR offers a solution to these needs with this range of products. Analogue indicators are essential to display an instantaneous electrical value with a needle that moves through a graduated scale.

M.1
FERROMAGNETIC OR MAGNETOELECTRIC Electric current is directly translated by a measurement element that moves the needle. There are two types of measurement elements Ferromagnetic (AC) The ferromagnetic indicator is composed of a coil that transmits the current measured, with a fixed iron element and moving iron element in its centre, connected to the instrument's axis and needle. The set moves by the repulsion effect produced by the magnetic field between both iron elements and the arc depends on the current transmitted by

Definition
The main operation of these instruments is provided by the type of measurement system used, either a ferromagnetic system to measure alternating current or a magneto-electric system to measure direct current. CIRCUTOR offers equipment for both systems. However, most systems are generally used to measure alternating current. In general, analogue instruments are used because the interpretation of electrical parameters is quicker and more visual. Therefore, in this case the user simply looks at the position of the needle and does not have to interpret a number on a digital display.

M1-4

Analogue instruments

the coil. This system is used to measure AC and DC voltage and current between 15 and 100 Hz and it measures the root mean square of alternating current. It can not be used to measure rectified and unfiltered AC currents.Magnetoelectric (DC) The magneto-electric indicator is composed of a permanent central magnet, surrounded by a magnetic casing that guarantees the insensitivity to the exterior magnetic field and there is a moving coil between both, where the needle is fixed. Two spiral springs create the antagonistic pair to move the needle on the scale zero. This system is used to measure DC currents and voltages, measuring mean values.

Electrical and mechanical features


Insulation voltage 2 kV, 50 Hz, 1min between the mechanism and the box and between electrically insulated terminals. Permanent overloads Voltage circuits: 1.2 Un Current circuits: 1.2 In (1.5 In for moving iron) Short duration overloads Voltage circuits: 2 Un during 5 s Current circuits: 5 In during 30 s 10 In during 5 s 40 In during 1 s Relays Contacts: NO / NC Interrupting power: 230 Vac, 8 A / 30 V dc, 5 A resistive load

Factors that influence the Class


Assembly position All instruments will be assembled in a vertical position. They can be supplied for vertical or horizontal assembly, on demand. The tolerance is 5. Room temperature The effects of temperature on the Class depend on the scope of the measurement. In general, instruments maintain their Class between +10 and +30C. This interval can be lower for particularly low measurement scopes. In these cases, the limit values are indicated on the scale. The instruments can be adjusted for temperatures out of the interval mentioned above, on demand.Temperature limits Measurement instruments and their accessories support variations in temperature between -25 and +40 C (55 C in the tropicalized version) with no permanent defects. Relative humidity The Class is maintained within the 25 and 80 % non-condensing relative humidity interval. Magnetic field All instruments maintain their Class under the influence of an exterior magnetic field with a value of 0.5 MV. Ferromagnetic support The nature and thickness of the panel's plate does not affect the Class, with the exception of highly sensi-

M1-5

Analogue instruments

tive instruments. In these cases, the scales are marked with the Fe symbol, followed by the plate's thickness. Auxiliary power supply The tolerance accepted for the nominal auxiliary power supply values is: voltage: -15 ... +10 % frequency: 45 ... 65 Hz Vibrations The instruments and their accessories support a minimum vibration with an amplitude of 0.25 mm and a frequency of 50 cycles. Said vibration is equivalent to the application of an acceleration equal to 2.5 g to the three perpendicular axes during 20 minutes. Degree of protection Under normal operating conditions, the instrument boxes have an IP 52 protection degree and terminals have an IP 00 protection degree. Optionally, boxes are offered with an IP 54 or IP 55 protection degree and their terminals with an IP 20 protection degree. Pointers In accordance with DIN 43802. With tube or blade pointers, on demand (Fig. 1) Tropicalization (TROP) Under TROP operation, and in accordance with the DIN 40040 Standard, the instruments are protected against corrosive environments and support temperatures between -25 and +55 C, with a non-condensing relative humidity of 95 %. Said humidity percentage is stated for a maximum temperature of 30 C and 30 days a year; during the rest of the year, the humidity must not exceed 75 %.Within this type of operation, the instruments can be adjusted for reference temperature values above 20 C. In these cases, the scales are marked with TROP, followed by the temperature value at which they are adjusted. Chokes The instruments and their accessories support five impacts, with an acceleration of 15 g, applied in the direction of the three perpendicular axes. Zero correction The regulation of adjustment lengths of the zero corrector on both sides of the

resting position does not exceed 2 % of the scale length. Boxes The boxes and frames of all instruments are made with self-extinguishing ABS material, in compliance with UL 94, and with a high resistance to impacts. The box and frame dimensions comply with the DIN 43700 and DIN 43718 Standards, respectively. Bases are made with self-extinguishing reinforced PPO, in compliance with UL 94, with a high resistance to impacts and a maximum electrical insulation. Standards IEC 51, VDE 410, DIN 43780, BS 89, UL 94, EN 60051 Certificates Lloyds Register of Shipping (Ask for different types). Scales In accordance with the Standards: DIN 43701 for scale end values. DIN 43802 to assess divisions. The divisions and numbering of standardised scopes follow the examples on Fig.2 and 3. The scale end values above 1000 are stated in thousands (k).

M1-6

Analogue instruments

Product selection table

HM Panel Ammeters

Milliammeter With switch With relays DIN rail With relays DIN rail Panel With switch With relays DIN rail With relays DIN rail -

EC EC EZC EC FA CEC EM 45 BC CBC BM 45 EC EZC EC F CEC EM 45 BC CBC BM45 BC

100..0.600 mA 5...100 A,.../5A .../5A .../5A .../5A 5...60 A, .../5A 5...60 A, .../60 mV .../60 mV 5...60 A, .../60 mV 150 ... 600 V, .../110 V 250 V, 500 V 150 ... 600 V 150 ... 600 V, .../110 V 300 V, 500 V, .../110 V 0..0.600 V .../60 mV 15..0.150 V 0...10 V, 0/4... 20 mA 0...10 V, 4... 20 mA, .../60 mV 0...10 V, 0/4... 20 mA

48 x 48, 72 x 72, 96 x 96, 144 x 144 72 x 72, 96 x 96 96 x 96 85 x 52 48 x 48, 72 x 72, 96 x 96, 144 x 144 96 x 96 85 x 52 48 x 48, 72 x 72, 96 x 96, 144 x 144 72 x 72, 96 x 96 96 x 96 85 x 52 48 x 48, 72 x 72, 96 x 96, 144 x 144 96 x 96 85 x 52 48 x 48, 72 x 72, 96 x 96, 144 x 144 85 x 52 1,5 1,5

90 240

BM Panel

90 P1

HM

90 240 P1

Voltmeters

BM Panel

90

Process indicators

BM Panel DIN rail Bimetallic Pointer Panel DIN rail Panel DIN rail Reeds Panel Bimetallic + HM Bimetallic Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase Single-phase Panel Three-phase Single-phase Three-phase -

90 1,5 240 90

ZC BM MC EMC MMC 45 HC HZC HM HLC WMC WTC YMC YTC FEMC FETC FMZ FTZ PIC PIC

Power demand meters

P1.2 ... / 5 A 85 x 52 48 x 48, 72 x 72, 96 x 96, 144 x 144 45...65 depending on the type 96 x 96, 144 x 144 85 x 52 72 x 72, 96 x 96, 144 x 144 400 V, .../5 A 400 V, .../5 A 96 x 96, 144 x 144 96 x 96, 144 x 144 1,5 1,5 0,5 3 90 240 90 P2 P1.2

Watt-meter Varmeter Electronic

Reed

Panel Panel

90 90 90

Phase-meters

cos 0.5 - 1 - 0.5 96 x 96, 144 x 144 cos 0 - 1 - 0 90 cos 0 - 1 - 0 1,5 240 P1

Induction

Scale extension P2 P1 P2 P2 P1 P2 P1 P1 P1

Specifications

System measurement

Scale angle

Range

Fixing

Class

Type

Size

M1-7

Analogue instruments

Moving-coil Ammeter
Analogue indicator to measure alternating current

Moving iron ammeters (AC)

Description
}} No need for auxiliary power supply, only the CEC 96 type. }} DIN boxes with dimensions: 48, 72, 96 and 144. }} Precision class 1.5 }} Measurement in true root mean square 100 mA ... 100 A }} Exchangeable scales for EC48, EC72, EC96, EM 45, EC 72 FA, EC 96 FA }} The alarm system can be fully configured for CEC 96

Features
EC Auxiliary power supply Consumption Frequency Input circuit Consumption Frequency 0.3 ... 1.5 VA 20 ... 100 Hz 1.2 In permanent Overloads 5 In during 30 s 10 In during 5 s 40 In during 1 s Class 1.5 % FS 1.2 In permanent 0.2 VA 45 ... 65 Hz EM EZC EC FA CEC 96 with 2 relays 230 V ac 2.5 VA 40 ... 90 Hz

Application
In alternating current applications, to control the state of the current quickly and visually.

Ambient conditions Operating temperature Limit temperature Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel Terminals Insulation voltage IP 52 IP 00 2 kV, 50 Hz, 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318, CE IP 52 IP 20 3 kV , 50 Hz, 1min IEC 51, IEC 1010, IEC 529, IEC 255, IEC 278, IEC 414, IEC 144, LLOYD'S (TEST. ESP. No. 1) panel DIN rail See the following table See the following table panel panel panel +10 ... +30 C - 25 ... +40 C 2000 m + 5 ... +55 C -25 ... +70 C

Standards

M1-8

Analogue instruments

Moving iron ammeters (AC)

Moving iron ammeter


Analogue indicator to measure alternating current
References

Ammeters, 90 Type Class Scale (mm) Dimensions (mm) a b c Weight (g) mA 100 150 250 300 400 500 600 A 5 10 15 20 25 30 40 50 60 75 100 .../5 A (*) M10212 M10213 M10214 M10215 M10216 M10217 M10218 M10219 M1021A M10210 M10222 M10223 M10224 M10225 M10226 M10227 M10228 M10229 M1022A M1022B M1022C M10220 M10232 M10233 M10234 M10235 M10236 M10237 M10238 M10239 M1023A M1023B M1023C M10230 M10242 M10243 M10244 M10245 M10246 M10247 M10248 M10249 M1024A M1024B M1024C M10240 M10252 M10253 M10254 M10255 M10256 M10257 M10258 M10259 M1025A M10250 M10111 M10112 M10114 M10115 M10116 M10117 M10118 M10121 M10122 M10124 M10125 M10126 M10127 M10128 M10131 M10132 M10134 M10135 M10136 M10137 M10138 M10142 M10142 M10144 M10145 M10146 M10147 M10148 M10151 M10152 M10154 M10155 M10156 M10157 M10158 48 48 66,2 85 72 72 49,2 180 96 96 49,2 220 144 144 71,8 430 85 52 65 142 EC 48 EC 72 EC 96 1,5 90 , P2 EC 144 EM 45 Type Accuracy class Scale (mm)

Ammeters, 240 EZC 72 EZC 96

Ammeters with phase switch EC 72 FA 1,5 EC 96 FA

Ammeters with 2 relays CEC 96

240, P2

90or, P1

90or, P2

Dimensions (mm) a b c Weight (g) mA .../5 A (*) M10920 M10930 M10521 M10531 M14810 72 72 49,2 180 96 96 49,2 220 72 72 49,2 180 96 96 49,2 220 96 96 85,3 435

* EZC72 / EZC96:
Scale included, indicate the transformer ratio .../1 A , on demand Different settings, on demand

* EC72 FA / EC96 FA:


Scale not included Exchangeable scales (see tables) .../1 A , on demand Different settings, on demand

* CEC96:
Scale included, indicate the transformer ratio Exchangeable scales (see tables) .../1 A , on demand

*Scale is not included, except in EC144 (equipment + scale included, indicate transformer ratio). *For exchangeable scales, see Tables. * .../1 A on demand * Different settings, on demand.

M1-9

Analogue instruments

Moving iron ammeters (AC)

Moving iron ammeter


Analogue indicator to measure alternating current
References Exchangeable scales, Moving Iron Ammeters
Type Equipment A 5/5 10/5 15/5 20/5 25/5 30/5 40/5 50/5 60/5 75/5 100/5 125/5 150/5 200/5 250/5 300/5 400/5 500/5 600/5 750/5 800/5 1 000/5 1 200/5 1 500/5 2 000/5 2 500/5 3 000/5 4 000/5 5 000/5 M102Z2 M102Z3 M102Z4 M102Z5 M102Z6 M102Z7 M102Z8 M102Z9 M102ZA M102ZB M102ZC M102ZD M102ZE M102ZF M102ZG M102ZH M102ZJ M102ZK M102ZL M102ZM M102ZN M102ZP M102ZQ M102ZR M102ZS M102ZT M102ZU M102ZV M102ZW M102Y2 M102Y3 M102Y4 M102Y5 M102Y6 M102Y7 M102Y8 M102Y9 M102YA M102YB M102YC M102YD M102YE M102YF M102YG M102YH M102YJ M102YK M102YL M102YM M102YN M102YP M102YQ M102YR M102YS M102YT M102YU M102YV M102YW M102X2 M102X3 M102X4 M102X5 M102X6 M102X7 M102X8 M102X9 M102XA M102XB M102XC M102XD M102XE M102XF M102XG M102XH M102XJ M102XK M102XL M102XM M102XN M102XP M102XQ M102XR M102XS M102XT M102XU M102XV M102XW M105X9 M105XA M102VB M102VC M102VD M102VE M102VF M102VG M102VH M102VJ M102VK M102VL M102VM M102VN M102VP M102VQ M102VR M102VS M102VT M102VU M102VV M102VW SEC 48 EC 48 SEC 72 EC 72 SEC 96 EC 96 SEM 45 EM 45 SEC 72 FA EC 72 FA SEC 96 FA EC 96 FA

M105Y9 M105YA M105YB M105YC M105YD M105YE M105YF M105YG M105YH M105YJ M105YK M105YL M105YM M105YN M105YP M105YQ M105YR M105YS M105YT M105YU M105YV M105YW

M105X9 M105XA M105XB M105XC M105XD M105XE M105XF M105XG M105XH M105XJ M105XK M105XL M105XM M105XN M105XP M105XQ M105XR M105XS M105XT M105XU M105XV M105XW

M1-10

Analogue instruments

Moving iron ammeters (AC)

Moving iron ammeter


Analogue indicator to measure alternating current
Coding table
M 1
Code

X
Milliammeters EC and EM

M 1 X
Code

Internal Code

Internal Code

Standard 2P

0 1 6 0 1

Standard 2P Setting 1P 5P

0 1 6

Setting Current input

1P 5P Standard (... / 5 A) ... / 1 A 1 5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 400 500 600 750 800 1000 1200 1500 2000 2500 3000 4000 5000

M 1 X EC Scales and Ammeters and EM scales


1 2 3 4 5 6 7 8 9 A B C D E F G H J K L M N P Q R S T U V W

Code

Internal Code

Standard 2P Setting Current input 1P 5P Standard (.../ 5 A) ... / 1 A

0 1 6 0 1

EC and EZC Ammeters

Ammeters and EC FA scales

M 1 X X X X 0 0
Code Setting Current input
Internal Code

X X

Standard 1P 5P Standard (.../ 5 A) ... / 1 A

0 6 0 1

Scales (*)

1
Code

Internal Code

100 125 150 200 250 300 400 Scale 500 600 750 800 1000 1200 2000 2500 Current input Standard (.../ 5 A) ... / 1 A

C D E F G H J K L M N P Q R S 0 1

CEC Ammeters

M1-11

Analogue instruments

Moving iron ammeters (AC)

Moving iron ammeter


Analogue indicator to measure alternating current
Dimensions
EC EZC

Type 48 mm 72 mm 96 mm 144 mm

Fig. EC 1-3 1-3-4 1-3-4 2-3-4

a 48 72 96 144

b 44,7 67,2 91 137

c 61 43,5 43,5 64,5

d 5,2 5,7 5,7 7,3

e 45 68 92 138

Type 72 mm 96 mm

Fig. EZC 1 1

a 72 96

b 67,2 91

c 43,5 43,5

d 5,7 5,7

e 68 92

Dimensions (mm)

Dimensions (mm) EC-FA EM45

Type 72 mm 96 mm

Fig. EC 1-3-4 1-3-4

a 72 96

b 67,2 91

c 43,5 43,5

d 5,7 5,7

e 68 92
+0,8 +0,8

Dimensions (mm)

Connections
EC / EZC EC-FA EM 45

M1-12

Analogue instruments

Moving iron voltmeter


Analogue indicator to measure alternating current

Moving iron voltmeters (AC)

Description
}} No need for auxiliary power supply, only the CEC 96 type }} DIN boxes with dimensions: 48, 72, 96 and 144 }} Precision class 1.5 }} Measurement in true root mean square or V ... 600 V ac }} Exchangeable scales for EC48, EC72, EC96, EM 45 }} The alarm system can be fully configured for CEC 96

Features
EC Auxiliary power supply Consumption Frequency Input circuit Consumption Frequency Overloads Class Ambient conditions 1 ... 4 VA 20 ... 100 Hz 1.5 Un permanent 2 Un during 5 s 1.5 % FS 0.2 VA 45 ... 65 Hz 1.2 Un permanent EM EZC EC F EC FN CEC 96 230 V ac 2.5 VA 40 ... 90 Hz

Application
In alternating current applications, to control the state of the voltage quickly and visually.

Operating temperature Limit temperature Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel terminals Insulation voltage panel

+10 ... +30 C - 25 ... +40 C 2000 m

+ 5 ... +55 C -25 ... +70 C

See the following table See the following table DIN rail panel panel panel panel

IP 52 IP 00 2 kV, 50 Hz, 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318, CE

IP 52 IP 20 3 kV , 50 Hz, 1min IEC 51, IEC 1010, IEC 529, IEC 255, IEC 278, IEC 414, IEC 144, LLOYD'S (TEST. ESP. No. 1)

Standards

M1-13

Analogue instruments

Moving iron voltmeter (AC)

Moving iron voltmeter


Analogue indicator to measure alternating current

References Voltmeters 90, 240 and with 2 relays


Voltmeters, 90 Voltmeters, 240 Voltmeters with 2 relays

Type Class Scale Dimensions (mm) a b c Weight (g) V 150 250 300 400 500 600 .../110 V(*)

EC 48

EC 72

EC 96 1,5 90 , P1

EC 144

EM 45

EZC 72 1,5

EZC 96 240, P1

CEC 96 1,5 90, P1

48 48 66,2 85 M10415 M10416 M10417 M10418 M10419 M10410

72 72 49,2 180 M10425 M10426 M10427 M10428 M10429 M10420

96 96 49,2 220 M10435 M10436 M10437 M10438 M10439 M10430

144 144 71,8 430 M10445 M10446 M10447 M10448 M10449 M10440 M10456 M10458 M10450 142 -

85 52 65

72 72 49,2 180 M11125 M11128 M11138 -

96 96 49,2 220 M11135

96 96 85,3 435 M14821 M14822 M14823 M14824 M14825 M14826 M14820

* EC48 / EC72 / EC96 / EC144 EM45:


*Scale not included, except in EC144 (equipment + scale included, indicate the transformer ratio) *For exchangeable scales, see Tables. *Different secondary voltages, on demand *1P or 1.2P setting, on demand

* EZC72 / EZC96
*Scale included, indicate the transformer ratio *Different secondary voltages, on demand *1P setting, on demand

* CEC96:
Scale included, indicate the transformer ratio

M1-14

Analogue instruments

Moving iron voltmeter (AC)

Moving iron voltmeter


Analogue indicator to measure alternating current

References

Voltmeters with phase switch


Three-phase (3 wires) Type Class Scale Dimensions (mm) a b c Weight (g) V 250 300 400 500 600 M10625 M10626 M10627 M10628 M10629 M10635 M10636 M10637 M10638 M10639 M10725 M10726 M10727 M10728 M10729 M10735 M10736 M10737 M10738 M10739 M11038 72 72 49,2 180 96 96 49,2 220 72 72 49,2 180 96 96 49,2 220 96 96 49,2 220 EC 72 F III EC 96 F III Three-phase (4 wires) EC 72 FIII +N 1,5 90 , P1 EC 96 F III *N With sequence-meter EC 96 FN-S

* Voltage inputs through transformers, on demand

Exchangeable scales, Moving Iron Voltmeters


Type Equipment V 1 000/110 3 300/110 6 600/110 13 200/110 15 000/110 20 000/110 22 000/110 25 000/110 M104Z1 M104Z2 M104Z3 M104Z4 M104Z5 M104Z6 M104Z7 M104Z8 M104Y1 M104Y2 M104Y3 M104Y4 M104Y5 M104Y6 M104Y7 M104Y8 M104X1 M104X2 M104X3 M104X4 M104X5 M104X6 M104X7 M104X8 M104V1 M104V2 M104V3 M104V4 M104V5 M104V6 M104V7 M104V8 SEC 48 EC 48 SEC 72 EC 72 SEC 96 EC 96 SEM 45 EM 45

* If the input of the unit requested is not .../110 V, indicate the ratio

M1-15

Analogue instruments

Moving iron voltmeter (AC)

Moving iron voltmeter


Analogue indicator to measure alternating current
Coding table
Direct EC and EC F

1
Code

M
voltmeters

1
Code

Internal Code

Internal Code Standard 1P 1.2P

EC Voltmeters through transformer and EZC

Setting

Standard 1.2P 1P Standard (.../110 V) .../100 V .../63.5 V .../57.8 V 1000 3300 6600 13200 15000 20000 22000 25000

0 1 0 1 2 3

Setting

0 2

Voltage input

1
Code

EC Scales and Voltmeter and EM scale

Scales (for equipment with inputs through the transformer and all ECs)

1 2 3 4 5 6 7 8

Internal Code Standard 1.2P 1P Standard (.../110 V) 0 1 0 1 2 3

Setting

Voltage input

.../100 V .../63.5 V .../57.8 V

M1-16

Analogue instruments

Moving iron voltmeter (AC)

Moving iron voltmeter


Analogue indicator to measure alternating current
Dimensions
EC EZC

Type 48 mm 72 mm 96 mm 144 mm

Fig. EC 1-3 1-3-4 1-3-4 2-3-4

a 48 72 96 144

b 44,7 67,2 91 137

c 61 43,5 43,5 64,5

d 5,2 5,7 5,7 7,3

e 45 68 92 138

Type 72 mm 96 mm

Fig. EZC 1 1

a 72 96

b 67,2 91

c 43,5 43,5

d 5,7 5,7

e 68 92

Dimensions (mm)

Dimensions (mm) EC-FN / EC-F EM45

Type 72 mm 96 mm

Fig. EC 1-3-4 1-3-4

a 72 96

b 67,2 91

c 43,5 43,5

d 5,7 5,7

e 68 92
+0,8 +0,8

Dimensions (mm)

Connections
EC / EZC EC-F EC-FN EM 45

M1-17

Analogue instruments

Moving-coil ammeter

Moving-coil ammeter (DC)

Analogue indicator to measure direct current

Description
}} No need for auxiliary power supply, only the CEC 96 type }} DIN boxes with dimensions: 48, 72, 96 and 144 }} Precision class 1.5 }} Measurement in DC 25 uA ... 60 A, or ... 60 mV }} Exchangeable scales for BC48, BC72, BC96, BM 45 }} The alarm system can be fully configured for CBC 96

Features
BC Auxiliary power supply Consumption Frequency Input circuit Consumption 60 mV 1.2 In permanent 5 In during 30 s 10 In during 5 s 40 In during 1 s 1.5 % FS 0.2 VA 1.2 In permanent 5 In during 30 s 10 In during 5 s 40 In during 1 s BM CBC 96 230 V ac 2.5 VA 40 ... 90 Hz

Overloads

Class Ambient conditions

Application
In direct current applications, to control the state of the current quickly and visually.

Operating temperature Limit temperature Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel terminals Insulation voltage Standards panel

+10 ... +30 C - 25 ... +40 C 2000 m

+ 5 ... +55 C -25 ... +70 C

See the following table See the following table DIN rail panel

IP 52 IP 00

IP 52 IP 20

2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318, CE IEC51, IEC 1010, IEC 529, IEC 255, IEC 278, IEC 414, IEC 144, LLOYDS (TEST. ESP. No. 1)

M1-18

Analogue instruments
Moving-coil ammeter (DC)

Moving-coil ammeter
Analogue indicator to measure direct current
References
BC: Ammeters 90 / BM: Ammeters 90, DIN rail / CBC96: Ammeters with 2 relays

Exchangeable scales
Ammeters, 90 Type Class Scale Dimensions (mm) a b c Weight (g) A 5 10 25 50 60 .../60 mV(*) M11412 M11413 M11416 M11419 M11410 M11422 M11423 M11426 M11429 M1142A M11420 M11432 M11433 M11436 M11439 M1143A M11430 M11442 M11443 M11446 M11449 M1144A M11440 M11452 M11453 M11456 M11459 M1145A M11450 M14830 48 48 66,2 75 72 72 49,2 170 96 96 49,2 210 144 144 71,8 420 85 52 65 110 96 96 85,3 435 BC 48 BC 72 BC 96 1,5 90 , P1 BC 144 BM 45 Ammeters with 2 relays CBC 96 1,5 90 , P1 Type Equipment A / mV 50/60 60/60 75/60 100/60 150/60 200/60 250/60 300/60 400/60 600/60 1 000/60 1 500/60 2 500/60 M114Z9 M114ZA M114ZB M114ZC M114ZE M114ZF M114ZG M114ZH M114ZJ M114ZL M114ZP M114ZR M114ZT M114Y9 M114YA M114YB M114YC M114YE M114YF M114YG M114YH M114YJ M114YL M114YP M114YR M114YT M114X9 M114XA M114XB M114XC M114XE M114XF M114XG M114XH M114XJ M114XL M114XP M114XR M114XT M114V9 M114VA M114VB M114VC M114VE M114VF M114VG M114VH M114VJ M114VL M114VP M114VR M114VT SBC 48 BC 48 SBC 72 BC 72 SBC 96 BC 96 SBM 45 BM 45

* BC48 / BC72 / BC96 / BC144 / BM45: *Scale is not included, except in EC144 (equipment + scale included, indicate transformer ratio) *For exchangeable scales, see Tables. External shunts, see M.7 *Different input ranges, shunt *Central zero adjustment, on demand *Inputs starting on 25 uA, on demand * CEC96: *Scale included, indicate the transformer ratio (shunt)

* If the input of the unit requested is not .../60mV, indicate the ratio.

Coding table
M 1
Code Setting

X X X

X SBC and SBM45 Scales

1 Code

Internal Code Standard Central zero Standard (.../60 mV) .../50 mV .../150 mV .../300 mV 50 60 75 100 150 200 0 1 0 1 3 5 9 A B C E F G H J K L P R T

Internal Code

Setting

Standard Central zero Standard (.../60 mV) .../50 mV .../150 mV .../300 mV

0 1 0 1 3 5

Shunt input

BC and BM45 Ammeters

range

Shunt input range

Scales

250 300 400 500 600 1000 1500 2500

M1-19

Analogue instruments

Moving-coil ammeter (DC)

Moving-coil ammeter
Analogue indicator to measure DC current References
BC CBC

BM45 Type 48 mm 72 mm 96 mm 144 mm Fig. BC 1-3 2-3-4 2-3-4 2-3-4 a 48 72 96 144 b 44,7 67,2 91 137 c 61 43,5 43,5 64,5 d 5,2 5,7 5,7 7,3 e 45 68 92 138

Dimensiones (mm)

Connections
BC CBC BM 45

M1-20

Analogue instruments

Moving-coil Voltmeter

Moving-coil voltmeter (DC)

Analogue indicator to measure DC voltage

Description
}} No need for auxiliary power supply, only the CEC 96 type }} DIN boxes with dimensions: 48, 72, 96 and 144 }} Precision class 1.5 }} Measurement in DC 25 uA ... 60 A, or ... 60 mV }} Exchangeable scales for BC48, BC72, BC96, BM 45 }} The alarm system can be fully configured for CBC 96

Features
BC Auxiliary power supply Consumption Frequency Input circuit Consumption Frequency Overloads Temp. Coefficient Class 1.5 % FS 1000 20 ... 100 Hz 1.5 Un permanent 2 Un permanent 5 s 0.2 VA 45 ... 65 Hz 1.2 Un permanent 100 ppm / C BM CBC 96 230 V ac 2.5 VA 40 ... 90 Hz

Application
In direct current applications, to control the state of the current quickly and visually.

Ambient conditions Operating temperature Limit temperature Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel terminals Insulation voltage Standards IP 52 IP 00 IP 52 IP 20 panel See the following table See the following table DIN rail panel +10 ... +30 C - 25 ... +40 C 2000 m + 5 ... +55 C -25 ... +70 C

2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318, CE IEC51, IEC 1010, IEC 529, IEC 255, IEC 278, IEC 414, IEC 144, LLOYDS (TEST. ESP. No. 1)

M1-21

Analogue instruments

Moving-coil voltmeter (DC)

Moving coil voltmeter


Analogue indicator to measure DC voltage

References BC: Voltmeters 90 BM: Voltmeters 90, DIN rail CBC96: Voltmeters with relay 90

Voltmeters, 90 Type Class Scale Dimensions (mm) a b c Weight (g) V 0..0.10 V 1 15 30 60 100 150 250 300 400 500 600 M11813 M11711 M11714 M11716 M11718 M11719 M1171A M1171B M1171D M1171E M1171F M11823 M11721 M11724 M11726 M11728 M11729 M1172A M1172B M1172D M1172E M1172F M11833 M11731 M11734 M11736 M11738 M11739 M1173A M1173B M1173D M1173E M1173F M11843 M11741 M11744 M11746 M11748 M11749 M1174A M1174B M1174D M1174E M1174F M11754 M11755 M11756 M11757 M11758 48 48 66,2 75 72 72 49,2 170 96 96 49,2 210 144 144 71,8 420 85 52 65 110 90 , P1 BC 48 BC 72 BC 96 BC 144 1,5 BM 45

Voltmeters with relay CBC 96

90 , P1 96 96 85,3 435

M14841 M14842 M14843 M14844 M14845 M14846

*Scale not included, indicate voltage input *Inputs of more than 10 mV, on demand

Coding table

M
BC and BM Voltmeters

1
Code

Internal Code
Standard Central zero

Setting

0 1

M1-22

Analogue instruments

Moving-coil voltmeter (DC)

Moving coil voltmeter


Analogue indicator to measure DC voltage

References
BC CBC

BM45 Type 48 mm 72 mm 96 mm 144 mm Fig. BC 1-3 2-3-4 2-3-4 2-3-4 a 48 72 96 144 b 44,7 67,2 91 137 c 61 43,5 43,5 64,5 d 5,2 5,7 5,7 7,3 e 45 68 92 138

Dimensiones (mm)

Connections
BC CBC BM 45

M1-23

Analogue instruments

Process indicators
Analogue indicator to measure a process signal

Description
}} Does not need an auxiliary power supply }} DIN boxes with dimensions: 48, 72, 96 and 144 }} Precision class 1.5 }} Measurement in DC of 0 ... 10 V, 0/4 ... 20 mA, .../60 mV }} Exchangeable scales for BC48, BC72, BC96, BM 45

Features
BC Input circuit Consumption Overloads Class Ambient conditions Operating temperature Limit temperature +10 ... +30 C - 25 ... +40 C 2000 m 1000 1.5 Un permanent 2 Un permanent 5 s 1.5 % FS VA BM ZC

Application
For the measurement of the mean value of voltages and currents in direct current circuits, even of the pulsating type, in a vast margin of values.

Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel terminals Insulation voltage Standards IP 52 IP 00 panel

See the following table See the following table DIN rail panel

IP 52 IP 20

2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318

M1-24

Analogue instruments

Process indicators
Analogue indicator to measure a process signal
References Coding table

BC: Process indicators 90

M 1 X
Code Setting

X X 0

Internal Code Standard Central zero 1 5 10 15 20 25 0 1 1 2 3 4 5 6 7 8 9 A B C D E F G H J K L M N P Q R S T U V W 0 1 2 3 4 8 9 A B C G H J K

Process indicators, 90 Type Class Scale Dimensions (mm) a b c Weight (g) Scope 0..0.10 V 0...20 mA 4...20 mA .../60 mV M11813 M11812 M11811 M11823 M11822 M11821 M11833 M11832 M11831 M11843 M11842 M11841 M11853 M11852 M11851 48 48 66,2 75 72 72 49,2 170 96 96 49,2 210 144 144 71,8 420 85 52 65 110 BC 48 BC 72 BC 96 1,5 90 , P1 BC 144 BM 45

30 40 50 60 75 100 125 150 200 250 300 400 500 600 750 800 1000 1200 1500 2000 2500 3000

BC and ZC process indicators

Scale

ZC: Process indicators, 240

Process indicators, 240 Type class Scale Dimensions (mm) a b c Weight (g) Scope 0..0.10 V 0...20 mA 4...20 mA .../60 mV M12513 M12511 M12510 M12523 M12521 M12520 M12533 M12531 M12530 M12543 M12541 M12540 48 4866,2 75 72 7249,2 170 96 9649,2 210 144 14471,8 420 ZC 48 ZC 72 1,5 240, P1 ZC 96 ZC 144

4000 5000 mA A kA mV V kV rpm rpm x 1000

Exchangeable scales
Type Equipment Scope 0..0.10 V 0...20 mA 4...20 mA M118Z3 M118Z2 M118Z1 M118Y3 M118Y2 M118Y1 M118X3 M118X2 M118X1 M118V3 M118V2 M118V1 SIP 48 BC 48 SIP 72 BC 72 SIP 96 BC 96 SIPM 45 BM 45

l (litres) m m2 m3 %

M1-25

Analogue instruments

Process indicators
Analogue indicator to measure a process signal
Dimensions
ZC BC

Type 48 mm 72 mm 96 mm 144 mm

Fig. ZC 1 1 1 1

a 48 72 96 144

b 44,7 67,2 91 137

c 61 43,5 43,5 64,5

d 5,2 5,7 5,7 7,3

e 45 68 92 138

Type 48 mm 72 mm 96 mm 144 mm

Fig. BC 1-3 2-3-4 2-3-4 2-3-4

a 48 72 96 144

b 44,7 67,2 91 137

c 61 43,5 43,5 64,5

d 5,2 5,7 5,7 7,3

e 45 68 92 138

Dimensiones (mm)

Dimensiones (mm)

BM

Connections
BC / ZC BM

M1-26

Analogue instruments

Power demand meters


Analogue indicator to measure alternating current and its maximeter

Description
}} Does not need an auxiliary power supply }} DIN boxes with dimensions 48, 72, 96 and 144 }} Class 3 }} Measurement in AC of .../5 A (on demand.../1 A) }} Exchangeable scales for MC48, MC72, MC96, MM 45, EMC72, EMC96 }} Thermal inertia times of 15 min (on demand, 8 and 30 min)

Features
MC Input circuit Consumption Overloads Accuracy Ambient conditions Operating temperature Limit temperature Altitude Build features +10 ... +30 C - 25 ... +40 C 2000 m 3 % FS 3.25 VA 1.5 In permanent 15 In during 1 s 3 % Bim.1.5 % HM 4.25 VA MMC EMC

Application
To control the alternating current and measure long overloads in the same unit, integrated within a determined period.

Dimensions Weight Type of box Degree of protection: Front panel terminals Insulation voltage Standards IP 52 IP 00 panel

See the following table See the following table DIN rail panel

IP 52 IP 00

2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318

M1-27

Analogue instruments

Power demand meters


Analogue indicator to measure alternating current and its maximeter
References

MC: Bimetallic power demand ammeters, 90 MMC: Bimetallic power demand ammeters, 90, DIN rail

EMC: Bimetallic power demand ammeters + Moving iron ammeter, 90

Bimetallic maximeter ammeters Type class Scale Dimensions (mm) a b c Weight (g) A ... / 5 A M12211 M12221 M12231 M12241 M12651 48 4866,2 110 72 7249,2 140 96 9649,2 210 144 14471,8 420 85 5265 MC 48 MC 72 MC 96 3 90 , P1.2 MC 144 MMC 45 Type class Scale

Bimetallic maximeter ammeters + Moving iron ammeter EMC 72 EMC 96 Bimetallic: 3 Moving iron: 1,5 Double scale 90, bimetallic: P1.2, moving iron P2 EMC 144

Dimensions (mm) a b c Weight (g) A ... / 5 A M12622 M12632 M12642 72 7249,2 220 96 9649,2 260 144 14471,8 470

* Scale not included. Indicate transformer ratio * For exchangeable scales, see Tables

* Scale not included. Indicate transformer ratio * For exchangeable scales, see Tables

Exchangeable scales
Exchangeable scales Type Equipment A 100/5 200/5 300/5 400/5 500/5 600/5 750/5 800/5 1 000/5 1 500/5 2 000/5 M122ZC M122ZF M122ZH M122ZJ M122ZK M122ZL M122ZM M122ZN M122ZP M122ZR M122ZS M122YC M122YF M122YH M122YJ M122YK M122YL M122YM M122YN M122YP M122YR M122YS M122XC M122XF M122XH M122XJ M122XK M122XL M122XM M122XN M122XP M122XR M122XS M126VC M126VF M126VH M126VJ M126VK M126VL M126VM M126VN M126VP M126VR M126VS M126YC M126YF M126YH M126YJ M126YK M126YL M126YM M126YN M126YP M126YR M126YS M126XC M126XF M126XH M126XJ M126XK M126XL M126XM M126XN M126XP M126XR M126XS SMC 48 MC 48 SMC 72 MC 72 SMC 96 MC 96 SMMC 45-A MMC 45 SEMC 72 EMC 72 SEMC 96 EMC 72

* If the input of the unit requested is not .../5 A, indicate the ratio.

M1-28

Analogue instruments

Power demand meters


Analogue indicator to measure alternating current and its maximeter
Coding table
M 1 Code X X X X 0 0 X

Dimensions
EMC / MC

MMC 45 power

demand

Internal Code

Setting

Standard (15 minutes) 8 minutes 30 minutes

0 1 2
Type MC48 MC72 EMC72 EMC96 EMC144 a 48 72 72 96 144 b 44,7 67,2 67,2 91 137 c 61 43,5 57,2 43,5 64,5 d 5,2 5,7 5,7 5,7 7,3 e 45 68 68 92
+0,8 +0,8 +0,8 +0,8 +1

M 1 X X X X
Code

Internal Code

MC and EMC Power demand meters and SMC and SEMC Scales

Setting

Standard (15 minutes) 8 minutes 30 minutes Standard (.../ 5 A) ... / 1 A 100 125 150 200 250 300 400 500 600

0 1 2 0 1 C D E F G H J K L M N P Q R S T U V W

138

Dimensions (mm)

MMC

Current input

Scale

750 800 1000 1200 1500 2000 2500 3000 4000 5000

Connections
EMC / MC

MMC

M1-29

Analogue instruments

Pointer Frequency meters


Analogue indicator to measure frequency

Description
}} Does not need an auxiliary power supply }} DIN box with dimensions: 48, 72, 96 and 144 }} Class 0.5 }} Built-in electronic converter

Features
HC Input circuit Consumption Frequency Overloads 2 ... 3 VA 50 ... 400 Hz 1.5 In permanent 15 In during 1 s Standard 230 Vac Optional 100-120 Vac380-440 Vac 0.5 % FS HM HZC

Application
Accurate and easy reading of frequency in alternating current circuits. The distortion of voltage (we shall measure its frequency) can reach 15% of the nominal voltage in the third order harmonic, while the Class is not affected.

Measurement voltage Accuracy Ambient conditions Operating temperature Limit temperature Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel Terminals Insulation voltage Standards IP 52 IP 00 panel

+10 ... +30 C - 25 ... +40 C 2000 m

See the following table See the following table DIN rail panel

IP 52 IP 00

2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318

Coding table
M 1
Code

Reed HC, HZC and HM

Internal Code Standard (45...55 Hz) 57..0.63 Hz 0 1 3 4 5 0 1 3 4

Frequency

55..0.65 Hz 45..0.65 Hz 47...53 Hz Standard (230 V) 100 ... 120 V 380 ... 400 V 440 V

Voltage

M1-30

Analogue instruments

Pointer Frequency meters


Analogue indicator to measure frequency

References

Pointer Frequency meters, 90


Frequency meters, 90 Type class Scale Dimensions (mm) a b c Weight (g) Hz 45...55 57...63 55...65 45...65 47...63 M12711 M12711001 M12711003 M12711004 M12711005 M12721 M12721001 M12721003 M12721004 M12721005 M12731 M12731001 M12731003 M12731004 M12731005 M12741 M12741001 M12741003 M12741004 M12741005 M12751 M12751001 M12751003 M12751004 M12751005 48 48 66,2 95 72 72 49,2 175 96 96 49,2 215 144 144 71,8 425 85 52 65 250 HC 48 HC 72 HC 96 0,5 90 HC 144 HM 45

Pointer Frequency meters, 240


Frequency meters, 240 Type class Scale Dimensions (mm) a b c Weight (g) Hz 45...55 57...63 55...65 45...65 47...63 M12831 M12831001 M12831003 M12831004 M12831005 M12841 M12841001 M12841003 M12841004 M12841005 96 96 101.2 180 144 144 102 520 HZC 96 0,5 240 HZC 144

Dimensions
HC HZC

Type 48 72 96 144

a 48 72 96 144

b 44,7 67,2 91 137

c 61 43,5 43,5 64,5

d 5,2 5,7 5,7 7,3

e 45 68 92
+0,8 +0,8 +0,8 +1

Type 96 144

a 96 144

b 91 137

c 95,5 94,7

d 5,7 7,3

e 92
+0,8 +1

138

138

Dimensions (mm)

Dimensions (mm)

Connections
HM HC / HZC HM

M1-31

Analogue instruments

Reed Frequency- meters


Analogue indicator to measure frequency

Description
}} Does not need an auxiliary power supply }} DIN box with dimensions: 72, 96 and 144 mm }} Class 0.5 }} Independent measurement of the wave shape

Features
HLC Input circuit Consumption Nominal operating frequency Overloads Measurement voltage 1 ... 3.6 VA 50 or 60 Hz 1.2 Un permanent 2 Un during 5 s Standard 230 Vac Optional 100...120 Vac / 380...440 Vac 0.5 % FS

Application
Measurement of the frequency in alternating current circuits, for any type of wave shape and under adverse environmental and physical conditions.

Accuracy Ambient conditions Operating temperature Limit temperature Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel Terminals Insulation voltage Standards

+10 ... +30 C - 25 ... +40 C 2000 m

See the following table See the following table panel

IP 52 IP 00 2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318

M1-32

Analogue instruments

Reed Frequency meters


Analogue indicator to measure frequency

References

Coding table
M 1 X X X X 0 0 X X

HLC Frequency meters

Code

Internal Code Standard (47...53 Hz/ 13 reeds) 57...63 Hz / 13 reeds 1 2 3 4 5 0 1 3 4 0

Reed Frequency meters Type Class Dimensions (mm) a b c Weight (g) Hz 47...53, 13 reeds 45..0.55, 11 reeds 47...53, 7 reeds 57..0.63, 13 reeds 55..0.65, 11 reeds 57..0.63, 7 reeds 60 Hz 50 Hz M12921 M12921002 M12921005 M12921001 M12921003 M12921004 M12931 M12931002 M12931005 M12931001 M12931003 M12931004 M12941 M12941002 M12941005 M12941001 M12941003 M12941004 72 72 49,2 230 96 96 49,2 300 144 144 71,8 423 HLC 72 HLC 96 0,5 HLC 144

Frequency / No. reeds

45..0.55 Hz / 11 reeds 55...65 Hz / 11 reeds 57...63 Hz / 7 reeds 47..0.53 Hz / 7 reeds Standard (230 V) 100 ... 120 V 380 ... 400 V 440 V

Voltage

Dimensions
HLC

Connections
HLC

Type 72 96 96 (c) 144

a 72 96 96 144

b 67,2 91 91 137

c 43,5 43,5 57,2 64,5

d 5,7 5,7 5,7 7,3

e 68 92 92
+0,8 +0,8 +0,8 +1

138

Dimensions (mm)

M1-33

Analogue instruments

Wattmeters

Analogue indicator to measure active power

Description
}} Does not need an auxiliary power supply }} DIN box with dimensions 96 and 144. Class 1.5 }} Built-in electronic converter }} Balanced and unbalanced single and three-phase circuits.

Features
WMC Voltage circuit Voltage Consumption Frequency Overloads Current circuit Nominal current Consumption Frequency ... 5 A 0.3 ... 1.5 VA 45 ... 65 Hz 1.2 In permanent 5 In during 30 s 10 In during 5 s 40 In during 1 s 1.5 % FS 400 V 1 ... 4 VA 45 ... 65 Hz 1.25 Un permanent 2 Un during 5 s WTC

Application
Measurement of active power in balanced or unbalanced single and three-phase circuits.

Overloads

Accuracy Ambient conditions Operating temperature Limit temperature Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel Terminals Insulation voltage Standards

+10 ... +30 C - 25 ... +40 C 2000 m

See the following table See the following table panel

IP 52 IP 00 2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318

M1-34

Analogue instruments

Wattmeters
Analogue indicator to measure active power
References

WMC: Single-phase wattmeters

Single-phase Type Class Scale Dimensions (mm) a b c Weight (g) Uphase-phase (*) M13031 96 96 49,2 290 400 V M13041 144 144 71,8 490 WMC 96 1,5 90 P1 (Simple profile) WMC 144

*Scale is NOT included for WMC 96. For exchangeable scales, see Tables. *Scale included for WMC 144. Indicate the transformer ratio, power and voltage scale base. *Other voltage values, on demand.

WTC: Three-phase wattmeters

Balanced three-phase Type Class Scale Dimensions (mm) a b c Weight (g) Uphase-phase (*)M13032 96 96 49,2 290 400 V M13032 144 144 71,8 490 WTC 96E WTC 144E

Three-phase 3 wires (ARON) WTC 96A WTC 144A 1,5 90 P1 (Simple profile) 96 96 62,9 430 110 V M13034 M13044 (*)M13033 144 144 71,8 640 96 96 62,9 430 WTC 96AN

Three-phase (4 wires) WTC 144AN

144 144 71,8 640 400 V M13043

*Scale is NOT included for WTC 96E and WTC 96AN. For exchangeable scales, see Tables. *Scale included for WTC 144E, WTC 96A, WTC144A and WTC 144AN. Indicate the transformer ratio, power and voltage scale base. *Other voltage values, on demand.

M1-35

Analogue instruments

Wattmeters
Analogue indicator to measure active power
References Exchangeable scales

Single-phase wattmeters
Exchangeable scales Single-phase Type Equipment A 50/5 75/5 100/5 150/5 200/5 300/5 400/5 500/5 600/5 1 000/5 1 500/5 2 000/5 3 000/5 4 000/5 5 000/5 Scale Base 20 kW 40 kW 60 kW 80 kW 120 kW 160 kW 200 kW 240 kW 400 kW 600 kW 800 kW 1.2 MW 1.6 MW 2.0 MW SWM 96 WMC 96 Code M130J9 M130JC M130JE M130JF M130JH M130JJ M130JK M130JL M130JP M130JR M130JS M130JU M130JV M130JW

Three-phase wattmeters
Exchangeable scales Three-phase Type Equipment A 50/5 75/5 100/5 150/5 200/5 300/5 400/5 500/5 600/5 1 000/5 1 500/5 2 000/5 3 000/5 4 000/5 5 000/5 Scale Base 30 kW 50 kW 60 kW 90 kW 120 kW 180 kW 240 kW 300 kW 360 kW 600 kW 900 kW 1.2 MW 1.8 MW 2.4 MW 3 MW SWT 96E WTC 96E Code M130K9 M130KB M130KC M130KE M130KF M130KH M130KJ M130KK M130KL M130KP M130KR M130KS M130KU M130KV M130KW SWT 96AN WTC 96AN Code M130L9 M130LB M130LC M130LE M130LF M130LH M130LJ M130LK M130LL M130LP M130LR M130LS M130LU M130LV M130LW

M1-36

Analogue instruments

Wattmeters
Analogue indicator to measure active power
Coding table
M 1 Code Current input X X X X 0 0 X X X

Internal Code Standard .../ 5 A ... / 1 A Standard (400 Vp-p) 110 Vp-p (a) 0 1 0 1 2 5 6 9 B C E F H J K L P R S U V W

Voltage

230 Vp-p 440 Vp-p 460 Vp-p 50 75 100 150 200 300 400 500 600 1000 1500 2000 3000 4000 5000

Wattmeters Scale range Primary current transformer

(a) For unbalanced ARON (3 wire) three-phase units, 100 V is considered the standard voltage

M 1
Code Wattmeter scales

X X X

Internal Code Standard .../ 5 A ... / 1 A Standard (400 V) 110 V (a) 0 1 0 1 2 5 6

Current input

Voltage

230 V 440 V 460 V

(a) For unbalanced ARON (3 wire) three-phase units, 100 V is considered the standard voltage

M1-37

Analogue instruments

Wattmeters
Analogue indicator to measure active power

Dimensions
WMC / WTC Type 96 E 96 A / AN 144 a 96 96 144 b 91 91 137 c 43,5 57,2 94,7 d 5,7 5,7 7,3 e 92 92
+0,8 +0,8 +1

138

Dimensions (mm)

Connections
WMC WTCE

WTCA

WTCAN

M1-38

Analogue instruments

Varmeters
Analogue indicator to measure reactive power

Description
}} Does not need an auxiliary power supply }} DIN box with dimensions 96 and 144. }} Class 1.5 }} Built-in electronic converter }} Balanced and unbalanced single and three-phase circuits.

Features
YMC Voltage circuit Voltage Consumption Frequency Overloads Current circuit Nominal current Consumption Frequency 50 Hz ( )
*1

YTC

400 V (*1) 1 ... 4 VA 50 Hz (*1) 1.25 Un permanent 2 Un during 5 s 20 ... 100 Hz

Application
Measurement of the power factor in balanced or unbalanced single and three-phase circuits.

... 5 A (*1) 0.3 ... 1.5 VA 20 ... 100 Hz 1.2 In permanent 5 In during 30 s 10 In during 5 s 40 In during 1 s 1.5 % FS

Overloads

Accuracy Ambient conditions Operating temperature Limit temperature Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel Terminals Insulation voltage Standards

+10 ... +30 C - 25 ... +40 C 2000 m

See the following table See the following table panel

IP 52 IP 00 2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318

(*1) Other values, on demand

M1-39

Analogue instruments

Varmeters
Analogue indicator to measure reactive power
References

YMC: Varmeters single-phase

YTC: Three-phase varmeters

Single-phase YMC 96 Class Scale a b c Weight (g) Uphase-phase Current Dimensions (mm) 96 96 49,2 290 400 V ... / 5 A M13231 M13241 144 144 71,8 490 1,5 90 P1 (simple profile) YMC 144 Class Scale

Balanced three-phase YTC 96E YTC 144E

Three-phase 3 wires (ARON) YTC 96A YTC 144A

Three-phase (4 wires) YTC 96AN YTC 144AN

90 P1 (simple profile) 96 96 49,2 290 400 V 144 144 71,8 490 96 96 62,9 430 110 V 144 144 71,8 640 96 96 62,9 430 400 V 144 144 71,8 640

Dimensions (mm) a b c Weight (g) Uphase-phase Current M13232 M13242 M13234 M13244 M13233 M13243

*Scale is NOT included for YMC 96. For exchangeable scales, see Tables. *Scale included for YMC 144. Indicate the transformer ratio, power and voltage scale base. *Other voltage values, on demand.

*Scale is NOT included for YTC 96E and YTC 96AN. For exchangeable scales, see Tables. *Scale included for YTC 144E, YTC 96A, YTC144A and YTC 144AN. Indicate the transformer ratio, power and voltage scale base. *Other voltage values, on demand.

Exchangeable scales

Single-phase varmeters
Exchangeable scales Single-phase Type Equipment A 50/5 75/5 100/5 150/5 200/5 300/5 400/5 500/5 600/5 1 000/5 1 500/5 2 000/5 3 000/5 4 000/5 5 000/5 Scale Base 20 kvar 40 kvar 60 kvar 80 kvar 120 kvar 160 kvar 200 kvar 240 kvar 400 kvar 600 kvar 800 kvar 1.2 Mvar 1.6 Mvar 2.0 Mvar SYM 96 YMC 96 Code M132J9 M132JC M132JE M132JF M132JH M132JJ M132JK M132JL M132JP M132JR M132JS M132JU M132JV M132JW

Three-phase varmeters
Exchangeable scales Three-phase Type Equipment A 50/5 75/5 100/5 150/5 200/5 300/5 400/5 500/5 600/5 1 000/5 1 500/5 2 000/5 3 000/5 4 000/5 5 000/5 30 kvar 45 kvar 60 kvar 90 kvar 120 kvar 150 kvar 240 kvar 300 kvar 360 kvar 600 kvar 900 kvar 1.2 Mvar 1.8 Mvar 2.4 Mvar 3.0 Mvar SYT 96E YTC 96E Code M132K9 M132KB M132KC M132KE M132KF M132KH M132KJ M132KK M132KL M132KP M132KR M132KS M132KU M132KV M132KW SYT 96AN YTC 96AN Code M132L9 M132LB M132LC M132LE M132LF M132LH M132LJ M132LK M132LL M132LP M132LR M132LS M132LU M132LV M132LW

M1-40

Analogue instruments

Varmeters
Analogue indicator to measure reactive power
Dimensions
YMC / YTC Type 96 E 96 A / AN 144 Dimensios (mm) a 96 96 144 b 91 91 137 c 43,5 57,2 94,7 d 5,7 5,7 7,3 e 92 92
+0,8 +0,8 +1

138

Connections
YMC YTCE

YTCA

YTCAN

M1-41

Analogue instruments

Varmeters
Analogue indicator to measure the reactive power
Coding table M 1
Code Current input

Internal Code Standard .../ 5 A ... / 1 A Standard (400 Vp-p) 110 Vp-p (a) 0 1 0 1 2 5 6 9 B C E F H J K L P R S U V W

Voltage

230 Vp-p 440 Vp-p 460 Vp-p 50 75 100 150 200 300 400 500 600 1000 1500 2000 3000 4000 5000

Varmeters Scale range Primary current transformer

(a) For unbalanced ARON (3 wire) three-phase units, 100V is considered the standard voltage

M 1
Varmeter scales
Code

X X X

Internal Code

Current input

Standard .../ 5 A ... / 1 A Standard (400 V) 110 V (a)

0 1 0 1 2 5 6

Voltage

230 V 440 V 460 V

(a) For unbalanced ARON (3 wire) three-phase units, 100V is considered the standard voltage

M1-42

Analogue instruments

Analogue indicator to measure cos

Electronic Phase-meters

Description
}} Does not need an auxiliary power supply }} DIN box with dimensions 96 and 144 mm }} Class 1.5 }} Built-in electronic converter }} Balanced single and three-phase circuits

Features
FEM / FETC Voltage circuit Consumption Frequency Overloads Current circuit 1 VA 40 ... 70 Hz 1.2 Un permanent 2 Un during 5 s 4 VA FMZ / FTZ

Application
Measurement of cos in balanced or unbalanced single and three-phase circuits.

Nominal current Consumption Frequency 1.5 VA

... 5 A 0.75 VA 20 ... 100 Hz 1.2 In permanent 5 In during 30 s 10 In during 5 s 40 In during 1 s 1.5 % FS

Overloads

Accuracy Ambient conditions Operating temperature Limit temperature Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel Terminals Insulation voltage Standards

+10 ... +30 C - 25 ... +40 C 2000 m

See the following table See the following table panel

IP 52 IP 00 2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318

M1-43

Analogue instruments

Electronic phase-meters
Analogue indicator to measure cos
References

Single-phase phase-meters 90

Single-phase phase-meters 240

FEMC 96 Class Scale Dimensions (mm) a b c Weight (g) V 100/3 110/3 100 110 230 400 440 500 96 96 62,9 480 cos M13431 M13432 M13433 M13434 M13435 M13436 M13437 M13438 1,5

FEMC 144 Class Scale Dimensions (mm) 144 144 71,8 690 0.5-1-0.5 M13441 M13442 M13443 M13444 M13445 M13446 M13447 M13448 a b c Weight (g) V 100/3 110/3 100 110 230 400 440 500

FMZ 96 1,5

FMZ 144

90 P1 (Simple profile)

240 P1 (Simple profile)

96 96 101,2 500 cos M13531 M13532 M13533 M13535 M13535 M13536 M13537 M13538

144 144 71,8 710 0.5-1-0.5 M13541 M13542 M13543 M13545 M13545 M13546 M13547 M13548

Three-phase phase-meters 90

Three-phase phase-meters 240

FETC 96 Class Scale Dimensions (mm) a b c Weight (g) V 100/3 110/3 100 110 230 400 440 500 M1343C M1343D M1343E M1343F M1343G M1343H 96 96 62,9 480 1,5

FETC 144 Class Scale Dimensions (mm) 144 144 71,8 690 V M1344C M1344D M1344E M1344F M1344G M1344H 100/3 110/3 100 110 230 400 440 500 a b c Weight (g)

FEMC 96 1,5

FEMC 144

90 P1 (Simple profile)

240 P1 (Simple profile) 96 96 62,9 480 cos 0.5-1-0.5 M13431 M13432 M13433 M13434 M13435 M13436 M13437 M13438 M13441 M13442 M13443 M13444 M13445 M13446 M13447 M13448 144 144 71,8 690

cos 0.5-1-0.5

M1-44

Analogue instruments

Electronic phase-meters
Analogue indicator to measure cos
Dimensions
FEMC / FETC FMZ / FTZ

Type 96 144

a 96 144

b 91 137

c 57,2 64,5

d 5,7 7,3

e 92
+0,8 +1

Type 96 144

a 96 144

b 91 137

c 95,5 64,5

d 5,7 7,3

e 92
+0,8 +1

138

138

Dimensions (mm)

Dimensions (mm)

Connections
FEMC FETC FMZ

FTZ

Coding table M 1
Code Secondary current Frequency

Electronic phase-meters

Internal Code Standard .../ 5 A ... / 1 A Standard (50 Hz) 60 Hz 0 1 0 1

M1-45

Analogue instruments

Analogue indicator to measure cos

Induction Phase-meters

Description
}} Does not need an auxiliary power supply }} DIN box with dimensions 96 and 144. }} Class 1.5 }} Balanced and unbalanced single and three-phase circuits. }} 4 quadrants

Features
PIC A / PIC B Voltage circuit Consumption Frequency Overloads Current circuit Nominal current Consumption Frequency 4 VA 20 ... 100 Hz 1.2 In permanent Overloads 5 In during 30 s 10 In during 5 s 40 In during 1 s Accuracy Ambient conditions Operating temperature Limit temperature Altitude Dimensions Weight Type of box Degree of protection: Front panel Terminals Insulation voltage Standards IP 52 IP 00 2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318 +10 ... +30 C - 25 ... +40 C 2000 m See the following table See the following table panel 1.5 % FS ... 5 A 2.5 VA 5 VA / 20 mA 49.5 ... 50.5 Hz 59.4 ... 60.6 Hz 1.2 Un permanent 2 Un during 5 s 15 mA 4 T - 5T 54 ... 66 Hz PIC E

Application
Measurement of cos in balanced or unbalanced single and three-phase circuits.

M1-46

Analogue instruments

Induction Phase-meters
Analogue indicator to measure cos
References

Induction Phase-meters 360, single-phase

Induction Phase-meters 360, three-phase

Type Class Scale

PIC 96 A 1,5

PIC 144 A Type Class Scale Dimensions (mm) a b c Weight (g) V 110 230 400

BALANCED PIC 96 B PIC 144 B 1,5 360, P1 96 96 101,2 1 410 144 144 102 1 460 cos M13634 M13635 M13636 M13644 M13645 M13646

UNBALANCED PIC 96 E PIC 144 E

360, P1 96 96 101,2 1 910 cos M13631 M13632 M13633 144 144 102 1 960 0-1-0 M13641 M13642 M13643

Dimensions (mm) a b c Weight (g) V 110 230 400

96 96 101,2 1 410 0-1-0 M13637 M13638 M13639

144 144 102 1 460

M13647 M13648 M13649

Dimensions

Coding table
M 1
Code Secondary current

Phase-meters

Induction

Internal Code Standard .../ 5 A ... / 1 A 0 1

C0 a b c d e 48 44 41 5 45+1

C1 72 66 43 5,2 68+1

C2 96 89,6 43 5,2 92+1

C3 144 137 64,5 7,1


138+1

C4 72 66 57,2 5,2 68+1

C5 96 89,6 57,2 5,2 92+1

C6 96 89,6 95,5 5,2 92+1

C7 144 137 94,7 7,1


138+1

Dimensions (mm)

Connections

M1-47

Analogue instruments

Bidirectional protection wattmeters


Analogue indicator to measure three-phase current
Description
Electronic instrument on the front panel (96x96) used to protect generators against overloads and inverse power. The instrument is composed of a power converter with an analogue output connected to the needle indicator with 2 relays. The unit measures and indicates the system's power constantly (measurement in 4 quadrants), sending an alarm signal when the power exceeds the set trip values. The alarm is indicated by activating the output relays. The two LEDS on the front panel can be used to view the status of output relays. The scale is exchangeable.

Features
PGR Input circuit Nominal current I n Current measurement range Current overload Impedance Auxiliary power supply Nominal value in AC Frequency Consumption Nominal value in DC Consumption 115 / 230 / 400 V 40 ... 80 Hz 2.5 VA 9-18 / 18-36 / 36-72 / 90-140 V 2.5 VA 0 ... 20 mA dc 0 ... 130 % In 5 In permanent 3

Application
}} The instrument has two independent relays: an overload and an inverse power relay. Overload protection The protection has these characteristics: }} Trip point adjustable between 0 and 100% of the scale base power }} Hysteresis adjustable between 1 and 50% of the scale base }} Delay adjustable between 0 and 30 s }} Inverse power protection. With various generators connected in parallel, one can start consuming power and working as a motor, under determined situations ("motorization"). The relay is activated when the circumstances are met. The protection system has the following characteristics:Trip point adjustable between 0 and 20% of the scale base power }} Delay is adjustable between 0 and 30 s. }} Relay interlocking* (latch): when the

Ambient conditions Operating temperature Limit temperature Altitude Build features Dimensions (mm) Weight (g) Type of box Degree of protection: Front panel Terminals Standards IP 52 IP 20 BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318 96 x 96 x 77.2 435 DIN rail +5 ... +55 C - 25 ... +70 C 2000 m

alarm condition is met, the relay is activated until the instrument's auxiliary power supply is not shut down (even when the alarm conditions disappear) }} Fault security: the relay bypass position is the same as when the alarm is triggered. Therefore, when the auxiliary power supply is shut down, the unit sends an alarm. *: The system can be supplied with no relay interlocking (latch), on demand.

M1-48

Analogue instruments

Bidirectional protection wattmeters


Analogue indicator to measure three-phase current
References

Single-phase wattmeters

Three-phase wattmeters

PGR 96 M Converter (See catalogue M2) Class Scale U/I 100...500 V .../5 A (*) CW-M 1,5 90 , P2 100 ... 500 V M14721 Converter (See catalogue M2) Class Scale U/I 100...500 V .../5 A (*)

PGR 96E CW-TE

PGR 96A CW-TA 1,5 90 , P2

PGR 96AN CW-TAN

100 ... 500 V M14722 M14724 M14723

Coding table
M 1
Code 50 60 75 100 125 150 200 250 300 400 Scales 500 600 750 800 1000 1200 1500 2000 2500 3000 4000 5000 Current input Standard (.../ 5 A) ... / 1 A Standard 220...240 V 380 ... 400 V 40/60 Hz

Dimensions
X X X 0 0 X X X
PGR

Internal Code

9 A B C D E F G H J K L M N P Q R S T U V W 0 1 0 3

PGR Wattmeter

Connections

Auxiliary power supply

M1-49

Analogue instruments

Synchronisation and marine applications equipment


2 EC / 2 HC / 2 HLC

Description
}} Does not need an auxiliary power supply }} DIN box with dimensions 96 and 144 mm }} Class 1.5 }} Double scale

Features
2 EC Input circuit Consumption Working frequency Overloads Measurement voltage Accuracy Ambient conditions Operating temperature Limit temperature Altitude Build features Dimensions See the following table See the following table panel +10 ... +30 C - 25 ... +40 C 2000 m 1.5 % FS 1 ... 4 VA 20 ... 100 Hz 2 ... 3 VA 1 ... 3.6 VA 2 HC 2 HLC

depending on the type (see table) 1.2 Un permanent 2 Un during 5 s Standard 230 Vac Optional 100-120 Vac380-440 Vac 0.5 % FS

Application

2 EC Double moving iron voltmeter (AC)


For the measurement and comparison of alternating currents from two generators or a generator in the network, when connected in parallel.

2 HC Double meter

Pointer

frequency-

Weight Type of box Degree of protection: Front panel Terminals Insulation voltage Standards IP 52 IP 00

For the measurement and easy comparison of frequencies in alternating current circuits coming from generators or between the network and generator, when connected in parallel.

IP 52 IP 00

2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318

2 HLC Double reed frequency-meter


For the measurement and easy comparison of frequencies in alternating current circuits coming from generators or between the network and generator, when connected in parallel. The measurement is independent of the wave shape. For applications in severe environmental and physical conditions.

M1-50

Analogue instruments

Synchronisation and marine applications equipment

2 EC / 2 HC / 2 HLC
References

2 EC: Double voltmeter

2 HC: Double Pointer frequency meter


}} Class 0.5 }} Built-in electronic converter

2 HLC: Double reed frequency meter


}} Class 0.5 }} Independent measurement of the wave shape
Type Class Scale Dimensions (mm) a b c Weight (g) Hz 47...53, 13 reeds M12932 M12932001 M12932002 M12932003 M12932004 M12932005 M12942 M12942001 M12942002 M12942003 M12942004 M12942005 57..0.63, 13 reeds 45..0.55, 11 reeds 55..0.65, 11 reeds 57..0.63, 7 reeds 47...53, 7 reeds 96 96 62,9 400 2 HLC 96 0,5 144 144 71,8 450 2 HLC 144

}} Class 1.5
Type Class Scale Dimensions (mm) a b c Weight (g) V 2 x .../100 2 x .../110 2 x 220 2 x 380 2 x 440 M13831 M13832 M13833 M13834 M13835 M13841 M13842 M13843 M13844 M13845 96 96 49,2 220 144 144 71,8 430 2 EC 96 1,5 90 2 EC 144

Type Class Scale

2 HC 96 0,5 90

2 HC 144

Dimensions (mm) a b c Weight (g) Hz 45...55 57...63 55...65 45...65 47...63 M12732 M12732001 M12732003 M12732004 M12732005 M12742 M12742001 M12742003 M12742004 M12742005 96 96 62,9 400 144 144 71,8 450

Coding table
2HLC Frequency meters
M 1 X X X X 0
Code

0 X

M 1
Code

X X X

Internal Code

Internal Code

400 (640) 440 (700) 660 (1050) 1000 (1600) 1200 (1920)

0 1 2 3 4 5 6 7 8 9 A B D E F G H J K L M

Standard (47...53 Hz/ 13 reeds) Frequency / No. reeds 57...63 Hz / 13 reeds 45..0.55 Hz / 11 reeds 55...65 Hz / 11 reeds Standard (400 V) Voltage 100 ... 120 V 440 V

0 1 2 3 0 1 4

Double voltmeters

2500 (4000) 3000 (4800) 3300 (5280) 4000 (6400) Nominal scale value (Scale base) 5000 (8000) 5500 (8800) 6500 (10560) 7200(11520) 9000 (14400) 10000 (16000) 11000 (17600) 12500 (20000) 15000 (24000) 20000 (32000) 22000 (35200) 24000 (38400) 25000 (40000)

M 1 X X X X 0 0 X X 2HC Frequency meters


Code Internal Code Standard (45...55 Hz) 57..0.63 Hz Frequency 55..0.65 Hz 45..0.65 Hz 47...53 Hz Standard (230 V) Voltage 100 ... 120 V 380 ... 400 V 440 V 0 1 3 4 5 0 1 3 4

M1-51

Analogue instruments

Synchronisation and naval application equipment

2 EC / 2 HC / 2 HLC

Dimensions
2 EC

Type 96 mm 144 mm

a 96 144

b 91 137

c 43,5 64,5

d 5,7 7,3

e 92+0,8 138+1

Dimensions (mm)

2 HC / 2 HLC

Type 96 mm 144 mm

a 96 144

b 91 137

c 57,2 64,5

d 5,7 7,3

e 92+0,8 138+1

Dimensions (mm)

Connections
2 EC / 2 HC / 2 HLC

M1-52

Analogue instruments

Synchronisation and marine applications equipment


SMC / STC / UC / CUC

Description

Features
SMC Input circuit Line: 5 VA Generator: 15 mA Line: 20 mA per circuit Generator: 15 mA per circuit STC UC CUC

SMC / STC Synchroscopes


}} Does not need an auxiliary power supply }} DIN box with dimensions: 96 and 144mm }} Class 1 }} For single and three-phase circuits

Consumption

3 mA

4 VA

Frequency Overloads Measurement voltage Accuracy Ambient conditions Operating temperature Front panel Altitude Build features Dimensions Weight Type of box Degree of protection: Front panel terminals Insulation voltage Standards

20 ... 100 Hz 1.2 Un permanent 2 Un during 5 s Standard 230 Vac

50 Hz

UC / CUC Sequence-meters
}} Does not need an auxiliary power supply }} DIN box with dimensions: 72 and 96 mm }} Class 1.5 }} Built-in voltage relay }} Low consumption

Optional 100-120 Vac380-440 Vac 1.5 % FE

+ 10 ... + 30 C - 25 ... + 40 C 2000 m

0 ... 70 C - 40 ... + 70 C

See the following table See the following table panel

IP 52 IP 00

IP 52 IP 00

2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318

M1-53

Analogue instruments

Synchronisation and marine applications equipment

SMC / STC / UC / CUC

Application

References

SMC / STC Synchroscopes


To provide a correct reading of the difference between the frequency and phase angle between two generators or a generator and the network, when connected in parallel. When the difference is zero, the instrument's needle does not move from the synchronisation mark located in the centre of the scale. The instrument scale is divided in two areas marked with the (+) and (-) signs. These signs indicate whether the machine being connected has a higher or lower frequency that the other one, respectively. Synchronism is achieved when the needle is on the (-) side, slowly turning towards (+). The needle of the instrument starts to turn in the correct direction when the difference in frequencies is 1.5 Hz for three-phase systems or 0.5 Hz for single-phase systems .

SM / STC: Single-phase synchroscopes

SM / STC: Three-phase synchroscopes

Type Class

SMC 96

SMC 144 1,5

Type Class

STC 96 1,5
a b c

STC 144

Dimensions (mm)
a b c Weight (g)

Dimensions (mm) 144 144 102 2250 M14441 M14442 M14443 M14444
Weight (g)

96 96 101,2 1700 M14431 M14432 M14433 M14434

96 96 101,2 1410 M14435 M14436 M14437 M14438

144 144 102 1960 M14445 M14446 M14447 M14448

V 110 230 400 500

V 110 230 400 500

UC / CUC Sequence-meters
The UC 72 and UC 96 types indicate the order of three-phase systems. The CUC 96 type indicates the sequence of phases and it has a built-in relay with a switched and voltage-free contact. The relay is deactivated in the absence of voltage or when the order of phases is incorrect. A fully electronic circuit, with no moving parts, for the activation of neon indicators. }} Scales: A GREEN and RED display indicate whether the phase sequence is CORRECT or INCORRECT, respectively.

UC / CUC: Sequence-meters

Type Control relay Dimensions (mm)


a b c Weight (g)

UC 72 NO 72 72 62,9 200 M13726 M13721 -

UC 96

CUC 96 YES

96 96 62,9 275 M13736 M13731 -

96 96 62,9 375 M13734 M13735

V 100 ...150 V 150 ... 500 V 230 400

M1-54

Analogue instruments

Synchronisation and marine applications equipment

SMC / STC / UC / CUC


Coding table
Synchroscopes and sequence-meters

1
Code

Internal Code Standard (50 Hz) 0 1

Frequency

60 Hz

Dimensions
SMC / STC

Connections
SMC STC

SMC Type 96 mm 144 mm

a 96 144

b 96 144

c 101,2 102

Dimensions (mm)

STC Type 96 mm 144 mm

a 96 144

b 96 144

c 101,2 102

Dimensions (mm)

UC / CUC

UC

CUC

Type 72 mm 96 mm

a 72 96

b 67,2 91

c 57,2 57,2

d 5,7 5,7

e 68+0,8 92+0,8

Dimensions (mm)

M1-55

Analogue instruments

Synchronisation and marine applications equipment


Synchro MAX / Synchro MAX PID

Synchro MAX / Synchro MAX PID


Equipment used to synchronise a generator with the network
Description
}} All parameters can be programmed on the keyboard on the front panel. }} Digital unit with 4-digit display and 30 auxiliary LEDs. }} Voltage, generator frequency and network measurement and display (TRMS), including the unbalance between the generator and the network. }} Automatic synchronisation by simply programming the contactor closing time. }} Wide range of frequencies (35...80 Hz) }} Standard power supply: 110, 230 and 400 V ac }} 2 operating modes: Manual, automatic and assisted }} Digital adjustment (without potentiometers) }} PI / PID CONTROL (depending on the type) OF THE SPEED OF THE GENERATOR WITH BUILT-IN PULSE OUTPUT }} Protection with password.

Features
Auxiliary power supply Standard values Frequency margin Maximum consumption Measurement circuit Measurement range Frequency Overload (permanent) Consumption Accuracy Voltage (R.M.S.) Frequency Phase angle Display Colour Presentation cycle Auxiliary LEDs Ambient conditions Storage temperature Operating temperature Altitude Build features Box colour Box material Degree of protection Weight Insulation voltage Standards BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318 Grey anthracite Self-extinguishing ABS Front panel IP 54 (optional IP 65) 0.35 kg 2 kV, during 1 min, between the mechanism and the box - 40 ... +70 C -10 ... + 65 C 2000 m CI 1 +/- 2 dig. +/- 0.01 Hz +/- 0.5 4 digits Red, high efficiency 2/s 30 30 ... 150 V, 110 ... 600 V 35 ... 80 Hz 800 V < 500 uA Alternating voltage 110, 230, 400 V ac (-10 / +15 %) 35 ... 450 Hz 10 VA

M1-56

Analogue instruments

Synchronisation and marine applications equipment

Synchro MAX / Synchro MAX PID

Unit's front panel

Analogue simulation Low frequency

High frequency

Enable Measurements displayed Phase Main voltage Generator voltage Earth leakage voltage Main frequency Generator frequency Frequency difference V V Fr
BB GEN

4 digit indicator

V%
BB

Frequency margin OK

FrGEN FR %

Voltage margin OK

Application
SynchroMax is a synchronism relay that has been designed to synchronise a generator with the network or with another generator used as reference. We can connect both in parallel in emergency or support applications when a greater power is needed.

Description
CIRCUTOR has two types of synchronism relays: SYNCHRO MAX and SYNCHRO MAX PID. hydraulic power plants, among many other applications. Here is an example of how SYNCHRO MAX moves forward to a time t brk (previously programmed by the user) to take into account the connection delay of the generator's contactor.

Synchro Max
Synchro Max is capable of adapting the generator's frequency with an integrated PI regulation algorithm, in order to connect it in parallel to the electrical network. In addition, it can be used to measure and display the voltage, phase and frequency parameters of the generator and network, as well as its differences.

Synchro Max PID


Synchro Max PID offers excellent standard Synchro Max measurement, display and programming features, with a powerful PID algorithm to control the generator's frequency. This type of control turns Synchro Max PID into a quick synchronisation device and, therefore, it offers the ideal solution to reduce synchronisation costs, since it minimises the time invested in such procedures. This type of control is perfect for small-scale

T t :: brk brk Contactor closing time Time for closing the contact

M1-57

Analogue instruments

Synchronisation and marine applications equipment

Synchro MAX / Synchro MAX PID

References

Coding table

M 1
SynchroMAX
Code

X X X

Internal Code Standard (400 V) 110 V 230 V 0 1 2

Type PID Control Frequency Dimensions (mm) a b c Vmeasurement 30 ... 150 110 ... 600

SYNCHRO MAX No

SYNCHRO MAX PID Yes 30 ... 70 Hz 96 96 62,9

Voltage power supply

M14624 M14625

M14634 M14635

Dimensions
SYNCROMAX

Connections

M1-58

Analogue instruments

MEG-1000
Insulation resistance meter

Description
}} Does not need an auxiliary power supply }} DIN box, with dimensions: 96x96 }} Class 1.5 }} Neutral insulated or impedance systems (IT network)

Features
Input circuit Consumption Frequency Overloads Accuracy Ambient conditions Operating temperature Limit temperature Altitude Build features Dimensions Weight Type of box Terminal protection degree Box protection degree Weight Insulation voltage Standards BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318 See the following table See the following table panel IP 00 IP 52 0.35 kg 2 kV, during 1 min, between the mechanism and the box + 10 ... +30 C - 25 ... + 40 C 2000 m 5 VA 20 ... 100 Hz 1.2 Un permanent 2 Un during 5s 1.5 % FS

Application
MEG-1000 measures and controls the insulation resistance between phase and earth in a neutral insulated or impedance line (IT), with the use of relays. The insulation resistance can be displayed with a galvanometric indicator located on the front of the unit. To carry out the measurements, the unit applies a continuous voltage of 24 V between the phase and earth, measuring the leakage current circulating through the network insulation resistors. This current determines the insulation resistance. The unit has two timed output relays, one acts as the maximum (triggered when the insulation resistance is lower than a determined value). In both relays, the trip point and connection delay time can be adjusted with potentiometers located on the back of the unit. When the insulation resistor is within the maximum and minimum values defined with the potentiometers, the NORMAL LED will be lit on the front panel. When the resistor is out of the margins defined, either exceeding or not reaching the normal levels, the ALARM LED will be lit on the front panel.

M1-59

Analogue instruments

MEG-1000
Insulation resistance meter

References

Type Class Scale Frequency Dimensions (mm) a b c Weight (g) (double scale) Code

MEG-1000 1,5 90 50 ... 60 Hz 96 96 73,8 0,708 0 ... 500 k 0.5 ... 5 M M15051

Dimensions

Connections

M1-60

Analogue instruments

CH

Hours run meter

Description

Features
Input circuit Current Frequency Display Digits 10 mA 50 or 60 Hz Mechanical 1,5 x 3.5 mm with magnifier 99 999,99

Application
}} Timers are used to measure time with a simple, easy and reliable system. }} Measurement of start-up and operating times. }} Modification and operating times. }} Production and quantity times. }} Data to provide information about the following:

Maximum value Ambient conditions Operating temperature limit temperature Type of box Terminal protection degree Box protection degree Weight Insulation voltage Standards

+10 ... +30 C -25 ... +40 C panel IP 00 IP 52 0.35 kg 2 kV, during 1 min, between the mechanism and the box BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318

M1-61

Analogue instruments

CH

Hours run meter

References

Coding table
M 1 Code Timer Frequency X X X X 0 0 X X

Internal Code Standard 50 Hz 60 Hz Standard (230 V) 24 V ac 0 1 0 6 1 8 A

Type Class Display Dimensions (mm)


a b c

CH 48

CH 72 1,5 5+2

CH 96

CH 45 5+1

Voltage

110 V ac 10..0.80 V dc 80...200 V dc

48 48 48 50 M14911

72 72 62,9 125 M14921

96 96 62,9 180 M14931

90 36 55 75 M14951

Weight (g) Code

Dimensions
CH 48

Connections

CH 72 / CH 96

CH 45

Type 72 mm 96 mm

a 72 96

b 67,2 91

c 57,2 57,2

d 5,7 5,7

e 68+0,8 92+0,8

Dimensions (mm)

M1-62

Analogue instruments

Accessories
Terminal cover
Type Code 72 x 72 mm M19922 96 x 96 mm M19923 144 x 144 mm M19924

Accessory

IP protection
Type IP 54 IP 65 48 x 48 mm M19931 M19941 72 x 72 mm M19932 M19942 96 x 96 mm M19933 M19943 144 x 144 mm M19934 M19944

Accessory

Options
Tropicalized, only on the panel Externally regulated pointer Anti-reflection glass Makrolon Glass Interior lighting (6 - 12 - 48 Vdc) panel only Prolongation of scales 1; 1.2; 2; 3; 4; 5; 6 Central zero Shifted zero

Coding table
M 1 Code X X X X 0 Internal Code Tropicalized, only on the panel
Externally regulated pointer

0 0 0 0 0 0 0

1 2 3 4 5 6 7

Anti-reflection glass Other options Makrolon Glass Interior illumination (6-12-48 Vdc) only on the panel Tropicalized + anti-reflection glass Tropicalized + Makrolon glass

M1-63