Sei sulla pagina 1di 222

Voltage regulator TAPCON 260

Operating Instructions 1801003/05


Protocol description for IEC 61850

All rights reserved by Maschinenfabrik Reinhausen Copying and distribution of this document and utilization and communication of its contents are strictly prohibited unless expressly authorized. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or ornamental design registration. The product may have been modified after this document went to press. We expressly reserve the right to make changes to the technical data, the design or the scope of delivery. Generally, the information provided and the arrangements agreed during processing of the relevant quotations and orders are binding. The original operating instructions were drawn up in German.

2 Safety

Table of Contents
1
1.1 1.2 1.3 1.4 1.5 1.6
1.6.1 1.6.2 1.6.3

Introduction .................................................................................. 9
Manufacturer ........................................................................................... 9 Subject to change without notice ............................................................. 9 Completeness ......................................................................................... 9 Supporting documents........................................................................... 10 Safekeeping .......................................................................................... 10 Notation conventions ............................................................................. 10
Abbreviations used ............................................................................................. 11 Hazard communication system ........................................................................... 12 Information system .............................................................................................. 13

2
2.1 2.2 2.3 2.4 2.5

Safety .......................................................................................... 15
General safety information..................................................................... 15 Appropriate use ..................................................................................... 15 Inappropriate use .................................................................................. 16 Personnel qualification .......................................................................... 16 Operator duty of care............................................................................. 16

3
3.1 3.2

Product description ................................................................... 19


Performance features ............................................................................ 21 Relay of the signals via IEC 61850 ........................................................ 22

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

2 Safety

3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 3.2.7

LLN0 - Logical node............................................................................................ 22 LPHD - Physical device ...................................................................................... 22 LPHD - Physical device ...................................................................................... 23 GGIO1 - IO card inputs ....................................................................................... 25 GGIO2 - UC1 card inputs ................................................................................... 26 GGIO3 - UC2 card inputs ................................................................................... 27 GGIO4 - UC3 card inputs (optional) ................................................................... 28

3.3 3.4 3.5


3.5.1 3.5.2

Operating modes................................................................................... 29 Scope of delivery................................................................................... 29 Hardware description ............................................................................ 30


Internal design .................................................................................................... 31 Communication Interfaces .................................................................................. 31

3.6
3.6.1 3.6.2 3.6.3 3.6.4

Operation and indicator elements .......................................................... 36


Operating concept .............................................................................................. 37 Description of the display.................................................................................... 38 Description of key functions ................................................................................ 40 Description of LEDs ............................................................................................ 41

4
4.1
4.1.1 4.1.2 4.1.3

Packaging, Transport and Storage ........................................... 43


Packaging ............................................................................................. 43
Purpose............................................................................................................... 43 Suitability, structure and production ................................................................... 43 Markings ............................................................................................................. 44

4.2 4.3

Transportation, receipt and handling of shipments ................................ 44 Storage of shipments ............................................................................ 45

5
5.1

Mounting ..................................................................................... 47
Unpacking ............................................................................................. 47

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

2 Safety

5.2 5.3
5.3.1 5.3.2 5.3.3 5.3.4 5.3.5 5.3.6

Mounting ............................................................................................... 47 Connection ............................................................................................ 48


Cable recommendation for standard connections .............................................. 48 Cable recommendation for optional connections ............................................... 49 Electromagnetic compatibility ............................................................................. 49 Connecting lines to the system periphery ........................................................... 56 Voltage regulator power supply .......................................................................... 57 Wiring the voltage regulator ................................................................................ 57

5.4

Function check ...................................................................................... 58

6
6.1
6.1.1 6.1.2 6.1.3

Commissioning .......................................................................... 59
Configuration ......................................................................................... 59
Setting the language ........................................................................................... 59 Selecting the control mode ................................................................................. 60 Controlling remote tap position indicator with BCD signal .................................. 61

6.2
6.2.1 6.2.2 6.2.3

Function tests ........................................................................................ 63


Function tests for control functions ..................................................................... 63 Function tests for additional functions ................................................................ 65 Function tests for parallel operation .................................................................... 68

7
7.1
7.1.1 7.1.2

Functions and settings .............................................................. 73


Key lock................................................................................................. 73
Activating key lock .............................................................................................. 73 Deactivating key lock .......................................................................................... 73

7.2
7.2.1 7.2.2 7.2.3

NORMset .............................................................................................. 74
Entering NORMset desired value 1 .................................................................... 76 Setting the primary voltage ................................................................................. 77 Setting the secondary voltage ............................................................................ 78

7.3

Parameters ............................................................................................ 79

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

2 Safety

7.3.1 7.3.2 7.3.3 7.3.4 7.3.5 7.3.6 7.3.7 7.3.8 7.3.9 7.3.10 7.3.11 7.3.12 7.3.13

Setting control parameters.................................................................................. 79 Setting desired value 1 ....................................................................................... 80 Setting desired value 2 ....................................................................................... 81 Setting desired value 3 ....................................................................................... 82 Bandwidth ........................................................................................................... 83 Setting delay time T1 .......................................................................................... 87 Setting control response T1 ................................................................................ 89 Activating/deactivating delay time T2 ................................................................. 90 Setting delay time T2 .......................................................................................... 91 Limit values ......................................................................................................... 91 Abnormal control response ............................................................................... 101 Compensation ................................................................................................... 105 Cross-monitoring .............................................................................................. 114

7.4
7.4.1 7.4.2 7.4.3 7.4.4 7.4.5 7.4.6 7.4.7 7.4.8

Configuration ....................................................................................... 123


Transformer data .............................................................................................. 123 General ............................................................................................................. 132 Parallel operation .............................................................................................. 145 Configuring analog inputs ................................................................................. 156 LED selection .................................................................................................... 164 Configuring transducer function ........................................................................ 167 Configuring measured value memory function (optional) ................................. 173 Communication interface SID ........................................................................... 190

7.5
7.5.1 7.5.2 7.5.3 7.5.4 7.5.5 7.5.6 7.5.7 7.5.8 7.5.9 7.5.10 7.5.11

Info ...................................................................................................... 195


Carrying out LED test ....................................................................................... 197 Querying status ................................................................................................. 198 Resetting parameters ....................................................................................... 200 Displaying real-time clock ................................................................................. 200 Displaying parallel operation ............................................................................ 200 Displaying data on CAN bus ............................................................................. 201 Displaying measured value memory ................................................................ 203 Displaying peak memory .................................................................................. 203 Displaying CIC1 card SCADA information........................................................ 204 Displaying CIC2 card SCADA information........................................................ 205 Displaying upcoming messages ....................................................................... 206

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

2 Safety

8
8.1 8.2 8.3

Interface description for IEC 61850 protocol ......................... 207


Physical connection ............................................................................. 207 Device-specific data points for TAPCON 260 .................................... 207 Downloading the ICD file ..................................................................... 208

9
9.1
9.1.1 9.1.2 9.1.3 9.1.4 9.1.5 9.1.6 9.1.7 9.1.8

Fault elimination ....................................................................... 209


Operating faults ................................................................................... 209
No control in AUTO mode ................................................................................. 209 Man Machine Interface ..................................................................................... 210 Incorrect measured values................................................................................ 211 Parallel operation faults .................................................................................... 212 Tap position capture incorrect .......................................................................... 213 Digital inputs ..................................................................................................... 214 General fault ..................................................................................................... 214 No solution ........................................................................................................ 214

9.2

Event message.................................................................................... 216

10
10.1 10.2 10.3 10.4 10.5 10.6 10.7

Technical Data .......................................................................... 217


Indicator elements ............................................................................... 217 Electrical data ...................................................................................... 217 Inputs and outputs ............................................................................... 217 Dimensions and weight ....................................................................... 218 Voltage and current measurement....................................................... 219 Ambient conditions .............................................................................. 219 Tests ................................................................................................... 219

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

2 Safety

10.7.1 10.7.2 10.7.3

Electrical safety................................................................................................. 219 EMC tests ......................................................................................................... 220 Environmental durability tests ........................................................................... 220

11

MR worldwide ........................................................................... 221

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

2 Safety

Introduction
This technical file contains detailed descriptions on the safe and proper mounting, connection, commissioning and monitoring of the product. It also includes safety instructions and general information about the product. This technical file is intended solely for specially trained and authorized personnel.

1.1

Manufacturer
The product is manufactured by: Maschinenfabrik Reinhausen GmbH Falkensteinstrae 8 93059 Regensburg Tel.: (+49) 9 41/40 90-0 Fax: (+49) 9 41/40 90-7001 E-Mail: sales@reinhausen.com Further information on the product and copies of this technical file are available from this address if required.

1.2

Subject to change without notice


The information contained in this technical file comprise the technical specifications approved at the time of printing. Significant modifications will be included in a new edition of the technical file. The document and version numbers of this technical file are shown in the footer.

1.3

Completeness
This technical file is incomplete without the supporting documentation.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

2 Safety

1.4

Supporting documents
The following documents apply to this product: Operating instructions Quick reference guide Connection diagrams

In addition, generally applicable legal and other binding regulations of European and national law and the regulations for accident prevention and environmental protection in force in the country of use must be complied with.

1.5

Safekeeping
This technical file and all supporting documents must be kept ready to hand and accessible for future use at all times.

1.6

Notation conventions
This section contains an overview of the abbreviations, symbols and textual emphasis used.

10

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

2 Safety

1.6.1

Abbreviations used
Abbreviation C A AC B BCD ca. CAN CIC CPU CT DC DIN DNP EMC ESC Hz I IEC IP kBaud kg kV LDC LED Fiber-optic cable max. MB MR MHz min. mm ms N PH Phi () ppm Definition Degrees Celcius Ampere Alternating Current Bandwidth Binary Coded Decimal circa Regulator Area Network Communication Interface Card Central Processing Unit Current Transformer Direct Current Deutsches Institut fr Normung (German Institute for Standardization) Distributed Network Protocol Electromagnetic compatibility Escape Hertz Current International Electrotechnical Commission Internet Protocol Kilobaud Kilogram Kilovolt Line Drop Compensation Light Emitting Diode Fiber-optic cable maximum Megabyte Maschinenfabrik Reinhausen Megahertz minimum Millimeter Millisecond Neutral Phase Phase angle Parts per million

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

11

2 Safety

Abbreviation s SCADA T TCP V VAct VRef V VT


Table 1

Definition Second Supervisory Control and Data Acquisition Time Transmission Control Protocol Voltage Actual voltage Reference voltage Volt Voltage Transformer
Abbreviations used

1.6.2

Hazard communication system


Warnings in this technical file use the following format: DANGER! Danger Consequences Action Action

The following signal words are used: Signal word Danger Warning Attention Note
Table 2

Hazard level Immediate threat of danger Possible threat of danger Possible dangerous situation Possible dangerous situation
Signal words in warning notices

Consequence of failure to comply Death or serious injury could occur Death or serious injury could occur Minor or moderate injury could occur Damage to property could occur

12

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

2 Safety

Pictograms warn of dangers: Picto gram Meaning Danger

Dangerous electrical voltage

Fire hazard

Danger of tipping

Table 3

Symbols used in warning notices

1.6.3

Information system
Information is designed to simplify and improve understanding of particular procedures. In this technical file they are laid out as follows: Important information

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

13

2 Safety

Safety

2.1

General safety information


This technical file contains detailed descriptions on the safe and proper mounting, connection, commissioning and monitoring of the product. Read this technical file through carefully to familiarize yourself with the product. Particular attention should be paid to the information given in this chapter.

2.2

Appropriate use
The product and associated equipment and special tools supplied with it comply with the relevant legislation, regulations and standards, particularly health and safety requirements, applicable at the time of delivery. If used as intended and in compliance with the specified requirements and conditions in this technical file as well as the warning notices in this technical file and attached to the product, then the product does not present any hazards to people, property or the environment. This applies throughout the product's full life, from delivery through installation and operation to disassembly and disposal. The operational quality assurance system ensures a consistently high quality standard, particularly in regard to the observance of health and safety requirements. Use is considered to be appropriate if the product is operated in accordance with this technical file and the agreed delivery conditions and technical data, and the associated equipment and special tools supplied with it are used solely for the intended purpose and in accordance with the specifications of this technical file. the product is used only with the transformer specified in the order.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

15

2 Safety

2.3

Inappropriate use
Use is considered to be inappropriate if the product is used other than as described in Appropriate use on page 15. Maschinenfabrik Reinhausen does not accept liability for damage resulting from unauthorized or inappropriate changes to the product. Inappropriate changes to the product without consultation with Maschinenfabrik Reinhausen can lead to personal injury, damage to property and operational disruption.

2.4

Personnel qualification
The product is designed solely for use in electrical energy systems and facilities operated by appropriately trained staff. This staff comprises people who are familiar with the installation, assembly, commissioning and operation of such products.

2.5

Operator duty of care


To prevent accidents, disruptions and damages as well as unacceptable adverse effects on the environment, those responsible for transport, installation, operation, maintenance and disposal of the product or parts of the product must ensure the following: All warning and hazard notices are complied with. Personnel are instructed regularly in all relevant aspects of operational safety, the operating instructions and particularly the safety instructions contained therein. Regulations and operating instructions for safe working as well as the relevant instructions for staff procedures in the case of accidents and fires are kept on hand at all times and are displayed in the workplace where applicable. The product is only used when in a sound operational condition and safety equipment in particular is checked regularly for operational reliability. Only replacement parts, lubricants and auxiliary materials which are authorized by the manufacturer are used. The specified operating conditions and requirements of the installation location are complied with.

16

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

2 Safety

All necessary devices and personal protective equipment for each activity are made available. The prescribed maintenance intervals and the relevant regulations are complied with. Fitting, electrical connection and commissioning of the product may only be carried out by qualified and trained personnel in accordance with this technical file. The operator must ensure appropriate use of the product.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

17

3 Product description

Product description
The voltage regulator serves to keep constant the output voltage of a transformer with an on-load tap-changer. To do this, the voltage regulator compares the transformer's measured output voltage (Vactual) with a defined reference voltage (Vreference). The difference between Vactual and Vdesired is the control deviation (dV). If the control deviation is greater than the specified bandwidth (B%), the voltage regulator emits a switching pulse after a defined delay time T1. The switching pulse triggers an on-load tap-changer tap change which corrects the transformer's output voltage. The voltage regulator parameters can be optimally adjusted to the line voltage behavior to achieve a balanced control response with a small number of on-load tap-changer operations. The following diagram (on page 20) shows an overview of voltage regulation.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

19

3 Product description

Figure 1

Overview of voltage regulation

20

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

3.1

Performance features
The voltage regulator is responsible for controlling tapped transformers. Apart from control tasks, the voltage regulator provides additional functions such as: Integrated protective functions: Undervoltage and overcurrent blocking Overvoltage detection with high-speed return Line drop compensation Z compensation to compensate for voltage fluctuations in the meshed grid Digital inputs and outputs which can be individually programmed on-site by the user Additional indicators using LEDs outside the display for freely selectable functions Display of all measured values such as voltage, current, active power, apparent power or reactive power, cos Cable connection using modern plug terminals Selection of 3 different desired values When ordering you can choose between tap position capture using analog signal 420 mA analog signal via resistor contact series digital signal via BCD code Additional digital inputs and outputs which can be freely parameterized by the customer Parallel operation of up to 16 transformers in 2 groups using the methods Master / Follower Circulating reactive current minimization

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

21

3 Product description

3.2

Relay of the signals via IEC 61850


The following signals are relayed via IEC 61850.

3.2.1
LLN0 class Attribute Name LN0 Data

LLN0 - Logical node

Attribute Type

Explanation Logical node zero Name

M/O/E

Remarks

Common Logical Node Information Mod Beh Health NamPlt


Table 4

ENC INS INS LPL

Mode Behaviour Health Name plate

M M M M

Status-only

IEC 61850 data points (LLNO - Logical node)

3.2.2
LPHD class Attribute Name LPHD Data

LPHD - Physical device

Attribute Type

Explanation Physical device information

M/O/E M

Remarks

Common Logical Node Information PhyNam PhyHealth Proxy


Table 5

DPL INS SPS

Physical device name plate Physical device health Indicates if this LN is a proxy

M M M

IEC 61850 data points (LPHD - Physical device)

22

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

3.2.3
ATCC class Attribute Name ATCC1

LPHD - Physical device

Attribute Type AVR

Explanation

M/O/E

Remarks

Common Logical Node Information Mod Beh Health ENC INS INS Mode Behaviour Health O M O status-only 1:=OK; 2:=function monitoring; 3:=no internal communication or parameter error

NamPlt Controls TapChg ParOp LTCBlk CirCur Master Follower SICmd1 SICmd2 SICmd3 VoltLvl1 VoltLvl2 VoltLvl3 Measured values CtlV LodA

LPL

Name plate

BSC DPC SPC SPC SPC SPC SPC SPC SPC SPC SPC SPC

Change Tap Position Parallel Independend Block Automatic Control Circulating current (parallel control) Master mode (parallel control) Follower mode (parallel control) Serial Interface Command 1 Serial Interface Command 2 Serial Interface Command 3 Voltage level 1 Voltage level 2 Voltage level 3

C M O E E E E E E E E E

direct-with-normal-security direct-with-normal-security direct-with-normal-security direct-with-normal-security direct-with-normal-security direct-with-normal-security direct-with-normal-security direct-with-normal-security direct-with-normal-security direct-with-normal-security direct-with-normal-security direct-with-normal-security

MV MV

Control Voltage Load Current (transformer secondary current)

M O

Unit: V Multiplier: none Unit: A Multiplier: none

Status Information Loc Auto SPS SPS Local operation Automatic Manual M O

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

23

3 Product description

OverV UnderV OverC MotDrv UInd1 UInd2 UInd3 UInd4 FuncMon ParErr Settings BndCtr BndWid CtlDlTmms LDCR LDCX BlkLV LimLodA LDC

SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS

Voltage high limit reached Voltage low limit reached Current overload Motor drive running User indication 1 User indication 2 User indication 3 User indication 4 Function monitoring Parameter error

E E E E E E E E E E

ASG ASG ING ASG ASG ASG ASG SPG

TmDlChr LDCZ

SPG SPG

TapBlkR

ING

TapBlkL

ING

Band center voltage (actual reference) Band width voltage (as percent of nominal voltage, FPF presumed) Control intentional time delay (FPF presumed, in seconds) Line drop voltage due to line resistance component (voltage) Line drop voltage due to line reactance component (voltage) Control voltage below which auto Lower commands blocked (relative) Limit Load Current (LTC Block Load Current, percentage) Line Drop Compensation is R and X or Z model (0=R and X, 1=Z compensation) Time delay linear or inverse characteristic (0=lin., 1=inv.) Line drop voltage due to line total impedance (percentage of nominal voltage) Tap position of Load Tap Changer where automatic Raise commands are blocked Tap position of Load Tap Changer where automatic

O O O O O O O O

Unit: V Multiplier: none Unit: none Multiplier: c

Unit: V Multiplier: none Unit: V Multiplier: none Unit: none Multiplier: c Unit: none Multiplier: c

O O Unit: none Multiplier: c

24

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

Lower commands are blocked


Table 6 IEC 61850 data points (ATCC - Voltage regulation)

3.2.4
GGIO class Attribute Name GGIO1

GGIO1 - IO card inputs

Attribute Type GPIO IO

Explanation

M/O/E

Remarks

Common Logical Node Information Mod Beh Health NamPlt Controls Measured values ENC INS INS LPL Mode Behaviour Health Name plate O M O O status-only 1:=OK; 3:=no internal communication

Status Information Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10 Settings Table 7

SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS

IO X1:31 IO X1:33 IO X1:16 IO X1:17 IO X1:14 IO X1:13 IO X1:11 IO X1:12 IO X1:29 IO X1:28

O O O O O O O O O O

IEC 61850 data points (GGIO1 - IO card inputs)

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

25

3 Product description

3.2.5
GGIO class Attribute Name GGIO2

GGIO2 - UC1 card inputs

Attribute Type

Explanation GPIO UC1

M/O/E

Remarks

Common Logical Node Information Mod Beh Health NamPlt Controls Measured values ENC INS INS LPL Mode Behaviour Health Name plate O M O O status-only 1:=OK; 3:=no internal communication

Status Information Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10 Settings Table 8

SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS

UC1 X1:11 UC1 X1:12 UC1 X1:14 UC1 X1:15 UC1 X1:16 UC1 X1:17 UC1 X1:30 UC1 X1:31 UC1 X1:32 UC1 X1:33

O O O O O O O O O O

IEC 61850 data points (GGIO2 - UC1 card inputs)

26

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

3.2.6
GGIO class Attribute Name GGIO3

GGIO3 - UC2 card inputs

Attribute Type

Explanation GPIO UC2

M/O/E

Remarks

Common Logical Node Information Mod Beh Health NamPlt Controls Measured values ENC INS INS LPL Mode Behaviour Health Name plate O M O O status-only 1:=OK; 3:=no internal communication

Status Information Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10 Settings Table 9

SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS

UC2 X1:11 UC2 X1:12 UC2 X1:14 UC2 X1:15 UC2 X1:16 UC2 X1:17 UC2 X1:30 UC2 X1:31 UC2 X1:32 UC2 X1:33

O O O O O O O O O O

IEC 61850 data points (GGIO3 - UC2 card inputs)

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

27

3 Product description

3.2.7
GGIO class Attribute Name GGIO4

GGIO4 - UC3 card inputs (optional)

Attribute Type

Explanation GPIO UC3

M/O/E

Remarks

Common Logical Node Information Mod Beh Health NamPlt Controls Measured values ENC INS INS LPL Mode Behaviour Health Name plate O M O O status-only 1:=OK; 3:=no internal communication

Status Information Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10 Settings Table 10

SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS

UC3 X1:11 UC3 X1:12 UC3 X1:14 UC3 X1:15 UC3 X1:16 UC3 X1:17 UC3 X1:30 UC3 X1:31 UC3 X1:32 UC3 X1:33

O O O O O O O O O O

IEC 61850 data points (GGIO4 - UC3 card inputs)

28

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

3.3

Operating modes
The voltage regulator can be operated in the following operating modes: AUTO/MANUAL In automatic mode (AUTO), the voltage is automatically controlled in accordance with the set parameters. The voltage regulator settings cannot be changed in automatic mode. In manual mode (MANUAL), no automatic control occurs. The motor-drive unit can be controlled via the voltage regulator's operating panel. The voltage regulator settings can be changed. LOCAL/REMOTE In remote mode (REMOTE), commands from an external control interface are executed. In this mode, manual operation of the RAISE, LOWER, MANUAL and AUTO keys is disabled.

3.4

Scope of delivery
The following items are included in the delivery: Scope of delivery Voltage regulator TAPCON 260 Technical files
Table 13 Scope of delivery

Please note the following: 1. 2. Use dispatch documents to check that the delivery is complete. Store the parts in a dry place until installation.

The functional range of the product is dependent on the equipment ordered or the product version and not on the content of this technical file.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

29

3 Product description

3.5

Hardware description
The individual assemblies are fitted in a standardized 19-inch plug-in housing. The front panels of the assemblies are secured to the plug-in housing at the top and bottom. An IEC 60603-2 plug connector provides the electrical connection. The assemblies are connected to one another via a data bus and separate direct current (DC) supply. This allows for an upgrade with additional plug-in units and extension cards at a later date. An LCD graphic display, LEDs and function keys are integrated in the front panel of the product.

Figure 2 1 2 3

Front view of device

19-inch plug-in housing (in accordance with DIN 41494 Part 5) Operating panel with display and LEDs Assembly for optional add-ons (e.g. TAPCON 240 LV)

30

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

3.5.1

Internal design
The device is controlled by a microregulator and includes isolated optocoupler inputs and floating output relay contacts in addition to the voltage and current transformers.

3.5.2
3.5.2.1

Communication Interfaces
Serial interface The parameters for the product can be set using a PC. The COM 1 (RS232) serial interface on the front panel is provided for this purpose. TAPCONtrol software is needed for parameterization. It can be obtained from the Download Center on the Maschinenfabrik Reinhausen website (www.reinhausen.com).

Figure 3 1 2 3

Voltage regulator connection to a PC.

PC with TAPCON -trol software Connection cable with RS232 / USB port Voltage regulator

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

31

3 Product description

3.5.2.2

SID card The SID interface card is used to connect the device to the control station system. The IEC 61850 protocol transfers the data. The diagram below shows the interfaces available and the operating and display elements on the SID card.

Figure 4 1 2 3 4

SID card

Reset key Status LED Interface for SIC card updates Ethernet RJ45

32

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

3.5.2.3

MC1 card The optional MC1 card is used to convert the SID card's electrical connection into a FH-ST type fiber-optic cable connection. In this case the wave length of the fiber-optic cable is 1300 nm. Terminals 1 and 2 on the MC1 card should be used to connect the voltage supply. Before commissioning, the TAPCON 260 connection diagrams should be checked. The diagram below shows the interfaces available and the operating and display elements on the MC1 card.

Figure 5 1 2 3

MC1 card

Terminal 1 and terminal 2 for the voltage supply Switch M/L ON/LINK TST Switch A/N ON/OFF

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

33

3 Product description

3.5.2.3.1

Technical Data Power supply Voltage Frequency Power consumption Insulation Temperature range Operation Transportation and storage 0...40 C -20...85 C 85~ V AC 110 V DC, 220 V DC 47...63 Hz approx. 6 W 4242 V DC

Requirement of the fiber-optic cable Connection type Fiber type Max. cable length Wave length Transmitted power (dBm) Received power (dBm)
Table 14

FH-ST Multimode 2 km 1310 nm Max. -14.0; typ. -16.8; min. -19.0 Min. rec. -31.8; typ. rec. -34.5; saturation -14.0

Technical data for MC1 card

3.5.2.3.2

Voltage supply connection The voltage is supplied via terminals 1 and 2 on the MC1 card. Terminal 1 2
Table 15

AC 85...264 V

DC 110/220 V GND

Voltage supply connection

34

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

3.5.2.3.3

Configuration The table below lists the positions and descriptions of the switches on the MC1 card. Switch MDI MDI-X A/N ON A/N OFF M/L ON LNK TST Description Switch position

When using a crossed or so-called Button not pressed patch cable between SID and MC1 card. 100 Mbit for TX and RX position in Button pressed "full duplex" or "half duplex" mode. If "M/L" (missing link) is activated, Button pressed an incorrect fiber-optic cable connection also indicates a fault with the electrical cable between the SID and MC1 card.
Positions and descriptions of the switches on the MC1 card

Table 16

3.5.2.3.4

LED status The MC1 card features various LEDs for displaying the current status. You will find an overview in the table below. LED PWR ON FDX LINK ACT M/L ON
Table 17

Status ON ON OFF ON ON ON OFF

Color Green Green Green Green Green

Description Supply created on MC1 card The connection operates in full duplex mode The connection operates in half duplex mode A connection has been established on the port Network traffic on port MissingLink is activated MissingLink is deactivated, the MC1 card operates in link test mode

LED status of MC1 card

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

35

3 Product description

3.6

Operation and indicator elements


The front of the voltage regulator is split into different areas for operating the device and displaying information. Below you can see an overview of the individual elements.

Figure 6 1 2 3 4 5 6

Voltage regulator operating panel

LEDs Keys for parameterization and configuration COM1 serial interface (RS232) Keys for operating the device Labeling strip for LEDs Setting options for display contrast

36

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

3.6.1

Operating concept
The voltage regulator's operating panel is split into an operation control level and a level for parameterization and configuration. The keys for operating the device are completely separate from those used for parameterization. At the operation control level, key activation is signaled visually by means of LEDs. The LEDs integrated in the RAISE/LOWER keys are illuminated during the entire tap change operation of the on-load tap-changer if "motor running" is signaled at the status input. This signal must have previously been parameterized. This visual monitoring option simplifies operation of the voltage regulator. The voltage regulator is equipped with a key lock to protect against unintentional operation. To activate or deactivate, press the ESC and F5 keys simultaneously.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

37

3 Product description

3.6.2

Description of the display

Figure 7 1 2 3 4 5 6 7 8 9 10

Main screen

Status line Measured voltage Vactual Reference voltage Vreference Other measured values (use Tap position (n-1, n, n+1) Bandwidth (upper and lower limit) Time bar for delay time T1 Highlighting for reference voltage Highlighting for measured voltage Remaining delay time T1 or to switch between them)

In auto and manual mode the measured value display can be set using the or keys. The following measured values can be displayed:

Control deviation (dV:) Current (I:)

38

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

Apparent power (Powr.:) Active power (P:) Reactive power (Q:) Phase angle (Phase:) Cosine (Cos:)

In the case of an event or a setting, the associated comments are displayed in the status line (display text "Messages").

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

39

3 Product description

3.6.3
Key RAISE

Description of key functions


Symbol Function In manual mode the motor-drive unit can be operated directly using the RAISE key. When RAISE is used, the motor-drive unit changes the on-load tap-changer and therefore the step voltage. In manual mode the motor-drive unit can be operated directly using the LOWER key. When LOWER is used, the motor-drive unit changes the on-load tap-changer and therefore the step voltage. Key without function. "Remote" operating mode is enabled or disabled via input IO-X1:31. Manual mode. For manual control of the motor-drive unit and parameterization of the voltage regulator. Auto mode. Voltage is controlled automatically. In auto and manual mode, the measured value display can be set using the arrow keys. They can also be used to switch between windows in the submenus. Confirms or saves a changed parameter in the parameter menu. Pressing the ESC key takes you to the menu level above, in other words, always back one menu level. Pressing this key displays the menu selection window. The function keys are menu selection keys. They are also used to scroll through the menu subgroups and input screens and to highlight decimal points which can be set by the user.

LOWER

REMOTE MANUAL AUTO Arrow keys NEXT/ PREV

ENTER ESC MENU F1-F5

The parameters can only be changed in manual mode, see table above.

key in the

40

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

3 Product description

3.6.4

Description of LEDs
The voltage regulator has 10 LEDs above the display. These indicate various operating statuses or events.

Figure 8 1 2 3 4 5 6 7 8 9 10

Description of LEDs Operating display Overcurrent blocking Undervoltage blocking Overvoltage blocking Parallel operation On NORMset On Freely configurable (LED1) Freely configurable (LED2) Freely configurable (LED3) Freely configurable (LED4)

Green Red Red Red Green Green Yellow Yellow Yellow Green/yellow/red

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

41

4 Packaging, Transport and Storage

Packaging, Transport and Storage

4.1
4.1.1

Packaging
Purpose
The packaging is designed to protect the packaged goods both during transport and for loading and unloading as well as during periods of storage in such a way that no (detrimental) changes occur. The packaging must protect the goods against permitted transport stresses such as vibration, knocks and moisture (rain, snow, condensation). The packaging also prevents undesired position changes of the packaged goods within the packaging during storage. The packaged goods must be prepared for shipment before actually being packed so that the goods can be transported safely, economically and in accordance with regulations.

4.1.2

Suitability, structure and production


The goods are packaged in a sturdy cardboard box. This ensures that the shipment remains in the intended transport position and that none of its components touches the load surface during transport or the floor after it is unloaded. The box is designed for a maximum load of 10 kg. Inlays inside the box stabilize the goods, preventing impermissible changes of position, and protect them from vibration.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

43

4 Packaging, Transport and Storage

4.1.3

Markings
The packaging bears a signature with symbols with instructions for safe transport and correct storage. The following symbols apply to the dispatch (of non-hazardous goods). Adherence to these symbols is mandatory.

Protect against moisture


Figure 9 Shipping pictograms

Top

Fragile

4.2

Transportation, receipt and handling of shipments


In addition to oscillation and shock stress, jolts must also be expected during transportation. In order to prevent possible damage, avoid dropping, tipping, knocking over and colliding with the product. If a crate falls from a particular height (e.g. when slings tear) or experiences an unbroken fall, damage must be expected regardless of the weight. Before acceptance, all deliveries must be checked by the recipient (acknowledgement of receipt) for the following: Completeness based on the delivery slip External damage of any type.

The checks must take place after unloading when the crate can be accessed from all sides. If external transport damage is detected on receipt of the shipment, proceed as follows: Immediately record the transport damage found in the shipping documents and have this countersigned by the carrier. In the event of severe damage, total loss or high damage costs, immediately notify the sales department at Maschinenfabrik Reinhausen and the relevant insurance company.

44

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

4 Packaging, Transport and Storage

After identifying the damage do not modify the condition of the shipment further and also retain the packaging material, until an inspection decision has been made by the transport company or the insurance company. Record the details of the damage immediately together with the carrier involved. This is essential for any claim for damages! If possible, photograph damage to packaging and packaged goods. This also applies to signs of corrosion on the packaged goods due to moisture inside the packaging (rain, snow, condensation). Name the damaged parts.

When damages are hidden, i.e. damages which are not determined until unpacking after the receipt of the shipment, proceed as follows: Make the party responsible for the damage liable as soon as possible by telephone and in writing, and prepare a damage report. Observe, in this regard, the time periods applicable to such actions in the respective country. Inquire about these in good time.

With hidden damage, it is very hard to make the transportation company (or other responsible party) liable. Any insurance claims for such damages can only be successful if relevant provisions are expressly included in the insurance terms and conditions.

4.3

Storage of shipments
Selection and arrangement of the storage location should meet the following requirements: Stored goods are protected against moisture (flooding, water from melting snow and ice), dirt, pests such as rats, mice, termites and so on, and against unauthorized access. Store the box on timber beams and planks as a protection against rising damp and for better ventilation. Carrying capacity of the ground under the goods is sufficient. Entrance and exit paths are kept free.

Check stored goods at regular intervals. Also take appropriate action after storms, heavy rain or snow and so on.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

45

5 Mounting

Mounting

5.1

Unpacking
The goods are packaged in a sturdy cardboard box. This ensures that the shipment remains in the intended transport position and that none of its components touches the load surface during transport or the floor after it is unloaded. Inlays inside the box stabilize the goods, preventing impermissible changes of position, and protect them from vibration. Unpack the voltage regulator as follows: 1. Remove the lid from the lower part of the cardboard box. The upper inlay contains the accessories supplied, the separate box labeled "Documentation" contains the device documents. 2. 3. 4. 5. 6. Check scope of supply for accessories. Take the box labeled "Documentation" out of the cardboard box. Remove the upper inlay from the packaging. The voltage regulator in the underlying inlay can now be freely accessed. Remove voltage regulator from the packaging.

The voltage regulator has been unpacked and can be mounted. For mounting, proceed as described in the Mounting section.

5.2

Mounting
After unpacking, the voltage regulator can be mounted. The voltage regulator's standardized plug-in housing is intended for fitting in a 19-inch control cabinet. We would recommend a design with a pivoting frame to allow easy access to the connections on the rear of the voltage regulator. The voltage regulator can be mounted in 4 different ways: Flush panel mounting 19" housing Flush panel mounting for half 19" housing Wall mounting for half 19" housing Wall mounting with terminal strip for half 19" housing

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

47

5 Mounting

5.3
5.3.1

Connection
Cable recommendation for standard connections
When wiring the voltage regulator, comply with the following recommendations from Maschinenfabrik Reinhausen.

Cable Power supply Voltage measurement Current measurement Relay* Relay* Signal inputs Signal inputs CAN bus
Table 18

Card SU MI/MI1 MI/MI1 IO

Terminal

Cable type

Wire diameter Max. length 2000 m

X1: 1/2 unshielded 1.5 mm 1/2 shielded 1.5 mm 5/6/9/10 unshielded 4 mm X1:1...10 unshielded 1.5 mm X1:19...26 UC X1:1...10 unshielded 1.5 mm IO X1:11...17 shielded 1.0 mm X1:27...34 UC X1:11...17 shielded 1.0 mm X1:27...34 CPU 1...5 shielded 1.0 mm * Observe notices (see below)

Recommendation for connection cable

NOTE Output relay malfunction Excessive electrical power can prevent the relay contacts from breaking the contact current. The effect of the cable capacitance of long control lines in control circuits operated with alternating current on the function of the relay contacts must be taken into account.

48

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

5 Mounting

5.3.2
Cable AC Analog inputs

Cable recommendation for optional connections


Card SU AD/AD 1 AN/AN 1 CIC CIC SID CIC MC1 Terminal X1/2:1/2 X1:1...3 X1 X8 X9 RJ45 X7 Cable type unshielded shielded shielded shielded shielded shielded, CAT 7 Optical fiber with MTRJ-ST duplex patch cable Wire diameter Max. length 1.5 mm 1.5 mm 1mm 0.25 mm 0.75 mm 400 m (< 25 /km) 25 m 1000 m (< 50 /km) 100 m -

Analog outputs RS-232 RS-485 Ethernet Media converter

Table 19

Recommendation for connection cable

5.3.3

Electromagnetic compatibility
The product was developed in compliance with the relevant EMC standards. To ensure compliance with the EMC standards, please note the following points.

5.3.3.1

Wiring requirement of installation site Note the following when selecting the installation site: The system's overvoltage protection must be effective. The system's ground connection must comply with all technical regulations. Separate system parts must be joined by a potential equalization. The voltage regulator and its wiring must be at least 10 m away from circuit-breakers, load disconnectors and busbars.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

49

5 Mounting

5.3.3.2

Wiring requirement of operating site Note the following when wiring the operating site: The connection cables must be laid in metallic cable ducts with a ground connection. Do not route lines which cause interference (e.g. power lines) and lines susceptible to interference (e.g. signal lines) in the same cable duct. Maintain a gap of at least 10 cm between lines causing interference and those susceptible to interference. Reserve lines must be grounded at both ends. The voltage regulator must never be connected using four-pin collective cables.

Figure 10 1 2 3 4

Recommended wiring

Cable duct for lines causing interference Interference-causing line (e.g. power line) Cable duct for lines susceptible to interference Line susceptible to interference (e.g. signal line)

50

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

5 Mounting

Signal lines must be routed in shielded cables. The individual conductors in the cable core (outgoing/return conductors) must be twisted in pairs. The shield must be fully (360) connected to the voltage regulator or a nearby ground rail.

Figure 11

Recommended shielding connection, do not extend the shield to the grounding point with a wire (pigtail).

NOTE Reduced effectiveness of the shielding. Using "pigtails" may considerably reduce the effectiveness of the shielding. Connect shield to cover all areas.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

51

5 Mounting

5.3.3.3

Wiring requirement in control cabinet Note the following when wiring the control cabinet: The control cabinet for fitting the voltage regulator must be prepared in accordance with EMC requirements: functional division of control cabinet (physical separation) constant potential equalization (all metal parts are joined) line routing in accordance with EMC requirements (separation of lines which cause interference and those susceptible to interference) optimum shielding (metal housing) overvoltage protection (lightning protection) collective grounding (main grounding rail) cable bushings in accordance with EMC requirements any protective inductors present must be interconnected The voltage regulator's connection cables must be laid in contact with the grounded metal housing or in metallic cable ducts with a ground connection. Signal and power/switching lines should be laid in separate cable ducts.

52

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

5 Mounting

The voltage regulator must be grounded at the screw provided using a ground strap (cross-section min. 8 mm). The voltage regulator's ground connection is a functional ground and serves to dissipate interfering currents.

Figure 12

Ground strap connection

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

53

5 Mounting

5.3.3.4

Information about shielding the CAN bus To ensure that the CAN bus operates correctly, the shielding must be connected as detailed for the following variants. Both voltage regulators share the same potential To ensure potential equalization between the voltage regulators, all voltage regulators must be connected to the same potential equalization rail. If the voltage regulators share the same potential, the CAN bus cable's shielding must be connected to both voltage regulators. Both voltage regulators have different potentials If the voltage regulators have different potentials, the CAN bus cable's shielding may only be connected to one voltage regulator. Note that the effectiveness of the shielding is less than if connected to both voltage regulators. NOTE Damage to the voltage regulator If the CAN bus cable's shielding is connected to 2 voltage regulators with different potentials, current may flow over the shielding. This current may damage the communication cards. Ensure that the CAN bus cable's shielding is only connected to one voltage regulator if both voltage regulators have different potentials. If neither connection variant is possible, we would recommend using fiber optic cables. Fiber optic cables decouple the voltage regulators and are not sensitive to electromagnetic interferences (surge and burst).

54

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

5 Mounting

Connecting the shielding The CAN bus cable's shielding must be secured to the intended point on the housing using the cable clips provided (see diagram below).

Figure 13

Securing the CAN bus cable's shielding to the intended point on the housing

Securing the CAN bus cable's shielding

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

55

5 Mounting

5.3.4

Connecting lines to the system periphery


Connect the lines, which are to be wired with the voltage regulator, to the system periphery, as shown in the connection diagrams supplied. WARNING! Electric shock Connection mistakes may endanger life Earth the voltage regulator using the grounding screw attached to the housing. Pay attention to the phase difference of the secondary terminals for the current and voltage transformers. Connect the output relays correctly to the motor-drive unit. NOTE Damages to the voltage regulator and system periphery An incorrectly connected voltage regulator can lead to damages in the monitoring system and system periphery. Prior to commissioning, be sure to check the entire configuration and the measuring and operating voltage.

To obtain a better overview when connecting cables, only use as many leads as necessary.

Use only the specified cables for connection. You will find a cable recommendation in the corresponding section (see "Cable recommendation for standard connections" on page 54). The voltage regulator is fully connected and can be wired up. To carry out the wiring, proceed as described in the Wiring (see "Wiring the voltage regulator" on page 63) section.

56

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

5 Mounting

5.3.5

Voltage regulator power supply


In the standard design, the voltage regulator is supplied with power via a multi-voltage mains unit. The permissible supply voltage is 93...265 V AC, DC. Alternatively the voltage regulator can be supplied with a supply mains unit for the 18...36 V DC or 36...72 V DC range.

5.3.6

Wiring the voltage regulator


Wire the voltage regulator as shown in the connection diagram. WARNING! Electric shock Connection mistakes may endanger life Earth the voltage regulator using the grounding screw attached to the housing. Pay attention to the phase difference of the secondary terminals for the current and voltage transformers. Connect the output relays correctly to the motor-drive unit. NOTE Damages to the voltage regulator and system periphery An incorrectly connected voltage regulator can lead to damages in the monitoring system and system periphery. Prior to commissioning, be sure to check the entire configuration and the measuring and operating voltage.

To obtain a better overview when connecting cables, only use as many leads as necessary.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

57

5 Mounting

5.4

Function check
Carry out a function check to test that the voltage regulator is wired correctly. Check the following: After being switched on, the screen displays the MR logo and then a voltage value. The green "Operating display" LED in the top left on the voltage regulator lights up.

The voltage regulator can now be configured. The actions required for this are described in the following chapter (see "Commissioning" on page 65).

58

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

6 Commissioning

Commissioning
Several parameters need to be set and function tests performed before commissioning the device. These are described in the following chapter.

6.1

Configuration
The relevant settings for commissioning are described in more detail in the following sections. A detailed description of the functions can be found in the associated operating instructions.

6.1.1

Setting the language


The display language can be set or changed as desired. The following languages are available: 1. English German French Spanish Italian Portuguese > Configuration > <00> Language. or General.

2. Press language. 3. Press .

to select the required

The language is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

59

6 Commissioning

6.1.2

Selecting the control mode


The voltage regulator can be commissioned in NORMset mode or manually. Instead of parameterizing the voltage regulator manually, the NORMset mode enables easy and user-friendly commissioning of the voltage regulator with a limited set of parameters. When this mode is selected, the factory settings for voltage regulation are accepted. NOTE Damages to the voltage regulator and system periphery An incorrectly connected voltage regulator can lead to damages in the monitoring system and system periphery. Prior to commissioning, be sure to check the entire configuration and the measuring and operating voltage.

We recommend using a registration device to record the transformer voltage (actual value) in order to evaluate how the voltage regulator is functioning.

1. 2. 3. 4. 5. 6.

Press

to select manual mode.

Select the NORMset mode. Set desired value 1. Set the primary voltage. Set the secondary voltage. Execute one tap-change operation manually.

When these parameters have been set, the regulator is ready to operate. The compensation settings cannot be carried out in NORMset mode. The desired value will be compared with the measured voltage on the voltage regulator. The actual value display can be set in V (voltage transformer secondary voltage) or kV (voltage transformer primary voltage) depending on the setting.

60

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

6 Commissioning

6.1.3

Controlling remote tap position indicator with BCD signal


The voltage regulator is equipped with a digital tap position indicator. The indicator is controlled as standard with a BCD signal or optionally with an analog signal. The tap position indicator signal must be converted into and transferred in BCD code if the digital remote tap position indicator is to function. The following is necessary in the motor-drive unit: a resistor contact series a downstream diode matrix the corresponding transfer lines between motor-drive unit and voltage regulator

Figure 14

BCD signal transfer between motor-drive unit and voltage regulator

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

61

6 Commissioning

1 2 3 4

Resistor contact series Diode matrix Transfer line Voltage regulator

Thanks to the diode matrix's linking function, the relevant parallel BCD signal is assigned to every on-load tap-changer operating position which is reproduced by the motor-drive unit's resistor contact series. BCD signal Operating position 10 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Table 20

8 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1

4 0 0 0 1 1 1 1 0 0 0 1 0 0 1 1 1 1 0 0

2 0 1 1 0 0 1 1 0 0 0 0 1 1 0 0 1 1 0 0

1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1

0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1

BCD code table for operating positions

62

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

6 Commissioning

6.2

Function tests
Before switching the voltage regulator from manual to automatic mode and therefore activating the automatic voltage regulation for your system, Maschinenfabrik Reinhausen recommends carrying out function tests. These function tests are described in the following sections. HINWEIS Schden an Spannungsregler und Anlagenperipherie Ein unsachgem angeschlossener Spannungsregler kann zu Schden an Spannungsregler und Anlagenperipherie fhren. Kontrollieren Sie vor Inbetriebnahme die Gesamtschaltung sowie Ist- und Betriebsspannung.

We recommend using a registration device to record the transformer voltage (actual value) in order to evaluate how the voltage regulator is functioning.

6.2.1

Function tests for control functions


The on-load tap-changer can only be controlled in manual mode using the or keys.

1. 2. 3. 4.

Establish supply voltage Press to select manual mode.

Set transformation ratios for voltage and current transformers and measuring set-up. Measure actual voltage and compare with that displayed by the voltage regulator. several times to display the operating values for current, Press output and phase angle. Compare operating values with operating measurement devices.

5. 6.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

63

6 Commissioning

7. 8. 9.

To set the desired value, manually control the on-load tap-changer until the desired voltage value is reached. Set desired voltage value Vdesired to this value. Set bandwidth "B %" depending on step voltage. Vn-1 Un [B % ] 0.6 Vnominal 100 %

10. Set switch time delay T1 to 20 s and control response to T1 linearly. 11. Press 12. Press to raise the on-load tap-changer 1 step. to select automatic mode.

After 20 s, the voltage regulator returns the on-load tap-changer to the


original operating position. 13. Press 14. Press to select manual mode. to lower the on-load tap-changer 1 step.

15. Activate the time delay T2 and set it to 10s. 16. Press 17. Press twice to raise the on-load tap-changer 2 steps. to select automatic mode.

After 20 s, the voltage regulator lowers the on-load tap-changer one


step and after another 10 seconds another step. to select manual mode. 18. Press

19. Set the delay times T1 and T2 to the desired values. If T2 is not used, it must be set to "OFF". We recommend a temporary setting of 100 seconds for the delay time T1 when commissioning the transformer. Depending on the operating conditions, you can also specify the delay time following a longer observation period. In this regard, it is useful to register the actual voltage process and the number of tap-change operations per day. If you wish the voltage regulator to exhibit an integral time response, set an integral control response for time delay T1. The greater the control deviation, the shorter the delay time.

64

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

6 Commissioning

6.2.2

Function tests for additional functions


The on-load tap-changer can only be controlled in manual mode using the or keys.

Checking and setting undervoltage blocking V< 1. 2. 3. Press to select manual mode.

Set the undervoltage blocking V< to 85 %. The desired voltage value should be adjusted such that the actual voltage is below the undervoltage blocking V<. Example: Actual voltage = 100 V, set desired value to a value greater than 100 V / 0.85 = 117 V.

The undervoltage V< LED will light up. After around 10 seconds the undervoltage message appears and the
signaling relay is activated. Contact IO-X1:18/19 opens and contact IO-X1:18/20 closes. to select automatic mode.

4.

Press

The regulator is blocked and does not therefore issue any control
commands. 5. 6. Press to select manual mode.

Set the operating values you want for desired value and undervoltage blocking.

Checking and setting overvoltage detection V> 1. 2. 3. Press to select manual mode.

Set overvoltage detection V> to 115 %. The desired voltage value should be adjusted such that the actual voltage is above the overvoltage detection V>. Example: Actual voltage = 100 V, set desired value to a value less than 100 V / 1.15 = 87 V.

The overvoltage V> LED will light up.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

65

6 Commissioning

The overvoltage message appears and the signaling relay is acti4. Press to select automatic mode.

vated. Contact IO-X1:18/19 opens and contact IO-X1:18/20 closes.

The LOWER output relay periodically emits a control command at approx. 1.5 s intervals. 5. 6. Press to select manual mode.

Set the operating values you want for desired value and overvoltage detection.

Set overcurrent blocking I> (and optionally undercurrent blocking I<). 1. Set overcurrent blocking I> (optionally undercurrent blocking I<) to the desired value. A function test is not necessary. Checking and setting activation of desired value 2 and desired value 3 1. 2. 3. Set desired value 2 to the value you want. Press to select manual mode.

Apply voltage L+ to terminal X4:17 (X4:17 = default setting).

Desired value 2 is shown on the main screen.


4. 5. 6. Set desired value 3 to the value you want. Press to select manual mode.

Apply voltage L+ to terminal X4:18 (X4:18 = default setting).

Desired value 3 is shown on the main screen.


7. Press to select automatic mode.

Checking and setting line drop compensation (LDC) A load current of 10 % of the nominal transformer current is needed for the following function tests in order to better detect the effects of control deviation.

Before you can check Z compensation, you must use the control system (IEC 61850) to check that the value of the LDC attribute in the ATCC node is 0.

66

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

6 Commissioning

1. 2. 3.

Press

to select manual mode.

Set parameters for line drop compensation and Z compensation to 0. Select the control deviation (dV) display on the main screen (press if necessary).

The measured voltage must be within the bandwidth.


4. Set line drop compensation "Vr line drop comp." to 20.0V.

The control deviation dV must be negative.


5. Set line drop compensation "Vr line drop comp." to -20.0V.

The control deviation dV must be positive.


If the control deviation appears in the opposite direction, change the polarity of the current transformer.

6.

Set line drop compensation "Vr line drop comp." to the operating value you want.

Checking and setting Z compensation Before you can check Z compensation, you must use the control system (IEC 61850) to check that the value of the LDC attribute in the ATCC node is 1.

1. 2. 3.

Press

to select manual mode.

Set parameters for line drop compensation and Z compensation to 0. Select the control deviation (dV) display on the main screen (press if necessary).

The measured voltage must be within the bandwidth.


4. Set the "Z compensation" and "Z comp. limit value" parameters to 15 %.

The control deviation dV must be negative.


If the control deviation appears in the opposite direction, change the polarity of the current transformer.

5.

Set the "Z compensation" and "Z comp. limit value" parameters to the operating values you want.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

67

6 Commissioning

Installation of the voltage regulator is now complete and it is commissioned for simplex mode. During operation, note the operating instructions provided. If the voltage regulator is to be used for parallel operation, then continue to the next section.

6.2.3

Function tests for parallel operation


To obtain perfect functioning in parallel operation, the voltage regulator must be commissioned in simplex mode. Make sure that the conditions below have been fulfilled.

All voltage regulators are set to the same operating parameters for voltage value, sensitivity and delay time T1. Set the circulating reactive current sensitivity to 0 % and the circulating reactive current blocking to 20 % (see operating instructions) for all voltage regulators. All settings should be undertaken in manual mode. Give each voltage regulator an individual address on the CAN bus (see operating instructions). 6.2.3.1 Function tests in accordance with the circulating reactive current method The following sections describe how to carry out function tests for parallel operation in accordance with the circulating reactive current method. 6.2.3.1.1 Setting circulating reactive current sensitivity 1. Adjust both transformers in simplex mode to the same voltage by means of the on-load tap-changer.

When both voltage regulators are in a state of equilibrium, then the


2. Connect the transformers in parallel and enable the parallel control.

value of the control deviation "dV [%]" is smaller than the set bandwidth "B %" and the time bar is not filled.

The two voltage regulators must still be in a state of equilibrium. The "Parallel operation" LED on the front panel is illuminated.
3. Switch one of the two transformers up one voltage step and the other transformer down one voltage step.

The two voltage regulators must still be in a state of equilibrium.

68

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

6 Commissioning

4.

Adjust the "circulating reactive current sensitivity" until the result displayed exceeds the set value for the bandwidth by approx. 0.2 % to 0.3 %.

The value for the result changes in the help text in the last line of the
display. 5. 6. Set the value given in step 4 for all voltage regulators in parallel operation. Select the AUTO operating mode for both voltage regulators.

The voltage regulators return the on-load tap-changers to the earlier


operating positions. If the earlier operating positions are not reached, then the "circulating reactive current sensitivity" should be increased. If the on-load tap-changers pass each other, then the "circulating reactive current sensitivity" should be reduced. After the parameter "circulating reactive current sensitivity" has been set, continue by setting the circulating reactive current blocking (see "Setting circulating reactive current blocking" on page 75). 6.2.3.1.2 Setting circulating reactive current blocking 1. 2. Press on 1 voltage regulator to select manual mode.

Using manual control, adjust the relevant motor-drive unit upwards (e.g. 1 - 2 steps) by the maximum permitted difference in operating positions between the parallel operating transformers.

When setting the circulating reactive current blocking in the following process step, wait approx. 2 to 3 seconds between the individual steps.

3.

From the set value of 20 %, reduce the circulating reactive current blocking in 1% intervals until the message "Parallel operation error: circulating reactive current limit exceeded" appears.

The LED lights up when the circulating reactive current blocking limit
is reached.

The voltage regulators block any further regulation. After 30 seconds (time adjustable) the signaling relay X5:12 (X5:12 =
default setting) responds. 4. Increase the circulating reactive current blocking again until the message "Parallel operation error: circulating reactive current limit exceeded" disappears.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

69

6 Commissioning

5.

Press position.

to select automatic mode.

The motor-drive unit is automatically returned to the original operating


6. Set the value determined for the circulating reactive current blocking on the other regulators as well.

If one or all voltage regulators indicate "Parallel operation error: circulating reactive current limit exceeded" although the control inputs are correctly connected for all the voltage regulators, then all the voltage regulators block. This could be due to various causes. Further information is given in the chapter "Troubleshooting" in the operating instructions.

6.2.3.2

Function tests in accordance with tap synchronization (master/follower/auto) The following sections describe how to carry out function tests for parallel operation in accordance with the master/follower tap synchronization method. Before starting the function test carry out the following steps: Select the relevant method and assign the master function to a voltage regulator. Assign the follower function to the other voltage regulators. Check the tap position display. The master and follower must be in the same step.

The function test can now be started.


1. 2. 3. Set the tapping direction. Set master to manual mode and proceed manually. Set follower to automatic mode.

The follower must follow the master control command.


4. 5. 6. Set master to AUTO mode. Set follower to MANUAL mode. Change follower by one step manually.

After expiry of the set delay time for parallel operation errors, the error
message "Tap difference to follower" appears on the master. 7. Set follower to AUTO mode.

70

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

6 Commissioning

The follower must follow the master control command.


8. 9. Set master to AUTO mode. Set follower to MANUAL mode.

10. Change the follower manually by the maximum permitted tap difference +1.

After expiry of the set delay time for parallel operation errors, the error
message "Parallel operation error: permitted tap difference to master exceeded" appears on the follower AND the error message "Parallel operation error: tap difference to follower" appears on the master.

11. Set follower to AUTO mode.

There is no response. All regulators remain blocked.


12. Set master and follower to MANUAL mode and adjust manually to the target step. Since, in parallel operation, the tap positions of the transformers which are running in parallel with one another are compared using the "automatic tap synchronization" method, it is absolutely essential that these transformers share the same position designation and that the "Raise" or "Lower" signals produce the same voltage change in all transformers. If instances arise where the follower voltage regulator(s) switch(es) in the opposite direction from the master voltage regulator step change, then the setting for the follower parameter must be changed from "Default" to "Swapped". The voltage regulator is now completely installed and commissioned. During operation, note the operating instructions provided.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

71

7 Functions and settings

Functions and settings


This chapter describes all the functions and setting options for the voltage regulator. The setting values appear in the relevant sections or in summary in a table. The chapters are laid out following the menu structure of the device. The voltage regulator functions are set using the keys on the device. Settings can only be carried out in manual mode (MANUAL) with the key lock deactivated. The procedure for activating or deactivating the key lock is described in the following sections.

7.1

Key lock
The voltage regulator is equipped with a key lock to protect against unintentional operation. Parameters can only be carried out in manual mode (MANUAL) with a deactivated key lock.

7.1.1

Activating key lock


To activate the key lock, proceed as follows: Press and at the same time.

A confirmation (see diagram) appears on screen for a short period. The key lock is activated. Parameters can no longer be entered.

7.1.2

Deactivating key lock


To deactivate the key lock, proceed as follows: Press and at the same time.

The key lock is deactivated. Parameters can be entered.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

73

7 Functions and settings

7.2

NORMset
As an alternative to parameterizing the voltage regulator manually, the NORMset mode enables easy commissioning of the voltage regulator with a limited set of parameters. When this mode is selected, the factory settings required for voltage regulation are adopted. When commissioning the voltage regulator in NORMset mode, the following parameters must be set: Desired value 1 Primary voltage Secondary voltage

When these 3 parameters have been set, the voltage regulator is ready to operate. Once NORMset has been activated, no additional settings can be undertaken for line drop compensation.

The desired value is compared with the measured voltage present on the voltage regulator depending on the unit defined, i.e. V (secondary voltage of voltage transformer) or kV (primary voltage of voltage transformer). If additional information on current and phase angle are required, connect the current transformer and adjust the current connection data (see "Setting the current transformer connection" on page 133). After the desired voltage level and voltage transformer data have been entered, if NORMset is activated the voltage regulator checks the grid conditions and automatically adapts other settings, composed partly of predefined parameters and default values. All other parameters required for simple voltage regulation are predefined in the factory. The procedure for activating or deactivating NORMset mode is described in the following sections. A manual tap-change operation is required once NORMset has been activated. This is how the voltage regulator determines the bandwidth required. If the transformer has been switched off, another manual tap-change operation is required.

74

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

If NORMset is activated, the bandwidth and delay time settings will be undertaken automatically by the voltage regulator. The following control parameters must be set in NORMset mode: Desired value 1 Primary voltage Secondary voltage The following parameters are not set automatically using the NORMset mode: Undervoltage limit Overvoltage limit Undercurrent limit Overcurrent limit If required, these parameters must be set manually.

1.

> Normset. <00> Normset activation. or to

2. To activate Normset, press select "On" . 3. Press .

or to perform a 4. Press manual tap-change operation. The LED for the NORMset operating display lights up. The NORMset mode is activated.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

75

7 Functions and settings

7.2.1

Entering NORMset desired value 1


Desired values set in kV apply to the primary voltage of the connected voltage transformer. Desired values set in V apply to the secondary voltage of the connected voltage transformer. All transformer data (see "Transformer data" on page 129) must be entered correctly. Settings in kV are only possible if you have previously entered the parameters for primary and secondary voltage.

Setting range 49 V 140 V


Table 21

Step size 0.1 V

Factory setting 100 V

Setting range for NORMset desired value 1 in V

Setting range 0 kV...9999 kV 0 kV...999.9 kV 0 kV...99.99 kV


Table 22

Step size 1 kV 0.1 kV 0.01 kV

Factory setting 1 kV

Setting range for NORMset desired value 1 in kV

To set desired voltage value 1, proceed as follows: 1. > Normset > 1x <01> Desired value 1. .

to highlight a digit. 2. Press The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to

Desired value 1 is set.

76

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.2.2

Setting the primary voltage


In general, the regulator only indicates the secondary voltage in V if you have not set the primary voltage. The primary voltage is only displayed if parameter "Display kV / V" has been set to kV (see "Setting the voltage display kV/V" on page 141). Example: Primary voltage No parameterization 110 kV
Table 23

Secondary voltage 100 V 100 V

kV or V V kV

Display 100 V 110 kV

Example of displayed values in V or kV

Setting range 0 kV...9999 kV 0 kV...999.9 kV 0 kV...99.99 kV


Table 24

Step size 1 kV 0.1 kV 0.01 kV

Factory setting 0 kV

Setting range for primary voltage in kV

To set the primary voltage, proceed as follows: 1. > Normset > 2x .

<02> Primary voltage. 2. Press to highlight the decimal place.

The decimal place is defined and the value can be changed. to highlight a digit. 3. Press The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to

The primary voltage is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

77

7 Functions and settings

7.2.3

Setting the secondary voltage


The secondary voltage is displayed and entered in V. Setting range 57 V 125 V
Table 25

Step size 0.1 V

Factory setting 100 V

Setting range for secondary voltage in V

To set the secondary voltage, proceed as follows: 1. > Normset > 3x <03> Secondary voltage. .

2. If necessary Press cimal place.

to highlight the de-

The decimal place is defined and the value can be changed. to highlight a digit. 3. Press The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to

The secondary voltage is set.

78

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3

Parameters
This section describes all the functions, parameters and recommended setting ranges for voltage regulation with the voltage regulator. To make it easier for you to find specific parameters, the description refers to subgroups of individual parameters with related functions.

7.3.1

Setting control parameters


This submenu contains all the parameters required for the control function. Desired values 1/2/3 Bandwidth Delay time T1 Control response T1 Delay time T2

The desired voltage level, Vtarget is specified as a fixed value. The desired value can be entered using the voltage regulator user interface, both in the NORMset mode subgroup and in the parameter mode subgroup. In addition, the voltage regulator also allows you to change the desired value during operation if this is necessary. The desired values are activated using binary inputs. Up to 3 desired values can be entered in parameter mode: Desired value 1 Desired value 2 Desired value 3

Desired value 1 is the default desired value.Desired values 2 or 3 are activated if there is a continuous signal at the pre-assigned IO-X1/17 or IO-X1/16 inputs (factory preset).If there is a signal at both inputs at the same time, desired value 2 is active. The following sections describe how to set the desired values.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

79

7 Functions and settings

7.3.2

Setting desired value 1


Desired values set in kV apply to the primary voltage of the voltage transformer. Desired values set in V apply to the secondary voltage of the voltage transformer. The transformer data (see "Transformer data" on page 129) must be entered correctly. Setting range 49 V 140 V
Table 26

Step size 0.1 V

Factory setting 100 V

Setting range for desired value 1 in V

Setting range 0.1 kV...999.9 kV 0.1 kV...99.9 kV 0.1 kV...99.99 kV


Table 27

Step size 1 kV 0.1 kV 0.01 kV

Factory setting 1kV

Setting range for desired voltage value 1 in kV

To set desired voltage value 1, proceed as follows: 1. > rameter. Parameter > Control pa-

<00> Desired value 1. 2. If you have already entered the transformer data, press "V" or "kV". to highlight a digit. 3. Press The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to to select the unit you want:

Desired value 1 is set.

80

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.3

Setting desired value 2


Desired value 2 is activated if there is a continuous signal at IO X1/17 or IO-X1/16 provided you previously programmed the IOs accordingly (on page 146). Setting range 49 V 140 V
Table 28

Step size 1V

Factory setting 100 V

Setting range for desired value 2 in V

Setting range 0.1 kV...999.9 kV 0.1 kV...999.9 kV 0.1 kV...99.99 kV


Table 29

Step size 1 kV 0.1 kV 0.01 kV

Factory setting 1 kV

Setting range for desired voltage value 2 in kV

To set desired voltage value 2, proceed as follows: 1. > Parameter > Control pa-

. rameter > 1x <01> Desired value 2 2. If you have already entered the transformer data, press "V" or "kV". to highlight a digit. 3. Press The digit position you want is highlighted and the value can be changed. 4. Press reduce it.. 5. Press . to increase the value or to to select the unit you want:

Desired value 2 is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

81

7 Functions and settings

7.3.4

Setting desired value 3


Desired value 3 is activated if there is a continuous signal at IO X1/17 or IO-X1/16 provided you previously programmed the IOs accordingly (see "Configuring control inputs IO1-X1:33/31" on page 145). Setting range 49 V 140 V
Table 30

Step size 1V

Factory setting 100 V

Setting range for desired value 3 in V

Setting range 0 kV...999.9 kV 0 kV...999.9 kV 0 kV...99.99 kV


Table 31

Step size 1 kV 0.1 kV 0.01 kV

Factory setting 1 kV

Setting range for desired voltage value 3 in kV

To set desired value 3, proceed as follows: 1. > rameter. > 2x . <02> Desired value 3. 2. If you have already entered the transformer data, press "V" or "kV". to highlight a digit. 3. Press The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to to select the unit you want: Parameter > Control pa-

Desired value 3 is set.

82

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.5

Bandwidth
The bandwidth is the permitted deviation of the measured voltage from the selected desired value. If the measured voltage is inside the bandwidth, then no control commands are issued to the on-load tap-changer. If the measured voltage deviates from the specified bandwidth, a tap-change command occurs after the set delay time T1. The on-load tap-changer carries out a tap-change in a positive or negative direction. If the level is persistently above or below the bandwidth, the "Function monitoring" alarm message is triggered after 15 minutes. The corresponding relay is also activated. The alarm message is only reset when the measured voltage returns to within the set.

Figure 15

Measured voltage and bandwidth over time

1 2 3 4 5 a b c d e

Vstep: Step voltage Vdesired: Desired value in V B%: Bandwidth range T1: Set delay time Vactual: Measured voltage Vactual outside the bandwidth, T1 starts Vactual within bandwidth before T1 lapses, no tap-change operation Vactual outside the bandwidth, T1 starts Vactual outside B% before T1 lapses, tap-change operation initiated Tap-change operation complete, Vactual within the bandwidth

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

83

7 Functions and settings

7.3.5.1

Visual display The deviation from the set bandwidth is shown visually in the voltage regulator display. The measured voltage mark shows whether the measured voltage is above, inside or below the set bandwidth. Progress of delay time T1 is indicated by the gradual filling of the time bar in the voltage regulator's display. The seconds display above this indicates the remaining delay time T1.

Figure 16

Visual display of deviation from desired value

1 2 3 4 5 7.3.5.2

Bandwidth (upper and lower limit) Time bar for delay time T1 Desired voltage value Measured voltage Remaining delay time T1

Determining bandwidth In order to be able to set the value correctly, the transformer's step voltage and nominal voltage must be known. The following value is recommended for the bandwidth "B %": Vn-1 Un [B % ] 0.6 Vnominal 100 %

84

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

where: Vn-1: Vn: Vnominal Step voltage of position n-1 Step voltage of position n Nominal voltage

The bandwidth must be selected in such a way that the output voltage of the transformer (Vactual) returns to within the specified tolerance range after the tap change. If too small a bandwidth is defined, the output voltage exceeds the bandwidth selected and the voltage regulator must immediately issue a tap-change command in the opposite direction. If a very large bandwidth is selected, this results in a major control deviation. Sample calculation The following transformer parameters are used by way of example for determining the recommended bandwidth: Nominal voltage: Step voltage of position 4: Step voltage of position 5: Vnominal = 11000 V Vstep4 = 11275 V Vstep5 = 11000 V

Following the recommendation for calculating bandwidth, our example results in: UStep4UStep5 [B % ]0.6 Vnominal 11275 V11000 V [B % ]0.6 11000 V 100 % 100 %

[B % ]1.5 %

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

85

7 Functions and settings

7.3.5.3

Setting the bandwidth Setting range 0.5 %...9 %


Table 32

Step size 0.01 %...1 %

Factory setting 1%

Setting range for bandwidth

The calculated bandwidth is entered as follows: 1. > rameter > 3x Parameter > . Control pa-

<03> Bandwidth. to highlight a digit. 2. Press The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to

The bandwidth is set.

86

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.6

Setting delay time T1


Delay time T1 delays the issuing of a tap-change command for a defined period. This function prevents unnecessary tap-change operations if the tolerance bandwidth is exited for a short time. If the current measured voltage leaves the bandwidth, delay time T1 starts. This is shown visually in the display by the time bar filling and the remaining time being indicated. If the control deviation is still present after the delay time, a tap-change command is issued. If during the delay time the measured voltage returns to within the bandwidth range, the delay time still running is counted down in seconds starting from the time already expired. The absolute time display disappears from the display. The time bar graph is shown hatched and shrinks steadily. If the measured voltage exceeds the set bandwidth once more whilst the time is not displayed, then the time delay is restarted from the remaining time. The advantage of counting the time back down is that, if the bandwidth is exceeded frequently, the voltage regulator does not start counting again at 0 seconds, but uses the time already elapsed as the starting point for beginning the next delay time.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

87

7 Functions and settings

Setting range 0 s...600 s


Table 33

Step size 1s

Factory setting 40 s

Setting range for delay time T1

To set the delay time T1, proceed as follows: 1. > rameter > 4x Parameter > . Control pa-

<04> Delay time T1. 2. Press to highlight a digit.

The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the time or to

The delay time T1 is set.

88

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.7

Setting control response T1


The delay time T1 can be set to linear or integral. With "Linear time" the voltage regulator responds with a constant delay time which is independent of the control deviation. If "Integral time" is set, the delay time decreases depending on the ratio of current control deviation to set bandwidth B, to a minimum of 1 second. The greater the control deviation (V) the shorter the response time. This means that the voltage regulator reacts faster to unexpectedly large voltage changes in the grid. The regulation accuracy therefore increases at the expense of switching frequency (see diagram).

Figure 17 1

V/B voltage change

"Delay time T1" parameter

V/B: Control deviation "V" as % of desired value as ratio to the set bandwidth "B" as % of desired value.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

89

7 Functions and settings

To set the control response T1, proceed as follows: 1. > Parameter > Control pa-

. rameter > 5x <05> Control response T1. 2. Press to select "T1 linear" or to

select "T1 integral". 3. Press .

The control response T1 is set.

7.3.8

Activating/deactivating delay time T2


The delay time T2 only takes effect if more than one tap-change operation is required for returning the voltage to within the specified bandwidth.With integral control response in particular, the time until release of an output pulse would increase after each tap change process. The first output pulse occurs after the set delay time T1. After the set delay time T2 has elapsed, additional pulses occur. These are needed to correct the existing control deviation. To activate/deactivate the delay time T2, proceed as follows: 1. > Parameter > . Control pa-

rameters > 6x

<06> T2 activation. 2. Press 3. Press . or to activate/deactivate T2.

The delay time T2 is activated/deactivated.

90

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.9

Setting delay time T2


The following section describes how to set the delay time T2. Setting range 1 s...10 s
Table 34

Step size 0.1 s

Factory setting 10 s

Setting range for delay time T2

In general, the delay time T2 should be greater than the pulse duration and the maximum operating time of the motor-drive unit. This applies to continuous settings in particular.

To set the delay time T2, proceed as follows: 1. > rameter > 7x Parameter > . Control pa-

<07> Delay time T2. 2. Press reduce it. 3. Press . to increase the time or to

The delay time T2 is set.

7.3.10

Limit values
This subgroup contains all the parameters required for monitoring the limit values. The limit values can be set as percentages or absolute values. For the "undervoltage" and "overvoltage" parameters, the inputs basically relate to the specified desired value. For "overcurrent" and "undercurrent", the values relate to the set rated current of the current transformer or the selected current transformer connection, respectively.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

91

7 Functions and settings

7.3.10.1

Activating/deactivating absolute limit values When you activate absolute limit values, these are used in place of those relating to the desired value. The following settings are possible: Setting Off On
Table 35

Effect The percentage values entered are used The absolute values entered are used
Activation/deactivation of absolute limit values

To activate/deactivate the absolute limit values, proceed as follows: 1. > Parameter > Limit values. <00> Absolute limit values. for "On" setting or for "Off"

2. Press setting. 3. Press .

The absolute limit value is activated/deactivated. 7.3.10.2 Setting the undervoltage V< limit value Undervoltage blocking prevents tap-change operations if there is a power cut. The voltage regulator output pulses are blocked and the red "V<" LED lights up as soon as the measured voltage falls below the set blocking value.

92

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

If the measured voltage falls below the set limit value, the signaling relay is permanently activated after around 10 seconds (IO-X1/18, IO-X1/19, IO-X1/20 contacts). If the measured voltage and/or supply voltage fails (< 30 V), the signaling relay is not activated. This function is a default setting and you can deactivate it (see "Activating/deactivating signal for undervoltage V< below 30 V" on page 106). The limit value for undervoltage blocking is set as a percentage of the set desired value. Setting range 60 %...100 % of desired value
Table 36

Step size 1%

Factory setting 90 %

Setting range for undervoltage blocking V< as percentage

To set the overvoltage blocking, proceed as follows: 1. > 1x > . <01> Undervoltage V< [%]. 2. Press reduce it. 3. Press . to increase the value or to Parameter > Limit values

The undervoltage blocking V< is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

93

7 Functions and settings

You can also set the "Undervoltage blocking" function as an absolute value. To do this, you must have also activated the "On" selection under "Absolute limit values". This setting is made as an absolute value in unit V. This value relates to the secondary transformer voltage. Setting range 34 V 160 V
Table 37

Step size 0.1 V

Factory setting 90 V

Setting range for undervoltage blocking V< in V, absolute values

If you use the key to change the display to unit kV, the value relates to the primary transformer voltage. Setting range 34 %...160 % of the primary transformer voltage
Table 38

Step size 1 kV

Factory setting 1 kV

Setting range for undervoltage blocking V<, absolute values in kV

This, for example, results in a setting range of 17 kV to 80 kV at a primary transformer voltage of 50 kV. To set the overvoltage blocking, proceed as follows: 1. > 2x > . <02> Undervoltage V< [V]. 2. If necessary press want, "V" or "kV". 3. Press reduce it. 4. Press . to select the unit you Parameter > Limit values

to increase the value or

to

The undervoltage blocking V< is set.

94

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.10.3

Setting the V> overvoltage limit value [%] When the overvoltage detection responds, the on-load tap-changer is activated by periodical control of the motor-drive unit until the measured voltage is less than the set overvoltage limit value. This is controlled by the output relay for the "Lower" switching direction at the intervals dictated by the set switching pulse duration without the set switching delay becoming active. At the same time, the "V>" LED is illuminated and a signaling relay is activated (IO-X1-X1/19, IO-X1/20 contacts) as long as there is overvoltage. You can set the interval for LOWER (see "Setting the switching pulse time" on page 142). Instead of the high-speed return control function, the control can also be blocked if the overvoltage value is exceeded. The V> overvoltage limit is entered as a percentage of the set desired value. Setting range 100 %...140 % of desired value
Table 39

Step size 1%

Factory setting 110 %

Setting range for V> overvoltage limit as percentage

To set overvoltage blocking, proceed as follows: 1. > 3x > . <03> Overvoltage V> [%]. 2. Press reduce it. 3. Press . to increase the value or to Parameter > Limit values

V> overvoltage blocking is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

95

7 Functions and settings

7.3.10.4

Setting the V> overvoltage limit value as an absolute value You can also set the "Overvoltage blocking" function as an absolute value. To do this, you must have also activated the "On" selection under "Absolute limit values". This setting is made as an absolute value in unit V. This value relates to the secondary transformer voltage. Setting range 100 V 160 V
Table 40

Step size 0.1 V

Factory setting 110 V

Setting range for overvoltage blocking V> in V, absolute value

If you use the key to change the display to unit kV, this value relates to the primary transformer voltage. Setting range 100 %...160 % of the primary transformer voltage
Table 41

Step size 1 kV

Factory setting 1 kV

Setting range for overvoltage blocking V> in kV, absolute value

This, for example, results in a setting range of 50 kV to 80 kV at a primary transformer voltage of 50 kV. To set overvoltage blocking, proceed as follows: 1. > 4x > . <04> Overvoltage V> [V]. 2. If necessary press want, "V" or "kV". 3. Press reduce it. 4. Press . to increase the value or to to select the unit you Parameter > Limit values

V> overvoltage blocking is set.

96

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.10.5

Setting limit value I> overcurrent The I> overcurrent blocking prevents tap-change operations during load currents which are higher than the selected limit value (e.g. overload). As soon as the measured current exceeds the set blocking value, control is blocked. The "I>" LED lights up and the relevant signaling relay is permanently activated (IO-X1/18, IO-X1/19, IO-X1/20 contacts). key to change The value is entered as a percentage. You can use the the input from a percentage [%] to absolute values in amps [A]. In both cases, the value relates to the primary transformer current. Setting range 50 %...210 %
Table 42

Step size 1%

Factory setting 110 %

Setting range for I> overcurrent blocking as %

Setting range 50 %...210 % of primary transformer current


Table 43

Step size 1A

Factory setting 1A

Setting range for I> overcurrent blocking in A

This, for example, results in a setting range of 50 A to 210 A at a primary transformer current of 100 A. To set the limit value I> overcurrent for overcurrent blocking, proceed as follows: 1. > 5x > . <05> Overcurrent I>. 2. If necessary press want: "%" or "A". 3. Press reduce it. 4. Press . to select the unit you Parameter > Limit values

to increase the value or

to

I> overcurrent blocking is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

97

7 Functions and settings

7.3.10.6

Activating/deactivating function monitoring If the measured value leaves the current bandwidth (desired value+/- bandwidth) for more than 15 minutes, the function monitoring relay is activated. This results in an alarm message on the display which is only reset when the measured value returns to within the current bandwidth. If the measured voltage is below 30 V, then the measured value is outside the bandwidth and the relevant relay is also activated after 15 minutes. You can deactivate this function if you want to avoid a function monitoring message when the transformer is switched off: 1. > 6x > . <11> Function monitoring. or to activate 2. Press (On)/deactivate (Off) function monitoring. 3. Press . Parameter > Limit values

The function monitoring is activated/deactivated for voltages <30 V.

98

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.10.7

Setting signaling delay time for undervoltage V< To prevent the undervoltage relay from activating as soon as a short-lived voltage dip occurs, a delay time can be set for this signal. The undervoltage LED will light up immediately in any case. Setting range 0 s...20 s
Table 44

Step size 0.1 s

Factory setting 10 s

Setting range for undervoltage V< delay for signal

To set the delay time for this signal, proceed as follows: 1. > 7x > . <12> Delay time V<. 2. Press to highlight a digit. Parameter > Limit values

The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the time or to

The signaling delay time for undervoltage V< is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

99

7 Functions and settings

7.3.10.8

Activating/deactivating undervoltage blocking V< The undervoltage blocking can either be activated or deactivated. If blocking is deactivated and the value falls below that specified for blocking, then a signal appears via the relay and LED. Control is not however blocked. To activate/deactivate the undervoltage blocking V<, proceed as follows: 1. > 8x > Parameter > Limit values

. <15> Blocking V<. or to to activate/deactivate

2. Press

undervoltage blocking. 3. Press .

Undervoltage blocking is activated/deactivated. 7.3.10.9 Activating/deactivating signal for undervoltage V< below 30 V Disabling the "undervoltage V<" signal can be useful in order to avoid error signals when the transformer is switched off (measured voltage V< 30 V at the voltage regulator). To disable the signal for undervoltage V<, proceed as follows: 1. > 9x > Parameter > Limit values

. <18> V< also below 30 V. or to activate

2. Press

(on)/deactivate (Off) the signal for undervoltage V<. 3. Press .

The signal for undervoltage V< is activated/deactivated.

100

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.11

Abnormal control response


You can use this function to set how the voltage regulator responds during an abnormal control response. To do this, the voltage regulator monitors, in automatic mode, the number of consecutive RAISE operations within a defined time period. If the maximum permissible number of tap-change operations is exceeded, the voltage regulator blocks any more RAISE operations for a time that you can set. As an option, MR can parameterize the voltage regulator such that a signal is output via a relay during the blocking time. An example of how the voltage regulator responds in this case is shown below.

Figure 18

Example of normal control response (left) and abnormal control response (right)

1 2 T1 B%

Controller blocked Defined time period for monitoring RAISE operations Delay time T1 Bandwidth B%

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

101

7 Functions and settings

7.3.11.1

Setting maximum number of RAISE operations This parameter is used to define the maximum permissible number of consecutive RAISE operations. Setting range 0...20
Table 45

Step size 1

Factory setting 0

Setting range for maximum number of RAISE operations

Setting 0 deactivates the function for monitoring abnormal control response. There is no limit to the maximum number of consecutive RAISE operations.

To set the maximum number of RAISE operations, proceed as follows: 1. > > 10x . Parameter > Limit values

<24> Max. operations in time. 2. Press reduce it. 3. Press . to increase the value or to

The maximum number of RAISE operations is set.

7.3.11.2

Setting time window for monitoring RAISE operations This parameter is used to define the time window for monitoring the number of consecutive RAISE operations. Setting range 0...1800 s
Table 46

Step size 1s

Factory setting 120 s

Setting range for time period for monitoring RAISE operations

102

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To set the time window, proceed as follows: 1. > Parameter > Limit values

. > 11x <25> Time window for steps. 2. Press reduce it. 3. Press . to increase the value or to

The time window is set.

7.3.11.3

Setting maximum number of RAISE operations This parameter is used to define the blocking time after the maximum permissible number of consecutive RAISE operations has been reached. Any further RAISE command during this blocking time is blocked. Setting range 0...600 s
Table 47

Step size 1s

Factory setting 300 s

Setting range for blocking time after the maximum permissible number of RAISE operations has been reached

To set the blocking time, proceed as follows: 1. > > 12x . Parameter > Limit values

<26> T block max. number of steps 2. Press reduce it. 3. Press . to increase the value or to

The blocking time is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

103

7 Functions and settings

7.3.11.4

Setting counting behavior This parameter can be used to define the counting behavior. All RAISE operations within the defined time period are counted as standard, even if they have been interrupted by a LOWER operation. Alternatively, you can stipulate that the counter is set to 0 during a LOWER operation. Parameters Off On
Table 48

Function LOWER operations do not affect the counting method. The counter is reset during a LOWER operation.
Setting range for blocking time after the maximum permissible number of RAISE operations has been reached

To set the blocking time, proceed as follows: 1. > > 13x . Parameter > Limit values

<27> Lower -> Raise counter 0. 2. Press want. 3. Press . or to set the option you

The required option is selected.

104

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.12

Compensation
The quality of the energy supply depends not only on the voltage at the busbar of the supply transformer (measurement value V), but also the voltage directly at the equipment. In some cases the line impedance - of the cables or overhead lines - needs to be taken into account for voltage regulation. A significant (load-dependent) voltage drop can occur in these cables. This voltage drop is dependent on the following factors at the consumer: Impedance (apparent resistance) Cable Electrical current Phase angle

The voltage regulator has two possible ways of balancing a load-related voltage drop between the transformer and the consumer: Line drop compensation Z compensation

Comparison between line drop compensation and Z Compensation Line drop compensation (vectorial compensation): provides more precise compensation of cable voltage drops requires several parameters requires full knowledge of the cable data

Z compensation: can be used with minor changes in the phase angle cos is not dependent on phase angle cos is simple to set can also be used in meshed grids

Both methods are described in more detail in the following sections.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

105

7 Functions and settings

7.3.12.1

Line drop compensation Line drop compensation requires exact cable data. Line voltage drops can be compensated very accurately using LDC. To set the line drop compensation correctly, you have to calculate the ohmic and inductive voltage drop, in relation to the secondary side of the voltage transformer in V. The existing measuring circuit also has to be set correctly. The setting values must first be calculated in order to enter the correct values for the ohmic and inductive voltage drops. Sample calculation: Vr Vx IN kCT kVT r x L LDC setting for ohmic line voltage drop in V LDC setting for inductive line voltage drop in V Nominal current in A of selected current transformer connection on voltage regulator: 0.2 A; 1 A or 5 A Current transformer ratio; for example 200 A/5 A Voltage transformer ratio Ohmic line resistance in /km per phase Inductive line resistance in /km per phase Length of line in km

Formula for calculating the ohmic voltage drop:

Formula for calculating the inductive voltage drop:

106

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Calculation:

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

107

7 Functions and settings

If the active and reactive voltage drops "Vr" and "Vx" are set correctly, then the voltage at the line end remains constant irrespective of the load. Figure name

Table 49

Line drop equivalent circuit

Table 50

Line drop compensation

The settings for the compensation methods are described in more detail below: 7.3.12.2 Setting the ohmic voltage drop Vr The calculated ohmic voltage drop must be entered in the "Vr" display. The compensation effect can be rotated by 180 in the display using a plus or minus sign. Line drop compensation and Z compensation can be used at the same time. So make sure that you set the parameter for the method of compensation not used to "0".

108

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Setting range -25 V...25 V


Table 51

Step size 0.1 V

Factory setting 0V

Setting range for ohmic voltage drop Vr

To set the ohmic voltage drop Vr, proceed as follows: 1. tion. <00> Line drop compensation Vr. to highlight a digit. 2. Press The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to > Parameter > Compensa-

The ohmic voltage drop Vr is set. 7.3.12.3 Setting the inductive voltage drop Vx The calculated inductive voltage drop must be entered in the "Vx" display. The compensation effect can be rotated by 180 in the display using a plus or minus sign. If you do not want to use a method of compensation, a "0" must be entered for both methods.

Line drop compensation and Z compensation can be used at the same time. So make sure that you set the parameter for the method of compensation not used to "0".

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

109

7 Functions and settings

Setting range -25 V...25 V


Table 52

Step size 0.1 V

Factory setting 0V

Setting range for inductive voltage drop Vx

To set the inductive voltage drop Vx, proceed as follows: 1. > tion > 1x Parameter > . Compensa-

<01> I> Line drop compensation Vx. to highlight a digit. 2. Press The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to

The inductive voltage drop Vx is set. 7.3.12.4 Setting Z compensation Z compensation can be used for example for minor changes to the phase angle cos . It can also be used for meshed grids. Z compensation is not however dependent on cos . To correctly set the parameters, you need to calculate the voltage increase (V) taking the current into account. Sample calculation: V VTr VLa I IN kCT Z compensation setting as % Transformer voltage with current I Voltage on line end with current I and on-load tap-changer in same operating position Load current in A Nominal current in A of selected current transformer connection on voltage regulator: 0.2 A, 1 A or 5 A Current transformer ratio; for example 200 A or 5 A

110

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Formula for determining the voltage increase V:

Calculation:

The calculated voltage increase percentage relates to the desired voltage value and must be entered in this display. If you do not want to use a method of compensation, a "0" must be entered for both methods.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

111

7 Functions and settings

Setting range 0 %...15 % of desired value


Table 53

Step size 0.1 %

Factory setting 0%

Setting range for Z compensation

To set the Z compensation, proceed as follows: 1. > tion > 2x Parameter > . Compensa-

<02> I> Z compensation. 2. Press reduce it. 3. Press . to increase the value or to

The Z compensation is set.

112

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.12.5

Setting the Z compensation limit value V If Z compensation is activated, you must limit the maximum permissible increase in voltage, with reference to the desired value, to avoid excessive voltage on the transformer. Setting range 0 %...15 % of desired value
Table 54

Step size 0.1 %

Factory setting 0%

Setting range for Z compensation limit value V

To set the limit value V, proceed as follows: 1. > Parameter > Compensa-

tion > 3x . <03> Z compensation limit value. 2. Press reduce it. to increase the value or to

. 3. Press The limit value V is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

113

7 Functions and settings

7.3.13

Cross-monitoring
Cross-monitoring permits the reciprocal monitoring of 2 voltage regulators. The voltage regulator detects potential errors in the following parts and reports them via the standard self-monitoring: Mains unit Processor error No program

Should an error occur, this is signaled via the status contact. The reciprocal cross-monitoring can therefore only be restricted to the following: No measured value and/or measurement card error With voltage regulators which check one another, the measured value of the other voltage regulator is supplied via second measurement inputs. The measured values calculated accordingly for the voltage regulators are obtained via the CAN bus and compared with the original measured values. If the measured values deviate, the "Measured value error" signal is issued via an output relay. The second measurement inputs should be considered separately from the first ones. This allows voltage regulators from different voltage levels to be checked. Checking voltage regulation within definable upper and lower limits A measured voltage is supplied to a voltage regulator via a second measurement input. In addition to this measured value, a separate desired value, a lower limit and an upper limit and a time delay can be set. If one of these limits is exceeded, a signal is issued via an output relay after the set time. If wired accordingly, relay contacts can block the raise/lower pulse to the motor-drive unit. Regulation of individual voltage regulators is not affected by limit value monitoring. In order to ensure communication between the monitoring voltage regulators via the CAN bus interface, the CAN address must be entered. "1" must be assigned as the CAN address for the first voltage regulator and "2" for the second one.

114

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.13.1

Setting V-desired for regulator 2 You can set the desired value of the voltage regulator to be monitored as an absolute value in V or kV units under this menu item. If you use the key to change the display, this value relates to the primary transformer voltage. If you change the display to V, this relates to the secondary voltage. Setting range 49 V 140 V
Table 55

Step size 0.1 V

Factory setting 100 V

Setting range for desired value for regulator 2 (V)

To enter the desired value for voltage regulator 2, proceed as follows: 1. > Parameter >

Cross-monitoring. <00> Vdesiredregulator 2. 2. Press reduce it. 3. Press . to increase the value or to

The desired value for voltage regulator 2 is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

115

7 Functions and settings

7.3.13.2

Setting undervoltage blocking V< (%) for regulator 2 You can set the limit value for undervoltage blocking of the voltage regulator to be monitored as an absolute value under this menu item. Setting range 34 V 160 V
Table 56

Step size 1V

Factory setting 60 V

Setting range for undervoltage blocking for regulator 2 (V)

To enter the limit value for undervoltage blocking for voltage regulator 2, proceed as follows: 1. > Parameter > .

Cross-monitoring > 2x <02> V< regulator 2. 2. Press reduce it. 3. Press .

to increase the value or

to

The limit value for undervoltage blocking is set as an absolute value.

116

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.13.3

Setting undervoltage blocking V< (%) for regulator 2 You can set the limit value for overvoltage blocking of the voltage regulator to be monitored as a percentage in this display. Setting range 60 %...100 %
Table 57

Step size 1%

Factory setting 60 %

Setting range for undervoltage blocking for regulator 2 (%)

To enter the limit value for undervoltage blocking for voltage regulator 2, proceed as follows: 1. > Parameter > .

Cross-monitoring > 1x <01> V< regulator 2. 2. Press reduce it. 3. Press .

to increase the value or

to

The limit value for undervoltage blocking is set as a %.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

117

7 Functions and settings

7.3.13.4

Setting V> overvoltage blocking for regulator 2 (%) You can set the limit value for overvoltage blocking of the voltage regulator to be monitored as a percentage in this display. Setting range 100 %...140 %
Table 58

Step size 1%

Factory setting 140 %

Setting range for overvoltage blocking for regulator 2 (%)

To enter the limit value for overvoltage blocking for voltage regulator 2, proceed as follows: 1. > Parameter > .

Cross-monitoring > 3x <03> V< regulator 2. 2. Press reduce it. 3. Press .

to increase the value or

to

The limit value for overvoltage blocking is set as a %.

118

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.13.5

Setting V> overvoltage blocking for regulator 2 (absolute values) You can set the limit value for overvoltage blocking of the voltage regulator to be monitored as an absolute value in this display. Setting range 34 V 160 V
Table 59

Step size 1V

Factory setting 140 V

Setting range for overvoltage blocking for regulator 2 (V)

To enter the limit value for overvoltage blocking for voltage regulator 2, proceed as follows: 1. > Parameter > .

Cross-monitoring > 4x <04> V< regulator 2. 2. Press reduce it. 3. Press .

to increase the value or

to

The limit value for overvoltage blocking is set as an absolute value.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

119

7 Functions and settings

7.3.13.6

Setting delay time for error message If an error is recorded by a monitoring voltage regulator, you can set the error message delay time in this display. Setting range 0 s...10 s
Table 60

Step size 1s

Factory setting 10 s

Setting range for error message delay time

To set the error message delay time for voltage regulator 2, proceed as follows: 1. > Parameter > .

Cross-monitoring > 5x <05> Error message. 2. Press reduce it. 3. Press .

to increase the value or

to

The error message delay time for regulator 2 is set.

120

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.3.13.7

Setting the secondary transformer voltage for regulator 2 In this display, you can set the secondary transformer voltage of the voltage regulator to be monitored. Setting range 57 V 110 V
Table 61

Step size 1V

Factory setting 100 V

Setting range for secondary transformer voltage for regulator 2 - V

Setting range 0 kV...9999 kV 0 kV...999.9 kV 0 kV...99.99 kV


Table 62

Step size 1 kV 0.1 kV 0.01 kV

Factory setting 0 kV

Setting range for secondary transformer voltage for regulator 2 - kV

To set the secondary transformer voltage of voltage regulator 2, proceed as follows: 1. > Parameter > .

Cross-monitoring > 6x <06> V sec regulator 2. 2. Press reduce it. 3. Press .

to increase the value or

to

The secondary transformer voltage of voltage regulator 2 is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

121

7 Functions and settings

7.3.13.8

Setting primary transformer voltage for regulator 2 In this display you can set the primary transformer voltage of the voltage regulator to be monitored. Setting range 0 kV...9999 kV 0 kV...999.9 kV 0 kV...99.99 kV
Table 63

Step size 1 kV 0.1 kV 0.01 kV

Factory setting 0 kV

Setting range for primary transformer voltage for voltage regulator 2

To set the primary transformer voltage of voltage regulator 2, proceed as follows: 1. > Parameter >

. Cross-monitoring > 7x <07> V prim voltage reg 2. 2. Press to highlight the decimal place.

The decimal place is defined and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to

The primary transformer voltage of voltage regulator 2 is set.

122

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4

Configuration
This section describes how to carry out all the settings for configuring system-specific data. To make it easier for you to find specific parameters, the description refers to subgroups of individual parameters with related functions.

7.4.1

Transformer data
The transformation ratios and measuring set-up for the voltage and current transformers used can be set in the relevant displays. The relevant settings are described in the following sections.

7.4.1.1

Setting the primary transformer voltage In general, the regulator only displays the secondary transformer voltage in V if you have not set the primary transformer voltage. The primary voltage is only displayed if you have previously set the "Display V / kV" parameter. The setting variants are shown in the table below. Primary voltage Secondary voltage With a kV or V setDisplay ting V kV 100 V 110 kV

No parameterization 100 V 110 kV 100 V


Table 64 Example of display variants

Setting range 0 kV... 9999 kV 0 kV...999.9 kV 0 kV...99.99 kV


Table 65

Step size 1 kV 0.1 kV 0.01 kV

Factory setting 100 kV

Setting range for primary transformer voltage

To set the primary transformer voltage, proceed as follows:

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

123

7 Functions and settings

1.

> Configuration > mer data. <00> Primary voltage.

Transfor-

to highlight the decimal place. 2. Press The decimal place is defined and the value can be changed. to highlight a digit. 3. Press The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to

The primary transformer voltage is set.

124

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.1.2

Setting the secondary transformer voltage The secondary transformer voltage is displayed and entered in V. Setting range 100 V 110 V
Table 66

Step size 0.1 V

Factory setting 100 V

Setting range for secondary transformer voltage

To set the secondary transformer voltage, proceed as follows: 1. > Configuration > Transfor-

mer data > 1x . <01> Secondary voltage. to highlight a digit. 2. Press The digit position you want is highlighted and the value can be changed. 3. Press reduce it. to increase the value or to

. 4. Press The transformer secondary voltage is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

125

7 Functions and settings

7.4.1.3

Setting the primary transformer current In general the voltage regulator displays the percentage current of the chosen measurement input. As soon as the primary rated current (e.g. 50 A) is set on the voltage regulator, the display in the Info menu switches over to "A" (amperes). The primary current is always displayed in "A" on the main screen or as "0" if no primary current is specified. Setting parameter Current feed Electrical connection 1A 1A 1A Display Info screen Primary / secondary current 100 % 1A 100 % (of primary current) 1A (of secondary current) Main screen 0A 0A 50 A (of primary current) 50 A (of primary current)

Primary current No parameterization No parameterization 50 A

Secondary current Unknown 1A Unknown

1A 50 A
Table 67 Example of unit displayed: % / A

1A

126

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Setting range 100 A 10,000 A


Table 68

Step size 1A

Factory setting 200 A

Setting range for primary transformer current

To set the primary transformer current, proceed as follows: 1. > Configuration > . Transfor-

mer data > 2x

<02> Primary current. 2. Press to highlight a digit.

The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press to increase the value or to

..

The primary transformer current is set.

7.4.1.4

Setting the current transformer connection The current transformer connection must be selected in order to obtain the correct display. If you set the current transformer connection to "Unknown" in the display, the percentage value is shown. However, if a connection is selected, the absolute value (in amps) is displayed. The following values can be set: 0.2 A 1A 5A

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

127

7 Functions and settings

To set the current transformer connection, proceed as follows: 1. > Configuration > Transfor-

. mer data > 3x <03> Current transformer connection. 2. Press terminal. 3. Press . or to select the required

The current transformer connection has been set.

7.4.1.5

Setting the phase difference for the current/voltage transformer The normal measuring circuit values can be set as follows: System Single-phase Three-phase Three-phase Three-phase Three-phase
Table 69

Setting 0 0 90 30 -30

Display 0 1PH 0 3PH 90 3PH 30 3PH -30 3PH

Setting options for the measuring circuits

Circuit a:

Figure 19

Circuit a - phase angle to be set 0;1PH

Voltage transformer VT is connected to phase and neutral. Current transformer CT is looped in phase.

128

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Voltage VU and current IU are in phase. The line phase voltage drop is determined by current IU.

Circuit a:

Figure 20

Circuit a - phase angle to be set 0;3PH

Voltage transformer VT is connected to U and N. Current transformer CT is looped in U. Voltage VU and current IU are in phase. The line phase voltage drop is determined by current IU.

Circuit b:

Figure 21

Circuit b - phase angle to be set 0;3PH

Voltage transformer VT is connected to U and V. Current transformer CT1 is looped in U and CT2 in V. Current transformer CT1and CT2 are connected crosswise in parallel. Current summation = IU + IV. Current IU + IV and voltage VU V are in phase. The line phase voltage drop is determined by current: (IU + IV)/ 3.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

129

7 Functions and settings

Circuit c:

Figure 22

Circuit c - phase angle to be set 90;3PH

Voltage transformer VT is connected to U and V. Current transformer CT is looped in W. Current IW ahead of voltage VU V by 90. The line phase voltage drop is determined by current IW.

Circuit d:

Figure 23

Circuit d - phase angle to be set 30;3PH

Voltage transformer VT is connected to U and V. Current transformer CT is looped in V. Current IV ahead of voltage VU v by 30. The line phase voltage drop is determined by current IV.

130

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Circuit e

Figure 24

Circuit e - phase angle to be set -30;3PH

Voltage transformer VT is connected to U and V. Current transformer CT is looped in U. Current IU lags behind voltage VU V by -30. The line phase voltage drop is determined by current IU.

To set the phase difference for the measured transformer circuit, proceed as follows: 1. > Configuration > . Transfor-

mer data > 4x

<04> Transformer circuit. or 2. Press phase difference. 3. Press . to select the required

The phase difference is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

131

7 Functions and settings

7.4.2

General
This submenu enables general settings, which are also required for commissioning, to be made on the device. You can change the following general settings: Language Regulator ID Baud rate (COM1 setting) Voltage display kV / V Current display %/A Duration of raise and lower pulse Configuration of free inputs/outputs (IOs) Display dimming Motor runtime

7.4.2.1

Setting the language The display language can be set or changed as desired. The following languages are available: 1. English German French Spanish Italian Portuguese > Configuration > <00> Language. or General.

2. Press language. 3. Press .

to select the required

The language is set.

132

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.2.2

Setting the regulator ID The regulator ID consists of a 4-digit sequence of digits and is used as additional identification for a voltage regulator. Identification is only used for the "TAPCON-trol - Software" visualization. If you do not want to set the regulator ID, the serial number and firmware version are the only features. The regulator ID can be used to ensure that the connection is established between the visualization software and a specific voltage regulator. During online communication, the software running on the PC queries this ID and compares it with the regulator data available. This enables accurate assignment of data or parameters.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

133

7 Functions and settings

To set the regulator ID, proceed as follows: 1. 1x > Configuration > General >

. <01> Regulator ID. to change the first digit.

2. Press

If you wish to enter a multi-digit sequence, proceed to step 3. If you do not wish to enter additional digits, proceed to step 7:

3. Press repeatedly (digit > 9) until another position appears. 4. If necessary press sition. and can be changed. 5. Press or to change the digit. to highlight a digit po-

The digit position you want is highlighted

6. Repeat steps 3 to 5 until all required digits have been entered. 7. Press .

8. The regulator ID is set.

7.4.2.3

Setting the baud rate In this display, you can set the baud rate for the COM1 interface, for example to define the speed of transfer for communication with the TAPCON-trol software. The following values can be set: 9.6 kilobaud 19.2 kilobaud 38.4 kilobaud 57.6 kilobaud

134

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To set the baud rate, proceed as follows: 1. 2x > Configuration > General >

. <02> Baud rate. or to select the required

2. Press baud rate. 3. Press .

The baud rate is set. 7.4.2.4 Setting the voltage display kV/V Switching the display from V to kV converts the measurements and setting values in the device on the primary side of the voltage transformer and displays them accordingly. However, the primary side is always displayed in kV and the secondary side always in V. The display can only be changed from V to kV if all the transformer data have previously been entered.

To change the desired unit for the voltage display, proceed as follows: 1. 3x > . <03> Display kV/V. 2. Press unit. 3. Press . or to to select the kV or V Configuration > General >

The required unit is set for the voltage display.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

135

7 Functions and settings

7.4.2.5

Setting current display unit In this display, you can set the unit for the limit values displayed for overcurrent and undercurrent as a percentage ("%") or absolute value ("A"). It is only possible to change from % to A if all the transformer data have previously been entered.

To set the desired unit for the current display, proceed as follows: 1. > 4x > . <04> Display %/A. 2. Press unit. 3. Press . or to to select the % or A Configuration > General

The required unit is set for the current display.

7.4.2.6

Setting the switching pulse time This display can be used to set the duration of the switching pulse for the motor-drive unit. If you set the raise or lower switching pulse time to 1.5 seconds for example, after the set delay time T1 or T2 there will be a switching pulse of 1.5 seconds. The waiting time between 2 consecutive switching pulses corresponds to the set delay time T1 or T2.

136

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Figure 25

Switching pulse in standard operating mode

1 2 3 4

T1 = set delay time Start of first raise/lower switching pulse Ti = switching pulse time (1.5 seconds) Start of second raise/lower pulse

In Quick Tap mode the next switching pulse can only take place after 1.5 seconds.

Figure 26

Switching pulse in Quick Tap mode

1 2 3

Start of first raise/lower switching pulse Ti = set switching pulse time (1.5 seconds) Earliest time for the next raise/lower switching pulse (1.5 seconds)

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

137

7 Functions and settings

A continuous pulse is output if you set the raise/lower switching pulse duration to 0. If the motor-drive unit does not start using the default setting (1.5 seconds), then please increase the pulse time.

Setting range 0 s...10 s


Table 70

Step size 0.1 s

Factory setting 1.5 s

Setting range for raise/lower switching pulse duration

To set the pulse duration, proceed as follows: 1. 5x > . <05> R/L pulse duration. 2. Press you want. 3. Press . or to set the pulse duration Configuration > General >

The R/L pulse duration is now set.

138

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.2.7

Configuring control inputs IO1-X1:33/31 You can assign functions to freely configurable control inputs in this display. You can assign the following functions to control inputs IO1-X1:33 and IO-X1:31: Possible function Off Master/Follower Local/Rem. Blocking LV S operation Function description No function selected Master mode active when signal on. Follower mode active when signal off. "Local" mode active. "Remote" mode off. Automatic regulation blocked T1/T2 deactivated. Raise/lower switching pulse occurs when value exceeds/falls below bandwidth. Signal: Motor protective switch was triggered. "Remote" mode active. "Local" mode off.

MPS tripped Remote/Loc.


Table 71

Possible functions for control inputs

You can assign the "Local/Remote" function to either control input IO-X1:z 2 0 or control input IO-X1:d 20. The functions described below can be set for this assignment: Manual/Auto and Raise/Lower can be set with F keys on the front panel Yes No Yes Yes No Manual/Auto and Raise/Lower can be set via control inputs for remote control or via a serial interface Yes Yes No No Yes

Setting at control input Off Local/Rem. Local/Rem. Remote/Local Remote/Local


Table 72

Signal

0 or 1 0 1 0 1

Setting options for "Local" and "Remote" modes

If both freely configurable control inputs, IO-X1:31 and IO-X1:33, have different or reversed settings, all voltage regulator functions are blocked. Example: If you have set both control inputs to "Local/Remote", and the signal is high (1), but low (0) on the other control input, the "Manual/Auto" and "Raise/lower" functions are not possible with either the F keys on the front panel or the inputs for remote messages or serial interface.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

139

7 Functions and settings

To assign functions to the control inputs, proceed as follows 1. 6x > . <06> IO1-X1:33. or repeatedly until the re2. Press quired function appears in the display. 3. Press . Configuration > General >

The function is assigned. All control inputs can be configured as described above. All the following control inputs are available: Control input IO1-X1:33 IO1-X1:31
Table 73

Press 6x 7x

Page number in the display <06> <07>

Freely configurable control inputs (IOs)

140

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.2.8

Configuring output relays IO1-X1:25/26 and IO1-X1:23/24 You can assign functions to freely configurable output relays in this display. You can assign the following functions to output relays IO1-X1:25/26 and IO-X1:23/24: Possible function Off Master/Follower Local/Rem. Undervoltage Overvoltage Desired value 2 Desired value 3 Motor drive runtime pulse> Motor drive runtime continuous> Motor running Bandwidth < Bandwidth >
Table 74

Function description No function selected Master mode active when signal on. Follower mode active when signal off. "Local" mode active. "Remote" mode off. Message: Undervoltage blocking. Message: Overvoltage blocking. Message: Desired value 2 Message: Desired value 3 Message: Pulse triggered; motor runtime exceeded. Message: Continuous signal; motor runtime exceeded. Message: Motor running Message: Value below bandwidth. Message: Bandwidth exceeded.

Possible functions for output relays

To assign functions to the output relays, proceed as follows: 1. 8x > . <08> IO1-X1:25/26. or repeatedly until the de2. Press sired function appears in the display. 3. Press . Configuration > General >

The function is assigned.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

141

7 Functions and settings

All output relays can be configured as described above. All the following outputs are available: Output relay IO1-X1:25/26 IO1-X1:23/24
Table 75

Press 8x 9x

Page number in the display <08> <09>

Freely configurable output relays (IOs)

7.4.2.9

Activating/deactivating display dimming If you activate this function, the display is automatically dimmed if no key is pressed within a period of 15 minutes. However, the display can still be read. Activating this function extends the lifespan of the display. The display returns to full brightness by pressing any key. 1. 10x > . <10> Display off. or 2. Press or off (OFF). 3. Press . to switch display on (ON) Configuration > General >

Display is switched ON/OFF.

7.4.2.10

Monitoring motor runtime The motor-drive unit's runtime can also be monitored by the voltage regulator. This function is used to identify motor-drive unit malfunctions during the tap-change operation and to trigger any actions needed. The corresponding control input must be correctly wired and parameterized to "Motor running" in order to use runtime monitoring. The motor runtime must also be set.

142

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

The motor-drive unit supplies the "Motor-drive unit running" signal during the tap-change operation. This signal is present until the tap-change operation is complete. The voltage regulator compares the duration of this signal with the motor runtime set. If the set motor runtime is exceeded, the voltage regulator triggers various actions: 1. 2. 3. 7.4.2.11 "Motor runtime monitoring" message Continuous signal via output relay "Motor-drive unit runtime exceeded" (optional) Impulse signal via output relay "Trigger motor protective switch" (optional)

Wiring and parameterizing control input/output relay If you want to monitor the motor runtime, the voltage regulator and motor-drive unit must be connected and parameterized as shown below.

Figure 27 1 2 3 4

Wiring for motor runtime monitoring

"Motor running" control input I/O "Motor protective switch triggered" control input I/O (optional) "Trigger motor protective switch" output relay I/O (optional) "Motor-drive unit runtime exceeded" output relay I/O (optional)

If you want to use the output relay, the feedback from the motor-drive unit "Motor protective switch triggered" must be wired to a control input and parameterized. This message resets the "Motor runtime exceeded" output relay when the motor protective switch is switched back on and activates the "Motor protective switch triggered" message.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

143

7 Functions and settings

Setting range 0 s...30 s


Table 76

Step size 0.1 s

Factory setting 0s

Setting range for motor runtime

To set the motor runtime, proceed as follows: If the runtime monitoring is set to "0.0 s" this equates to it being switched off.

1.

> > 11x .

Configuration >

General

<11> Motor runtime. to highlight a digit. 2. Press The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to

The motor runtime is set.

144

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.3

Parallel operation
Mains power supply sometimes requires an increase in the short-circuit capacity or the throughput capacity at a site. For this reason, tapped transformers are connected in parallel. A safer and more cost effective parallel operation is achieved if the joint capacity of the transformers connected in parallel is utilized without overloading individual transformers. Compliance with the following general conditions is recommended for operating transformers in parallel: Identical rated voltage Ratio of transformer output (<3:1) Maximum deviation of short-circuit voltages (VK) for transformers connected in parallel 10 % Same number of switching groups

You can use the voltage regulator to control up to 16 transformers on a busbar connected in parallel in one or 2 groups without detecting the system topology. Information is swapped using the CAN bus. Parallel operation is activated using one of 2 status inputs or the control system. There are 2 reasons for setting up parallel operating mode: 1. 2. To increase the short-circuit capacity To increase the throughput capacity

Parallel control can take one of two forms: Parallel operation following the "Circulating reactive current minimum" principle Parallel operation following the "Tap synchronization" (master/follower) principle

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

145

7 Functions and settings

7.4.3.1

Selecting parallel operation method The following sections describe which parallel operation methods can be selected and set. Four different methods can be assigned to the voltage regulators: Circulating reactive current Recommended transformer data No tap position capture required

Tap synchronization (master/follower) Transformers with identical ratings Tap position capture required

Automatic tap synchronization Off Parallel operation is deactivated

Before activating a parallel operation method, additional requirements must be met: Correct individual CAN bus addresses must be set (0). The parallel operation group 1 or 2 must be selected or activated using a predefined IO.

The following sections describe how to activate a parallel operation method.

146

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.3.2

Deactivating parallel operation To deactivate the parallel operation method, proceed as follows: 1. > operation. Configuration > Parallel

<00> Parallel operation method. or to Deactivate the parallel 2. Press operation method by selecting "Off". 3. Press .

The parallel operation method is deactivated. 7.4.3.3 Selecting circulating reactive current sensitivity When circulating reactive current is selected, then parallel operation is carried out using the circulating reactive current minimization method. The circulating reactive current is calculated from the transformer currents and their phase angles. A voltage proportional to the circulating reactive current is added to the independently operating voltage regulators as a correction for the measurement voltage. This voltage correction can be reduced or increased using the circulating reactive current sensitivity setting. The circulating reactive current sensitivity method is suited to transformers connected in parallel with a similar nominal output and nominal voltage VK and to vector groups with the same and different step voltages. This does not require any information about the tap position. This parallel operation method requires each transformer in the parallel vector group to be controlled by a separate voltage regulator.

When setting the "circulating reactive current" parallel operation method, the values for blocking and circulating reactive current sensitivity must first be set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

147

7 Functions and settings

To select the "circulating reactive current" parallel operation method, proceed as follows: 1. > operation. Configuration > Parallel

<00> Parallel operation method. 2. Press or repeatedly until "circulat-

ing reactive current" appears in the display The parallel operation method "Circulating reactive current" is selected.

7.4.3.4

Defining the master tap synchronization method With this parallel operation method the voltage regulator is designated as the master. This voltage regulator takes control while all other follower voltage regulators comply with the control commands of the master. The master compares the tap positions of the followers with its own tap position using the CAN bus. If there is a tap difference, the master directs the followers to be adjusted to the same tap position. If the specified master fails, then the error message "Parallel operation error: no master available" appears in the display. In addition, depending on the configuration of the "Simplex mode blocking" parameter, those voltage regulators which are set accordingly are blocked or continue in simplex mode.

Please note that each voltage regulator must be assigned an address using the "CAN Address" display. Each address may only be used once. Only when all voltage regulators are registered can they communicate with one another using the CAN bus and use the "master/follower" method.

148

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To specify the "master" parallel operation method, proceed as follows: 1. > Configuration > Parallel

operation. <00> Parallel operation method. or repeatedly until "Master" 2. Press appears in the display. 3. Press .

The "Master" parallel operation method is selected. 7.4.3.5 Specifying the follower tap synchronization method With this parallel operation method the voltage regulator is designated as the follower. This voltage regulator receives the control commands from the master and as the follower has to comply with them. To define the "Follower" parallel operation method, proceed as follows: 1. > Configuration > Parallel

operation. <00> Parallel operation method. or repeatedly until "Follow2. Press er" appears in the display. 3. Press .

The "Follower" parallel operation method is selected.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

149

7 Functions and settings

7.4.3.6

Specifying the follower tap synchronization method With this parallel operation method, the voltage regulator with the lowest CAN address within the same parallel operation group is automatically selected as master. This voltage regulator undertakes the measurement and adjusts the on-load tap-changer in order to correct the voltage if a deviation occurs. As with the "Master" parallel operation method, the voltage regulator compares the tap position of the followers with its own tap position using the CAN bus. If there is a tap difference, the voltage regulator directs the followers to be adjusted to the same tap position. If there is a tap position difference between the master and follower which is larger than the maximum set tap difference , then the "Parallel operation error" signal is issued. Automatic regulation blocks. Please note that each voltage regulator must be assigned an address using the "CAN Address" display. Each address may only be used once. Only when all voltage regulators are registered can they communicate with one another using the CAN bus and use the "master/follower" method.

To specify the "Automatic tap synchronization" parallel operation method, proceed as follows: 1. > operation. Configuration > Parallel

<00> Parallel operation method. or repeatedly until "Auto 2. Press synchronization" appears in the display. 3. Press .

The "Automatic tap synchronization" parallel operation method is selected.

150

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.3.7

Selecting parallel operation control As an option, the voltage regulator can be fitted with a plug-in card for parallel operation with an existing parallel operation control unit when extending existing systems. The following parallel control units can be connected: SKB 30E VC 100E-PM/PC

The settings required for parallel control must be undertaken in accordance with the relevant valid operating instructions. If you do not have a parallel control unit, you must select the "Off" selection in the "SKB parallel operation" display. The possible selections are described in more detail in the table below. Selection On Off
Table 77

Function Parallel operation control with existing parallel control unit (plug-in card needed; see above) Parallel operation control via CAN bus
Possible setting for SKB

To select the type of parallel operation control, proceed as follows: 1. > Configuration > . Parallel

operation > 1x

<01> SKB parallel operation. 2. Press "Off". 3. Press . to select "On" or to select

The type of parallel control is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

151

7 Functions and settings

7.4.3.8

Entering CAN bus address So that all voltage regulators can communicate using the CAN bus, each voltage regulator requires a unique identifier. Addresses can be set from 1 to 16. If the value is set to 0, then no communication takes place. Setting range 0...16
Table 78

Step size 1

Factory setting 1

Setting range for CAN bus address

To enter the CAN bus address, proceed as follows: 1. > Configuration > . Parallel

operation > 2x

<02> CAN address. 2. Press reduce it. 3. Press . to increase the value or to

The CAN bus address is saved. 7.4.3.9 Specifying circulating reactive current sensitivity The sensitivity of the circulating reactive current is a measure of its effect on the behavior of the voltage regulator. A setting of 0% has no effect. With circulating reactive current relating to the rated current on the current transformer, if you set the value to 10 % for example, this would cause the voltage in the voltage regulator to be corrected by 10%. This correction to the voltage can be increased or decreased with this setting to attain the optimum value. As soon as you change the circulating reactive current sensitivity value, the value for the result changes in the help text in the display.

152

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Setting range 0 %...100 %


Table 79

Step size 0.1 %

Factory setting 0%

Setting range for circulating reactive current sensitivity.

To set the circulating reactive current sensitivity, proceed as follows: 1. > Configuration > . Parallel

operation > 3x <03> Stability. 2. Press reduce it.

to increase the value or

to

to highlight the decimal place. 3. Press The decimal place is highlighted and the value can be changed. 4. Press .

The circulating reactive current sensitivity is set. 7.4.3.10 Setting the blocking threshold for the maximum permitted circulating reactive current In this display, you can set the limit value for the maximum permitted circulating reactive current in relation to the rated current of the current transformer. If, during parallel operation, the circulating reactive current exceeds the set limit value, then the following event is activated. "Problem with parallel operation"

As a result, all voltage regulators operating in parallel are blocked. Depending on the set delay time, the "Parallel operation fault" signaling relay is activated (UC-X1/1 and UC-X1/2 signaling relay contact). The corresponding LED lights up. Setting the delay time for the parallel operation error message (see "Setting the delay time for the parallel operation error message" on page 160).

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

153

7 Functions and settings

Setting range 0.5 %...20 %


Table 80

Step size 0.1 %

Factory setting 20 %

Setting range for circulating reactive current blocking

To set the blocking threshold for the maximum permitted circulating reactive current, proceed as follows: 1. > Configuration > . Parallel

operation > 4x <04> Blocking. 2. Press reduce it. 3. Press .

to increase the value or

to

The blocking threshold for the maximum permitted circulating reactive current is set. 7.4.3.11 Setting the delay time for the parallel operation error message If the voltage regulator detects an error during parallel operation, the following error message is issued: "Problem with parallel operation"

This message can be issued with a delay so that there is no brief fault message if the motor-drive units involved in the parallel operation have different runtimes. If a parallel operation error occurs, then the relevant LED immediately lights up. The message is however only issued at the output relay after the set delay time. Automatic regulation is blocked and the on-load tap-changers can only be adjusted in manual mode. Setting range 1 s...30 s
Table 81

Step size 1s

Factory setting 5s

Setting range for parallel operation error message delay time

154

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To set the delay time for the parallel operation error message, proceed as follows: 1. 5x > . <05> Error message. 2. Press reduce it. 3. Press . to increase the value or to Configuration > General >

The delay time for the parallel operation error message is set. 7.4.3.12 Selecting the follower tapping direction As in parallel operation the tap positions of the transformers which are running in parallel are compared according to the "Tap synchronization master/follower" method, it is absolutely essential that these transformers have the same position designation and that the "Raise" or "Lower" signals produce the same voltage change in all transformers. Should a scenario arise where the follower switches in the opposite direction to the master's tap change, you will have to change this parameter setting from "Default" to "Swapped". The following settings are possible: Default Swapped
Table 82

dV>0 = tapping direction toward position 1 dV<0 = tapping direction toward position n

Tapping directions

To select the tapping direction, proceed as follows: Please note whether the voltage regulator is defined as master or follower when setting the tapping direction. The tapping direction can only be changed for a follower.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

155

7 Functions and settings

1.

>

Configuration > .

Parallel

operation > 6x

<06> Tapping direction swapped. or 2. Press tapping direction. 3. Press . to select the required

The tapping direction is selected.

7.4.4

Configuring analog inputs


The analog input is used to record the tap position of an analog signal transmitter: Resistor contact series (200 - 2,000 ohms) Or injected current (0/4 - 20 mA)

Adjustment to the existing signal transmitter must be carried out during commissioning. 7.4.4.1 Setting lower limit value (%) for input 1 To configure the analog input, the lower value of the input signal must be specified. With injected current as the transmitter signal, 0 % should be entered for 0 mA. 20 % should be entered for 4 mA. Example: Tap position Minimum tap position 1
Table 83

Current 4 mA

Value 20 % of analog input signal range

Example for configuring the analog input

If the signal transmitter for capturing the tap position is a resistor contact series, then 20 % should generally be set.

156

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Setting range 0 %...100 %


Table 84

Step size 0.1 %

Factory setting 0%

Setting range of analog value - lower limit value as %

To assign the analog value for the lower limit, proceed as follows: 1. > > Configuration > Analog inputs. <00> Input 1, lower limit. to highlight a digit. 2. Press The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to Continue

The analog value for the lower limit is assigned. 7.4.4.2 Setting upper limit value (%) for input 1 To configure the analog input, the upper value of the input signal must be specified. With impressed current as the transmitter signal, 20 % should be entered for 0 mA. Example: Tap position Maximum tap position 19
Table 85

Current 20 mA

Value 100 % of analog input signal range

Example for configuring the analog input (maximum)

If the signal transmitter for capturing the tap position is a resistor contact series, then 100 % should generally be set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

157

7 Functions and settings

Setting range 0 %...100 %


Table 86

Step size 0.1 %

Factory setting 100 %

Setting range of analog value - upper limit value as %

To assign the analog value for the upper limit, proceed as follows: 1. > > Configuration > Analog inputs > 1x <01> Input 1, upper limit. to highlight a digit. 2. Press The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to . Continue

The analog value for the upper limit is assigned. 7.4.4.3 Setting lower limit value (absolute) of input 1 To configure the analog input, an absolute value must be assigned to the lower value of the applied signal. Example: You can set "1" for the lowest tap position.

158

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Setting range -999.9...999.9


Table 87

Step size 0.1 / 1

Factory setting 0.0

Setting range for lower limit value (absolute value)

1. >

>

Configuration > Analog inputs > 2x .

Continue

<02> Input 1, lower value. 2. Press reduce it. 3. Press . to increase the value or to

The lowest tap position is set. 7.4.4.4 Setting upper limit value (absolute) for input 1 To configure the analog input, an absolute value must be assigned to the upper value of the applied signal. Example: You can set "25" for the highest tap position. Setting range -999.9...999.9
Table 88

Step size 0.1 / 1

Factory setting 0.0

Setting range for upper limit value (absolute value)

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

159

7 Functions and settings

To set the highest tap position, proceed as follows: 1. > > Configuration > Continue

Analog inputs > 3x . <03> Input 1, upper value. to increase the value or to

2. Press reduce it. 3. Press .

The highest tap position is set. 7.4.4.5 Setting lower limit value (%) for input 2 To configure the analog input, the lower value of the input signal must be specified. With injected current as the transmitter signal, 0 % should be entered for 0 mA. 20 % should be entered for 4 mA. Example: Tap position Minimum tap position 1
Table 89

Current 4 mA

Value 20 % of analog input signal range

Example for configuring the analog input

If the signal transmitter for capturing the tap position is a resistor contact series, then 20 % should generally be set. Setting range 0 %...100 %
Table 90

Step size 0.1 %

Factory setting 0%

Setting range of analog value - lower limit value as %

160

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To assign the analog value for the lower limit, proceed as follows: 1. > > Configuration > . Continue

Analog inputs > 4x <04> Input 2, lower limit. to highlight a digit.

2. Press

The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to

The analog value for the lower limit is assigned. 7.4.4.6 Setting upper limit value (%) for input 2 To configure the analog input, the upper value of the input signal must be specified. With impressed current as the transmitter signal, 20 % should be entered for 0 mA. Example: Tap position Maximum tap position 19
Table 91

Current 20 mA

Value 100 % of analog input signal range

Example for configuring the analog input (maximum)

If the signal transmitter for capturing the tap position is a resistor contact series, then 100 % should generally be set. Setting range 0 %...100 %
Table 92

Step size 0.1 %

Factory setting 100 %

Setting range of analog value - upper limit value as %

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

161

7 Functions and settings

To assign the analog value for the upper limit, proceed as follows: 1. > > Configuration > . Continue

Analog inputs > 5x <05> Input 2, upper limit. to highlight a digit.

2. Press

The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to

The analog value for the upper limit is assigned. 7.4.4.7 Setting lower limit value (absolute) of input 2 To configure the analog input, an absolute value must be assigned to the lower value of the applied signal. Example: You can set "1" for the lowest tap position.

162

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Setting range -999.9...999.9


Table 93

Step size 0.1 / 1

Factory setting 0.0

Setting range for lower limit value (absolute value)

1. >

>

Configuration > Analog inputs > 6x .

Continue

<06> Input 2, lower value. 2. Press reduce it. 3. Press . to increase the value or to

The lowest tap position is set. 7.4.4.8 Setting upper limit value (absolute) for input 2 To configure the analog input, an absolute value must be assigned to the upper value of the applied signal. Example: You can set "25" for the highest tap position. Setting range -999.9...999.9
Table 94

Step size 0.1 / 1

Factory setting 0.0

Setting range for upper limit value (absolute value)

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

163

7 Functions and settings

To set the highest tap position, proceed as follows: 1. > > Configuration > Continue

Analog inputs > 7x . <07> Input 2, upper value. to increase the value or to

2. Press reduce it. 3. Press .

The highest tap position is set.

7.4.5

LED selection
The settings in this subgroup can be used to assign inputs or functions to the 4 free LEDs. These would then light up during an event. The function required must have been set in advance. To label the LEDs, you can remove the label strip underneath and label individually using transferable lettering.

164

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.5.1

Functions available for LEDs An overview of all possible functions which you can assign to the LEDs is provided in the table below. Possible functions Off IO1:25 IO1:23 IO1:21 IO1:18 UC1:2 UC1:4 UC1:6 UC1:8 UC1:10 UC1:19 UC1:21 UC1:23 UC1:25 UC1:27 UC2:2 UC2:4 UC2:6 UC2:8 UC2:10 UC2:19 UC2:21 UC2:23 UC2:25 UC2:27 IO1:33 IO1:31 IO1:29 IO1:28 IO1:17 IO1:16 IO1:14 IO1:13 IO1:11 IO1:12 Function description LED deactivated Signal issued at IO1:25 input Signal issued at IO1:23 input Signal issued at IO1:21 input Signal issued at IO1:18 input Signal issued at UC1:2 input Signal issued at UC1:4 input Signal issued at UC1:6 input Signal issued at UC1:8 input Signal issued at UC1:10 input Signal issued at UC1:19 input Signal issued at UC1:21 input Signal issued at UC1:23 input Signal issued at UC1:25 input Signal issued at UC1:27 input Signal issued at UC2:2 input Signal issued at UC2:4 input Signal issued at UC2:6 input Signal issued at UC2:8 input Signal issued at UC2:10 input Signal issued at UC2:19 input Signal issued at UC2:21 input Signal issued at UC2:23 input Signal issued at UC2:25 input Signal issued at UC2:27 input Signal issued at IO1:33 input Signal issued at IO1:31 input Signal issued at IO1:29 input Signal issued at IO1:28 input Signal issued at IO1:17 input Signal issued at IO1:16 input Signal issued at IO1:14 input Signal issued at IO1:13 input Signal issued at IO1:11 input Signal issued at IO1:12 input

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

165

7 Functions and settings

Possible functions UC1:33 UC1:32 UC1:31 UC1:30 UC1:17 UC1:16 UC1:15 UC1:14 UC1:12 UC1:11 UC2:33 UC2:32 UC2:31 UC2:30 UC2:17 UC2:16 UC2:15 UC2:14 UC2:12 UC2:11 SI:bef1 SI:bef2 Undervoltage Overvoltage Overcurrent Parameter error Motor protection Blocking Circulating reactive current Master Follower Automatic Bandwidth < Bandwidth >
Table 95

Function description Signal issued at UC1:33 input Signal issued at UC1:32 input Signal issued at UC1:31 input Signal issued at UC1:30 input Signal issued at UC1:17 input Signal issued at UC1:16 input Signal issued at UC1:15 input Signal issued at UC1:14 input Signal issued at UC1:12 input Signal issued at UC1:11 input Signal issued at UC2:33 input Signal issued at UC2:32 input Signal issued at UC2:31 input Signal issued at UC2:30 input Signal issued at UC2:17 input Signal issued at UC2:16 input Signal issued at UC2:15 input Signal issued at UC2:14 input Signal issued at UC2:12 input Signal issued at UC2:11 input Signal issued at SI:bef1 input Signal issued at SI:bef2 input Undervoltage present Overvoltage present Overcurrent present Parallel operation error present Motor protective switch tripped Control blocked Parallel operation selected using circulating reactive current method Voltage regulator in parallel operation activated as master Voltage regulator in parallel operation activated as follower Auto mode active Value below bandwidth Value above bandwidth

Possible functions for LEDs

166

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

A function can be assigned to an LED if desired. As soon as the corresponding event occurs, the selected LED lights up. There is a total of 6 LEDs available, each of which can be assigned an input or a function. To assign a function to an LED, proceed as follows (Example: "LED 1"): 1. > Continue > <00> LED 1. LED selection.

or repeatedly until the re2. Press quired function appears in the display. 3. Press .

The function is assigned. All additional LEDs can be assigned as described above. The LEDs available can be called up as follows: Press LED LED 1 LED 2 LED 3 LED 4 red LED 4 green
Table 96

Characteristics . Single-colored Single-colored Single-colored Two-colored Two-colored


Freely-configurable LEDs

Page number in the display <00> <01> <02> <03> <04>

1x 2x 3x 4x

7.4.6

Configuring transducer function


Depending on the configuration and version of the transducer module 2 or 4, the transducer module can be used to obtain measured values as analog values in the following ranges: The following values are available: V1 V2 (optional via a second measurement input) I1 Active current Reactive current

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

167

7 Functions and settings

Active power Reactive power Apparent power Tap position Desired value

If the analog outputs have not been set as you want them in the factory, the section below describes how you can change them for measuring transducer 1. Please undertake the settings form measuring transducers 2 to 4 in the same way. 7.4.6.1 Assigning measurement parameter of outputs 1 to 4 In this display you can assign a measurement parameter to be transferred to the transducer output. Possible settings Off (no assignment) V1 (kV) I1 (A) Tap position Desired value V2 (kV) - optional via a second measurement input Active current Reactive current Apparent power Active power Reactive power
Table 97 Measurement parameters for outputs 1 to 4

Factory setting

Off

168

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

In order to assign a measurement parameter to the measuring transducer output, proceed as follows (example using transducer 1/2; "output 1 measured value"): 1. > > Configuration > Continue > Continue

Measuring trans-

ducer 1/2. <00> Output 1 measured value. or repeatedly until the de2. Press sired measurement parameter is displayed. 3. Press .

The desired measurement parameter is assigned. 7.4.6.2 Assigning minimum physical parameter In this display you can assign a minimum physical parameter to the transducer output. Possible settings 4 mA 0 mA -1 mA -4 mA -10 mA -20 mA 0V -10 V
Table 98 Minimum physical parameters for outputs 1 to 4

Factory setting

4 mA

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

169

7 Functions and settings

To assign the lower physical parameter to the measuring transducer, proceed as follows: 1. > > Configuration > Continue > . Continue

Measuring trans-

ducer 1/2 > 1x

<01> Output 1, lower. or repeatedly until the de2. Press sired physical parameter is displayed. 3. Press .

The desired physical parameter is assigned. 7.4.6.3 Assigning maximum physical parameter In this display you can assign a maximum physical parameter to the transducer output. Possible settings 1 mA 10 mA 20 mA 10 V
Table 99 Maximum physical parameters for outputs 1 to 4

Factory setting

20 mA

170

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To assign the upper physical parameter to the measuring transducer, proceed as follows: 1. > > Configuration > Continue > . Continue

Measuring trans-

ducer 1/2 > 2x

<02> Output 1, top. or repeatedly until the de2. Press sired physical parameter is displayed. 3. Press .

The desired physical parameter is assigned. 7.4.6.4 Assigning minimum absolute value In this display you can assign a minimum limit value to the transducer output as an absolute value. Setting range -9999...9999 -999.9...999.9 -99.99..99.99
Table 100

Step size 1 0.1 0.01

Factory setting 0

Setting range for lower limit value for measuring transducer.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

171

7 Functions and settings

To assign the minimum absolute value, proceed as follows: 1. > > Configuration > Continue > . Continue

Measuring trans-

ducer 1/2 > 3x

<03> Output 1, lower value. 2. Press reduce it. 3. Press . to increase the value or to

The minimum absolute value is assigned. 7.4.6.5 Assigning maximum absolute value In this display you can assign a maximum limit value to the transducer output as an absolute value. Setting range -9999...9999 -999.9...999.9 -99.99..99.99
Table 101

Step size 1 0.1 0.01

Factory setting 0

Setting range for upper limit value for measuring transducer

To assign the maximum absolute value, proceed as follows: 1. > > Configuration > Continue > . Continue

Measuring trans-

ducer 1/2 > 4x

<04> Output 1, value top. 2. Press reduce it. 3. Press . to increase the value or to

The minimum absolute value is assigned.

172

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.7

Configuring measured value memory function (optional)


You can undertake measured value memory settings in this subgroup. This configures the event memory and plotter function. The "Measured value plotter" module (8MB) can be used to save the data listed below and display and evaluate this either on the display or using the TAPCONtrol visualization software. For more detailed information, please refer to the respective technical files for both the hardware and visualization software. The following values are displayed: Measured values On-load tap-changer position Voltage Active current Reactive current Calculated values Active power Reactive power Apparent power Output factor Calculation of the values stated depends on the measured values captured and the parameters set, for example: Current measuring circuit Primary current Voltage transformer data from primary and secondary sides A correct calculation can only be undertaken if the configuration data are correctly entered in full.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

173

7 Functions and settings

7.4.7.1

Average value memory and event memory The measured value plotter is split into the following areas: Average value memory In the average value memory, all measured and calculated values are averaged and saved using the average value intervals you set. You can set the average value intervals in stages between 1 and 40 seconds. You can set the average value interval (see "Setting time difference of average value interval" on page 186). Event memory Data is always saved to the event memory with the highest resolution without first being averaged. You can also determine how much memory space is to be made available exclusively for the event memory (see "Setting size of event memory" on page 187). The memory size is 8MB. The measured value plotter is equipped with event triggering such that an event is triggered depending on the undervoltage and/or overvoltage limit value that you can set. The data recorded here are stored in the measured value memory's event memory. To allow instances where values exceed or fall below the limit values to be better evaluated, the chronological sequence for the measured and calculated values also includes the last 10 seconds before the value exceeds or falls below the limit value. Event is saved for a maximum of 5 minutes. Only the time-based processes for values measured and calculated during the event are stored in the event memory.

If the event memory is full, the oldest values are overwritten by the new values measured. You can access information about the current event memory content via the "Info" menu.

174

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.7.2

Chronological sequence of voltage's effective value The measured value memory records the chronological sequence of the voltage's effective value. The chronological sequence for the tap positions is also shown to allow the control path to undergo an initial analysis. The voltage sequence can be displayed on the voltage regulator. The voltage and tap position can be displayed jointly using the TAPCONtrol visualization software. You must set the system date and system time if records are to feature the right times. The following sections describe how you can set these.

7.4.7.3

Setting system time You can set the system time in this display. The time format can be set using the 24-hour format: HH:MM:SS

To set the system time, proceed as follows: 1. > > Configuration > Continue .

Continue > <06> Time. or

Memory > 6x

2. Press

to select the number to

be edited. The digit position you want is highlighted and can be changed. 3. Press 4. Press . or to edit the digit.

The system time is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

175

7 Functions and settings

7.4.7.4

Setting system date You can set the system date in this display. The system date can be set from 01.01.2001 to 12.29.2099 and has the following format: DD:MM:YY

To set the system date, proceed as follows: 1. > > Configuration > Continue > <07> Date. or to select the number to 2. Press be edited. The digit position you want is highlighted and can be changed. 3. Press 4. Press . or to edit the digit. Continue .

Memory > 7x

The system date is set. 7.4.7.5 Setting undervoltage threshold (%) In this display you can set the undervoltage threshold as a percentage. If the voltage falls below the set undervoltage threshold, high-resolution measured values are saved for as long as this situation prevails. Setting range 60 %...100 %
Table 102

Step size 1%

Factory setting 90 %

Setting range for undervoltage V< threshold as percentage

176

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To set the undervoltage threshold, proceed as follows: 1. > > Configuration > Continue

Continue > Memory. <00> Threshold V<. to increase the value or to

2. Press reduce it. 3. Press .

The undervoltage threshold is set. 7.4.7.6 Setting undervoltage threshold (absolute value) In this display you can set the undervoltage threshold as an absolute value. If the voltage falls below the set undervoltage threshold, high-resolution measured values are saved for as long as this situation prevails. Entries can be made either in V or kV. If you enter the absolute value in V, it relates to the secondary transformer voltage. If you enter the absolute value in KV, it relates to the primary voltage. Setting range 40 V 160 V 0 kV...2 kV
Table 103

Step size 0.1 V / 1 V 1 kV

Factory setting 90 V 1 kV

Setting range for undervoltage V< threshold as absolute value

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

177

7 Functions and settings

To set the undervoltage threshold, proceed as follows: 1. > > Configuration > Continue

Continue > Memory. 1x <01> Threshold V<. to select the unit you

2. If necessary press want, "V" or "kV".

to highlight the 3. If V is selected, press decimal place. The decimal place is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to

The undervoltage threshold is set. 7.4.7.7 Setting overvoltage threshold (%) In this display you can set the overvoltage threshold as a percentage. If the voltage exceeds the set overvoltage threshold, high-resolution measured values are saved for as long as this situation prevails. Setting range 100 %...140 %
Table 104

Step size 1%

Factory setting 110 %

Setting range for V> overvoltage threshold as percentage

178

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To set the overvoltage threshold, proceed as follows: 1. > > Configuration > Continue .

Continue > Memory > 2x <02> Threshold V>. to increase the value or to

2. Press reduce it. 3. Press .

The overvoltage threshold is set. 7.4.7.8 Setting overvoltage threshold (absolute value) In this display you can set the overvoltage threshold as an absolute value. If the voltage exceeds the set overvoltage threshold, high-resolution measured values are saved for as long as this situation prevails. Entries can be made either in V or kV. If you enter the absolute value in V, it relates to the secondary transformer voltage. If you enter the absolute value in KV, it relates to the primary voltage. Setting range 40 V 160 V 0 kV...2 kV
Table 105

Step size 0.1 V / 1 V 1 kV

Factory setting 110 V 1 kV

Setting range for V> overvoltage threshold as absolute values

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

179

7 Functions and settings

To set the overvoltage threshold, proceed as follows: 1. > > Configuration > Continue

Continue > <03> V> memory.

Memory. 3x

2. If necessary press want, "V" or "kV".

to select the unit you

to highlight the 3. If V is selected, press decimal place. The decimal place is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to

The overvoltage threshold is set. 7.4.7.9 Setting time difference of average value interval The voltage regulator's long-term memory has a capacity of 8 MB. The memory is split into the average value memory and event memory. Depending on the setting, intervals of 1; 2; 4; 10; 20 or 40 (on page 189) seconds are saved in the average value memory. Setting range 1 s...40 s
Table 106

Step size 1 s / 2 s / 6 s / 10 s / 40 s

Factory setting 1s

Setting range for average value interval

When you set the average value interval, the complete memory is cleared once the change is confirmed.

180

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To set the mean value interval, proceed as follows: 1. > > Configuration > Continue .

Continue > Memory > 4x <04> Average value interval. to increase the time or to

2. Press reduce it. 3. Press .

The mean value interval is set.

7.4.7.10

Setting size of event memory The event memory stores instances of values exceeding or falling below the preset threshold values. It stores this information in high resolution. Refer to the table below for the maximum number of events, depending on the size of the event memory: Size of event memory Maximum number of events
Table 107

256 kB 20

512 kB 40

1024 kB 80

2048 kB 160

Size of event memory

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

181

7 Functions and settings

Below you will find examples which illustrate how the event memory works:

Figure 28

For an event lasting less than 5 minutes

1 2 3 4

Duration: 10 seconds Duration: 10 seconds High-resolution recording Low-resolution recording

Figure 29

For an event lasting more than 5 minutes

1 2 3 4 5 6

Duration: 10 seconds Duration: Around 5 minutes Duration: 10 seconds Duration: 10 seconds High-resolution recordings Low-resolution recording

182

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

The high-resolution data are first saved 10 seconds before the event. After an event has lasted 5 minutes, data are saved with a low resolution. If the voltage returns to the bandwidth, this is considered a new event. This new event has a 10-second run-in time and a 10-second follow-up time. The table below shows the memory time. Depending on the average value interval and the size of the event memory, it is a maximum of 401 days. Average value interval 1s 2s 4s 10 s 20 s 40 s
Table 108

Size of event memory 256 kB 10 d 20 d 40 d 100 d 201 d 401 d 512 kB 9d 19 d 38 d 96 d 193 d 386 d 1024 kB 8d 17 d 35 d 89 d 178 d 356 d 2048 kB 7d 14 d 29 d 73 d 147 d 295 d

Memory time of measured value memory

When you set the average value interval, the complete memory is cleared once the change is confirmed.

To set the size of the event memory, proceed as follows: 1. > > Configuration > Continue > <05> Event memory. or 2. Press size you want. 3. Press . to set the event memory Continue .

Memory > 5x

The event memory size is set.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

183

7 Functions and settings

7.4.7.11

Time plotter You will find the time plotter function under "Info". The desired value you have set is automatically displayed here. The units of voltage per unit are defined by the software and you can change them at any time. However, the set values which are dependent on parameterization are adopted when you call the time plotter function back up again. You can undertake the following settings in the time plotter function: Division of time axis Voltage range Retrace time Retrace date

7.4.7.11.1

Visual display of time plotter function The time plotter is displayed as follows: Desired value/actual value display

Figure 30

Desired value and actual value display of time plotter

1 2 3 4

Desired value display Actual value display Actual value display Desired value display

184

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Overvoltage/undervoltage display

Figure 31

Voltage display of time plotter

1 2 3

Overvoltage and undervoltage bar Undervoltage value Overvoltage value

Description of symbols

Figure 32

Other time plotter symbols

1 2 3 4 5

Move time axis back Move time axis forward Increase set values by one unit Select values to set Decrease set values by one unit

The following sections describe how to run the above functions.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

185

7 Functions and settings

7.4.7.11.2

Moving time axis Here you can set the reporting times in the setting box. We would always recommend choosing the highest possible resolution given the range displayed. Refer to the table for the time axis division and the resulting duration of the range shown.

Figure 33

Reporting times which can be set

1 2

Horizontal grid lines (the set reporting time range is between the horizontal grid lines) Setting box for reporting times displayed

Steps which can be set (grid width) Displayed range (in full display)
Table 109

15 s 3.5 min

30 s 7 min

1 min 14 min

2.5 min 35 min

5 min 70 min

10 min 140 min

Duration of range displayed

186

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Proceed as follows to undertake settings: 1. > Info > 1x .

Time plotter. 2. Press to highlight the setting box for the

reporting times. The setting box is highlighted and the value can be changed. 3. Press step or to move the display forwards one to move it back one step.

The time axis is set.

7.4.7.11.3

Setting voltage range In this display the voltage range is shown in the area between the horizontal grid lines. You can restrict the area between the horizontal grid lines in the corresponding setting box. Depending on the display setting, you can display the voltage range to be displayed in V or kV (see "Setting the voltage display kV/V" on page 141).

Figure 34

Voltage range which can be set

1 2

Horizontal grid lines (the set voltage range is between the horizontal grid lines) Setting box for voltage range displayed

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

187

7 Functions and settings

The voltage range to be displayed is divided as follows: Division of ranges


Table 110

0.5 V 1 V 2V 0.1kV 0.2 kV 0.5 kV

5V 1kV

10 V 2 kV

15 V 5 kV 10 kV 20 kV

Voltage range between the horizontal grid lines

To set the voltage range, proceed as follows: 1. > Info > 1x Time plotter. .

twice to highlight the setting box 2. Press for voltage range. The setting box is highlighted and the value can be changed. to advance one unit or 3. Press move back one unit. The voltage range is set. to

7.4.7.11.4

Setting retrace time This function allows you to move the sequence to a precise time in order to trace how voltage has behaved in the past. Any time between the present time and the oldest time in the memory can be set. The time is entered in the following format: HH:MM:SS

188

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To move the sequence to a precise time, proceed as follows: 1. > Info > 1x .

Time plotter. 2. Press three times to highlight the setting

box for retracing. The setting box is highlighted and the value can be changed. to advance the time or 3. Press move it back. to

The retrace time is set. The sequence for the specified time appears in the display.

7.4.7.11.5

Setting retrace date This function allows you to move the sequence to a precise date in order to trace how voltage has behaved in the past. Any date between the present date and the oldest time in the memory can be set. The date is entered in the following format: DD:MM:YY

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

189

7 Functions and settings

To move the sequence to a precise time, proceed as follows: 1. > Info > 1x .

Time plotter. 2. Press four times to highlight the setting

box for retracing. The setting box is highlighted and the value can be changed. 3. Press or to advance the date by one digit to move it back one digit.

The retrace date is set. The sequence for the specified day appears in the display.

7.4.8

Communication interface SID


The following section describes how to configure the communication interface.

7.4.8.1

Assigning a network mask In this display, you can assign a valid, individual IP address to the Ethernet module of the SID card. Setting range 0.0.0.0...255255255255
Table 111

Step size 1

Factory setting 0.0.0.0

Setting range for the network mask

190

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To assign a network mask, proceed as follows: 1. 12x <12> Network screen. to mark a position. 2. Press The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to > Configuration > General >

The network mask is assigned.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

191

7 Functions and settings

7.4.8.2

Assigning network address In this display, you can assign a valid, individual IP address to the Ethernet module of the SID card. Setting range 0.0.0.0...255255255255
Table 112

Step size 1

Factory setting 0.0.0.0

Setting range for network address

To assign a network address, proceed as follows: 1. 13x > . <13> Network address. to mark a position. 2. Press The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to Configuration > General >

The network address is assigned.

192

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.8.3

Entering the time server address In this display, you can enter the IP address of the SNTP time server to ensure that time is synchronized in the communication network. Setting range 0.0.0.0...255255255255
Table 113

Step size 1

Factory setting 0.0.0.0

Setting range for the time server address

In order to enter the time server address of the SNTP server, proceed as follows: 1. 14x > . <14> Time server address. to mark a position. 2. Press The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to Configuration > General >

The time server IP address is entered.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

193

7 Functions and settings

7.4.8.4

Entering gateway You can enter the gateway address in this display. Setting range 0.0.0.0...255255255255
Table 114 Setting range for gateway

Step size 1

Factory setting 0.0.0.0

To enter the gateway address, proceed as follows: 1. 15x > . <15> Gateway. to mark a position. 2. Press The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to Configuration > General >

The gateway address is entered.

194

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

7.4.8.5

Entering IED name You can assign a device name (IED Name) in this display. To enter the IED name, proceed as follows: 1. 16x > . <16> IED name. to mark a position. 2. Press The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to Configuration > General >

The IED name is entered.

7.5

Info
You can view general information about on the voltage regulator in this display. You can call up the following information: General information about the device Functional reliability of the LEDs (LED test) Parallel operation Parameters Upcoming messages Input/output status Status of UC1 card Status of UC2 card RTC (real-time clock) Data on CAN bus

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

195

7 Functions and settings

Measured values Peak memory Measured value memory Time plotter

Figure 35

Info screen

1 2 3 4 5 6

Type designation Software version Date of issue Size of EEPROM / ID number of module Flash memory RAM memory

The current measured values are shown in this display. The following measured values can be displayed:

Figure 36

Measured values

196

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

1 2 3 4 5 6

V1 = voltage at first measurement input I1 = current at first measurement input Phase difference of V1 to I1 V2 = voltage at second measurement input Reactive current at first measurement input Iactive1 = active current at first measurement input

To display the measured values, proceed as follows: > Info > 1x <01> Measured values.

7.5.1

Carrying out LED test


An LED function test can be carried out based on the information displayed. This checks whether all the LEDs are functioning properly. This function only tests the functional reliability of the LEDs. The underlying function is not therefore tested.

To carry out the LED test, proceed as follows: 1. > Info > 2x <02> LED TEST. for the LED you want to test. .

2. To carry out the function test, press any F key

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

197

7 Functions and settings

Key ... + ... +

LED no. LED 1 ... LED 5 LED 6 ... LED 9 All LEDs

Table 115

Selecting the LEDs for tests

7.5.2

Querying status
All active messages or signals from all cards are displayed in the status displays. The displays have the following structure:

Figure 37

Status display

1 2 3 4

Signalling status Control inputs/output relays Signalling status Control inputs/output relays

The following sections describe how you can display the respective status windows. 7.5.2.1 Displaying input/output status The status of the respective optocoupler inputs is shown under "INPUT / OUTPUT-STATUS". As soon as a continuous signal is present at the input, it is shown in the display with a "1". "0" indicates no signal at the input.

198

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To query the status, proceed as follows: > Info > 3x

<03> INPUT/OUTPUT STATUS.

7.5.2.2

Querying status of UC1 card The status of the respective optocoupler inputs is shown under "UC1 CARD STATUS". As soon as a continuous signal is present at the input, it is shown in the display with a "1". "0" indicates no signal at the input. To query the status, proceed as follows: > Info > 4x

<04> UC1 CARD STATUS.

7.5.2.3

Querying status of UC2 card The status of the respective optocoupler inputs is shown under "UC2 CARD STATUS". As soon as a continuous signal is present at the input, it is shown in the display with a "1". "0" indicates no signal at the input. To query the status, proceed as follows: > Info > 5x

<06> UC3 CARD STATUS.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

199

7 Functions and settings

7.5.3

Resetting parameters
With this display you can reset your settings to the factory settings. To reset the parameters, proceed as follows: If you reset the parameters to the factory settings, then your settings are permanently deleted.

1.

> Info > 6x <06> Parameter. and .

2. Press 3. Press

at the same time.

All parameters have been reset to the factory settings.

7.5.4

Displaying real-time clock


A counter is started when the voltage regulator is first switched on. This continues to run even if the device is switched off. To display the real-time clock, proceed as follows: > Info > 7x <07> RTC. .

7.5.5

Displaying parallel operation


This display indicates the control number for parallel operation (= CAN bus address) and the number of voltage regulators which are currently operating in parallel.

200

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

Proceed as follows to display the parallel operation data: > Info > 8x .

<08> Parallel operation.

7.5.6

Displaying data on CAN bus


The CAN bus data of all voltage regulators running in parallel are shown in this display.

Figure 38 1 2 3 4 5

Display for CAN bus data

CAN bus address of voltage regulator Voltage in volts Active current in % Reactive current in % Tap position

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

201

7 Functions and settings

The additional CAN bus data of all voltage regulators running in parallel can also be shown in this display.

Figure 39

Display for additional CAN bus data

1 2 3 4 5 6 7

Group input 1 Group input 2 Circulating reactive current parallel operation (0 = deactivated; 1 = activated) "Master" tap synchronization (0 = deactivated; 1 = activated) "Follower" tap synchronization (0 = deactivated; 1 = activated) "Auto" tap synchronization (0 = deactivated; 1 = activated) Voltage regulator blocks group because parallel operation is experiencing a fault (0 = is not blocked; 1 = is blocked)

202

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

To display the CAN bus data, proceed as follows: 1. > Info > 9x .

<09> DATA ON CAN BUS. The CAN bus data are displayed. If you want to display more data, go to step 2: 2. Press and keep held down.

The additional information is displayed until you release the key.

7.5.7

Displaying measured value memory


As an option, the voltage regulator can be equipped with a long-term memory module. You can display information about the memory in this window. To display the measured value memory, proceed as follows: > Info > 12x .

<12> MEASURED VALUE MEMORY.

7.5.8

Displaying peak memory


The minimum and maximum voltage measured since the last reset and the minimum and maximum on-load tap-changer tap positions are shown here. All values recorded are stored with a time and date. The minimum and maximum values continue to be stored in an internal fixed value memory even in the event of power failure.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

203

7 Functions and settings

Figure 40

Peak memory: Minimum (left) and maximum values (right)

1 2 3 4 5 6 7 8

Maximum measured voltage V1 Maximum on-load tap-changer tap position Time (HH:MM:SS) and date (DD.MM.YY) of maximum measured voltage V1 Time (HH:MM:SS) and date (DD.MM.YY) of maximum recorded tap position Time (HH:MM:SS) and date (DD.MM.YY) of minimum recorded tap position Time (HH:MM:SS) and date (DD.MM.YY) of minimum measured voltage V1 Minimum on-load tap-changer tap position Minimum measured voltage V1

To display the peak memory, proceed as follows: > Info > 13x <13> Peak memory. .

7.5.9

Displaying CIC1 card SCADA information


The following information on the SCADA connection is displayed under "CIC1 card SCADA information". Protocol Data format BOOT version

204

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

7 Functions and settings

If necessary, you can also reset the Ethernet connection. To display the SCADA information on the CIC1 card, proceed as follows: > Info > 14x <14> CIC1 card SCADA information.

The SCADA information on the CIC1 card is displayed. If necessary, you can reset the Ethernet connection. Press and at the same time to reset the Ethernet connection.

7.5.10

Displaying CIC2 card SCADA information


The following information on the SCADA connection is displayed under "CIC2 card SCADA information". Protocol Data format BOOT version

If necessary, you can also reset the Ethernet connection. To display the SCADA information on the CIC2 card, proceed as follows: > Info > 15x <15> CIC2 card SCADA information.

The SCADA information on the CIC2 card is displayed. If necessary, you can reset the Ethernet connection. Press and at the same time to reset the Ethernet connection.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

205

7 Functions and settings

7.5.11

Displaying upcoming messages


This display shows upcoming messages, such as: Undervoltage Overvoltage Fault in parallel operation etc.

To display the upcoming messages, proceed as follows: > Info > 13x . <16> UPCOMING MESSAGES.

206

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

8 Interface description for IEC 61850 protocol

Interface description for IEC 61850 protocol

8.1

Physical connection
The connection to system level takes the form of a network cable via the RJ45 port on the rear of the TAPCON 260. The speed is automatically set to 10 or 100 Mbit. Before commissioning the TAPCON 260, the customer/system developer and MR should compare configuration data. On request, MR will send the ICD (Intelligent electronic device Configuration Description) file to the customer/system developer and the compared configuration details are returned as a CID (Configured Intelligent electronic Device) file. The parameters for the TCP/IP address, subnet mask and time server address can also be set later on. This can either be done directly via corresponding screens on the TAPCON 260 itself or via the "TAPCON-trol system" visualization software, i.e. on a PC or laptop. The system time for the SID card is set via the SNTP (Simple Network Time Protocol) time server. The product was developed in compliance with the relevant EMC standards. In order to maintain EMC standards, note the descriptions provided in the Electromagnetic compatibility (see "Electromagnetic compatibility" on page 55) chapter.

8.2

Device-specific data points for TAPCON 260


The device-specific data points and presettings can be found in the device's ICD file. The MICS (Model Implementation Conformance Statement) and PICS (Protocol Implementation Conformance Statement) can be requested for the device.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

207

8 Interface description for IEC 61850 protocol

8.3

Downloading the ICD file


You can download the ICD file via FTP from the communication unit (SID) using an Internet browser. To do this, you need to know the configured IP address in order to establish the Ethernet connection. Proceed as follows to download the ICD file: 1. 2. 3. Enter ftp://gast@<IP address> in your browser (in the example in the diagram below, the IP address is 192.168.0.1). Use "Save as" to save the ICD file (in this example ATCC.ICD) on the local PC. Other files, such as the Model Implementation Conformance Statement, are located in the misc folder and can also be saved on the local PC using "Save as".

The ICD file is downloaded.

Figure 41

Downloading the ICD file using an Internet browser

208

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

9 Fault elimination

Fault elimination
The following chapter describes how to eliminate simple operating faults and the meaning of possible event messages.

9.1

Operating faults
If faults occur in the device during operation, these can usually be remedied by the user. The tables below are intended to provide assistance in recognizing and remedying faults.

9.1.1

No control in AUTO mode


Cause Local/Remote switch in motor-drive unit switched to LOCAL Connection missing. Remedy Check operating mode. Correct if necessary.

Characteristics/detail Voltage regulator control commands have no effect. RAISE/LOWER LEDs light up periodically

Blocking

Check wiring as per connection diagram. Reverse power lock active. Check parameter. Correct if necessary. Negative power flow. Check current transformer polarity. Control inputs (IOs) have Check parameterization of IOs. duplicate parameterization. Correct if necessary. One of the IOs is paramete- Check parameterization and rized with "Blocking" and status in info screen (inhas an appropriate input put/output status). signal. Correct if necessary. NORMset active. Carry out manual tap-change operation with or keys. Check parameter. Correct if necessary.

Undercurrent blocking active.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

209

9 Fault elimination

Characteristics/detail Blocking LED V< illuminated Blocking LED V> illuminated Blocking LED I> illuminated Bandwidth set too high
Table 116

Cause Undervoltage blocking active

Remedy Check parameter. Correct if necessary.

Overvoltage blocking active. Check parameter. Correct if necessary. Overcurrent blocking active. Check parameter. Correct if necessary. Calculate sensitivity:Step voltage x 100 / nominal voltage

Troubleshooting: No control in AUTO mode

9.1.2

Man Machine Interface


Cause REMOTE selected. Remedy Select LOCAL mode.

Characteristics/detail Keys Does not switch between MANUAL/AUTO Keys MANUAL and AUTO LEDs do not light up.

Parameter error.

Reset to factory settings.

Contrast incorrectly set. Display No display. Voltage supply interrupted. Fuse faulty.

Set contrast using resistor contact series in front panel. Check voltage supply. Replace fuse.

210

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

9 Fault elimination

Characteristics/detail Display Different brightness on several voltage regulators. LEDs Freely configurable LED lights up. LEDs LED flashes irregularly. LEDs Status LED of SID card not flashing. COM1 Cannot be connected to PC using TAPCONtrol.
Table 117

Cause Display dimming activated/deactivated.

Remedy Check "Display dimming" setting.

Customized LED parameterization. Input signal not constant.

Check parameter. Correct if necessary. Check input signal.

Network address, network mask, gateway addresses, time server address or IED name not set. Different baud rates set.

Check the network address, network mask, gateway addresses, time server address and IED name parameters. Check "Baud rate" parameter (voltage regulator and TAPCONtrol). Correct if necessary.

Troubleshooting: Man Machine Interface

9.1.3

Incorrect measured values


Cause Connection has no contact in the plug terminal. Insulation trapped. Wire not inserted far enough. Circuit breaker tripped. Voltage drop on measuring lead. Possible sources of fault: Leads laid in parallel. Tap-change operations. Remedy

Characteristics/detail

Measured voltage No measured value.

Check wiring and plug terminal.

Measured voltage Measured value too low. Measured voltage Measured value fluctuates too much.

Check fuse. Check measured voltage at plug terminal. Check measured voltage at plug terminal. Increase distance from source of interference. Install filter if necessary.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

211

9 Fault elimination

Characteristics/detail Measured current No measured value. Measured current Measured value too high. Measured value too low.

Cause Line to current transformer interrupted. Do not remove short-circuiting jumper in current transformer. Ratio not correctly parameterized. Incorrect input connected.

Remedy Check wiring. Remove short-circuiting jumper.

Correct parameterization. Check assignment of plug terminals.

Phase angle V/I.

Fault in external transformer Check transformer circuit . circuit. Compare with system connection diagram. Correct parameters. Compare measurement values on info screen. Transpose current transformer connection. Transformer circuit Check polarity of transformer incorrectly parameterized. circuit. Correct if necessary. Check circuit. Correct if necessary. Check measurement points. Correct if necessary.
Troubleshooting: Incorrect measured values

Table 118

9.1.4

Parallel operation faults


Cause "Parallel operation method" parameter deactivated. Remedy Activate "Parallel operation method" parameter Select parallel operation method (see "Selecting parallel operation method" on page 152). CAN bus address of voltage Set CAN bus address (anything regulator set to "0". but 0)

Characteristics/detail Parallel operation cannot be activated. LED not lit up.

212

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

9 Fault elimination

Characteristics/detail

Problem with CAN bus. Device not listed.

Cause Voltage regulator incorrectly connected (plug twisted, offset). Voltage regulators have the same CAN bus addresses.

Remedy Check connections. Connect as shown in connection diagram. Issue different CAN bus addresses Enter CAN bus address (1) (see "Entering CAN bus address" on page 158).

Table 119

Troubleshooting: Parallel operation

9.1.5

Tap position capture incorrect


Cause Remedy Check wiring. Connect as shown in connection diagram. Check parameter. Set parameter Lower limit value (%) for input 1 and 2 FB. Shield line. Increase distance from source of interference. Lay interference lines separately. Route signal in separate lines (filter, shielded lines). Connect signal as shown in connection diagram. Check wiring Display UC1 card status FB (see "Querying status of UC1 card" on page 205)/Display UC2 card status FB (see "Querying status of UC2 card" on page 205). Connect as shown in connection diagram.

Characteristics/detail

Step display incorrect. Plus or minus sign incorrect.

Digital input activated.

"Lower value" analog input not correctly parameterized

Step display incorrect. Display fluctuates.

Interference.

No step display. "-" is displayed.

No measurement signal. No L- for digital input.

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

213

9 Fault elimination

Characteristics/detail

Cause Impermissible signal combination.

No step display. "?" is displayed. "Motor running" signal present.

Remedy Check wiring Display UC1 card status FB (see "Querying status of UC1 card" on page 205)/Display UC2 card status FB (see "Querying status of UC2 card" on page 205). Check signal sequence Display input/output status FB (see "Displaying input/output status" on page 204).

Table 120

Troubleshooting: Tap position capture

9.1.6

Digital inputs
Cause Intermittent DC voltage. Supply voltage too low. Remedy Check source of DC voltage. Check signal transmitter. Check wiring. Reset parameter to factory settings.

Characteristics/detail Signal discontinuous. No signal Info screen <13> showing 0.


Table 121

Troubleshooting: Digital inputs

9.1.7

General fault
Cause Fuse tripped. Supply voltage too low.
Troubleshooting: General faults

Characteristics/detail No function Supply voltage. Relays chatter


Table 122

Remedy Check all fuses. Replace if necessary. Check supply voltage.

9.1.8

No solution
If you cannot resolve a problem, please contact Maschinenfabrik Reinhausen. Please have the following data to hand: Serial number

214

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

9 Fault elimination

This can be found: Outer right side when viewed from the front Info screen ( > Info)

Please provide answers to the following questions: Has a firmware update been carried out? Has there previously been a problem with this device? Have you previously contacted Maschinenfabrik Reinhausen about this issue? If yes, then who was the contact?

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

215

9 Fault elimination

9.2

Event message
Remark Message is displayed if the voltage falls below the set "V<" limit value. Parameter setting: (see "Setting the undervoltage V< limit value" on page 98) Message is displayed if the voltage exceeds the set "V>" limit value. Parameter setting: (see "Setting the V> overvoltage limit value [%]" on page 101) Message is displayed in the event of overcurrent. Parameter setting: (see "Setting limit value I> overcurrent" on page 103). With tap synchronization: The tap positions of the voltage regulators running in parallel were not the same for longer than the set parallel operation signal delay. One of the voltage regulators running in parallel is not signaling a valid tap position. Neither of the voltage regulators running in parallel is set as master. One of the voltage regulators running in parallel is using the circulating reactive current method. There is no information about the system topology. With circulating reactive current method: The voltage regulator's circulating reactive current was longer than the set parallel operation signal delay and greater than the set limit value One of the voltage regulators running in parallel is using the tap synchronization method. There is no information about the system topology. There is a signal on at least one of the group inputs, but no other voltage regulator was found in the same group.

Event message Undervoltage

Overvoltage

Overcurrent

Parameter error

Motor protection Function monitoring


Table 123 Possible events

Signal issued at "Motor protective switch" input. A message is issued if the voltage regulator detects a control deviation for 15 minutes and this is not compensated for.

216

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

10 Technical Data

10

Technical Data

10.1

Indicator elements
Display LEDs LCD, monochrome, graphics-capable 128 x 128 pixels 15 LEDs for operation display and messages of which 4 LEDs are freely programmable (3x yellow, 1x green/red)
Indicator elements

Table 124

10.2

Electrical data
Power supply 110 (-20%)...350 V DC 88...265 V AC Optional: 36...72 V DC or 18...36 V DC 25 VA

Power consumption
Table 125

Electrical data

10.3

Inputs and outputs


Control voltage of inputs Contact loadability of outputs
Table 126

40...250 V DC With pulsating DC voltage, the voltage minimum must always exceed 40 V. min. 12 V / 100 mA max. AC 250 V / 5 A max. DC see diagram

Inputs and outputs

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

217

10 Technical Data

Figure 42 1

Maximum contact loadability of outputs with direct current

Ohmic load

10.4

Dimensions and weight


Housing (W x H x D) Weight
Table 127

19-inch plug-in housing in accordance with DIN 41494 Part 5 483 x 133 x 178 mm 5.0 kg
Dimensions and weight

218

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

10 Technical Data

10.5

Voltage and current measurement


Voltage transformer Measuring range: 49...140 V Effective value: 40...60 Hz Intrinsic consumption: < 1 VA 0.2 / 1 / 5 A Effective value: 40...60 Hz Intrinsic consumption: < 1 VA Overload capacity: 2 x IN (continuously), 40 x IN / 1s Voltage measuring: < 0.3 % 40 ppm/C Current measuring: < 0.5 % 40 ppm/C

Current transformer

Measuring error
Table 128

Voltage and current measurement

10.6

Ambient conditions
Operating temperature Storage temperature
Table 129

-25C...+70C -30C...+85C

Permissible ambient conditions

10.7
10.7.1

Tests
Electrical safety
EN 61010-1 Safety requirements for electrical measurement and control and regulation equipment and laboratory instruments Dielectric test with operating frequency 2.5 kV / 1 min Dielectric test with impulse voltage 5 kV, 1.2 / 50 s Level of contamination 2, overvoltage category III
Electrical safety

IEC 61131-2 IEC 60255 IEC 60 644-1


Table 130

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

219

10 Technical Data

10.7.2

EMC tests
IEC 61000-4-2 IEC 61000-4-3 IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-6 IEC 61000-4-8 IEC 61000-4-11 IEC 61000-4-29 IEC 61000-6-2 IEC 61000-6-4
Table 131 EMC tests

Electrostatic discharges (ESD) 6 kV /8 kV Electromagnetic fields (HF) 10 V/m 80...3000 MHz Fast transients (burst) 2 kV Surge transient immunity 2 kV HF interference immunity (lines) 10 V, 150 kHz...80 MHz Power frequency magnetic field immunity 30 A/m, 50 Hz, continuous Voltage dips, short interruptions and voltage variations immunity tests Voltage dips, short interruptions and voltage variations on d.c. input power port immunity tests Immunity requirements for industrial environments Emission standard for industrial environments

10.7.3

Environmental durability tests


DIN EN 60529 IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-3 IEC 60068-2-30
Table 132

Degree of protection IP20 Dry cold - 25 C / 20 hours Dry heat + 70 C / 16 hours Constant moist heat + 40 C / 93% / 2 days, no dew Cyclic moist heat (12 + 12 hours) + 55 C / 93 % / 6 cycles

Environmental durability tests

220

TAPCON 260

1801003/05 EN

Maschinenfabrik Reinhausen 2013

11 MR worldwide

11

MR worldwide
Italy Reinhausen Italia S.r.l. Via Alserio, 16 20159 Milan Phone: +39 02 6943471 Fax: +39 02 69434766 E-mail: sales@it.reinhausen.com Japan MR Japan Corporation German Industry Park 1-18-2 Hakusan, Midori-ku Yokohama 226-0006 Phone: +81 45 929 5728 Fax: +81 45 929 5741 Luxembourg Reinhausen Luxembourg S.A. 72, Rue de Prs L-7333 Steinsel Phone: +352 27 3347 1 Fax: +352 27 3347 99 E-mail: sales@lu.reinhausen.com Malaysia Reinhausen Asia-Pacific Sdn. Bhd Level 11 Chulan Tower No. 3 Jalan Conlay 50450 Kuala Lumpur Phone: +60 3 2142 6481 Fax: +60 3 2142 6422 E-mail: mr_rap@my.reinhausen.com P.R.C. (China) MR China Ltd. (MRT) 360 4E 200120 86 21 61634588 86 21 61634582 mr-sales@cn.reinhausen.com mr-service@cn.reinhausen.com Russian Federation OOO MR Naberezhnaya Akademika Tupoleva 15, Bld. 2 ("Tupolev Plaza") 105005 Moscow Phone: +7 495 980 89 67 Fax: +7 495 980 89 67 E-mail: mrr@reinhausen.ru South Africa Reinhausen South Africa (Pty) Ltd. No. 15, Third Street, Booysens Reserve Johannesburg Phone: +27 11 8352077 Fax: +27 11 8353806 E-Mail: support@za.reinhausen.com South Korea Reinhausen Korea Ltd. Baek Sang Bldg. Room No. 1500 197-28, Kwanhun-Dong, Chongro-Ku Seoul 110-718, Korea Phone: +82 2 767 4909 Fax: +82 2 736 0049 E-mail: you-mi.jang@kr.reinhausen.com U.S.A. Reinhausen Manufacturing Inc. 2549 North 9th Avenue Humboldt, TN 38343 Phone: +1 731 784 7681 Fax: +1 731 784 7682 E-mail: sales@reinhausen.com

Australia Reinhausen Australia Pty. Ltd. Ground Floor 6-10 Geeves Avenue Rockdale N. S. W. 2216 Phone: +61 2 9556 2133 Fax: +61 2 9597 1339 E-mail: sales@au.reinhausen.com Brazil MR do Brasil Indstria Mecnica Ltda. Av. Elias Yazbek, 465 CEP: 06803-000 Embu - So Paulo Phone: +55 11 4785 2150 Fax: +55 11 4785 2185 E-mail: vendas@reinhausen.com.br Canada Reinhausen Canada Inc. 1010 Sherbrooke West, Suite 1800 Montral, Qubec H3A 2R7, Canada Phone: +1 514 286 1075 Fax: +1 514 286 0520 Mobile: +49 170 7807 696 E-mail: m.foata@ca.reinhausen.com India Easun-MR Tap Changers Ltd. 612, CTH Road Tiruninravur, Chennai 602 024 Phone: +91 44 26300883 Fax: +91 44 26390881 E-mail: easunmr@vsnl.com Indonesia Pt. Reinhausen Indonesia German Center, Suite 6310, Jl. Kapt. Subijanto Dj. BSD City, Tangerang Phone: +62 21 5315-3183 Fax: +62 21 5315-3184 E-Mail: c.haering@id.reinhausen.com Iran Iran Transfo After Sales Services Co. Zanjan, Industrial Township No. 1 (Aliabad) Corner of Morad Str. Postal Code 4533144551 E-mail: itass@iran-transfo.com

Maschinenfabrik Reinhausen 2013

1801003/05 EN

TAPCON 260

221

1801003/05 EN

04/13

Maschinenfabrik Reinhausen GmbH Falkensteinstrasse 8 93059 Regensburg

Phone: Fax: Email:

+49 941 4090 0 +49 941 4090 7001 sales@reinhausen.com

www.reinhausen.com

Potrebbero piacerti anche