MiCOM Protection Portfolio

P900 P800 P700 P600 P500 P400 P300 P200 P100

Frequency Protection Relays Autoreclose, Breaker Fail ... Busbar Protection Schemes Transformer Protection Relays Line Differential and Unit Schemes Distance Protection Relays Generator Protection Relays Universal Motor Protection Relay Feeder Management Relays

P4xx = distance

> MiCOM Distance Protection - Product Selection and Setting Tips - January 2005

Approximate Guidance: Speed


MiCOM

V 735/800kV 380/500kV P442 220/275kV 110/145kV 66/69kV 20/33kV P430 1.5 cyc. 1.25 cyc.
MiCOM
TRIP ALAR M OUT OF SERVIC E H EAL THY EDIT

TRIP ALARM OUT OF SERVI CE HEAL THY EDIT

= = =

CLEA R READ ENTER

G C G

P437

P443

= = =

CLEAR READ ENTER

G C G

Trip Speed 1 cyc.

(Note: P432 one-box solution also available: a derivative of fast P437 relay) Main Protection Backup Protection
3 > MiCOM Distance Protection - Product Selection and Setting Tips - January 2005 3

Approximate Guidance: Characteristics


MiCOM

V 735/800kV 380/500kV 220/275kV 110/145kV 66/69kV 20/33kV P430 Polygon Quad P442
MiCOM
TRIP ALAR M OUT OF SERVIC E H EAL THY EDIT

TRIP ALARM OUT OF SERVI CE HEAL THY EDIT

= = =

CLEA R READ ENTER

G C G

Mho Quad P437 P443

= = =

CLEAR READ ENTER

G C G

Trip Speed

1.5 cyc.

1.25 cyc.

1 cyc.

Mho and/or Quadrilateral Polygon / Quadrilateral


4 > MiCOM Distance Protection - Product Selection and Setting Tips - January 2005 4

Typical HV/EHV Product Selection

Choose P44x family or P437 to give full-scheme relay performance. Choose P441/P442 for a multifunction distance relay for general applications. Offers quadrilateral characteristics, with a proven installed base of products. Choose P437 for high speed tripping on HV/EHV systems, where quadrilateral/polygon characteristics are preferred. Choose P443 where guaranteed sub-cycle tripping is required (mho or quadrilateral), and in any mho characteristic applications.

Mix and match in dual main protection applications!


5 > MiCOM Distance Protection - Product Selection and Setting Tips - January 2005 5

Differences and Similarities

This presentation examines the main areas where each distance relay is set to operate in a particular way:
Reasons for differences Typical settings

To aid the reader, a symbol is used to signify which model the feature relates to:

Flash & symbol to identify P441 / P442 family Flash & symbol to identify P443 MiCOMho Flash & symbol to identify P437

P442 P443 P437

> MiCOM Distance Protection - Product Selection and Setting Tips - January 2005

Distance Zones

> MiCOM Distance Protection - Product Selection and Setting Tips - January 2005

MiCOM Distance Protection Characteristics Available


jX jX Zn R R MHO Zs MemoryPolarised MHO Zn jX

Zn

Zn R Offset MHO

P443

P443

P443

Zn R Quadrilateral

Zn R Polygon

P442
8

P443

P437

P443

P437
8

> MiCOM Distance Protection - Product Selection and Setting Tips - January 2005

Using P442 family relays Setting of Right-Hand resistive reach


Five Quadrilateral Zones X Z3 Zp Z2 Z1 This line serves as the load blinder, and the resistive coverage, in one setting

R Z4 Directional Line

P442
9 > MiCOM Distance Protection - Product Selection and Setting Tips - January 2005 9

Quadrilateral Characteristic Advantages


Zone reach setting (Z) and Resistive reach (R) setting are independent
Allows resistive reach to be set exactly according to the fault arc coverage required No need to rely on characteristic expansion - you get what you set!

Resistive reach setting acts as the load blinder


Makes characteristic applicable to lines of all lengths, without risking load encroachment trips

Characteristic simplicity - easy to test and commission


Resistive reach is constant throughout the length of the zone

P442
10 > MiCOM Distance Protection - Product Selection and Setting Tips - January 2005

P443

P437
10

Zone Reaches and Residual Compensation

11

> MiCOM Distance Protection - Product Selection and Setting Tips - January 2005

11

P443 Easy Setting of Distance Protection Zones


GROUP 1 LIN E PARAM ETERS Line Length Line Impeda nce Line Angle Residua l Comp Residua l Angle M utua l Comp M utua l Angle M utua l cut- off (k) Pha se Rota tion Trip M ode
GROUP 1 DISTAN CE ELEMEN TS PHASE DISTAN CE Z1 Pha se Rea ch Z1 Pha se Angle GROUN D DISTAN CE Z1 Ground Rea ch

%
Easy Set Mode: Automatic Reach Conversion

Z1 Ground Angle Z1 Residua l Comp Z1 Residua l Angle

P443
12 > MiCOM Distance Protection - Product Selection and Setting Tips - January 2005 12

MiCOM Distance Summary

13

> MiCOM Distance Protection - Product Selection and Setting Tips - January 2005

13

P441/P442 Summary

Versatile distance relay for all HV EHV applications Extremely secure - Delta techniques, for fault detection, directionality and phase selection
Patented algorithms used in 3 generations of numerical relays

Overhead line and/or cable applications Efficient use of panel space - size 40TE (P441) or 60TE (P442) Menu-driven software for setting and analysis
Intuitive setting Common Px40 training modules

Comprehensive back up protection

Universal distance protection - with a proven installed base


P442
14 > MiCOM Distance Protection - Product Selection and Setting Tips - January 2005 14

P437 Summary
Distance protection for application up to and including the highest system voltages Design experience - 3rd generation of numerical distance protection from the same design team Proven V<, I>> and shaped Z< starting for high sensitivity
Z< starter acts as a load blinder, to ensure stability when no tripping is wanted

Maintains and manages the stability of the grid


Out of step tripping to control system separation

An ideal complement to P44x family relays in dual-main distance protection applications

Advanced protection and control in a Modular platform


P437
15 > MiCOM Distance Protection - Product Selection and Setting Tips - January 2005 15

P443 MiCOMho Summary


Mho and quadrilateral elements available within one device - line/cable type and length not needed at time of ordering Load blinder avoids spurious or cascade tripping, without desensitising the protection Selectable mho characteristic polarising permits control over expansion - allowing support for compensated and non-compensated applications The relay self-sets zone reaches from protected line data - simple setting mode Superimposed (I) fault and power swing detection requires no starters to be set Easy to set and apply

High Speed Distance Protection Designed for Ease of Application


16 > MiCOM Distance Protection - Product Selection and Setting Tips - January 2005