CMX 220 Installation Guide


Andover Controls Corporation i

www.PDF-Zoo.com

Version D

Reproduction or distribution forbidden. Copyright 1997 by Andover Controls. Subject to change without notice.

Order No. 30-3001-203

Copyright 1997 Andover Controls Corporation 300 Brickstone Square Andover, Massachusetts 01810 All Rights Reserved. Published by the Engineering Department at Andover Controls Corporation.

IMPORTANT NOTICE
This product is subject to change without notice. This document does not constitute any warranty, express or implied. Andover Controls Corporation reserves the right to alter capabilities, performance, and presentation of this product at any time.

ii

CMX 220 Installation Guide

www.PDF-Zoo.com

Preface
The Infinity CMX Installation Guide presents instructions for installing the various CMX controllers on an EnergyNet network. It first presents site preparation information and then step-by-step installation instructions. We recommend you read EnergyNet and Infinet Configuration Guide to plan your entire network before installing a single controller.

Andover Controls Corporation

iii

www.PDF-Zoo.com

iv

CMX 220 Installation Guide

www.PDF-Zoo.com

Contents

Installing the CMX Controller


Site/System Setup Requirements .............................................................2 Cabinet Dimensions .......................................................................4 Power Requirements ......................................................................4 Built-in Modem .............................................................................5 Audio Speaker Connector ..............................................................5 Infinet Cables .................................................................................5 Number of Infinet Controllers on CMX Infinet ............................6 Lightning Protection ......................................................................6 Building Ground Requirements .....................................................7 Inspecting the Ground ....................................................................8 Environmental Requirements ........................................................8 Laying Out the Site Setup ..............................................................8 Installing the CMX Controller ...............................................................10 Unpacking ....................................................................................10 Parts Required ..............................................................................10 Mounting and Wiring ..................................................................10 Connecting the AC Power Cable to the Power Supply ......................................................................12 Finding Ports for Connecting Other Cables .................................13 Connecting the Terminal Screen .................................................14 Connecting to the Built-in Modem ..............................................15

Andover Controls Corporation

www.PDF-Zoo.com

Wiring Infinet to CMX ................................................................16 Connecting the Audio Speaker ....................................................17 Powering Up the CMX ..........................................................................18 Connecting the Battery ................................................................19 Interpreting Status Lights Inside Cabinet ...............................................20 Using the CLEAR MEMORY Button .........................................21 Connecting the Andover Controls Service Tool ..........................21

AppendixRS-232 Port Pinouts

vi

CMX 220 Installation Guide

www.PDF-Zoo.com

Figures
Figure 1. Dimensions and Eyelets for Mounting CMX Controller .....11 Figure 2. Metal Plate and Screw for Power Supply Wire ....................12 Figure 3. Cable Ports and Connectors on the CMX 220 Controller ....15 Figure 4. Infinet Cable Wiring ............................................................16 Figure 5. Audio Speaker Wiring ..........................................................17 Figure 6. System Activity Status Lights ..............................................20 Figure A-1. Pinouts for Cables Connecting to RS-232 Ports on CMX Controller .................................................................. A-3

Andover Controls Corporation

vii

www.PDF-Zoo.com

Tables

Table 1.

Number of Infinet Controllers Allowed on Various Models of CMX ..................................................................... 6

viii

CMX 220 Installation Guide

www.PDF-Zoo.com

Installing the CMX Controller


The Infinity CMX (with or without a built-in modem) is a unique controller. You can connect a terminal to it and program it just as you would an Infinity CX controller, yet it belongs on the Infinet. You can connect four, 16, or 64 Infinet controllers to the CMX, depending on which particular model number you have. From the CMX you can program the Infinet controllers. Every CMX controller has a 2-pin speaker connection where you can connect an audio speaker for use with your modem. You can also connect to a terminal or printer over a modem from the CMX. This manual covers the following: Site/System Setup Requirements Installing the CMX Connecting to the Infinet Powering Up the Controller Interpreting Status Lights inside Cabinet

The appendix gives the pinouts for the RS-232 port cables.

Warranty Registration
Your warranty is effective for 18 months starting on the date the system is shipped.

Infinity CMX Installation Guide

www.PDF-Zoo.com

Site/System Setup Requirements


Before you proceed to install the system, you should map out where you plan to install each controller, terminal/workstation, and modem. When planning the sites, be aware of any electrical interference that may occur. You also need to be aware of cabinet dimensions, power requirements, cable limitations, and environmental requirements.

Warning
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions in this manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Note
This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.

Avis
Le prsent appareil numrique nmet pas de bruits radiolectriques dpassant les limites applicables aux appareils numriques de la class A prescrites dans le Rglement sur le brouillage radiolectrique dict par le ministre des Communications du Canada.

Infinity CMX Installation Guide

www.PDF-Zoo.com

Warning
All wiring and installations must comply with local, state, and national electrical codes.

Warning about Telephone Service


Type of Service: The Infinity CMX controller is designed to be used on standard device telephone lines. It connects to the telephone line by means of a standard jack called the USOC RJ 11C (or USOC FJ45S). Connection to the telephone company provided coin service (central office implemented systems) is prohibited. Connection to party lines service is subject to state tariffs. Telephone Company Procedures: The goal of the telephone company is to provide you with the best service it can. In order to do this, it may occasionally be necessary for them to make changes in their equipment, operations, or procedures. If these changes might affect your service or the operation of your equipment, the telephone company will give you notice, in writing, to allow you to make any changes necessary to maintain uninterrupted service. If you have any questions about your telephone line, such as how many pieces of equipment you can connect to it, the telephone company will provide this information upon request. In certain circumstances, it may be necessary for the telephone company to request information from you concerning the equipment which you have connected to your telephone line. Upon request of the telephone company, provide the FCC registration number and the ringer equivalence number (REN) of the equipment which is connected to your line; both of these items are listed on the equipment label. The sum of all of the RENs on your telephone lines should be less than five in order to assure proper service from the telephone company. In some cases, a sum of five may not be usable on a given line.

Infinity CMX Installation Guide

www.PDF-Zoo.com

Warning about Telephone Service


If Problems Arise: If any of your telephone equipment is not operating properly, you should immediately remove it from your telephone line, as it may cause harm to the telephone network. If the telephone company notes a problem, they may temporarily discontinue service. When practical, they will notify you in advance of this disconnection. If advance notice is not feasible, you will be notified as soon as possible. When you are notified, you will be given the opportunity to correct the problem and informed of your right to file a complaint with the FCC. In the event repairs are ever needed on the Infinity CMX controller, they should be performed by Andover Controls Corporation or an authorized representative of Andover Controls Corporation. For information contact Andover Controls at 300 Brickstone Square, Andover, Massachusetts 01810.

Cabinet Dimensions
Each Infinity CMX cabinet is approximately 11.5 10.6 2.45 in.

Power Requirements
Warning
Be sure your installation complies with local, state, and national electrical codes.

Caution
The CMX should receive power from its own independent, unswitched circuit. The CMX requires 24 VAC +/-20%, 50/60 Hz rated at 20 VA.

Infinity CMX Installation Guide

www.PDF-Zoo.com

Built-in Modem
The built-in modem, an optional feature of the CMX, has a 2400 baud rate.

Audio Speaker Connector


The speaker you may connect can have as much amplification as you want, but you must provide the power for it.

Infinet Cables
The maximum cable length for Infinet is 4,000 ft at 19,200 baud (up to 32 Infinet controllers). You can extend Infinet beyond 4,000 ft or put more than 32 Infinet controllers on less than 4,000 ft by using the InfiLink 200 amplification module. Cables that form Infinet are 24-gauge, single-twisted-pair, tinned, shielded copper wire. Use the following cables1 or their equivalents:

Note
You must use shielded cables for Infinet to ensure compliance with the Class A FCC limits and to communicate reliably. Brand Rex # H 9002 (single-pair) Anixter # 9J2401021 (single-pair plenum cable) The cable should have a nominal impedance of 100 and a nominal velocity of propagation of 78%. Capacitance of Infinet cable should be nominal, below 12.5 pF/ft between conductors and below 22 pF/ft between the conductor connected to ground and the next conductor.

1. You can also use any cables you may already have in place for ACNET or LBUS.

Infinity CMX Installation Guide

www.PDF-Zoo.com

Number of Infinet Controllers on CMX Infinet


You can have up to 64 Infinet controllers on a single CMX Infinet. shows the various model numbers and the number of Infinet controllers you can have on each.The differences between the CMX 220 and the

Table 1. Number of Infinet Controllers Allowed on Various Models of CMX


No. Ctlrs. 4 16 64 Model CMX w/No Command Line Option 220 221 222 Model CMX with Command Line Option 230 231 232

CMX 230 are differences in what you can program them to do. For details, see the Andover Controls Infinity CX Programmers Guide.

Lightning Protection
Warning
When running cables (Infinet or input/output wire) between buildings you must install lightning arresters for Infinet to prevent electromagnetic disturbances. Use lightning arresters at each point where Infinet cable enters or exits a building. Use the following arrester: Two pair gas tube arrester, Andover Controls # 01-2100-299.

Infinity CMX Installation Guide

www.PDF-Zoo.com

Building Ground Requirements


Warning
Be sure that all Infinity products from Andover Controls Corporation are grounded to true earth ground. This kind of ground protects the equipment from voltage transients and other power surges in the area. We cannot guarantee that the controller system will operate as documented unless you properly ground all controllers.

Warning
Be sure to have your grounds inspected before you begin the installation process to be sure your municipality follows the National Electrical Code. Many municipalities do not and often have substandard electrical grounds. An example of a substandard ground is a galvanized steel cold water pipe. As the pipe corrodes, it does not act as a true ground. The corrosion acts as an insulator, raising the potential of the pipe with respect to the ground. When lightning strikes in the area of the installation, it drastically changes the potential of the earth. Since properly grounded Andover Controls units respond to changes in potential more rapidly than poorly grounded electrical systems, a poorly grounded building tries to reach ground through the Andover Controls system. The surge of current can destroy electronic components on the controller board. Surges of much lower potential than lightning also impact the reliability of Andover Controls equipment.

Infinity CMX Installation Guide

www.PDF-Zoo.com

Inspecting the Ground


You can check your ground as follows: 1. Check your ground by first inspecting the building power distribution panel for earth ground termination. If the ground termination is any of the following, it is not adequate and must be corrected: Does not exist. Is connected to a corroded or galvanized pipe. Is connected using a small gauge wire (less than 14 AWG). 2. Be sure your Andover Controls cabinet is connected to the ground with a copper conductor that terminates at the distribution panel.

Environmental Requirements
The CMX controllers operate in rooms with temperatures ranging from 40 to 120F and with humidity between 10 and 95%, noncondensing. The controller must be in an Underwriter Laboratories approved enclosure.

Laying Out the Site Setup


You may want to draw a map of where you plan to put each controller and store it in a notebook. If you have not already done so, read the EnergyNet and Infinet Configuration Guide for information on how to design a configuration. You put only one CMX controller on an Infinet. You connect a terminal to the CMX.1 If your unit has a modem jack, you can instead connect a telephone line from it to a distant terminal (on a modem). If your unit has a modem jack, you can have not only a direct-connected terminal on the RS-232 port, but also a telephone line to a distant terminal (on a modem). However, you can operate only one of the terminals
1. In some situations, you may want to put a printer on CMX instead of a terminal. 8 Infinity CMX Installation Guide

www.PDF-Zoo.com

at any given time. The distant terminal automatically logs out the nearby terminal; so when planning your site, remember you can use only one terminal or the other at a given time and schedule time accordingly. You cannot connect an LBUS to a CMX controller. You cannot have an Infinity CX controller on the same Infinet with a CMX controller. Find the tag attached to each controller that gives the number of the controller. Before you remove any tags, be sure the tag has all of the following information on it: Location of the controller. Serial number. Model name and number. Then collect the tags. Youll need to know where your controllers are located when you later assign a name to each controller and each input and output.

Infinity CMX Installation Guide

www.PDF-Zoo.com

Installing the CMX Controller


Unpacking
Be careful when unpacking the unit to not damage the packaging materialyou must reuse it if you ship the product back for repair.

Parts Required
To install a single controller you start with the following parts: CMX Controller AC Power Cable Infinet Cable Telephone Cable (for connecting to optional built-in modem) Your Own Optional Speaker and Speaker Cable (not provided) RS-232 Cables for Terminal (see the appendix for specifications)

Mounting and Wiring


Caution
You must encase the CMX in a UL approved cabinet to keep its Open Class rating. (STILL NOT APPROVED) Figure 1 shows the back and sides of the controller and the positions of the eyelets for mounting.

Warning
Never drill holes in the CMX cabinet or boards. A metal shaving could easily short circuit the electronics. 1. Pull the cable for a terminal through the middle opening on the left side of the cabinet. 2. Pull cables for Infinet through the lower left side opening. 3. Pull the AC cable through the opening on the top left side of the cabinet.
10 Infinity CMX Installation Guide

www.PDF-Zoo.com

Figure 1. Dimensions and Eyelets for Mounting CMX Controller


0.281 +.003 -.000 Hole Thru Install PEM Self-Clinching Standoff # BSO-8632-24-CI or Equivalent from Farside, 5 Places 2.000 .015 6.550 R .117 Full RAD 4 Places 3.275 .45 4 Places

R .20 4 PLCS 11.50

10.400 8.75

MATERIAL GRAIN

5.200

.23
REF

.90 .55 1.59 9.72 .03 10.54 .05

Infinity CMX Installation Guide

11

www.PDF-Zoo.com

Connecting the AC Power Cable to the Power Supply


Warning
Be sure the controller is not receiving AC power while you are wiring it, or you could receive an electrical shock that is life-threatening. 1. Open the cabinet door. Look to the upper left corner. You should see three screws labeled GND, RET, and 24V. You must wire the AC power to the three screws.

Caution
Be sure to connect all three wires, GND, RET, and 24V. Otherwise, the controller could malfunction. 2. Notice that the three wires at the end of your AC cable are black, white, and green. 3. Place the green wire under the metal plate behind the top screw, labeled GND. 4. Tighten the screw with a flathead screw driver. Figure 2 shows the position of the plate, where to place the wire, and how the screw fits on the plate. You can see how the screw holds the plate in place once you tighten it.

Figure 2. Metal Plate and Screw for Power Supply Wire


Metal Plate

Insert Wire Here

12

Infinity CMX Installation Guide

www.PDF-Zoo.com

5. Place the white wire under the metal plate behind the middle screw, labeled RET. 6. Tighten the screw with a flathead screw driver. 7. Place the black wire under the metal plate behind the bottom screw, labeled 24V. 8. Tighten the screw with a flathead screw driver.

Finding Ports for Connecting Other Cables


Figure 3 shows the inside of the CMX controller.

UserPort
Notice that the CMX has one RS-232 communication port, labeled USERPORT. You can attach a terminal (directly or via a modem) to this port. USERPORT cannot connect to an LBUS or Infinet cable and cannot connect to a modem. You may connect a printer to it, but since it is the only port and a terminal is required, in most situations a terminal belongs there.

Modem Connector (Phone Jack)


The connector labeled MODEM is phone jack (RJ 11) on the left side of the controller. You connect a telephone cable to the phone jack that connects to a modem and either terminal or printer at a distant site.

Infinet Connector
The Infinet connector is just to the left and below from the RS-232 port on the left side of the board.

External Speaker Connector


The speaker connector is the 2-pin connector just below the telephone jack for the modem.

Infinity CMX Installation Guide

13

www.PDF-Zoo.com

Service Port
The port labeled SERVICE PORT connects the Andover Controls Service Tool to the CMX controller. You can carry around the tool and plug it in as required to see how the controller system is functioning. See your Andover Controls representative about availability of the tool.

Connecting the Terminal Screen


Connect the terminal or computer (running an emulation package such as CROSSTALK) to the CMX controller as follows: 1. Set up the terminal or computer on a table within cables length of the controller. 2. Open the front of your controller cabinet. 3. Either purchase a cable with pinouts matching those in the appendix or make one. Use that cable in the next step. 4. Plug one end of the cable into the RS-232 port labeled USERPORT on the CMX. 5. String the cable through the cable hole on the left side of the controller. 6. Plug the other end of the cable into the terminal port.

14

Infinity CMX Installation Guide

www.PDF-Zoo.com

Figure 3. Cable Ports and Connectors on the CMX 220 Controller

Connecting to the Built-in Modem


If your CMX has a built-in modem, you connect a telephone line to the modem as follows: 1. Open your cabinet door and look for the MODEM label. The telephone jack is to the left of it.
Infinity CMX Installation Guide 15

www.PDF-Zoo.com

2. Run telephone cable from the wall jack through the opening on the left side of the controller to the telephone jack (RJ 11 connector).

Wiring Infinet to CMX


You wire the beginning of Infinet to the Infinity CMX controller. After that you wire the Infinet to each Infinet controller.

Note
You must use shielded cables for Infinet to ensure compliance with the Class A FCC limits and to ensure reliable communications. You wire the Infinet to the CMX using the following procedure: 1. Open the front of the controller cabinet. Notice that to the lower left is a port labeled Infinet. Notice that the end of the Infinet cable has two wires and a shield. You wire them to the block terminal connector on the Infinet port. 2. String the cable through the cable hole on the lower left side of the controller. Figure 4 illustrates how to wire the Infinet cable to the removable block terminal connector in the lower left corner of the CMX.

Figure 4. Infinet Cable Wiring


Infinet Connection
WHITE + BLACK SHLD BLACK WHITE

1. Trim back the shield over the wires.

16

Infinity CMX Installation Guide

www.PDF-Zoo.com

2. Take the first wire for the incoming Infinet and the first wire for the outgoing Infinet and slip both in the hole beneath the screw labeled with a plus sign (top). 3. Tighten the screw down on them until the screw holds the wires in place. 4. Slip the second (usually black) wire from each Infinet cable under the screw labeled with a minus sign (middle) and tighten the screw down on them. 5. Slip the shields from the incoming and outgoing Infinet cables under the screw labeled SHLD (bottom) and tighten the screw down on them.

Connecting the Audio Speaker


You may connect any standard audio speaker/amplifier to the 2-pin connector below the phone jack for the modem, as long as you provide the required power for the amplifier. Figure 5 shows how you wire it.

Figure 5. Audio Speaker Wiring


Audio Speaker Connection Signal GND

Infinity CMX Installation Guide

17

www.PDF-Zoo.com

Powering Up the CMX


Before you proceed, be sure the following are correct: 1. Be sure the AC power is wired properly. Check to be sure all three wires have been connected. 2. Be sure the controller has a true earth ground. 3. Be sure you have used the proper cables and correct lengths. 4. Be sure the Infinet has been properly wired. Double check that the ground wire is under the negative screw. 5. Be sure that Infinet cable shields are properly connected. If you have completed all previous sections in this manual and installed all Infinet controllers, you are now ready to power up the CMX controller. To start the controller, turn on the AC power source (or close the power connection) and the controller starts automatically. (The real-time clock is always running on battery power, independent of AC power.) The following occurs (also occurs when you press the CLEAR MEMORY button): 1. The CPU light begins flashing and flashes every 0.2 sec. 2. The TD light immediately starts flashing to show the USERPORT is transmitting data. 3. The INFINET TD light immediately starts flashing to show the Infinet is transmitting data. 4. The RD light begins flashing only if data is being received from the USERPORT. This may not happen immediately. 5. The INFINET RD light begins flashing only if data is being received from Infinet. This may not happen immediately.

18

Infinity CMX Installation Guide

www.PDF-Zoo.com

6. If the CPU light flashes every 0.1 sec, it means the CPU has failed a RAM or ROM test. See the Andover Controls Infinet Controller Troubleshooting Guide.

Connecting the Battery


Once you have closed the AC power connection, you connect the battery. The battery (3.5 V lithium battery) is to the right and below the transformer (the yellow box in the upper left corner). 1. A small plastic tab separates the battery terminal from the controller. 2. Pull out the plastic tab to activate the battery.

Infinity CMX Installation Guide

19

www.PDF-Zoo.com

Interpreting Status Lights Inside Cabinet


Open the cabinet door and you see a string of green, yellow, and red lights, some of them flashing. Figure 6 shows how the lights appear.

Figure 6. System Activity Status Lights


CPU (UserPort) RD (UserPort) TD (Modem Only) CXD INFINET TD SCAN ERROR INFINET RD All these lights, except of course the ERROR light, turn on when the power comes up. The lights blink to indicate activity. The purposes of the five lights are as follows: CPUFlashes every 0.2 sec that the controller is active. RDFlashes every 0.5 sec when the modem is receiving data. TDFlashes every 0.5 sec when the modem is transmitting data. DCDLights up to indicate the modem is sending a carrier detect signal, which means it is on-line.

20

Infinity CMX Installation Guide

www.PDF-Zoo.com

INFINET RDFlashes every 0.5 sec when the Infinet is receiving data. SCANFlashes once for every scan of the controller. ERRORLights up if the controller fails the internal integrity check. INFINET TDFlashes every 0.5 sec when the Infinet is transmitting data.

Using the CLEAR MEMORY Button


The CLEAR MEMORY button is the red button in the lower center of controller. You press the red button only to cold start the controller.

Connecting the Andover Controls Service Tool


The SERVICE PORT, on the far left side of the bottom of the controller, is to connect the Andover Controls Service Tool to an the CMX. The service tool will access all Infinet controllers on the same Infinet. For information on availability of the Andover Controls Service Tool, contact your Andover Controls representative.

Infinity CMX Installation Guide

21

www.PDF-Zoo.com

22

Infinity CMX Installation Guide

www.PDF-Zoo.com

Appendix

RS-232 Port Pinouts


Table A-1 shows the pinouts for the RS-232 port on the Infinity CMX controller. If you choose, you may use a standard 25-pin ribbon cable for connecting a modem to either a controller or a terminal. However, to connect any terminal to a controller, you should use a cable with the required pinouts. Figure A-1 shows the required and optional pinouts for cables connecting a terminal to the controller, a modem to the controller, and a modem to the terminal.

Infinity CMX Installation Guide

A-1

www.PDF-Zoo.com

Table A-1. Pinouts for RS-232 Comm Port1 with Male DB25 Connector to Terminal
Pin Number Purpose 1 2 3 4 5 7 9 10 Chassis TD RD RTS CTS GND +V V Direction --From To From To --From From Required NO YES YES YES YES YES NO NO

1. To and from are in relation to the Infinity CMX controller. A-2 Infinity CMX Installation Guide

www.PDF-Zoo.com

Figure A-1. Pinouts for Cables Connecting to RS-232 Ports on CMX Controller
Female End Connecting to VT 100 or IBM PS/2 (25-pin) 2 3 7 Female End Connecting to Infinity CMX 2 3 7

Female End Connecting to IBM AT (9-pin) 2 3 5

Female End Connecting to Infinity CMX 2 3

7 Female End Connecting to Modem 2 3 4 5 Female End Connecting to ICS AC 220 2 3 4 5

Infinity CMX Installation Guide

A-3

www.PDF-Zoo.com

A-4

Infinity CMX Installation Guide

www.PDF-Zoo.com

Index
A
AC power wiring 12 Andover Controls Service Tool using 21

G
ground correcting 8 inspecting 8 requirements 7

C
cabinet dimensions 4 cable for Infinet 5 for lightning protection 6 Infinet port 13 LBUS port 13 RS-232 pinouts A-1 circuit requirements for power 4 codes complying with 4 communication ports locations of 13 computer connecting 14 configuration planning 8 CPU light inside 20

I
Infinet connecting 16 lightning arrester for 6 Infinet cable connecting 16 Infinet cable numbers 5 INFINET RD light inside 21 INFINET TD light inside 21

L
lightning arrester for Infinet 6

M
modem baud rate of 5 mounting steps to 10

D
DCD light inside cabinet 20 dimensions cabinet 4

P
parts requirements 10 power requirements 4 circuit 4 power surges preventing 7 powerup executing 18 procedure to prepare for 18

E
enclosure Underwriter Laboratories requirements 8, 10 ERROR light inside 21

R F
features unique to CMX 1 RD light inside 20 repair packaging required to ship for 10

TCX 870 Installation Guide

Index-1

www.PDF-Zoo.com

requirements parts 10 RS-232 port pinouts A-1

S
SCAN light inside 21 service port location of 14 purpose of 21 shields for Infinet cable connecting 17 speaker amplification 5

T
TD light inside 20 temperatures for operating 8 terminal connecting 14

U
Underwriter Laboratories enclosure requirements 8, 10

W
wiring connecting Infinet cable 16 correct wire gauge for ground 8

Index-2

TCX 870 Installation Guide

www.PDF-Zoo.com

30-3001-203

Infinity CMX 220 Installation Guide Rev D