Sei sulla pagina 1di 44

Series 101/121 Differential Pressure Switches

Form 468

eld-mounted instruments that incorporate a exible modular design providing cost effective sensing solutions. The two-piece piston design allows for complete differential pressure reversal without damage. See Principle description on page 2.

Series 101/121 differential pressure switches are rugged,

Basic models with standard wetted parts are normally suitable for air, oil, water and non-corrosive process uids. See the Quick Selection Guide on page 4. Corrosive service and special requirements may require optional components. See How to Order on page 3. Series 101/121 differential pressure switches are suited for low-to-high differential pressure, uid power or process applications where high and varying static pressures, high overrange, proof, shock pressure or cycle rates are expected. 101NN 121NN

Application Information

101AG 121AG

101L 121L

sorinc.com sorinc.com 913-888-2630

Registered :2008 RegisteredQuality QualitySystem Systemto toISO ISO9001 9001 :2008

Form 468 913-888-2630 1/20

Series 101/121 Differential Pressure Switch


NC NO C

Principle

Fl

Fh = Force, Hi Pressure Fl = Force, Lo Pressure Fs = Force, Range Spring Fd Fd = Force, Resultant Differential Fd = Fh - (Fl + Fs)
Process pressure is sensed by a diaphragm-piston combination. Hi-side system pressure acts on the piston to product force Fh. It is counteracted by the adjustable range spring force Fs and Lo-side system pressure acting on the backside of the piston to produce force Fl . The resultant force Fd acts on the piston and overcomes the force of the adjustable range spring [Fd = Fh (Fl + Fs)] and moves a shaft that actuates (deactuates) an electrical switching element.

Fh A

Fs

Features and Benets

Modular Design Wide range of electrical enclosures available.


Delivery Routine shipments 7 to 10 working days. Emergency shipments via air same day.

Construction Rugged, high cycle rate tolerance, long life, not critical to vibration, high overrange and proof pressures, withstands full Hi and Lo side pressure reversals, excellent corrosion resistance to hostile environments.

Service Factory service engineers and area factory representatives provide effective and prompt worldwide service.

Wetted Parts Wide selection of materials.

Instrument Quality High repeatability, narrow dead band, negligible temperature effect and static inuence.

Field Adjustable Excellent resolution of Set Points, adjustment, no special tools required. No-charge factory calibration.

Safety Certied to IEC 61508 (SIL) SOR products are certied to IEC 61508 for non-redundant use in SIL1 and SIL2 Safety Instrumented Systems for most models. For more details or values applicable to a specic product, see the Safety Integrity Level Quick Guide (Form 1528).

Warranty 3 years from date of manufacture.


UL, CSA, ATEX, GOST Approved Models Meets most code and customer requirements.

Form 468

2/20

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Series 101/121 Differential Pressure Switch


Model Number System

How to Order

101NN-K3-N4-C1A-YY
Series Housing Switching Adjustable Element Range Diaphragm & O-Ring Pressure Port Accessories

Basic Series 101/121 differential pressure switches with standard wetted parts are normally suitable for air, oil, water and non-corrosive processes. Refer to the Quick Selection Guide section on page 4. Corrosive service and particular customer requirements may require optional components. Refer to the How to Order section on this page or the dedicated page to locate optional components, such as: housings, switching elements, diaphragm systems, pressure ports and accessories. Each position in the model number, except Accessories, must have a designator. The Series 101/121 differential pressure switches in this catalog are suitable for a wide variety of process and uid power applications. Specic application requirements can normally be met by selecting optional components, such as, switching elements and diaphragm systems. Certain applications may require customized specials. Consult local representative or the factory. Weathertight, conventional explosion proof and hermetically sealed explosion proof models are presented in this catalog.

Quick Selection Guide

Applications

Steps 1 through 5 are required; Step 6 is optional. Orders must have complete model numbers, i.e. each component must have a designator. Order information must include: a) Set Point (increasing or decreasing) b) If decreasing Set Point, state from what greater Set Point is approached c) Normal system (static) pressure Step 1: Select Housing for type of service (pages 5 & 6). Step 2: Select electrical Switching Element for housing and electrical service (pages 6 & 7). Step 3: Select Adjustable Range according to Set Point (page 8). Step 4: Select Diaphragm and O-Ring for process compatibility and containment (page 9). Step 5: Select Pressure Port for process connection (page 9). Step 6: Select Accessories as required for service (page 10). If Agency Listed, Certied or Approved differential pressure switches are required, see page 11 for components that must be specied.
sorinc.com 913-888-2630 Form 468 Registered Quality System to ISO 9001 :2008

How to Order

3/20

Series 101/121 Differential Pressure Switch


Specify model number from table below.
Typical Dead Band (psi) 0.5 15 amps 250 VAC

Principle

Model Number

Range (psid)

Electrical Rating

Electrical Connection

Housing Material

101NN - K3 - N4 -C1A

3 to 30

101NN - K45 - N4 - C1A


Weathertight NEMA 4, 4X, IP65

10 to 75

1.5

3/4 NPT(F)

Aluminum

121NN - K45 - N4 - C1A

75 to 500

10

101L - K3 - N4 - C1A

3 to 30

0.5 15 amps 250 VAC

101L - K45 - N4 - C1A


Hazardous Locations Class I, Groups C & D; Class II, Groups E, F & G; Divisions 1 & 2

10 to 75

1.5

3/4 NPT(F)

Cast Iron

121L K45 - N4 - C1A

75 to 500

10

101AG - EF3 - N4 - C1A

3 to 30

1.0 15 amps 250 VAC 1/2 NPT(M)

101AG - EF45 - N4 - C1A


Hazardous Locations Class I, Groups A, B, C & D; Class II, Groups E, F & G; Divisions 1 & 2

10 to 75

3.0

Aluminum

121AG - EF45 - N4 - C1A

75 to 500

20

Product Specications
Pressure Port Maximum Working Pressure 101 121 1/4 NPT(F) 500 psi 1,000 psi Wetted Materials Diaphragm O-Ring Pressure Connection Teon-Coated Polyimide Buna-N 316SS; CF-8M Cast Alloy

Design and specications are subject to change without notice. For latest revision, see www.sorinc.com.

Form 468

4/20

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Series 101/121 Differential Pressure Switch


General Purpose NEMA 1
Electrical: 3/4 NPT(F)-Right Material: Aluminum Electrical: 3/4 NPT(F)-Left, Right Material: Aluminum

Step 1: Housing

101NN-K3-N4-C1A-YY

Electrical: Exposed Contacts Material: Aluminum

PP

P3

Open bracket with exposed switching element does not meet NEMA 1.

See Agency Listings page 11. See Switching Element Groups 1, 2, 3, 4 page 6.

See Switching Element Groups 1, 2, 3, 4 page 6.

See Switching Element Groups 1 & 3 page 6.

H3

Weathertight NEMA 4, 4X, IP65


Electrical: 3/4 NPT(F)-Right Material: Aluminum

NN
See Agency Listings page 11. See Switching Element Groups 1, 2, 3, 4 page 6.

Electrical: 3/4 NPT(F)-Left, Right Material: Aluminum

N3

Electrical: 3/4 NPT(F)- Right Material: Aluminum Cover: heavy duty with Viton gasket

See Agency Listings page 11. See Switching Element Groups 1, 2, 3, 4 page 6.

See Agency Listings page 11. See Switching Element Groups 1, 2, 3, 4 page 6.

N4

Electrical: 3/4 NPT(F)-Right Material: Carbon Steel

N6
See Switching Element Groups 1 & 3 page 6.

RN RM

Electrical - RN: 3/4 NPT(F)-Right Electrical - RM: M20 x 1 .5 - Right Six-place compression type terminal block. Material: Aluminum
See Agency Listings page 11. Switching Element Groups 1, 2, 3, 4, 5 page 6.

RT RS

Electrical-RT: 3/4 NPT(F)-Right Electrical-RS: M20 x 1.5-Right Six-place compression type terminal block Material: 316SS
See Agency Listings page 11. Switching Element Groups 1, 2, 3, 4, 5 page 6.

Electrical: 3/4 NPT(F)-Right Manual reset only Six-place compression type terminal block Material: Aluminum

See Agency Listings page 11. See Switching Element Group 7 page 6.

RB

Hazardous Locations Hermetically Sealed Switches


Contains UL Listed, CSA Certied, ATEX and SAA Approved hermetically sealed switching element. Contains UL Listed, CSA Certied, ATEX and SAA Approved hermetically sealed switching element. Contains UL Listed, CSA Certied and SAA Approved hermetically sealed switching elements. Electrical: 3/4 NPT(F)-Top Material: Copper-free** aluminum Weathertight: NEMA 4/4X

Electrical: 1/2 NPT(M)-Top Material: Copper-free** aluminum

Electrical: 1/2 NPT(M)-Top

See Switching Element Group 5 page 6. UL Listed Class I, Groups C & D; Class II, Groups E, F & G; Divisions 1 & 2 as an outlet box only. Electrical: 3/4 NPT(F)-Right Material: Cast Iron Weathertight with Option CG

AG

See Switching Element Group 5 page 6. UL Listed Class I, Groups C & D; Class II, Groups E, F & G; Divisions 1 & 2 as an outlet box only. Electrical: 3/4 NPT(F)-Right Six-place compression type terminal block with Option LL Material: Copper-free** aluminum Weathertight

AH

Material: 316SS

See Switching Element Group 6 page 6.

*BA

Hazardous Locations Conventional Explosion Proof


Separate electrical and set point adjustment compartments. Weathertight Six-place compression type terminal block UL Listed with WV option. ATEX Approved with CL option. CSA Certied with CS option. Multi-Listed with ML option. See page 11. Electrical: 3/4 NPT(F)-Left, Right Material: Aluminum

See Switching Element Groups 1 & 3 page 6. UL Listed Class I, Groups C & D; Class II, Groups E, F & G; Divisions 1 & 2 as an outlet box only. Electrical: 3/4 NPT(F)-Left, Right, Top Material: Cast Iron Weathertight with Option CG

*L

See Switching Element Groups 1, 2, 3, 4 page 6. UL Listed Class I, Groups C & D; Class II, Groups E, F & G; Divisions *B3 1 & 2 as an outlet box only. Electrical: 3/4 NPT(F)-Left, Right, Top Six-place compression type *B4 terminal block with Optional LL Material: Copper-free** aluminum Weathertight

*LC

Electrical: M20 x 1.5, Left, Right Material: Aluminum

*S

See Switching Element Groups 1, 2, 3, 4, 7 page 6. See Switching Element Groups 1 , 3, 7 page 6. Class I, Groups A, B, C, D; Class II, Groups E, F, G; Divisions 1 & 2 as an outlet box only. Electrical: 3/4 NPT(F)-Left, Right, Top Material (Housing): Aluminum Material (Cover): Aluminum Line Mounted. Weathertight with Option CG. *TA See Switching Element Groups 1 & 3 page 6.

*SC

*B5 *B6

Electrical: M20 x 1.5, Left, Right Material: Cast Iron

Electrical: 3/4 NPT(F)-Left, Right Material: Cast Iron

Switching Element Groups 1, 2, 3, 4, 5 page 6.

* Not recommended for direct mount where vibration is expected. Housing should be securely mounted to a at surface (bulkhead or panel rack) or pipe stanchion. ** Consult the factory.
sorinc.com 913-888-2630 Form 468 Registered Quality System to ISO 9001 :2008

5/20

Principle

Series 101/121 Differential Pressure Switch


Switching Element Group / Housing Compatibility
Group 1 2 Group Group 3

Step 1: Housing

101NN-K3-N4-C1A-YY
Group 5

Group 4

Group 6 EB, JB, JR, KB

Group 7

A, AA, B, BB, C*, E, GG, KK, LL, YY T EE, G, J, JJ, K, KA, L, S, W, Y *C micro switch is not available in L, S, and TA housings

AF, AG, EF, EG, JF, JG

D, M

Step 2: Switching Element


DC Rating Resistive Volts 125 125 125 125 125 Amps .4* .5 .5* .5* .5 1.5
Minimum Maximum

101NN-K3-N4-C1A-YY
Dead Band Multiplier SPDT 1 1 1.5 2 2 2.5 1.5 3.5 DPDT 4 3.5 4 4 4.5 3 Designator SPDT K KA J G A L E C DPDT KK N/A JJ GG AA LL EE N/A

Switching Element Service Normal Service AC Low Power Gold Contacts Wide Dead Band AC AC or DC Wide Dead Band DC Narrow Dead Band DC Very Wide Dead Band DC Very HighCapacity DC Magnetic Blow-Out Hi-Ambient Temperature Rating - 400F Wide Adjustable Dead Band Narrow Adjustable Dead Band Manual Reset Decreasing Pressure (Automatic Actuation Increasing Pressure) Manual Reset Increasing Pressure (Automatic Actuation Decreasing Pressure) Corrosion Resistant Explosion Proof Hermetically Sealed Switching Element Corrosion Resistant Explosion Proof Lower Power Service Hermetically Sealed Gold Contacts ATEX Approved II 2 G EEx d IIC Microswitch Only Form 468

Electrical Contact Type

Electrical Connection Type

AC Rating Volts 250 125 125 Amps 15 1 1 15 11 15 5 15

Volts 30 28 30 30 30 30 -

Amps 5* 1* 1 5 10* 5* -

Single Switching Element SPDT -(1) SPDT Double Switching Element DPDT - (2) SPDT Simultaneous actuation/deactuation at increasing/decreasing Set Points.

250 250 250 250 250

K, KA, G, L, C, N, S, Y, W Switching Elements - Screw Terminals. All other switching elements - 18 18 AWG color-coded wire leads except when terminal blocks are specied.

125 250 250 250 250 250

10 5 5 5 15 15

125 125 125 125 125 -

10 .3

3.5 2 1.5 1 2.5 to 5 1 to 3

4 3.5 -

S B Y W T H

N/A BB YY N/A N/A N/A

.5* .3* .4* -

D 250 15 125 .5 1.5 M 250 250 250 250 125 125 125 15 5 11 5 1 1 1 125 125 125 125 .4* .5* .5 .5* 30 30 30 30 28 30 30 5* 5* 5 5* 1* 1 1 1.5 3 2 1.5 2.5 3.5 5 3.5 4 4 KB N/A AF EF JR N/A JF

N/A

N/A N/A EB AG EG N/A JB JG

250

250

0.25

30

BD

N/A

Cross reference compatibility chart above to ensure that switching element will t in housing. 6/20
Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Series 101/121 Differential Pressure Switch


Notes 1. AC/DC electrical ratings for switching elements K, KK, KA, J, JJ, G, GG, A, AA, L, LL, E, EE, C, S, B, BB, Y, YY, W, T, H, D and M are UL Recognized and CSA Certied with conditions and exceptions specied in Note 3. 2. The hermetically sealed switching element capsule is UL Listed, CSA Certied, ATEX and TestSafe Approved as a snap switch in accordance with the following table with conditions and exceptions specied in Note 3.
Agency
UL Listed CSA Certied TestSafe Approved ATEX Approved

Step 2: Switching Element

101NN-K3-N4-C1A-YY
4. DPDT switching elements have wire leads except when supplied in housings RN, RT, RM, RS, RB, B3, B4, B5, B6. 5. Switching element minimum/maximum ambient temperatures: -40 to 167oF (-40 to 75oC) AF, AG, EB, EF, EG, JB, JF, JG, JR, KB -65 to 400oF (-54 to 204oC) B, Y, W -65 to 250oF (-54 to 120oC) A, E, J -65 to 180oF (-54 to 80oC) All others 6. Dead band multipliers must be applied to the typical dead band gures given in the specication tables on page 8. 7. Switching elements B, W and Y have an Elgiloy spring. Experience indicates good service in atmospheres with corrosive gases - H2S, ammonia, etc. CAUTION: The switching element assembly has been precisely positioned in the housing at the factory for optimum performance. Any inadvertent movement or replacement in the eld will degrade performance, could render the device inoperative and may void the warranty unless factory authorized procedures are followed.

Hazardous Location Conditions


Class I, Groups A, B, C & D; Class II, Groups E, F & G; Divisions 1 & 2 Ex s Zone 2 IIC T4 IP65 Ex tD A22 T105C IP65 II 2 G EEx m II

Designator
AF, EF, AG, EG, KB, EB, JB, JF, JG, JR AF, EF, AG, EG, KB, EB AF, EF, AG, EG, JF, JG

3. DC electrical ratings are for resistive loads only. DC ratings marked with an asterisk (*) are not agency recognized or certied but have been veried by testing or experience.

sorinc.com 913-888-2630

Form 468 Registered Quality System to ISO 9001 :2008

7/20

Series 101/121 Differential Pressure Switch

Step 3: Adjustable Range

101NN-K3-N4-C1A-YY
This table lists designators for corresponding adjustable ranges, dead bands, maximum system pressure and maximum differential pressure. Adjustable range is expressed for increasing pressure: the Set Point must be within the adjustable range. Dead band is expressed as typical at mid-range. See dead band considerations at the bottom of this page.
Series and 4th Designator
(see example)

Adjustable Range
(increasing pressure)

Typical Mid-Range Dead Band psi .5 1.5 10 bar .03 .10 .7

Maximum System Pressure psi 500 1000 bar 34 69

Maximum Differential Pressure psid 500 1000 bar 34 69

psid 3 to 30 10 to 75 75 to 500

bar .2 to 2.1 .7 to 5.2 5.2 to 34.5

101 - 3 101 121


- -

45 45

Notes 1. Ambient temperature range: -30 to 180oF (-34 to 80oC). Check restrictions, page 7, for optional electrical switching elements and page 9 for optional diaphragm systems. 2. Metric bar (mbar) values are practical equivalents of the mathematical conversions. This data appears on the product nameplate when metric engineering units are specied.

3. CAUTION: When the process could be considered dirty in terms of suspended particles, it is recommended that 20-micron in-line lters be installed on the Hi and Lo pressure ports. 4. To achieve optimum performance, the 101/121 should be calibrated under simulated system operating conditions.

Dead Band Considerations


1. Dead band values are expressed as typical expected at mid-adjustable range and 50% maximum system pressure (static pressure) using the standard K switching element. 2. Dead bands are xed (non-adjustable), except when T or H switching elements are used. 3. A dead band multiplier must be applied to the typical dead band value shown in adjustable range above whenever an optional switching element is specied. 4. Dead band can be widened by selecting an optional switching element with a multiplier greater than 1.0. 5. Use of metal diaphragms may have additional impact on Dead band values. Contact the factory for details. Example: Model 101NN-G3-N4-C1A Typical Dead Band 0.7 psid G-Switching Element muliplier 2 Corrected Typical Dead Band 0.7 x 2 = 1.4 psid
Switching Element Designators K, KA, W D, E, J, JR, KB, M, Y A, B, EF, G L, YY, JF AF, EE C, EB, EG, JJ, S AA, BB, GG, JB, JG, KK LL AG T (Adjustable) H (Adjustable)
Form 468

Dead Band Multiplier 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 2.5 to 5.0 1.0 to 3.0
sorinc.com 913-888-2630

8/20

Registered Quality System to ISO 9001 :2008

Series 101/121 Differential Pressure Switch


Material & Systems
O-Ring (wetted) Viton Buna-N Viton Viton Buna-N Viton Diaphragm (wetted primary) Hastelloy-B 316SS TCP Teon-Coated Polyimide Viton

Step 4: Diaphragm & O-Ring

101NN-K3-N4-C1A-YY
Designator H4 M2 M4 N1
Standard

N4 S1

Notes 1. N4 diaphragm system is standard. It is normally suitable for air, oil, water and non-corrosive processes. 2. Other diaphragm and o-ring combinations may be available. Consult the factory or the SOR representative in your area for more information. 3. Wetted parts have been selected as representing the most suitable commercially available material for use in the service intended. However, they do not constitute a guarantee against corrosion or permeation, since processes vary from plant to plant and concentration of harmful uids, gases or solids vary from time to time in a given process. Empirical experience by users should be the nal guide. Alternate materials based on this are generally available.

4. Differential pressures exceeding 100 psid may affect Set Point when M2, M4, or H4 diaphragm and o-ring combination is used. 5. Dead bands are higher when using metal diaphragm options. Consult the factory. 6. This table shows allowable minimum and maximum temperatures for o-rings.

O-Ring Material Viton Buna-N TCP-Teon Coated Polyimide Diaphragm

F 32 to 400 -32 to 200 -30 to 400

C 0 to 204 -34 to 93 -34 to 204

Step 5: Pressure Port

101NN-K3-N4-C1A-YY
Material 316SS; CF-8M Cast Alloy Connection Size 1/4 NPT(F) 1/4 BSP(F) Designator C1A C1B

Notes 1. C1A pressure port is standard. It is normally suitable for air, oil, water and non-corrosive processes.

2. Other pressure port materials and connection sizes may be available. Consult the factory or the SOR representative in your area for more information.

sorinc.com 913-888-2630

Form 468 Registered Quality System to ISO 9001 :2008

9/20

Series 101/121 Differential Pressure Switch


Accessory/Option & Description
Wetted parts are cleaned for industrial oxygen service. ATEX Approved differential pressure switch. See Agency Listings on page 11 for details.

Step 6: Accessories

101NN-K3-N4-C1A-YY
Designator
BB CL CS CG CV DS GC GG KK LL ML PK PP PY RR SB TB TT VV WV X YY ZZ

CSA Certied differential pressure switch. Available with PP, NN, RB, RN, RT, B3 and B6. Housing has earth (ground) lug. See Agency Listings on page 11 for details. Neoprene cover gasket (o-ring) to make L, S and TA explosion proof housings weathertight. Canadian Registration Number (CRN) - Process ratings may be affected. Consult the factory for details. CSA Dual Seal Approval. See Agency Listings on page 11 for details Cemented cover gasket on weathertight housings. Sealed electrical lead adapter. Provides protection to housing interior, switching element and dry side of pressure sensing assembly from condensate in the electrical conduit and corrosive atmospheres. (Protrudes approximately 2 from housing.) Breather Drain Crouse Hinds ECD-15 for Hazardous Locations Class I, Groups C & D, Class II, Groups E, F & G; on S or SC housings only. Sintered metal plug in weathertight housing.

Terminal block. 6-place compression type standard in B and R series housings. Optional in LC and SC housings. Multi-Listed differential pressure switch. ATEX, CSA & UL. Available with B3 & B6 housings. See Agency Listings on page 11 for details. Pipe (stanchion) mounting kit for (1-1/2 to 2 pipe). Order as a separate line item for UL Listed and CSA Certied pressure switches. Tag, ber. Attached with plastic wire to housing. Stamped with customer specied tagging information. Powder coat epoxy coating. No coating on stainless steel parts or plated screws. (500 hours-salt spray) Tag, stainless steel. Attached with stainless steel wire to housing. Stamped with customer specied tagging information. (2 lines, 18 characters and spaces per line.) Stainless steel body, force transmitter and adjusting nut for corrosive environments. Standard on stainless steel housings. Explosion proof weathertight electrical junction box with screw terminals. Aluminum 3/4 NPT(F) top or right conduit connections as required. UL Listed and CSA Certied Class I, Groups A, B, C & D; Class II, Groups E, F & G; Divisions 1 & 2. (L, LC, S, SC and TA housing.) Includes cover o-ring for weathertight applications. Oversize stainless steel nameplate or separate stainless steel tag. Permanently attached to housing. Stamped with customer specied tagging information. Fungicidal varnish. Covers exterior and interior except working parts. UL Listed differential pressure switch. Available with B3 and B6 housings. See Agency Listings on page 11 for details. X is used as a sufx to the model number for special requirements not keyed elsewhere in the model number by an X. Each X must by completely identied in the text of the order or inquiry. When more than one X is required, use X followed by the number of such items. For example, X3 means three separate otherwise unidentiable requirements. Epoxy coating. Exterior only. Polyamide epoxy with 316SS pigment (200 hours-salt spray). Chained cover with captive screws to conform to former JIC specication.

Representative Information Only: A slash and a three-digit number (/000) appearing after the last accessory designator letter in the model number denotes special administrative procedures with respect to factory representatives. It is not part of the model number and is used only by the factory or a factory representative.

Test Certicates
Certicates Calibration Hydrostatic Pressure Test Inspection Report Compliance / Conformance Dielectric Test Insulation Resistance Typical Material of Wetted Parts Form 468 C1 C2

C3

C4

C5

C6

C8

B1

B4

B5

B6

B7

A1

A2

A3

A4

A5

A6

A7

A8

10/20

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Series 101/121 Differential Pressure Switch


UL
Piston Housing Switching Element A, AA, AF, AG, B, BB, C, E, EE, EF, EG, G, GG, H, J, JF, JG, JJ, K, KA, KK, L, LL, P, S, T, W, Y, YY Spring Diaphragm & O-Ring

Agency Listings

For Hazardous Locations Class I Groups B, C, D; Class II, Groups E, F, G; Divisions 1 & 2 Pressure Port Material & Connection Size Accessories WV or ML Required ALL ALL ALL All except CG, GC, GG, HB, HT, KK, LL, ME, TB, ZZ

ALL

B3, B6

CSA

For Hazardous Locations Class I, Groups A, B, C, D; Class II, Groups E, F, G; Divisions 1 & 2 Piston Housing Switching Element A, AA, AF, AG, B, BB, C, E, EE, EF, EG, G, GG, H, J, JF, JG, JJ, K, KA, KK, L, LL, P, S, T, W, Y, YY Spring Diaphragm & O-Ring Pressure Port Material & Connection Size Accessory CS or ML Required ALL ALL ALL All except CG, GC, GG, HB, HT, KK, LL, ME, TB, ZZ

ALL

B3, B6

For General Purpose and Weathertight (CSA Enclosed 4) PP (General Purpose) NN (Enclosed 4), N6 101 RN (Enclosed 4) RM, RT, RS RB (Enclosed 4) For Dual Seal Approval ALL AG, AH AF, AG, EF, EG, JF, JG ALL M2, M4, N4 C1A, C2A DS Required CV, PP, RR, TT, YY A, AA, B, BB, C, E, EE, G, GG, GA, H, J, JJ, JL, K, KK, KA, L, LL, N, S, T, W, Y, YY A, AA, AF, AG, B, BB, C, E, EE, EF, EG, G, GG, GA, H, J, JJ, JL, JF, JG, K, KK, KA, L, LL, N, S, T, W, Y, YY D, DA, M (Manual Reset only) ALL ALL ALL CS Required

All except GC, LL

ATEX

EEx d IIC T6/T5 Piston Housing Switching Element Spring Diaphragm & O-Ring Pressure Port Material & Connection Size Accessory CL (for all Hsgs) or ML (for B3/B6 Hsgs) Required ALL ALL ALL All except CG, GC, GG, HB, HT, KK, LL, ME, TB, ZZ

ALL

B3, B4, B5, B6

A, AA, AF, AG, B, BB, C, E, EE, EF, EG, G, GG, H, J, JF, JG, JJ, K, KA, KK, L, LL, P, S, T, W, Y, YY

Ex ia IIC T6...T4 Gb ALL RN, RM, RT, RS J, JJ, JF, JG ALL ALL ALL CL

sorinc.com 913-888-2630

Form 468 Registered Quality System to ISO 9001 :2008

11/20

Series 101/121 Differential Pressure Switch

Manual Reset

101RB-D3-N4-C1A-YY
Series 101/121 Differential Pressure Switches in this catalog may be specied with manual reset electrical switching elements D or M. D actuates automatically on increasing pressure. M actuates automatically on decreasing pressure. Depress the button, covered by the weathertight boot to manually reset. Housings must be RB weathertight or S explosion proof because of the requirement of a hub for the manual reset assembly. Refer to page 3 for order instructions. RB-Weathertight S-Explosion Proof

Approximate Weights
Housing AG, H3 AH, NN, N3, N4, PP, P3 RM, RN BA, N6, RB RT L, LC, SC TA B3. B4 B5, B6 Weight (lbs.) 2.5 3 3.5 4 4.5 5 5.5 9 11 (kgs) 1.25 1.5 1.75 2 2.25 2.5 2.75 4.5 5.5 Accessory PK Pipe Kit TB Junction Box with Terminal Block Add (lbs.) 1.5 5 (kgs) 0.7 2.25

Actual shipping weights may vary from the charted values because of product material, conguration and packaging requirements.

Form 468

12/20

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Series 101/121 Differential Pressure Switch

Glossary of Terms

SOR recognizes that there is no industry convention with respect to terminology and denitions pertinent to pressure switches. This glossary applies to SOR Pressure Switches. Adjustable Range The span of pressure between upper and lower limits within which the pressure switch may be adjusted to actuate/deactuate. It is expressed for increasing differential pressure. Dead Band The difference in pressure between the increasing Set Point and the decreasing Set Point. It is expressed as typical, which is an average with the increasing Set Point at midadjustable range for a pressure switch with the standard K switching element. It is normally xed (nonadjustable). Differential Pressure Switch A bi-stable electromechanical device that actuates/deactuates one or more electrical switching element(s) at a predetermined discrete differential pressure (Set Point) upon rising or falling differential pressure. DPDT Switching Element DPDT is two synchronized SPDT switching elements that actuate together at increasing Set Point and deactuate together at decreasing Set Point. Discrete SPDT switching elements allow two independent circuits to be switched; i.e., one AC and one DC. The synchronization linkage is factory set, and is not eld adjustable. Synchronization is veried by connecting test lamps to the switching elements and observing them go On simultaneously at actuation and Off simultaneously at deactuation Hermetically Sealed A welded steel capsule with glass-to-metal, factory-sealed, electrical leads that isolates the electrical switching element(s) from the environment. Maximum Differential Pressure The maximum difference in pressure that may be continuously applied between the Hi and Lo (Lo and Hi) pressure ports without causing permanent change of Set Point, leakage or material failure. Overrange The maximum input pressure that may be continuously applied to the pressure switch without causing permanent change of Set Point, leakage or material failure. Proof Pressure The maximum input pressure that may be continuously applied to the pressure switch without causing leakage or catastrophic material failure. Permanent change of Set Points may occur, or the device may be rendered inoperative. Repeatability The ability of a pressure switch to successively operate at a Set Point that is approached from a starting point in the same direction and returns to the starting point over three consecutive cycles to establish a pressure prole. The closeness of the measured Set Point values is normally expressed as a percentage of full scale (maximum adjustable range pressure). Set Point That discrete pressure at which the pressure switch is adjusted to actuate/deactuate on rising or falling pressure. It must fall within the adjustable range and be called out as increasing or decreasing differential pressure. SPDT Switching Element Single-Pole, Double Throw (SPDT) has three connections: C Common, NO Normally Open and NC Normally Closed, which allows the switching element to be electrically connected to the circuit in either NO or NC state.
Form 468 Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

13/20

Series 101/121 Differential Pressure Switch

Dimensions

Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certied drawings for a particular model number. Dimensions are expressed as millimeters over inches (Linear = mm/in.)

Weathertight - Nonhazardous Service (NEMA 4, 4X IP65)

Drawing 0090603

Housing: N6
SALES PAGE MODEL # SALES ORDER # LINE ITEM # PURCHASE ORDER #
1

108.1 4.25 52.4 2.06 69.9 2.75 33.3 1.31 ** 56.5 2.22 28.6 1.13 26.1 1.03

ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT (BOTH SIDES ON N3 & P3 HSGS)

PROCESS CONNECTION SIZE 1/4 NPTM SHOWN 1/2 NPTF 1/2 NPTM 3/4 NPTF

LENGTH A 29.7 1.17 37.6 1.48 34.8 1.37 39.9 1.57

154.1 6.07

CLEARANCE SLOTS 6.4 FOR HARDWARE WITH 0.25 63.5 76.2 MIN TO MAX 2.50 3.00 MOUNTING CENTERS

40.5 1.59

HOUSING GROUP NN & N3 N4 PP & P3

** DIMENSION SHOWN 4.6 0.18 1.5 SUBTRACT 0.06 ADD

61.9 2.44 28.6 1.13

7.1 0.28

ISO-9001

14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM


DRAWN BY

PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN

K MITCHELL
CHECKED BY

J REHM
ENGINEER APPROVAL

J MODIG
DATE

A TYP

1/4 NPTF LO SIDE PROCESS CONNECTION


TITLE

10 OCT 2011
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR.

Drawing 0090602
Form 468

38.1 1.50

1/4 NPTF HI SIDE PROCESS CONNECTION

DIMENSION DRAWING 101/121 NN, N3, N4, PP & P3 EO NUMBER: 5123


DRAWING NUMBER REV

60.3 2.38

SCALE: 1.00
DO NOT SCALE PRINT

0090602 SHEET 1 OF 1

3
DWG SIZE

Model Name: 0090602.ASSEM/2/2

Reset Form

Housing: NN, N3, N4


14/20
Registered Quality System to ISO 9001 :2008 sorinc.com 913-888-2630

Series 101/121 Differential Pressure Switch

Dimensions

Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certied drawings for a particular model number. Dimensions are expressed as millimeters over inches (Linear = mm/in.)

Weathertight - Non-hazardous Service (NEMA 4, 4X IP65)

Drawing 0090604

Housing: RB Manual Reset


MODEL # SALES ORDER # LINE ITEM # PURCHASE ORDER #

SALES PAGE

107.3 4.22 52.0 2.05 69.9 2.75 33.3 1.31 65.6 2.58 28.6 1.12 26.2 1.03 HOUSING RL RM RN ELECTRICAL CONNECTION SEE CHART RS RT ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT LH & RH M20 X 1.5 F RH ONLY 3/4 NPTF STD 1/2 NPTF OPT RH ONLY M20 X 1.5 F RH ONLY 3/4 NPTF STD 1/2 NPTF OPT RH ONLY 3/4 NPTF STD 1/2 NPTF OPT LH & RH M20 X 1.5 F LH & RH M20 X 1.5 F LH & RH

179.1 7.05 CLEARANCE SLOTS 6.4 FOR HARDWARE 0.25 WITH

RU 40.5 1.59 RW RY

63.5 76.2 MIN TO MAX 2.50 3.00 MOUNTING CENTERS

61.9 2.44 28.6 1.13 1/4 NPTF HI SIDE PROCESS CONNECTION 1/4 NPTM PROCESS CONNECTION OPTIONAL

1/4 NPTF LO SIDE PROCESS CONNECTION

ISO-9001

14685 W 105TH ST LENEXA, KS 66215 U 913-888-2630 SORINC.COM


DRAWN BY

PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN

K MITCHELL
CHECKED BY

M SMITH S BOAL
DATE

ENGINEER APPROVA

17 OCT 201
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR.
TITLE

29.7 1.17 TYP

DIMENSION DRAWING 101/121 R-SERIES HOUSING

Drawing 0090605

38.1 1.50

7.1 0.28

EO NUMBER: 5123 SCALE: 0.85


DO NOT SCALE PRINT

DRAWING NUMBER

REV

0090605 SHEET 1 OF 1

DWG

Housing: RM, RN, RS, RT


Model Name: 0090605.ASSEM/3/3+

Reset F

sorinc.com 913-888-2630

Form 468 Registered Quality System to ISO 9001 :2008

15/20

Series 101/121 Differential Pressure Switch

Dimensions

Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certied drawings for a particular model number. Dimensions are expressed as millimeters over inches (Linear = mm/in.)

General Purpose - Non-hazardous Service

Drawing 0090601

Housing: H3 Open Bracket


SALES PAGE MODEL # SALES ORDER # LINE ITEM # PURCHASE ORDER #
1

108.1 4.25 52.4 2.06 69.9 2.75 33.3 1.31 ** 56.5 2.22 28.6 1.13 26.1 1.03

ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT (BOTH SIDES ON N3 & P3 HSGS)

PROCESS CONNECTION SIZE 1/4 NPTM SHOWN 1/2 NPTF 1/2 NPTM 3/4 NPTF

LENGTH A 29.7 1.17 37.6 1.48 34.8 1.37 39.9 1.57

154.1 6.07

CLEARANCE SLOTS 6.4 FOR HARDWARE WITH 0.25 63.5 76.2 MIN TO MAX 2.50 3.00 MOUNTING CENTERS

40.5 1.59

HOUSING GROUP NN & N3 N4 PP & P3

** DIMENSION SHOWN 4.6 0.18 1.5 SUBTRACT 0.06 ADD

61.9 2.44 28.6 1.13

7.1 0.28

ISO-9001

14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM


DRAWN BY

PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN

K MITCHELL
CHECKED BY

J REHM
ENGINEER APPROVAL

J MODIG
DATE

A TYP

1/4 NPTF LO SIDE PROCESS CONNECTION


TITLE

10 OCT 2011
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR.

Drawing 0090602
Model Name: 0090602.ASSEM/2/2

38.1 1.50

1/4 NPTF HI SIDE PROCESS CONNECTION

DIMENSION DRAWING 101/121 NN, N3, N4, PP & P3 EO NUMBER: 5123


DRAWING NUMBER REV

60.3 2.38

SCALE: 1.00
DO NOT SCALE PRINT

0090602 SHEET 1 OF 1

3
DWG SIZE

Housing: PP, P3 NEMA 1


Form 468

Reset Form

16/20

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Series 101/121 Differential Pressure Switch

Dimensions

Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certied drawings for a particular model number. Dimensions are expressed as millimeters over inches (Linear = mm/in.)

Conventional Explosion Proof - Hazardous Service


Class I, Group C, D; Class II, Group E, F, G: Divisions 1 & 2

MODEL #

SALES ORDER #

LINE ITEM #

PURCHASE ORDER #

108.0 4.25 (TYP)

149.5 5.88 71.4 2.81 54.0 2.13 (TYP)


SALES ORDER #

106.4 4.19

Drawing 0090606
MODEL # Housing: L

34.0 1.34

8.7 0.34
PURCHASE ORDER #

ELECTRICAL CONNECTION 3/4 NPT(F)(STD) 1/2 NPT(F)(OPT)

LINE ITEM #

207.4 8.17

108.0 4.25 (TYP)


126.2 4.97

149.5 5.88 71.4 2.81 7.1 MOUNTING 54.0 0.28 2.13 HOLE (TYP 4) (TYP)

106.4 4.19

34.0 1.34

8.7 0.34

72.3 2.85

28.6 1.13

ELECTRICAL CONNECTION 3/4 NPT(F)(STD) 1/2 NPT(F)(OPT)


14685 W 105TH ST LENEXA, KS 913-888-2630 SORINC.COM M

207.4 8.17

1/4 NPT(F) LO SIDE PROCESS CONNECTION 1/4 NPT(F) HI SIDE PROCESS CONNECTION 7.1 MOUNTING 0.28 HOLE (TYP 4)

ISO-9001

DRA

LENGTH A

29.7 1/4 NPT(M) = (SHOWN) 1.17 1/2 NPT(F) = 37.6 1.48 34.8 1.37

A (TYP)

126.2 4.97

38.1 1.50

PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN

CHE

JR

ENG

SB

DAT

THIS DRAWING IS THE EXCLUSIVE PROPERTY O NO USE WHATSOEVER OF THE INFORMATION CON HEREON, NOR REPRODUCTION IN WHOLE OR PAR MADE WITHOUT THE EXPRESS WRITTEN PERMISSIO
TITLE

1/2 NPT(M) =

72.3 2.85

39.9 3/4 NPT(F) = 1.57


Model Name: 0091068.ASSEM/3/0+

28.6 1.13 1/4 NPT(F) LO SIDE PROCESS CONNECTION

DIM DWG 101/121 LC EO NUMBER: 5090 SCALE: 0.50


DO NOT SCALE PRINT DRAWING NUMBER

14685 W 0091068
OF

ISO-9001 SHEET 1

LENGTH A

NPT(M) = (SHOWN) Drawing1/4 0091068 1.17 1/2 NPT(F)LC = Housing: 1.48 1/2 NPT(M) = sorinc.com 1.37 913-888-2630 39.9 3/4 NPT(F) = 1.57
Model Name: 0091068.ASSEM/3/0+

29.7

A (TYP)

38.1 1.50

1/4 NPT(F) HI SIDE PROCESS CONNECTION

PRODUCT CERTIFIC ALL DIMENSION UNLESS OTHER

LINEAR

37.6 34.8
TITLE

THIS DRAWING I NO USE WHATSOEV HEREON, NOR REPR MADE WITHOUT THE

Form 468 Registered Quality System to ISO 9001 :2008

DIM DWG 101/121 L EO NUMBER: 5090 SCALE: 0.50


DO NOT SCALE PRINT

17/20

Series 101/121 Differential Pressure Switch

Dimensions

Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certied drawings for a particular model number. Dimensions are expressed as millimeters over inches (Linear = mm/in.)

Conventional Explosion Proof - Hazardous Service


Class I, Group C, D; Class II, Group E, F, G: Divisions 1 & 2

MODEL #

SALES ORDER #

LINE ITEM #

PURCHASE ORDER #

108.0 4.25 (TYP)

142.9 5.63 71.4 2.81 54.0 2.13 (TYP)

106.4 4.19

34.0 1.34

8.7 0.34

Drawing 0090607
7.78 MODEL # Housing: S 197.7

ELECTRICAL CONNECTION 3/4 NPT(F)(STD) 1/2 NPT(F)(OPT) OR PLUGGED(OPT) (TYP 3) SALES ORDER #

LINE ITEM #

PURCHASE ORDER #

126.2 4.97

72.3 2.85

108.0 4.25 (TYP)

142.9 5.63
7.1 MOUNTING 71.4 0.28 2.81 HOLE (TYP 4) 54.0 2.13 (TYP) 1/4 NPT(F) LO SIDE ELECTRICAL PROCESS CONNECTION CONNECTION 28.6 3/4 NPT(F)(STD) 1.13 1/4 NPT(F) HI SIDE 1/2 NPT(F)(OPT) PROCESS CONNECTION OR PLUGGED(OPT) (TYP 3)

106.4 4.19

34.0 1.34

8.7 0.34
ISO-9001

14685 W 105TH ST LENEXA, KS 6 913-888-2630 SORINC.COM

DRAW

LENGTH A

A 197.7 (TYP) 7.78

29.7 1/4 NPT(M) = (SHOWN) 1.17 1/2 NPT(F) = 37.6 1.48 34.8 1.37

38.1 1.50

PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN

MS

CHEC

J RE

ENGI

SB

DATE

126.2 4.97

THIS DRAWING IS THE EXCLUSIVE PROPERTY OF NO USE WHATSOEVER OF THE INFORMATION CON HEREON, NOR REPRODUCTION IN WHOLE OR PART MADE WITHOUT THE EXPRESS WRITTEN PERMISSION
TITLE

1/2 NPT(M) = 3/4 NPT(F) =


Model Name: 0090609.ASSEM/3/0+

DIM DWG 101/121 SC

39.9 1.57

72.3 2.85

7.1 MOUNTING 0.28 HOLE (TYP 4) 1/4 NPT(F) LO SIDE PROCESS CONNECTION 28.6 1.13

EO NUMBER: 5090 SCALE: 0.50


DO NOT SCALE PRINT

DRAWING NUMBER

0090609 SHEET 1 OF

1468
ISO-9001

LENGTH A

A (TYP) 29.7

1/4 NPT(F) HI SIDE PROCESS CONNECTION

1/4 NPT(M) = (SHOWN) 1.17 Drawing 0090609 1/2 NPT(F) = Housing: SC 1.48 37.6 34.8 1.37

38.1 1.50

PRODUCT CERTI ALL DIMENSIO UNLESS OTHE

LINEA

THIS DRAWIN NO USE WHATSO HEREON, NOR RE MADE WITHOUT T


TITLE

Form 468

1/2 NPT(M) = 3/4 NPT(F) =

18/20

39.9 1.57

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

DIM DWG 101/121 SCALE: 0.50

EO NUMBER: 509

DO NOT SCALE PRIN

Model Name: 0090609.ASSEM/3/0+

Series 101/121 Differential Pressure Switch

Dimensions

Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certied drawings for a particular model number. Dimensions are expressed as millimeters over inches (Linear = mm/in.).

Conventional Explosion Proof - Hazardous Service


Class I, Groups C, D; Class II, Groups E, F, G: Divisions 1 & 2
MODEL # SALES ORDER # LINE ITEM # SALES PAGE
1

PURCHASE ORDER #

150.1 5.91 75.1 2.95 80.0 3.15 40.0 1.58 110.3 4.34 ELECTRICAL CONNECTION SEE CHART 35.3 1.39 9.5 0.38

41.2 1.62 232.2 9.14 CLEARANCE 6.4 FOR 0.25 MOUNTING HARDWARE 127.1 5.00 1/4 NPTF LO SIDE PROCESS CONNECTION 1/4 NPTF VENT CONNECTION LH & RH

HOUSING B3 & B6 33.4 1.32 B4 & B5 J4 26.6 1.05

ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT LH & RH M20 X 1.5 F LH & RH 3/4 PFF RH ONLY

14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM ISO-9001


DRAWN BY

28.6 1.13 29.7 1.17 TYP

PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN

K MITCHELL
CHECKED BY

M SMITH
ENGINEER APPROVAL

S BOAL
DATE

24 JUN 2011
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR.
TITLE

Drawing 0090610

Housing: B3, B4, B5, B6


Model Name: 0090610.ASSEM/5/0+

38.1 1.50

1/4 NPTF HI SIDE PROCESS CONNECTION

1/4 NPTM PROCESS CONNECTION OPTIONAL

DIMENSION DRAWING 101/121 B & J EO NUMBER: 4441 SCALE: 0.69


DO NOT SCALE PRINT DRAWING NUMBER REV

0090610 SHEET 1 OF 1

5
DWG SIZE

Reset Form

Class I, Groups B, C, D; Class II, Groups E, F, G; Divisions 1 & 2

Drawing 0090611

Housing: TA
sorinc.com 913-888-2630

Class I, Groups A, B, C, D; Class II, Groups E, F, G; Divisions 1 & 2


Form 468 Registered Quality System to ISO 9001 :2008

19/20

Series 101/121 Differential Pressure Switch

Dimensions

Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certied drawings for a particular model number. Dimensions are expressed as millimeters over inches (Linear = mm/in.)

Hermetically Sealed Explosion Proof - Hazardous Service


Class I, Groups A, B, C, D; Class II, Groups E, F, G; Divisions 1 & 2
MODEL # SALES ORDER # LINE ITEM # SALES PAGE
1

PURCHASE ORDER #

121.0 4.77 60.5 2.38 108.0 4.25 54.0 2.13

ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT M20 X 1.5 F OPT FACTORY SEALED LEADS COLOR CODED AND MARKED 457.2 MINIMUM LENGTH 18.00

PROCESS CONN SIZE 1/4 NPTM SHOWN 1/2 NPTF 37.4 1.47 1/2 NPTM 3/4 NPTF 1 ADD

LENGTH A 29.7 1.17 37.6 1.48 34.8 1.37 39.9 1.57

41.6 FOR M20 X 1.5 F 1.64 ELECTRICAL CONNECTION

1 215.9 8.50

CLEARANCE 6.4 FOR 0.25 MOUNTING HARDWARE


14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM
DRAWN BY

ISO-9001

82.3 3.24 28.6 1.13 A TYP

1/4 NPTF LO SIDE PROCESS CONNECTION

7.1 0.28

PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN

K MITCHELL
CHECKED BY

M SMITH
ENGINEER APPROVAL

S BOAL
DATE

14 SEP 2011
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR.
TITLE

Drawing 0090612

1/4 NPTF HI SIDE PROCESS CONNECTION 38.1 1.50 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL 54.7 2.15 84.9 3.34

DIMENSION DRAWING 101/121 BA EO NUMBER: 5095 SCALE: 0.70


DO NOT SCALE PRINT DRAWING NUMBER REV

Housing: BA

0090612 SHEET 1 OF 1

5
DWG SIZE

Model Name: 0090612.ASSEM/4/2

Reset Form

Drawing 0091067

Housing: AG, AH

Form 468

Form 468 (07.12) 2012 SOR Inc. sorinc.com

Registered Quality System to ISO 9001 :2008 14685 West 105th Street, Lenexa, Kansas 66215 913-888-2630 Toll Free 800-676-6794913-888-2630 sorinc.com 20/20

Adjustable Dead Band Pressure Switches


Form 281

pressure switch should be used when there is a requirement for an adjustable and wide dead band between the increasing and decreasing set points.

The adjustable dead band

Alarm: Hi Lo Control: On Off

Function

V1 Weathertight Housing

V3 Weathertight Explosion Proof Hermetically Sealed Switches


Design and specications are subject to change without notice. For latest revision, see www.sorinc.com.

Features and Benets

3-year warranty from date of manufacture Safety Certied to IEC 61508 (SIL) SOR products are certied to IEC 61508 for non-redundant
use in SIL1 and SIL2 Safety Instrumented Systems for most models. For more details or values applicable to a specic product, see the Safety Integrity Level Quick Guide (Form 1528).

Wide adjustable dead band Independent adjustments for increasing and decreasing Set Points Field adjustable with ne resolution of Set Points Instrument quality high repeatability High overrange and proof pressures Exceptionally long life Not critical to vibration Wide selection of wetted parts materials for process compatibility and containment

sorinc.com Form 281 913-888-2630

Registered Quality Quality System System to to ISO ISO 9001 9001 :2008 Registered :2008

sorinc.com Form 281 913-888-2630 1/16

Adjustable Dead Band Pressure Switches

Principle

The SOR Adjustable Dead Band pressure switch incorporates two industry proven Static O Ring pressure sensing elements. Media pressure on the areas of the pistons counteracts the forces of the range springs each adjustable by a separate adjusting nut and moves the piston shafts to operate the lever assembly which, in turn, actuates and deactuates the electrical switching element. Each pressure sensing element of the Adjustable Dead Band pressure switch is a force balance piston-actuated assembly sealed by a exible diaphragm and an o-ring that is static. The only wetted parts are the single pressure port, two diaphragms, and two o-rings all indicated with asterisks (*) in this illustration.
Electrical Switching Element (Explosion Proof Model has Hermetically Sealed Switching Element Capsule)

Screw Terminal Block (Weathertight Model Only) Lever Assembly Calibration Scale Decreasing Set Point Adjusting Nut Piston Assembly Pressure Range Spring *Diaphragm *O-Ring

Calibration Scale Housing Increasing Set Point Adjusting Nut Piston Assembly Pressure Range Spring *Diaphragm *O-Ring *Pressure Port

Principle Schematic
The lever assembly travel illustrated here has been exaggerated for clarity.

No Pressure: Electrical switching element is deactuated.

Pressure greater than decreasing Set Point but less than increasing Set Point. Electrical switching element remains deactuacted.

Actuation

Deactuation

Pressure equal to or greater than increasing Set Point: Electrical switching element is actuated.
Form 281

Pressure less than increasing Set Point but greater than decreasing Set Point: Electrical switching element remains actuated.

Pressure equal to or less than decreasing Set Point: Electrical switching element is deactuated.
sorinc.com 913-888-2630

2/16

Registered Quality System to ISO 9001 :2008

Adjustable Dead Band Pressure Switches


Model Number System

How to Order

5V1-LA3-N6-C1A-YY

Housing Switching Element

Diaphragm

Pressure Port

Accessories

Information and data in this catalog are formatted to provide a convenient guide to assist instrument engineers, plant engineers and end users in selecting pressure switches for their unique applications. Steps 1 through 5 are required. Step 6 is optional. Orders must have complete model numbers, i.e. each component must have a designator. Step 1: Select Adjustable Range from pages 4, 5 and 6 to ll in and . Step 2: Select Housing. Weathertight or explosion proof/weathertight (page 6). Step 3: Select electrical Switching Element for electrical service (page 7). Step 4: Select Diaphragm and O-Ring for process compatibility and containment (page 8). Step 5: Select Pressure Port for process compatibility and connection (page 9). Step 6: Select Accessories required for service (page 9). If Agency Approved, Certied or Listed pressure switches are required, see page 10 for components that must be specied.

How to Order

sorinc.com 913-888-2630

Form 281 Registered Quality System to ISO 9001 :2008

3/16

Adjustable Dead Band Pressure Switches

Step 1: Adjustable Range

5V1-LA3-N6-C1A-YY
Six adjustable dead band ranges are available. Each adjustable range is displayed on a grid (pages 5 and 6). Determine the correct adjustable range for the application by checking increasing and decreasing Set Point requirements against the tables. In the example below, a contact closure is required when pressure increases to 160 psi. The same contact must open when pressure decreases to 60 psi. Since 60 psi is within the blue eld, the example grid range is correct for the application. When the correct range grid is selected, insert range designators and from that grid into the model number.

Step 1 Find the specied increasing Set Point at the top of the graph.

Increasing Set Point (psi)


80 200 100 120 160 200 240

5-3 Decreasing Set Point (psi)


160

Step 2 Find the specied decreasing Set Point along the left edge of the graph.

120

80

40 20 0 1

Step 3 Following the vertical line down from the increasing Set Point. Follow the horizontal line across from the decreasing Set Point. Any point within the blue eld is acceptable. 5
2

5V1-LA3-N6-C1A-YY
1st and 4th places in model number

Form 281

4/16

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Adjustable Dead Band Pressure Switches

Step 1: Adjustable Range

5V1-LA3-N6-C1A-YY

Increasing Set Point (psi)


22 5 9 13 17 21 25 80 20 30

Increasing Set Point (psi)


40 60 80 100

Decreasing Set Point (psi)

Decreasing Set Point (psi)

18

Overrange 750 psi 50 bar Proof 1000 psi 70 bar

Overrange 1500 psi 100 bar Proof 2500 psi 170 bar 60

14

10 80 6 40 2 0 1

40

20 10

Increasing Set Point (psi)


80 200 100 120 160 200 240 Overrange 1500 psi 100 bar 5-3 Proof 2500 psi 170 bar 150 350 300 200

Increasing Set Point (psi)


250 350 450

Decreasing Set Point (psi)

160

120

Decreasing Set Point (psi)

Overrange 2500 psi 170 bar Proof 3875 psi 267 bar

200

80

100 50 0

40 20 0 1

sorinc.com 913-888-2630

Form 281 Registered Quality System to ISO 9001 :2008

5/16

Adjustable Dead Band Pressure Switches


Increasing Set Point (psi)
300 800 400 600 800 1000 1500 600 Overrange 2500 psi 170 bar Proof 3875 psi 267 bar 600

Step 1: Adjustable Range

5V1-LA3-N6-C1A-YY
Increasing Set Point (psi)
900 1200 1500 1750 Overrange 2500 psi 170 bar Proof 3875 psi 267 bar

Decreasing Set Point (psi)

Decreasing Set Point (psi) 5

1200

900

400

600

200 100 0 1

300 200 100 0

45

Step 2: Housing

5V1-LA3-N6-C1A-YY
Service Description
Weathertight for non-hazardous service. NEMA 4, 4X & IP65 Electrical conduit connection: 3/4 NPT(F) Material: 356 aluminum Use LA or SA switching element and terminal block. Shipping weight: 4 pounds (2 kgs) See cutaway view on page 2; dimensions on page 14. Explosion proof and weathertight. NEMA 4, 4X & IP65. Class I, Group A, B, C, D; Class II, Group E, F, G; Division 1 & 2 Electrical conduit connection: 3/4 NPT(F) Material: 356 aluminum Use AG switching element; hermetically sealed SS capsule Shipping weight: 5 pounds (2.5 kgs)

Designator

Non-Hazardous Locations

V1

(UL Listed/CSA Certied, ATEX and SAA Approved Snap Switch)

Hazardous Locations

V3

Form 281

6/16

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Adjustable Dead Band Pressure Switches

Step 3: Switching Elements

5V1-LA3-N6-C1A-YY
Maximum Ambient Temperature

Switching Element Service


Normal Service AC Very High Capacity DC Magnetic Blow-out

Contact Form

Electrical Connection Type

AC Rating Volts
250

DC Rating Resistive Volts


125

Designator

Amps
15

Amps
.5 1.5 Min. 10.0 Max.

Volts
30

Amps Deg F Deg C SPDT DPDT


10* 180 80 LA N/A

SPDT

Screw Terminal Block

125

10

125

180

80

SA

N/A

AC or DC

DPDT

18 18 AWG color-coded wire leads 3/4 NPT(M) conduit connection

250

11

125

.5*

30

5.0

160

70

N/A

AG

1. The switching elements shown above are UL Listed and CSA Certied. The DC current rating marked (*) is not UL Listed but has been veried by testing and/or experienced. 2. The hermetically sealed switching element capsule is UL Listed, CSA Certied and SAA Approved as a snap switch in accordance with the following table. 3. Consult the factory for availability of SAA Approved units.

Agency UL Listed

Hazardous Location Conditions Class I, Group A, B, C, D; Class II, Group #, F, G; Division 1 & 2

Designator

CSA Certied SAA Note 3 Approved ATEX Approved

AG Ex s Zone 2 IIC T4 IP65 Ex tD A22 T105 C IP65 II 2 G EEx m II

sorinc.com 913-888-2630

Form 281 Registered Quality System to ISO 9001 :2008

7/16

Adjustable Dead Band Pressure Switches


Notes 1. N4 diaphragm system is standard. It is normally suitable for air, oil, water and noncorrosive processes. 2. Other diaphragm and o-ring combinations may be available. Consult the factory or the SOR representative in your area for more information. 3. Wetted parts have been selected as representing the most suitable commercially available material for use in the service intended. However, they do not constitute a guarantee against corrosion or permeation, since processes vary form plant to plant and concentration of harmful uids, gases or solids vary from time to time in a given process. Emperical experience by users should be the nal guide. Alternate materials based on this are generally available. 4. Specify N3 diaphragm system for high cycle rate, high shock applications where Buna-N and TCP are compatible with the process. 5. This table shows allowable minimum and maximum temperature for o-rings.
O-Ring Material Viton Viton GLT Kalrez* Aas Buna-N Neoprene EPR TCP Teon Coated Polyimide Diaphragm F 32 to 400 -20 to 400 5 to 400 25 to 400 -30 to 200 -30 to 400 C 0 to 204 -29 to 204 -15 to 204 -4 to 204 -34 to 93 -34 to 204

Step 4: Diaphragm and O-Ring

5V1-LA3-N6-C1A-YY
O-Ring (Wetted) Viton Kalrez Viton Kalrez Viton Kalrez Viton Kalrez Viton GLT Buna-N Viton Neoprene Kalrez Aas EPR Viton Buna-N Buna-N Kalrez Kalrez EPR Aas Buna-N Neoprene Viton Viton GLT Buna-N Viton Neoprene Kalrez EPR Ethylene Propylene EPR Ethylene Propylene Tantalum Kalrez TCP Teon-Coated Polyimide Buna-N Neoprene Viton TCP Teon-Coated Polyimide 316L SS Diaphragm (Wetted) Monel Hastelloy-B Hastelloy-C Carpenter-20 Designator A4 A6 H4 H6 J4 J6 L4 L6 M1 M2 M4 M5 M7 M8 M9 Note 6 N1 N3 Note 4 N4 Standard
Note 1

N5 N6 N7 N8 P1 R1 S1 S2 W2 W4 W5 W6 Y1

*Kalrez or equivalent Peruoroelastomer (FFKM) o-rings

6. M9 diaphragm system is suggested for steam applications up to 400oF. 7. Dead bands are slightly higher when using H, J, W, N3, or N6 series diaphragm options. Consult the factory.

Form 281

8/16

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Adjustable Dead Band Pressure Switches


Material Aluminum Alloy 356 copper-free casting 316SS CF-8M Casting Connection 1/4 NPT(F) 1/2 NPT (F) 1/4 NPT(F) 1/2 NPT (F)

Step 5: Pressure Port

5V1-LA3-N6-C1A-YY
Designator B1A B2A C1A C2A

Step 6: Accessories

5V1-LA3-N6-C1A-YY
Accessory / Option & Description Designator

Wetted parts are cleaned for industrial oxygen service. CSA Certied pressure switch. Available with V1 housing. Housing has earth (ground) lug. See agency listings on page 10 for details. Cemented cover gasket on weathertight housing. Universal terminal box, 1/2 NPT(F). 316SS. Explosion proof. FM Approved; CSA Certied. See form 657 (Catalog GI-30). Vacuum protector plate retains diaphragm system in the pressure switch if subjected to intermittent vacuum greater than 10 in Hg. If a pressure switch is subjected to continuous, rapid changes of vacuum, other protection may be available (consult factory). Material matches or exceeds pressure port material. Compliance to NACE Certication MR0175/ISO 15156* Pipe (stanchion) mounting kit for (1-1/2 to 2 pipe). Order as a separate line item for CSA Certied pressure switches. Tag, ber. Attached with plastic wire to housing. Stamped with customer-specied tagging information. Powder coat epoxy coating. No coating on stainless steel parts or plated screws. (500 hours-salt spray) Tag, stainless steel. Attached with stainless steel wire to housing. Stamped with customer specied tagging information. (2 lines, 18 characters and spaces per line.) Stainless steel piston and cylinder disc for corrosion resistance. Explosion proof and weathertight electrical junction box with screw terminals. Aluminum 3/4 NPT(F) top or right conduit connections as required. UL Listed and CSA Certied Class I, Groups A, B, C & D; Class II, Group E, F & G; Division 1 & 2. Includes cover o-ring for weathertight applications. (V3 housing only.) Oversize stainless steel nameplate. Permanently attached to housing. Stamped with customer specied tagging information Fungicidal varnish. Covers exterior and interior except working parts. Epoxy coating. Exterior only. Polyimide epoxy with 316SS pigment. (200 hours-salt spray) Chained cover with captive screws to conform to former JIC specication X is used as a sufx to the model number for special requirements not keyed elsewhere in the model number by an X. Each X must be completely identied in the text of the order or inquiry. When more than one X is required, use X followed by the number of such items. For example, X3 means three separate, otherwise unidentiable requirements.
sorinc.com 913-888-2630

BB CS GC HT

MM NC PK PP PY RR SP TB

TT VV YY ZZ X

Form 281 Registered Quality System to ISO 9001 :2008

9/16

Adjustable Dead Band Pressure Switches


Certicates Calibration Hydrostatic Pressure Test Inspection Report Compliance / Conformance Dielectric Test Insulation Resistance Typical Material of Wetted Parts C1 C2 C3 C4 C5 C6 C8 B1 B4 B5 B6 B7 A1

Test Certicates

A2

A3

A4

A5

A6

A7

A8

Agency Listings
The following combinations only are available as approved, certied or listed by the agencies shown. Some components are for products not offered in this catalog. Certain components or combinations may acquire additional approval, certication or listing between print dates of this catalog. Contact the factory for the most current information. CSA Enclosure 4 (Weathertight) Piston All Housing V1 Switching Element LA, SA Spring All Diaphragm & O-Ring All Pressure Port Material & Connection Size All Accessories/ Option CS Required All except TB

Form 281

10/16

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Adjustable Dead Band Pressure Switches

Glossary of Terms

SOR recognizes that there is no industry convention with respect to terminology and denitions pertinent to pressure switches. This glossary applies to SOR Pressure Switches.

Adjustable Range The span of pressure between upper and lower limits within which the pressure switch may be adjusted to actuate/deactuate. Dead Band The difference in pressure between the increasing Set Point and decreasing Set Point. Decreasing Set Point That discrete pressure at which the pressure switch is adjusted to deactuate on falling pressure. It must fall within the adjustable range. Hermetically Sealed A welded steel capsule with glass-to-metal, factory-sealed, electrical leads that isolates the electrical switching element(s) from the environment. Increasing Set Point That discrete pressure at which the pressure switch is adjusted to actuate on rising pressure. It must fall within the adjustable range. Overrange The maximum input pressure that may be continuously applied to the pressure switch without causing permanent change of Set Point, leakage or material failure. Pressure Switch A bi-stable electromechanical device that actuates/deactuates one or more electrical switching element(s) at a predetermined discrete pressure/vacuum (Set Point) upon rising or falling pressure/vacuum.

Proof Pressure The maximum input pressure that may be continuously applied to the pressure switch without causing leakage or catastrophic material failure. Permanent change of Set Point may occur, or the device may be rendered inoperative. Repeatability The ability of a pressure switch to successively operate at a Set Point that is approached from a starting point in the same direction and returns to the starting point over three consecutive cycles to establish a pressure prole. The closeness of the measured Set Point values is normally expressed as a percentage of full scale (maximum adjustable range pressure). SPDT Switching Element Single-Pole, Double Throw (SPDT) has three connections: C Common, NO Normally Open and NC Normally Closed, which allows the switching element to be electrically connected to the circuit in either NO or NC state. DPDT Switching Element DPDT is two synchronized SPDT switching elements which actuate together at increasing Set Point and deactuate together at decreasing Set Point. Discrete SPDT switching elements allow two independent circuits to be switched; i.e., one AC and one DC. The synchronization linkage is factory set, and is not eld adjustable. Synchronization is veried by connecting test lamps to the switching elements and observing them go On simultaneously at actuation and Off simultaneously at deactuation.

sorinc.com 913-888-2630

Form 281 Registered Quality System to ISO 9001 :2008

11/16

Adjustable Dead Band Pressure Switches

Dimensions

Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certied drawings for a particular model number. Dimensions are expressed as millimeters over inches (Linear = mm/in.).

Drawing 0090300

Pipe Mounting Kit: PK

Drawing 0091353

Junction Box with Terminal Block: TB


Form 281

12/16

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Adjustable Dead Band Pressure Switches

Dimensions

Drawing 0090763

Junction Box with Terminal Block: HT

Weights

V1 Housing 4 lbs (2 kgs)

V3 Housing 5 lbs (2.5 kgs)

Accessory Pk Pipe Kit TB Junction box with Terminal Block

Add lbs 1.5 5

kgs 0.7 2.25

Actual shipping weights may vary from the charted values because of product material, conguration and packaging requirements.

sorinc.com 913-888-2630

Form 281 Registered Quality System to ISO 9001 :2008

13/16

Adjustable Dead Band Pressure Switches

Housing Dimensions

Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certied drawings for a particular model number. Dimensions are expressed as millimeters over inches (Linear = mm/in.).

Drawing 0090236

Non-Hazardous Locations Weathertight NEMA 4, 4X, IP65 Housing Designator: V1

Drawing 0090325

Contains Explosion Proof, Hermetically Sealed Switching Element Capsule: UL Listed, CSA Certied, ATEX and SAA Approved

Hazardous Locations

Housing Designator: V3
Form 281

14/16

Registered Quality System to ISO 9001 :2008

sorinc.com 913-888-2630

Notes

sorinc.com 913-888-2630

Form 281 Registered Quality System to ISO 9001 :2008

15/16

SOR offers a full line of commercial-grade process instruments.

echOsonix Level Transmitters

Pressure

Temperature

Level Switches

Flow Switches

Level
Temperature Switches

Flow

Pressure Switches

Process Instrumentation

We Deliver Quality On Time


SOR Inc.
14685 West 105th Street Lenexa, Kansas 66215 Phone 913-888-2630 Toll Free 800-676-6794 Fax 913-888-0767 sorinc.com

SOR Europe, Ltd.


Farren Court Cowfold West Sussex RH13 8BP United Kingdom Phone +44 (0) 1403 864000 Fax +44 (0) 1403 864040

SOR - China
Room 903, No. 10 Building Wan Da Plaza No. 93 Jian Guo Road Chao Yang District Beijing, China 100022 Phone +86 (10) 5820 8767 Fax +86 (10) 58 20 8770

Form 281 Registered Quality System to ISO 9001:2008

16/16

sorinc.com Form 281 (03.12) 2012 SOR Inc. 913-888-2630 Registered Quality System to ISO 9001 :2008

Adjustable Dead Band

Pressure Switches
General Instructions
These instructions provide information for installation, process and electrical connections and field calibration of SOR Adjustable Dead Band Pressure Switches. The pressure sensing elements are a pair of force-balanced, pistont actuated assemblies sealed by flexible diaphragms and o-rings that are static. The only wetted parts in this arrangement are the single pressure port, two sensing assembly diaphragms and o-rings. Media pressure on the area of the pistons counteracts the force of the range springs (adjustable by the adjusting nuts), which moves the piston shafts only a few thousandths of an inch to operate the lever assembly which actuates and deactuates the electrical switching element.
NOTE: If you suspect that a product is defective, contact the factory or the SOR Representative in your area for a return authorization number (RMA). This product should only be installed by trained and competent personnel.

Installation
Adjustable Dead Band Pressure Switches may be secured to bulkheads, panels or pipe stanchions with suitable bolts. When mounting the pressure switch to an irregular or uneven flat surface, install rubber washers on the mounting bolts between the housing and the mounting surface. Line mounting by either the process connection or the electrical conduit connection is not recommended.
Failure to place washers between the housing and the mounting surface may result in torsional forces on the housing that could cause false trips or render the pressure switch inoperative. Failure to mount the housing on a flat mounting surface may result in torsional forces on the housing that could cause false trips or render the pressure switch inoperative.

Design and specifications are subject to change without notice. For latest revision, go to www.sorinc.com
Form 466 (05.13) SOR Inc. Registered Quality System to ISO 9001

1/4

Safety Integrity Level (SIL) Installation Requirements


The SOR pressure switches have been evaluated as Type-A safety related hardware. To meet the necessary installation requirements for the SIL system, the following information must be utilized: Proof Test Interval shall be one year. Units may only be installed for use in Low Demand Mode. Products have a HFT (Hardware Fault Tolerance) of 0, and were evaluated in a Form 1538 (03.12) 2012 SOR Inc. 1oo1 (one out of one) configuration.

Process Connection
Securely connect the process line to the pressure port using two wrenches: one to hold the hexagonal flats on the pressure port, the other to tighten the process pipe or tube fitting.
Ensure that the process connection is tightened and positioned so that any binding and torsional forces imposed on the pressure switch are minimal. Do not loosen the pressure port from the body because leakage could result or the pressure switch could be rendered inoperative.

Electrical Connection
Ensure that wiring conforms to all applicable local and national electrical codes and install unit(s) according to relevant national and local safety codes.

V1 Weathertight
Common C1

SPDT: Screw terminal block with marked insulation. Normally Open NO1 Normally Closed NC1

V3 Explosion proof DPDT (2-SPDT): Hermetically sealed switching element


capsule has 18 - 18 AWG wire leads color coded and marked. Common C1 - Blue C2 - Yellow Normally Open NO1 - Black NO2 - Brown Normally Closed NC1 - Red NC2 - Orange

GR - Ground (earth) green wire connected to each hermetically sealed switching element capsule.

Calibration

Remove the housing cover. Connect a suitable variable pressure source with a calibrated reference gauge to the
pressure port. Connect an ohmmeter or test lamp across the switching element contact terminals to monitor contact continuity. Use a 3/4 open-end wrench to turn the adjusting nuts. Slowly increase pressure to the pressure port. The continuity tester will indicate that the contacts have changed state when increasing set point is reached. Note pressure at increasing set point. If increasing set point is too low, turn the left adjusting nut clockwise to raise the increasing set point. If increasing set point is too high, turn the left adjusting nut counterclockwise to lower the increasing set point.
2/4
Form 466 (05.13) SOR Inc.

Slowly decrease pressure to the pressure port. The continuity tester will indicate that
contacts have changed state when decreasing set point is reached. Note pressure at decreasing set point.If the decreasing set point is too low, turn the right adjusting nut clockwise to raise the decreasing set point. If the decreasing set point is too high, turn the right adjusting nut counterclockwise to lower the decreasing set point. The left adjusting nut must always be lower than the right adjusting nut when calibration is complete. Repeat Steps 3 and 4 until desired set points are obtained. If the pressure switch fails to respond to pressure change during calibration, increasing/decreasing set points may be too close together. See Form 281 for minimum/maximum dead band capabilities. Replace the housing cover.
Overtravel has been preset at the factory. The 3/16 overtravel adjustment screw on the lever assembly has been precisely positioned for optimum performance. Any inadvertent movement could render the device inoperative and void the warranty.

Increasing Set Point Adjustment To raise the increasing set point, turn the left adjusting nut clockwise. To lower the increasing set point, turn the left adjusting nut counterclockwise.

Decreasing Set Point Adjustment To raise the decreasing set point, turn the right adjusting nut clockwise. To lower the decreasing set point, turn the right adjusting nut counterclockwise.

The left adjusting nut must always be lower than the right adjusting nut when calibration is complete.

Principle of Operation Actuation Deactuation

No pressure applied. Electrical switching element is deactuated.

Pressure greater than decreasing set point but less than increasing set point: Electrical switching element remains deactuated.

Pressure equal to or greater than increasing set point: Electrical switching element is actuated.

Pressure less than increasing set point but greater than decreasing set point: Electrical switching element remains actuated.

Pressure equal to or less than decreasing set point: Electrical switching element is deactuated.

Piston movement exaggerated for clarity in drawings above.

Form 466 (05.13) SOR Inc.

3/4

Dimensions
V1 Housing
*Add 6.4 for non-aluminum ports. 0.25

Linear = mm/inches

Drawing 0090236

V3 Housing
*Add 6.4 for non-aluminum ports. 0.25

Linear = mm/inches

Drawing 0090325

Dimensions are for reference only. Contact the factory for certified drawings for a particular model number.

Printed in USA

www.sorinc.com

14685 West 105th Street, Lenexa, KS 66215 913-888-2630 800-676-6794 USA Fax 913-888-0767 4/4
Registered Quality System to ISO 9001 Form 466 (05.13) SOR Inc.

Differential Pressure Switches


General Instructions
CAUTION: Failure to mount the housing on a at mounting surface may result in torsional forces on the housing that could cause false trips or render the pressure switch inoperative. 2. Line mounting by either process connection or electrical conduit connection is not recommended for housings with integral mounting pads. 3. Suggested mounting orientation is high side process pressure port at 6 oclock. However, the device can be mounted in any position. Optional breather drains should be positioned to allow moisture to escape from the housing interior. Breather drains must be kept clear of paint and foreign matter. CAUTION: For B-Series Housings One vent hole should be tted with a suitable breather to maintain weathertight rating NEMA 4, 4X, IP65 or vented to a safe area. Piping should be minimum 1/4 diameter and maximum 5 meters long (based on process uid SG 1.0). The other vent hole may be plugged.

Series 101/121

Mini-Hermet Models

General Purpose and Weathertight Models

B-Series Models

General
These instructions provide information for installation, electrical connection, process connection and calibration of Series 101/121 Differential Pressure Switches. B-Series models (B3, B4, B5, B6) may be ATEX Approved with the addition of a CL option at the end of the model string. Specic information and instructions concerning these models will be found throughout the following pages. NOTE: SOR discourages eld modications and eld repair. Products should be returned to SOR for inspection and necessary repair work. Contact the factory for a return authorization number. Any eld work should be performed by qualied instrument technicians using factory-authorized procedures. Principle of Operation Process pressure is sensed by a diaphragm and piston assembly. The piston responds to differential pressure and moves a shaft that actuates (deactuates) an electrical switching element. Low side pressure and an adjustable range spring oppose high side pressure. Adjustment of the range spring determines the set point. (See Calibration.) CAUTION: Use care during installation to avoid moving the electrical switching element or its housing. Movement of either could change calibration or render the device inoperative. Design and specications are subject to change without notice.

Process Connection
Connect the process lines to the pressure ports using two wrenches: one to hold the hex ats on the pressure port, the other to tighten the process pipe or tube tting. The high pressure side (stamped HI) and the low pressure side (stamped LO) have 1/4 NPT(F) or 1/4 BSP(F) process connections as standard. IMPORTANT: Rigid process piping must be arranged to minimize bending or twisting forces which could disturb the positioning of internal parts and change calibration or render the device inoperative after installation. Use care to avoid loosening the pressure port from the body or the body from the electrical housing.

Installation
This product should only be installed by trained and competent personnel. 1. Secure the housing to a bulkhead, panel rack or pipe stanchion with suitable bolts. IMPORTANT: When bolting housings with integral mounting pads to irregular or uneven surfaces, install rubber washers between the housing and the mounting surface to prevent deformation of the housing.
For latest revision, see www.sorinc.com SOR Form 506 (04.05) Printed in USA

Electrical Connection
Ensure that wiring conforms to all applicable local and national electrical codes and install unit(s) according to relevant national and local safety codes. NOTE: For B-Series ATEX Certied Models Electrical conduit connection threads may be of non-ISO thread form. Check the product nametag for relevant thread form information before attempting to connect to the electrical conduit connection. In the event a tting is used, check the adaptor body for thread size information.
Page 1 of 4

Registered Quality System to ISO 9001

CAUTION: Electrical power must be disconnected from explosion proof models before the cover is removed. Failure to do so could result in severe personal injury or substantial property damage. When making electrical connections, use care to avoid movement of the electrical switching element. Electrical connections are either screw terminals, terminal blocks or 18-gauge, 18-inch wire leads. Screw terminal and terminal block points are identied on the insulation card inside the electrical housing. Refer to the wiring schematic in Figure 1 for wire lead color codes.

on the interior wall of the housing. If coarse or precise set point calibration is required, calibrate according to the appropriate procedure. WARNING: For B-Series Housings The electrical compartment cover must remain sealed and the Allen locking screw tightened at all times to prevent removal of the cover while the pressure switch is in service. Removal of the cover while the pressure switch is in service in a hazardous location could result in severe personal injury or substantial property damage. Coarse Calibration Procedure 1. Connect variable pressure source to test gauge and HI side pressure port. 2. Connect test light or ohmmeter across C Common and NO Normally Open switching element contacts. 3. Raise pressure and note test gauge reading when circuit closes. 4. Slowly drop pressure and note test gauge reading when circuit opens. 5. Turn set point adjustment clockwise to increase set point, or counterclockwise to decrease set point. 6. Repeat Steps 3, 4 and 5 until contacts change at desired increasing or decreasing differential pressure set point. Precise Calibration Procedure The precise calibration procedure references system (static) pressure. Set point accuracy is enhanced by calibrating the differential pressure switch under simulated service pressure conditions. The following test apparatus is recommended. 1. 2. 3. 4. Differential pressure gauge Variable pressure source Block/bleed and equalizer valves Test light or ohmmeter

Wire Lead Color Code


SPDT
LO
Blue (C) Black (NO) Red (NC)

HI

Differential Pressure

DPDT (2-SPDT)
LO
Blue (C) Black (NO) Red (NC) Yellow (C2) Brown (NO2) Orange (NC2)

No. 1

HI

No. 2

Differential Pressure

FIGURE 1
NOTE: Storing excess wire or making wire lead splices inside the pressure switch housing should not be done and may interfere with the pressure switch operation.

Determine whether the critical set point occurs on increasing or decreasing differential pressure, and calibrate using the appropriate procedure: For Critical Set Point on Increasing Differential Pressure 1. Connect the continuity test lamp or ohmmeter across the C - Common and NO - Normally Open switching element / contacts. 2. Close the bleed valve(s), open the equalizer valve and raise pressure equally on both HI and LO sides to the static pressure that the differential pressure switch will see under normal operating conditions. 3. With static pressure stable, close the equalizer valve to isolate the HI side from the LO side. 4. Keeping high side pressure steady, slightly open the LO side bleed valve to reduce the LO side pressure (increase differential pressure) until desired differential pressure set point appears on indicator. Close bleed valve to stabilize differential pressure. Check the status of the electrical contacts against the following differential pressure trend graphs. Follow the instructions under the graph that matches the status of the contacts. See SOR Form 468 for reference dimension drawings. For certied dimension drawings contact factory.

Calibration
Mini-Hermet models Remove the weathertight cap. Use a 1/8 hex Allen wrench to turn the adjusting screw to the desired set point. Turn the adjusting screw clockwise (in) to increase the set point and counterclockwise (out) to decrease the set point. Use either the coarse or the precise set point calibration procedure. CAUTION: Do not unthread the adjusting screw more than two threads below the ush point of housing as calibration could be adversely affected. All Other Models Use a 3/4-inch open-end wrench to turn hex adjusting nut clockwise to increase set point, and counterclockwise to decrease set point. An approximate set point can be obtained by sighting across top of adjusting nut to the calibration scale
Page 2 of 4

SOR Form 506 (04.05) Printed in USA

Set Point OK

Contacts Open Set Point Too High

Contacts Closed Set Point Too Low

Make

Differential Pressure

Make

Break Make Break

Critical Increasing Set Point

Break

0 Time

0 Time

0 Time

If contacts make precisely at critical increasing differential pressure set point, repeat Steps 2 - 4 as desired to verify calibration. Calibration is complete.

If contacts are open when critical increasing differential pressure is reached, turn set point adjustment counterclockwise (out) until contacts make. Repeat Steps 2-4.

If contacts are closed when critical increasing differential pressure is reached, turn set point adjustment clockwise (in) until contacts break. From this point, turn set point adjustment counterclockwise (out) until contacts make. Repeat Steps 2-4.

For Critical Set Point on Decreasing Differential Pressure


1. Connect the continuity test lamp or ohmmeter across the C - Common and NO - Normally Open contacts. 2. Close the bleed valve(s), open the equalizer valve, and raise pressure equally on both HI and LO sides to the normal operating high side pressure. 3. With normal HI side pressure stable, close the equalizer valve to isolate the HI side from the LO side. 4. Slightly open the LO side bleed valve to reduce LO side pressure (increase differential pressure) until the normal operating differential pressure appears on the digital indicator. Close the bleed valve to stabilize differential pressure. Contacts should close (make) by the time normal operating differential pressure is reached. If the contacts are still open at normal operating differential pressure, turn the set point adjustment counterclockwise (out) until the contacts make. 5. Keeping the high side pressure steady, slightly open the equalizer valve to increase LO side pressure (decrease differential pressure) until the desired differential pressure set point appears on the digital indicator. Close the equalizer valve to stabilize differential pressure. Check the status of the electrical contacts against the following differential pressure trend graphs. Follow the instructions under the graph that matches the status of the contacts.

Set Point OK

Contacts Open Set Point Too High

Contacts Closed Set Point Too Low

Normal Operating Differential Pressure Differential Pressure Make Critical Decreasing Set Point 0 Time 0 Time

Make

Break Make Break

0 Time

If contacts break precisely at critical decreasing differential pressure set point, repeat steps 2-5 as desired to verify calibration. Calibration is complete.

If contacts are open when critical decreasing differential pressure is reached, turn set point adjustment counterclockwise (out) until contacts make. From this point, turn set point adjustment clockwise (in) until contacts break. Repeat Steps 2-5.

If contacts are closed when critical increasing differential pressure is reached, turn set point adjustment clockwise (in) until contacts break. Repeat Steps 2-5.

SOR Form 506 (04.05) Printed in USA

Page 3 of 4

Operation
For B-Series ATEX Certied Models
Maximum Surface Temperature T6 Rating - 85oC T5 Rating - 100oC

Basic and 4th Designator 101 101 121

Adjustable Range psid 3 to 30 10 to 75 75 to 500 bar .2 to 2.1 .7 to 5.2 5.2 to 34 AC Rating Volts 250 125 125 250 250 250 250 250 125 250 250 250 250 250 250 125 125 Amps 15 1 1 15 11 15 5 15 10 5 5 5 15 15 5 1 1

Maximum System Pressure psi 500 500 1000 bar 34 34 69

Maximum Differential Pressure psi 500 500 1000 bar 34 34 69

45 45

Designator SPDT K KA J G A L E C S B Y W T H AF EF JF DPDT KK N/A JJ GG AA LL EE N/A N/A BB YY N/A N/A N/A AG EG JG

DC Rating Resistive Volts 125 125 125 125 125 125 125 125 125 125 125 Amps 0.4 0.5 0.5 0.5 0.5
1.5 Minimum 10.0 Maximum

Volts 30 28 30 30 30 30 30 28 30

Amps 5 1 1 5 10 5 5 1 1

0.3 0.5 0.3 0.4 0.5 -

ATEX Marking Information


For B-Series ATEX Certied Models
Manufacturers Registered Trademark ATEX Listing Information Product Type Identication

Thread Form Information

Product Model Identication

Serial Number (First Two Numbers Indicate Year of Manufacture)

14685 West 105th Street, Lenexa, Kansas 66215


Page 4 of 4

913-888-2630

Fax 913-888-0767

www.sorinc.com

Registered Quality System to ISO 9001

SOR Form 506 (04.05) Printed in USA

Potrebbero piacerti anche