Introduction
Natural Ventilation systems rely on natural driving forces, such as wind and temperature difference between a building and its environment, to drive the ow of fresh air through a building. Both work on the principle of air moving from a high pressure to a low pressure zone. Natural ventilation systems are usually integrated into building systems where there is some mechanical support; these are called mixed mode or hybrid ventilation buildings. The main benet of some augmentation by mechanical systems is that there is less unpredictability with indoor environment conditions, though it will result in greater energy use. Natural ventilation can be an appropriate choice when compared to air conditioning in the temperate climate of Victoria, particularly as the nights are cool and this can be used to pre-cool the building (see CH2 for case study of natural ventilation used for night purge www.ch2.com.au). It can save substantial amounts of energy by decreasing or eliminating the need for mechanical cooling. It may also improve the buildings indoor air quality. Buildings with well-designed natural ventilation systems often provide very comfortable and pleasant environments for the occupants.
Suitability
Most suited to: > Buildings with a narrow plan or atria with oor plate width of 15m or less > Sites with minimal external air and noise pollution (though still possible if they are present) > Open plan layouts Not suited to: > Buildings with a deep oor plan > Buildings that require precise temperature and humidity control > Buildings with individual ofces or small spaces > Buildings with continual heat loads above 3540 W/m2 > Locations with poor air quality
Benets
> The main savings are due to cooling energy reduction (roughly equivalent to an economy cycle), not needing to run HVAC fans and increased occupant satisfaction. > A Sydney study showed a 25 33% reduction of energy use in a naturally ventilated mixed mode building with high occupant comfort satisfaction scores > Reference 8 . > International studies in similar climatic regions using natural ventilation only (not mixed mode), show capital costs savings in the region of 10 15% > Reference 3 and energy costs that are 40% lower than air-conditioned equivalents > Reference 2 . > Increased fresh air supply to a space may result in higher thermal comfort levels and increased productivity. > Natural ventilation systems may have an increased robustness, exibility and adaptability.
The ow through a building is related to the size of the openings (both inlets and outlets), restrictions along the ow path, furnishings and the distance between openings. Basic principles for sizing and placing openings are: > The area of the opening at intake must be equal to or 25% smaller than the area of opening for exhaust. > Air ow will take the line of least resistance so follow the ow line to check for dead spots (areas where fresh air does not go). > Consider security, privacy and noise transfer.
Cross ventilation
Cross ventilation depends on two continuously changing factors: wind availability and wind direction. Consequently, it is a somewhat unreliable source for providing air ow and thermal comfort. In cross ventilation the wind creates a high pressure zone where it impacts the building and a low pressure zone on the leeward side, drawing air through the building > Figure 1 . Pressure is highest near the centre of the windward wall diminishing to the edges as the wind nds other ways to move around the building so air intakes are preferable near the centre or the high pressure zones. To determine the amount of natural ventilation that you will obtain from an opening, in a given space, standard formulas are used. A very worthwhile but technical reference is the CIBSE guideline Natural Ventilation in Non-Domestic Buildings AM 10 > Reference 2 provides standard formulas to determine the amount of ventilation from an opening in a given space as it is affected by internal t-out and distances.
Windward side
Leeward side
> Will work well if the room is up to 5 times the width of the ceiling height > Figure 2 .
Low pressure zone
> If cross ventilation is not possible placing windows on adjacent walls, at 90 degrees to each other, will work but limit room size to 4.5 m x 4.5 m. > In a standard ofce, partitions should not be higher than 1200mm, but this will depend on opening sizes.
> Figure 2 Cross ventilation rule of thumb effective for up to ve times the ceiling height
> Partitions should not obstruct air path. Design spaces so that they are parallel to main ventilation path > Figure 3 . > Place high emission equipment such as printers in separate mechanically ventilated rooms on the east or west facades as these are the areas of highest heat load from the sun with least benet from windows.
> Elements such as overhangs can help or hinder air ow and should be carefully integrated into CFD modelling. > Openings should be fully operable by occupants if a manual operational strategy is chosen. This requires easy access to opening mechanisms as well as training and appropriate information to work well. > Provide inlet openings on the windward side (pressure zone) and outlets on the leeward side (suction zone). > The inlet location affects airow patterns far more signicantly than outlet location. Inlet location should be a higher priority (if faced with a choice) as a high inlet will direct air toward the ceiling and may bypass the occupied level. > Ensure windows have effective seals to avoid unwanted inltration. > Orient the building and openings to maximize exposure to prevailing winds. > Consider designing cross-ventilation openings that are secure enough to be left open at night, so that natural ventilation can provide additional night time cooling benets.
> Figure 3 For effective cross ventilation ensure partitions are designed to minimise resistance
> Concentrate ventilation openings in spaces most likely to require cooling. > Minimize solar gain use shading devices like overhangs, awnings and ns to control solar gain. > Awning windows work for air intakes, hopper windows for outow. Double hung windows are ideal for single sided ventilation because they provide high and low openings in the one unit. Casement windows are suitable to catch breezes when the prevailing wind direction is consistent. > Window insect screens decrease the ow rate of slow breezes more than stronger breezes (60% decrease at 2.4 km/h, 28% decrease at 9.7km/h) > Reference 4 . > Only the clear opening area of a window can be used to calculate capacity.
Case study Single sided ventilation State Emergency Services HQ South Melbourne
This building uses single sided natural ventilation to all the open plan ofce areas. Air comes in via oor level attenuated grills and is expelled through high level attenuated louvers. Being near a busy roadway the air is drawn through a system to minimise air and noise pollution. The natural ventilation system is integrated with the nearby tunnel controls so that air intake closes when tunnel venting occurs and wind directions are unfavourable. Sophisticated design and integrated modelling was requires to ensure sufcient air pressure could be achieved.
Cost Limitations
Capital costs for a fully naturally ventilated building may be 1015% lower than air-conditioned equivalents > Reference 3 . Costs for cross ventilation are low to moderate. Buildings that use natural ventilation may have higher initial costs because operable windows typically cost 5% to 10% more than xed glazing, but the savings from not using air conditioning will offset this added cost. Hybrid systems will be more expensive because of the higher cost for operable windows and interlocking controls for the HVAC system. Costs vary greatly depending on installation of HVAC system key criteria that determine cost are the complexity of the system and if it is manually or automatic controlled. This cost can vary between $50$150 per square metre (2006/7 prices).
The benets of natural ventilation are threatened by poor management and operation. Problems associated with building openings are: > Safety people may fall out > Security and re > Outdoor Noise > Internal Acoustics > Insects, odours, dust and air pollution > Fluctuation of internal temperature
In stack ventilation, air movement is created by cool air being drawn into the space low down to replace warmer air that naturally rises as it is warmed and is then exhausted at the top see > Figure 4 . To obtain cooling, the incoming air must be cooler than the ambient internal temperature. The cool air may be drawn from a shaded or landscaped space or from over a body of water, a thermally massive labyrinth or other source of cooling. Stack ventilation works best in spaces with high ceilings and where cross ventilation is not feasible.
Solar Chimney
Solar chimneys are a method of enhancing stack ventilation. Additional height and well designed air passages increase the air pressure differential. Chimneys should be constructed to capture solar radiation to increase the heat of the air at the top and increase the difference in temperature between incoming and out-owing air. The increase in natural convection that occurs from these measures enhances the draw of air through the building > Figure 5 > Figure 6 .
Outlet
Inlet
> Figure 4 Pressure effect from stack ventilation, make sure height difference between openings is maximised > Reference 1
The design considerations with the integration of stack ventilation are similar to those for wind driven ventilation discussed above. The most important issue is ensuring that the pressure within the stack remains high, so that air is always travelling upwards and out and therefore drawing fresh air in. The main points to consider when designing stack ventilation are: > Effective across a width of 5 times the vertical distance from inlet to exhaust. > Chimneys can be used as the exhaust point if the temperature inside can be kept warmer than the ambient internal building temperature. > Design chimneys to minimise pressure drops to allow movement of air, for example through techniques discussed below. > The function of solar chimneys is improved by techniques to increase the air temperatures at the top of the chimney such as glass panels and dark coloured surfaces to capture solar radiation > The exhaust must be placed on the leeward side to take advantage of negative wind pressures to draw the air out and not block ow with positive pressure. It may require operable vents on all faces to respond to different wind directions. > The function of solar chimneys is improved by shaping the roof to aid air ow over it, in the manner of an aerofoil, to increase the negative pressure on the exhaust side. > Design of chimney to ensure that pressure remains low (i.e. air inside is warmer than outside) to maintain correct ow direction in cool weather, for example use glass or dark heat-absorbing material near the top of the chimney. > In unpredictable climatic areas fans could be used, these could be run by solar panels on the solar chimney. Caution needs to be used when using fans that they do not interfere with natural air ow.
Exhaust air
Insulation Damper Metal absorber with black selective coating Replacement air drawn from cool side of house
Fresh air
> Figure 5 Cross section of Victoria Barracks, Sydney, showing air ow path of cross ow natural ventilation incorporating a solar chimney.
Making natural ventilation work, Andrew Martin and Jason Fitzsimmons, BSRIA GN 7/2000.
> Reference 4 Passive Solar Guidelines (Residential) www.greenbuilder.com/sourcebook/PassSolGuide3.html > Reference 5 Gage S. A., Hunt G.R. and Linden P.F. (2001) Top down ventilation and cooling. Journal of Architectural and Planning Research 18:4, p.286. > Reference 6 Chilengwe N. and Sharples S. (2003) Low and High Pressure Experimental Analysis of Ventilators for Natural Ventilation in Buildings. International Journal of Ventilation 2:2, pp. 149-158. > Reference 7 Heiselberg P (2002) Principles of Hybrid Ventilation. Hybrid Ventilation Centre, Aalborg University. http://hybvent.civil.auc.dk/puplications/report/ Principles%20of%20H%20V.pdf > Reference 8 Rowe, D. (1996) Mixed mode climate control AIRAH Vol 50, Issue 12.
> Reference 3