UNITROL 6800 Alarm and Event List

FOR SW RELEASE V 2.1.21

Contents

Document No.: Version

3BHS258033 E01 Rev. 07 / 2008

ABB
Nr ID Name

Events

Description

Display events on the ECT (Excitation Control Terminal): Touch Events The Event Logger contains a table with the last 1000 entries. As soon as this window is selected, an automatic upload will start. If a new entry occurs, the panel reads this out of the UNITROL System and the table will automatically be updated.
Dynamic list of actual events Event logger table

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Rp Fault: The monitoring of Converter 1 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 1 20000 ThyrFlt_Rp_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Tn Fault: The monitoring of Converter 1 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 2 20001 ThyrFlt_Tn_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Sp Fault: The monitoring of Converter 1 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 3 20002 ThyrFlt_Sp_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Rn Fault: The monitoring of Converter 1 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 4 20003 ThyrFlt_Rn_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Tp Fault: The monitoring of Converter 1 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 5 20004 ThyrFlt_Tp_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Sn Fault: The monitoring of Converter 1 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 6 20005 ThyrFlt_Sn_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI1. Fuse Rp Fault: Branch Fuse Rp blown

Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter) 7 20006 FuseFlt_Rp_CCI1

Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters:

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

CCI1. Fuse Tn Fault: Branch Fuse Tn faulty

Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 8 20007 FuseFlt_Tn_CCI1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Fuse Sp Fault: Branch Fuse Sp faulty

Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 9 20008 FuseFlt_Sp_CCI1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI1. Fuse Rn Fault: Branch Fuse Rn faulty

Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 10 20009 FuseFlt_Rn_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

10

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
TFFDnumOfPeriods

Description

Further steps: ----

CCI1. Fuse Tp Fault: Branch Fuse Tp faulty

Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 11 20010 FuseFlt_Tp_CCI1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

11

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Fuse Sn Fault: Branch Fuse Sn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 12 20011 FuseFlt_Sn_CCI1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI1. Overcurrent in Phase R detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 13 20012 TOCD_R_CCI1 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

12

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Further steps:

Description

CCI1. Overcurrent in Phase S detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 14 20013 TOCD_S_CCI1 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ----

13

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Overcurrent in Phase T detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 15 20014 TOCD_T_CCI1 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---CCI1. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: N-1 16 20015 UfOpCeil_CCI1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon

Further steps: ----

14

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI1. Device Type Error

Description

Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 1

17

20016

DevTypeErr_CCI1

Default reaction: - Converter Trip

Related parameters: ----

Further steps: ---CCI1. Address Error

Possible reasons: - Wrong HEX Switch setting at CCI 1

Default reaction: 18 20017 AddressErr_CCI1 - Converter Trip

Related parameters: ----

Further steps: ----

15

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Link Fault detected by AC 800PEC

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

19

20018

LinkFault_CCI1

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to CCI CCI1. Redundant Power 1 fail

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 20 20019 RedPwrFail1_CCI1 - Converter Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply CCI1. Redundant Power 2 fail

Possible reasons: - Power supply fault at input 2 (X2:1-2) 21 20020 RedPwrFail2_CCI1 Default reaction: - Converter Redundancy Fault

Related parameters:

16

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

CCI1. Precision Power fail

Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing

Default reaction: 22 20021 PrciPwrFail_CCI1 - Converter Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board CCI1. CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

23

20022

CPUWatchdog_CCI1

Default reaction: - Converter Trip

Related parameters: ----

Further steps:

17

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Reboot device

Description

- Download installer archive - Replace board

CCI1. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

24

20023

UfFreeze_CCI1

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UfEnaADCFreezeMon

Further steps: - Replace board CCI1. Synchronous Voltage measurement failure

Possible reasons: - One Phase of the AC-connection lost

Default reaction: 25 20024 USynInPhase_CCI1 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaInPhaseMon

Further steps: - Check cabling

18

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 26 20025 USynOpCeil_CCI1 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon

Further steps: - Replace board CCI1. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

27

20026

USynFreeze_CCI1

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaADCFreezeMon

Further steps: - Replace board CCI1. Synchronous Voltage measurement failure

Possible reasons: - Two or all three connections lost 28 20027 USynAllLost_CCI1

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaAllLostMon

19

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling

CCI1. Link Fault detected by CCI

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1)

Default reaction: 29 20028 SelfTrip_CCI1 - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to AC 800PEC CCI1. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses

Possible reasons: - Internal short circuit at a TWIN confuguration (Cold Standby)

Default reaction: - Converter Trip 30 20029 AdvFuseBlow_CCI1 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown

Further steps: - Check thyristors - Check fuses

20

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

31

20030

IConvOpCeil_CCI1

Default reaction: - Converter Trip

Related parameters: Prot_Protection \ IconvEnaADCFreezeMon

Further steps: - Replace board CCI1. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 32 20031 IConvFreeze_CCI1 - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon

Further steps: - Replace board

21

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI1. Cooling failure

Description

Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters

Default reaction: 33 20032 CoolingFailure_CCI1 - Converter TRIP

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord

Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI1. Fan 1 Supply 1 fault

Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 34 20033 Fan1Supply1Flt_CCI1 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

22

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace pressure sensor

Description

CCI1. Fan 1 Supply 2 fault

Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

Default reaction: 35 20034 Fan1Supply2Flt_CCI1 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

23

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI1. Fan 2 Supply 1 fault

Description

Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 36 20035 Fan2Supply1Flt_CCI1 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI1. Fan 2 Supply 2 fault

Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

37

20036

Fan2Supply2Flt_CCI1

Default reaction: - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps:

24

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace fan

Description

- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

CCI1. Fan Supply Miniature Circuit Breaker 1 fault

Possible reasons: - Fan 1 defective

Default reaction: - Converter Redundancy fault 38 20037 MCB1Fault_CCI1 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI1. Fan Supply Miniature Circuit Breaker 2 fault

Possible reasons: - Fan 2 defective 39 20038 MCB2Fault_CCI1 Default reaction: - Converter Redundancy fault

Related parameters:

25

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

CCI1. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 40 20039 ThyrTemp1Lev1Fl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

26

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 41 20040 ThyrTemp2Lev1Fl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI1. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 42 20041 ThyrTemp3Lev1Fl_CCI1 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

27

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI1. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 43 20042 ThyrTemp4Lev1Fl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

28

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 44 20043 ThyrTemp5Lev1Fl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI1. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 45 20044 ThyrTemp6Lev1Fl_CCI1 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

29

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI1. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 46 20045 AirTemp1Lev1Flt_CCI1 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

30

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: 47 20046 AirTemp2Lev1Flt_CCI1 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI1. Thyristor Rp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 48 20047 ThyrTemp1SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

31

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Re-check sensor circuit

Description

CCI1. Thyristor Tn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open >156 C - Sensor short-circuit < -13 C

Default reaction: - Converter alarm 49 20048 ThyrTemp2SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

32

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Sp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 50 20049 ThyrTemp3SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI1. Thyristor Rn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 51 20050 ThyrTemp4SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

33

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Tp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 52 20051 ThyrTemp5SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI1. Thyristor Sn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 53 20052 ThyrTemp6SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

34

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Air Temperature 1 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 54 20053 AirTemp1SensFlt_CCI1 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit CCI1. Air Temperature 2 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 55 20054 AirTemp2SensFlt_CCI1 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit

35

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI1. Snubber Switch fault

Description

Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch

Default reaction: N-1 56 20055 SnubberSwiFlt_CCI1 - Converter alarm TWIN - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord

Further steps: - Re-check sensor circuit CCI1. Snubber Fuse fault

Possible reasons: ----

Default reaction: 57 20056 SnubberFuseFlt_CCI1 ----

Related parameters: ----

Further steps: ----

36

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI1. Thyristor Fuse fault

Description

Possible reasons: - Digital input for fuse supervision activated

Default reaction: 58 20057 ThyristorFuseFl_CCI1 - Converter alarm

Related parameters: ----

Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI1. Converter cabinet Door fault

Possible reasons: - Digital input for open door activated

Default reaction: 59 20058 DoorFlt_CCI1 - Converter alarm

Related parameters: ----

Further steps: - Close converter cabinet door CCI1. Software Version fault

Possible reasons: - Wrong converter interface SW version 60 20059 VersionFlt_CCI1

Default reaction: - Converter Trip

Related parameters: ----

37

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Download required software version

CCI1. NegConvFault_CCI1

Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration

Default reaction: 61 20060 NegConvFault_CCI1 - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord

Further steps: - Re-check HW input CCI1. PulseBlock_CCI1 of HW

Possible reason: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive

62

20061

PulseBlockFault_CCI1

Default reaction: - Converter trip

Related parameters: ----

Further steps: - Re-check of HW input 63 20062 TestPosition_CCI1

38

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
64

ID
20063

Name
Event2_31_CCI1

Events

Description

CCI1. Thyristor Rp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

65

20064

ThyrTemp1Lev2Fl_CCI1

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI1. Thyristor Tn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 66 20065 ThyrTemp2Lev2Fl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature

39

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

fault of the other converters (n-1) - Clean air inlet filters

CCI1. Thyristor Sp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

67

20066

ThyrTemp3Lev2Fl_CCI1

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

40

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Thyristor Rn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

68

20067

ThyrTemp4Lev2Fl_CCI1

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI1. Thyristor Tp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 69 20068 ThyrTemp5Lev2Fl_CCI1

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

41

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

CCI1. Thyristor Sn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

70

20069

ThyrTemp6Lev2Fl_CCI1

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

42

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1. Air Temperature 1 ( Thyristor Cooler Input ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 71 20070 AirTemp1Lev2Flt_CCI1

Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI1. Air Temperature 2 ( Air outlet chimney ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: - Converter alarm 72 20071 AirTemp2Lev2Flt_CCI1 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level

43

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90

20072 20073 20074 20075 20076 20077 20078 20079 20080 20081 20082 20083 20084 20085 20086 20087 20088 20089

Event3_08_CCI1 Event3_09_CCI1 Event3_10_CCI1 Event3_11_CCI1 Event3_12_CCI1 Event3_13_CCI1 Event3_14_CCI1 Event3_15_CCI1 Event3_16_CCI1 Event3_17_CCI1 Event3_18_CCI1 Event3_19_CCI1 Event3_20_CCI1 Event3_21_CCI1 Event3_22_CCI1 Event3_23_CCI1 Event3_24_CCI1 Event3_25_CCI1

44

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
91 92 93 94 95 96

ID
20090 20091 20092 20093 20094 20095

Name
Event3_26_CCI1 Event3_27_CCI1 Event3_28_CCI1 Event3_29_CCI1 Event3_30_CCI1 Event3_31_CCI1

Events

Description

CCI2. Thyristor Rp Fault: The monitoring of Converter 2 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 97 20100 ThyrFlt_Rp_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

45

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Tn Fault: The monitoring of Converter 2 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 98 20101 ThyrFlt_Tn_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

46

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Sp Fault: The monitoring of Converter 2 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 99 20102 ThyrFlt_Sp_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

47

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Rn Fault: The monitoring of Converter 2 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 100 20103 ThyrFlt_Rn_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

48

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Tp Fault: The monitoring of Converter 2 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 101 20104 ThyrFlt_Tp_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

49

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Sn Fault: The monitoring of Converter 2 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 102 20105 ThyrFlt_Sn_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI2. Fuse Rp Fault: Branch Fuse Rp blown

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 103 20106 FuseFlt_Rp_CCI2

Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters:

50

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

CCI2. Fuse Tn Fault: Branch Fuse Tn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 104 20107 FuseFlt_Tn_CCI2 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

51

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Fuse Sp Fault: Branch Fuse Sp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 105 20108 FuseFlt_Sp_CCI2 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI2. Fuse Rn Fault: Branch Fuse Rn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 106 20109 FuseFlt_Rn_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

52

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
TFFDnumOfPeriods

Description

Further steps: ----

CCI2. Fuse Tp Fault: Branch Fuse Tp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 107 20110 FuseFlt_Tp_CCI2 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

53

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Fuse Sn Fault: Branch Fuse Sn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 108 20111 FuseFlt_Sn_CCI2 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI2. Overcurrent in Phase R detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 109 20112 TOCD_R_CCI2 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

54

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Further steps:

Description

CCI2. Overcurrent in Phase S detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 110 20113 TOCD_S_CCI2 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ----

55

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Overcurrent in Phase T detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 111 20114 TOCD_T_CCI2 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---CCI2. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: N-1 112 20115 UfOpCeil_CCI2 - Converter alarm Twin - Converter alarm

Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon

Further steps: ----

56

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI2. Device Type Error

Description

Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 2

113

20116

DevTypeErr_CCI2

Default reaction: - Converter Trip

Related parameters: ----

Further steps: ---CCI2. Address Error

Possible reasons: - Wrong HEX Switch setting at CCI 2

Default reaction: 114 20117 AddressErr_CCI2 - Converter Trip

Related parameters: ----

Further steps: ----

57

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Link Fault detected by AC 800PEC

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

115

20118

LinkFault_CCI2

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to CCI CCI2. Redundant Power 1 fail

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 116 20119 RedPwrFail1_CCI2 - Converter Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply CCI2. Redundant Power 2 fail

Possible reasons: - Power supply fault at input 2 (X2:1-2) 117 20120 RedPwrFail2_CCI2 Default reaction: - Converter Redundancy Fault

Related parameters:

58

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

CCI2. Precision Power fail

Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing

Default reaction: 118 20121 PrciPwrFail_CCI2 - Converter Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board CCI2. CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

119

20122

CPUWatchdog_CCI2

Default reaction: - Converter Trip

Related parameters: ----

Further steps:

59

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Reboot device

Description

- Download installer archive - Replace board

CCI2. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

120

20123

UfFreeze_CCI2

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UfEnaADCFreezeMon

Further steps: - Replace board CCI2. Synchronous Voltage measurement failure

Possible reasons: - One Phase of the AC-connection lost

Default reaction: 121 20124 USynInPhase_CCI2 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaInPhaseMon

Further steps: - Check cabling

60

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 122 20125 USynOpCeil_CCI2 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon

Further steps: - Replace board CCI2. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

123

20126

USynFreeze_CCI2

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaADCFreezeMon

Further steps: - Replace board CCI2. Synchronous Voltage measurement failure

Possible reasons: - Two or all three connections lost 124 20127 USynAllLost_CCI2

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaAllLostMon

61

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling

CCI2. Link Fault detected by CCI

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1)

Default reaction: 125 20128 SelfTrip_CCI2 - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to AC 800PEC CCI2. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses

Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby)

Default reaction: - Converter Trip 126 20129 AdvFuseBlow_CCI2 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown

Further steps: - Check thyristors - Check fuses

62

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

127

20130

IConvOpCeil_CCI2

Default reaction: - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaADCFreezeMon

Further steps: - Replace board CCI2. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 128 20131 IConvFreeze_CCI2 - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon

Further steps: - Replace board

63

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI2. Cooling failure

Description

Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters

Default reaction: 129 20132 CoolingFailure_CCI2 - Converter TRIP

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord

Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI2. Fan 1 Supply 1 fault

Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 130 20133 Fan1Supply1Flt_CCI2 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

64

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace pressure sensor

Description

CCI2. Fan 1 Supply 2 fault

Possible reasons: - Fan 1 defective - Supply 2 missing - pressure sensor defective - Dirty filters

Default reaction: 131 20134 Fan1Supply2Flt_CCI2 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

65

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI2. Fan 2 Supply 1 fault

Description

Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 132 20135 Fan2Supply1Flt_CCI2 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI2. Fan 2 Supply 2 fault

Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

133

20136

Fan2Supply2Flt_CCI2

Default reaction: - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps:

66

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace fan

Description

- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

CCI2. Fan Supply Miniature Circuit Breaker 1 fault

Possible reasons: - Fan 1 defective

Default reaction: - Converter Redundancy fault 134 20137 MCB1Fault_CCI2 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI2. Fan Supply Miniature Circuit Breaker 2 fault

Possible reasons: - Fan 2 defective 135 20138 MCB2Fault_CCI2 Default reaction: - Converter Redundancy fault

Related parameters:

67

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

CCI2. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 136 20139 ThyrTemp1Lev1Fl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

68

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 137 20140 ThyrTemp2Lev1Fl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI2. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 138 20141 ThyrTemp3Lev1Fl_CCI2 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

69

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI2. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 139 20142 ThyrTemp4Lev1Fl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

70

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 140 20143 ThyrTemp5Lev1Fl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI2. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 141 20144 ThyrTemp6Lev1Fl_CCI2 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

71

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI2. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 142 20145 AirTemp1Lev1Flt_CCI2 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

72

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Air Temperature 2 ( Air outlet chimmey ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: 143 20146 AirTemp2Lev1Flt_CCI2 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI2. Thyristor Rp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 144 20147 ThyrTemp1SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

73

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Re-check sensor circuit

Description

CCI2. Thyristor Tn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 145 20148 ThyrTemp2SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

74

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Sp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 146 20149 ThyrTemp3SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI2. Thyristor Rn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 147 20150 ThyrTemp4SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

75

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Tp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 148 20151 ThyrTemp5SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI2. Thyristor Sn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 149 20152 ThyrTemp6SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

76

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Air Temperature 1 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 150 20153 AirTemp1SensFlt_CCI2 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit CCI2. Air Temperature 2 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 151 20154 AirTemp2SensFlt_CCI2 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit

77

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI2. Snubber Switch fault

Description

Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch

Default reaction: N-1 152 20155 SnubberSwiFlt_CCI2 - Converter alarm TWIN - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord

Further steps: - Re-check sensor circuit CCI2. Snubber Fuse fault

Possible reasons: ----

Default reaction: 153 20156 SnubberFuseFlt_CCI2 ----

Related parameters: ----

Further steps: ----

78

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI2. Thyristor Fuse fault

Description

Possible reasons: - Digital input for fuse supervision activated

Default reaction: 154 20157 ThyristorFuseFl_CCI2 - Converter alarm

Related parameters: ----

Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI2. Converter cabinet Door fault

Possible reasons: - Digital input for open door activated

Default reaction: 155 20158 DoorFlt_CCI2 - Converter alarm

Related parameters: ----

Further steps: - Close converter cabinet door CCI2. Software Version fault

Possible reasons: - Wrong converter interface SW version 156 20159 VersionFlt_CCI2

Default reaction: - Converter Trip

Related parameters: ----

79

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Download required software version

CCI2. NegConvFault_CCI2

Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration

Default reaction: 157 20160 NegConvFault_CCI2 - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord

Further steps: - Re-check HW input CCI2. PulseBlock_CCI2 by hardware

Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive

158

20161

PulseBlockFault_CCI2

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Re-check HW input 159 20162 TestPosition_CCI2

80

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
160

ID
20163

Name
Event2_31_CCI2

Events

Description

CCI2. Thyristor Rp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

161

20164

ThyrTemp1Lev2Fl_CCI2

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI2. Thyristor Tn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 162 20165 ThyrTemp2Lev2Fl_CCI2 - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

81

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

CCI2. Thyristor Sp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

163

20166

ThyrTemp3Lev2Fl_CCI2

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

82

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Rn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

164

20167

ThyrTemp4Lev2Fl_CCI2

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI2. Thyristor Tp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 165 20168 ThyrTemp5Lev2Fl_CCI2

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

83

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

CCI2. Thyristor Sn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

166

20169

ThyrTemp6Lev2Fl_CCI2

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

84

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Air Temperature 1 ( Thyristor Cooler Input ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 167 20170 AirTemp1Lev2Flt_CCI2

Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI2. Air Temperature 2 ( Air outlet chimney ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: - Converter alarm 168 20171 AirTemp2Lev2Flt_CCI2 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level

85

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

169 1'341 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187

20172 21500 20174 20175 20176 20177 20178 20179 20180 20181 20182 20183 20184 20185 20186 20187 20188 20189 20190

Event3_08_CCI2 Event4_14 Event3_10_CCI2 Event3_11_CCI2 Event3_12_CCI2 Event3_13_CCI2 Event3_14_CCI2 Event3_15_CCI2 Event3_16_CCI2 Event3_17_CCI2 Event3_18_CCI2 Event3_19_CCI2 Event3_20_CCI2 Event3_21_CCI2 Event3_22_CCI2 Event3_23_CCI2 Event3_24_CCI2 Event3_25_CCI2 Event3_26_CCI2

86

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
188 189 190 191 192

ID
20191 20192 20193 20194 20195

Name
Event3_27_CCI2 Event3_28_CCI2 Event3_29_CCI2 Event3_30_CCI2 Event3_31_CCI2

Events

Description

CCI3. Thyristor Rp Fault: The monitoring of Converter 3 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 193 20200 ThyrFlt_Rp_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

87

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Thyristor Tn Fault: The monitoring of Converter 3 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 194 20201 ThyrFlt_Tn_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

88

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Thyristor Sp Fault: The monitoring of Converter 3 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 195 20202 ThyrFlt_Sp_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

89

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Thyristor Rn Fault: The monitoring of Converter 3 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 196 20203 ThyrFlt_Rn_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

90

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Thyristor Tp Fault: The monitoring of Converter 3 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 197 20204 ThyrFlt_Tp_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

91

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Thyristor Sn Fault: The monitoring of Converter 3 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 198 20205 ThyrFlt_Sn_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI3. Fuse Rp Fault: Branch Fuse Rp blown

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 199 20206 FuseFlt_Rp_CCI3

Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters:

92

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

CCI3. Fuse Tn Fault: Branch Fuse Tn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 200 20207 FuseFlt_Tn_CCI3 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

93

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Fuse Sp Fault: Branch Fuse Sp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 201 20208 FuseFlt_Sp_CCI3 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI3. Fuse Rn Fault: Branch Fuse Rn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 202 20209 FuseFlt_Rn_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

94

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
TFFDnumOfPeriods

Description

Further steps: ----

CCI3. Fuse Tp Fault: Branch Fuse Tp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 203 20210 FuseFlt_Tp_CCI3 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

95

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Fuse Sn Fault: Branch Fuse Sn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 204 20211 FuseFlt_Sn_CCI3 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI3. Overcurrent in Phase R detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 205 20212 TOCD_R_CCI3 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

96

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Further steps:

Description

CCI3. Overcurrent in Phase S detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 206 20213 TOCD_S_CCI3 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---1'342 20214 SW_Reboot

97

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Overcurrent in Phase T detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 207 20215 TOCD_T_CCI3 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---CCI3. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: N-1 208 20216 UfOpCeil_CCI3 - Converter alarm Twin - Converter alarm

Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon

Further steps: ----

98

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI3. Device Type Error

Description

Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 3

209

20217

DevTypeErr_CCI3

Default reaction: - Converter Trip

Related parameters: ----

Further steps: ---CCI3. Address Error

Possible reasons: - Wrong HEX Switch setting at CCI 3

Default reaction: 210 20218 AddressErr_CCI3 - Converter Trip

Related parameters: ----

Further steps: ----

99

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Link Fault detected by AC 800PEC

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

211

20219

LinkFault_CCI3

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to CCI CCI3. Redundant Power 1 fail

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 212 20220 RedPwrFail1_CCI3 - Converter Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply CCI3. Redundant Power 2 fail

Possible reasons: - Power supply fault at input 2 (X2:1-2) 213 20221 RedPwrFail2_CCI3 Default reaction: - Converter Redundancy Fault

Related parameters:

100

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

CCI3. Precision Power fail

Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing

Default reaction: 214 20222 PrciPwrFail_CCI3 - Converter Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board CCI3. CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

215

20223

CPUWatchdog_CCI3

Default reaction: - Converter Trip

Related parameters: ----

Further steps:

101

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Reboot device

Description

- Download installer archive - Replace board

CCI3. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

216

20224

UfFreeze_CCI3

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UfEnaADCFreezeMon

Further steps: - Replace board CCI3. Synchronous Voltage measurement failure

Possible reasons: - One Phase of the AC-connection lost

Default reaction: 217 20225 USynInPhase_CCI3 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaInPhaseMon

Further steps: - Check cabling

102

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 218 20226 USynOpCeil_CCI3 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon

Further steps: - Replace board CCI3. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

219

20227

USynFreeze_CCI3

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaADCFreezeMon

Further steps: - Replace board CCI3. Synchronous Voltage measurement failure

Possible reasons: - Two or all three connections lost 220 20228 USynAllLost_CCI3

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaAllLostMon

103

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling

CCI3. Link Fault detected by CCI

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1)

Default reaction: 221 20229 SelfTrip_CCI3 - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to AC 800PEC CCI3. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses

Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby)

Default reaction: - Converter Trip 222 20230 AdvFuseBlow_CCI3 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown

Further steps: - Check thyristors - Check fuses

104

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

223

20231

IConvOpCeil_CCI3

Default reaction: - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaADCFreezeMon

Further steps: - Replace board CCI3. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 224 20232 IConvFreeze_CCI3 - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon

Further steps: - Replace board

105

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI3. Cooling failure

Description

Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters

Default reaction: 225 20233 CoolingFailure_CCI3 - Converter TRIP

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord

Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI3. Fan 1 Supply 1 fault

Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 226 20234 Fan1Supply1Flt_CCI3 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

106

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace pressure sensor

Description

CCI3. Fan 1 Supply 2 fault

Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

Default reaction: 227 20235 Fan1Supply2Flt_CCI3 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

107

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI3. Fan 2 Supply 1 fault

Description

Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 228 20236 Fan2Supply1Flt_CCI3 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI3. Fan 2 Supply 2 fault

Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

229

20237

Fan2Supply2Flt_CCI3

Default reaction: - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps:

108

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace fan

Description

- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace preasure sensor

CCI3. Fan Supply Miniature Circuit Breaker 1 fault

Possible reasons: - Fan 1 defective

Default reaction: - Converter Redundancy fault 230 20238 MCB1Fault_CCI3 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI3. Fan Supply Miniature Circuit Breaker 2 fault

Possible reasons: - Fan 2 defective 231 20239 MCB2Fault_CCI3 Default reaction: - Converter Redundancy fault

Related parameters:

109

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

CCI3. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 232 20240 ThyrTemp1Lev1Fl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

110

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 233 20241 ThyrTemp2Lev1Fl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI3. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 234 20242 ThyrTemp3Lev1Fl_CCI3 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

111

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI3. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 235 20243 ThyrTemp4Lev1Fl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

112

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 236 20244 ThyrTemp5Lev1Fl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI3. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 237 20245 ThyrTemp6Lev1Fl_CCI3 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

113

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI3. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 238 20246 AirTemp1Lev1Flt_CCI3 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

114

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Air Temperature 2 ( Air outlet chimmey ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: 239 20247 AirTemp2Lev1Flt_CCI3 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI3. Thyristor Rp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 240 20248 ThyrTemp1SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

115

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Re-check sensor circuit

Description

CCI3. Thyristor Tn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 241 20249 ThyrTemp2SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

116

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Thyristor Sp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 242 20250 ThyrTemp3SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI3. Thyristor Rn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 243 20251 ThyrTemp4SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

117

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Thyristor Tp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 244 20252 ThyrTemp5SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI3. Thyristor Sn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 245 20253 ThyrTemp6SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

118

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Air Temperature 1 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 246 20254 AirTemp1SensFlt_CCI3 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit CCI3. Air Temperature 2 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 247 20255 AirTemp2SensFlt_CCI3 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit

119

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI3. Snubber Switch fault

Description

Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch

Default reaction: N-1 248 20256 SnubberSwiFlt_CCI3 - Converter alarm TWIN - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord

Further steps: - Re-check sensor circuit CCI3. Snubber Fuse fault

Possible reasons: ----

Default reaction: 249 20257 SnubberFuseFlt_CCI3 ----

Related parameters: ----

Further steps: ----

120

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI3. Thyristor Fuse fault

Description

Possible reasons: - Digital input for fuse supervision activated

Default reaction: 250 20258 ThyristorFuseFl_CCI3 - Converter alarm

Related parameters: ----

Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI3. Converter cabinet Door fault

Possible reasons: - Digital input for open door activated

Default reaction: 251 20259 DoorFlt_CCI3 - Converter alarm

Related parameters: ----

Further steps: - Close converter cabinet door CCI3. Software Version fault

Possible reasons: - Wrong converter interface SW version 252 20260 VersionFlt_CCI3

Default reaction: - Converter Trip

Related parameters: ----

121

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Download required software version

CCI3. NegConvFault_CCI3

Possible reasons: - The DI12 signal of Converter I/O does not match converter configuration

Default reaction: 253 20261 NegConvFault_CCI3 - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord

Further steps: - Re-check HW input CCI3. PulseBlock_CCI3 by hardware

Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive

254

20262

PulseBlockFault_CCI3

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Re-check HW input 255 20263 TestPosition_CCI3

122

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
256

ID
20264

Name
Event2_31_CCI3

Events

Description

CCI3. Thyristor Rp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

257

20265

ThyrTemp1Lev2Fl_CCI3

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI3. Thyristor Tn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 258 20266 ThyrTemp2Lev2Fl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature

123

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

fault of the other converters (n-1) - Clean air inlet filters

CCI3. Thyristor Sp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

259

20267

ThyrTemp3Lev2Fl_CCI3

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters 1'343 20268 ForceAuto

124

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Thyristor Rn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

260

20269

ThyrTemp4Lev2Fl_CCI3

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI3. Thyristor Tp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 261 20270 ThyrTemp5Lev2Fl_CCI3

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

125

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

CCI3. Thyristor Sn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

262

20271

ThyrTemp6Lev2Fl_CCI3

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

126

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3. Air Temperature 1 ( Thyristor Cooler Input ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 263 20272 AirTemp1Lev2Flt_CCI3

Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI3. Air Temperature 2 ( Air outlet chimney ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: - Converter alarm 264 20273 AirTemp2Lev2Flt_CCI3 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level

127

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282

20274 20275 20276 20277 20278 20279 20280 20281 20282 20283 20284 20285 20286 20287 20288 20289 20290 20291

Event3_08_CCI3 Event3_09_CCI3 Event3_10_CCI3 Event3_11_CCI3 Event3_12_CCI3 Event3_13_CCI3 Event3_14_CCI3 Event3_15_CCI3 Event3_16_CCI3 Event3_17_CCI3 Event3_18_CCI3 Event3_19_CCI3 Event3_20_CCI3 Event3_21_CCI3 Event3_22_CCI3 Event3_23_CCI3 Event3_24_CCI3 Event3_25_CCI3

128

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
283 284 285 286 287 288

ID
20292 20293 20294 20295 20300 20301

Name
Event3_26_CCI3 Event3_27_CCI3 Event3_28_CCI3 Event3_29_CCI3 Event3_30_CCI3 Event3_31_CCI3

Events

Description

CCI4. Thyristor Rp Fault: The monitoring of Converter 4 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 289 20302 ThyrFlt_Rp_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

129

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Thyristor Tn Fault: The monitoring of Converter 4 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 290 20303 ThyrFlt_Tn_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

130

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Thyristor Sp Fault: The monitoring of Converter 4 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 291 20304 ThyrFlt_Sp_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

131

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Thyristor Rn Fault: The monitoring of Converter 4 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 292 20305 ThyrFlt_Rn_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ---CCI4. Thyristor Tp Fault: The monitoring of Converter 4 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty 293 20306 ThyrFlt_Tp_CCI4 - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip

132

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

CCI4. Thyristor Sn Fault: The monitoring of Converter 4 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)

Default reaction: 294 20307 ThyrFlt_Sn_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps:

133

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

CCI4. Fuse Rp Fault: Branch Fuse Rp blown

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction

Default reaction: N-1 295 20308 FuseFlt_Rp_CCI4 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

134

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Fuse Tn Fault: Branch Fuse Tn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 296 20309 FuseFlt_Tn_CCI4 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI4. Fuse Sp Fault: Branch Fuse Sp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 297 20310 FuseFlt_Sp_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

135

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
TFFDnumOfPeriods

Description

Further steps: ----

CCI4. Fuse Rn Fault: Branch Fuse Rn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 298 20311 FuseFlt_Rn_CCI4 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

136

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Fuse Tp Fault: Branch Fuse Tp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 299 20312 FuseFlt_Tp_CCI4 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI4. Fuse Sn Fault: Branch Fuse Sn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 300 20313 FuseFlt_Sn_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

137

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
TFFDnumOfPeriods

Description

Further steps: ----

CCI4. Overcurrent in Phase R detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 301 20314 TOCD_R_CCI4 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ----

138

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Overcurrent in Phase S detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 302 20315 TOCD_S_CCI4 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---1'344 20316 ForceManual CCI4. Overcurrent in Phase T detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 303 20317 TOCD_T_CCI4 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps:

139

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

CCI4. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: N-1 304 20318 UfOpCeil_CCI4 - Converter alarm Twin - Converter alarm

Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon

Further steps: ---CCI4. Device Type Error

Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) 305 20319 DevTypeErr_CCI4 - Wrong installer archive loaded to CCI 4

Default reaction: - Converter Trip

140

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Related parameters:

Description

Further steps: ----

CCI4. Address Error

Possible reasons: - Wrong HEX Switch setting at CCI 4

Default reaction: 306 20320 AddressErr_CCI4 - Converter Trip

Related parameters: ----

Further steps: ---CCI4. Link Fault detected by AC 800PEC

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

307

20321

LinkFault_CCI4

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to CCI

141

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Redundant Power 1 fail

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 308 20322 RedPwrFail1_CCI4 - Converter Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply CCI4. Redundant Power 2 fail

Possible reasons: - Power supply fault at input 2 (X2:1-2)

Default reaction: 309 20323 RedPwrFail2_CCI4 - Converter Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CCI4. Precision Power fail

Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing 310 20324 PrciPwrFail_CCI4 Default reaction: - Converter Trip

Related parameters: ----

142

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling and power supply - Replace board

CCI4. CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 311 20325 CPUWatchdog_CCI4 - Converter Trip

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board CCI4. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure 312 20326 UfFreeze_CCI4 Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UfEnaADCFreezeMon

143

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Replace board

CCI4. Synchronous Voltage measurement failure

Possible reasons: - One Phase of the AC-connection lost

Default reaction: 313 20327 USynInPhase_CCI4 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaInPhaseMon

Further steps: - Check cabling CCI4. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 314 20328 USynOpCeil_CCI4 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon

Further steps: - Replace board

144

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

315

20329

USynFreeze_CCI4

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaADCFreezeMon

Further steps: - Replace board CCI4. Synchronous Voltage measurement failure

Possible reasons: - Two or all three connections lost

Default reaction: 316 20330 USynAllLost_CCI4 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaAllLostMon

Further steps: - Check cabling CCI4. Link Fault detected by CCI

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) 317 20331 SelfTrip_CCI4

Default reaction: - Converter Trip

Related parameters: ----

145

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check optical link cabling to AC 800PEC

CCI4. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses

Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby)

Default reaction: - Converter Trip 318 20332 AdvFuseBlow_CCI4 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown

Further steps: - Check thyristors - Check fuses CCI4. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

319

20333

IConvOpCeil_CCI4

Default reaction: - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaADCFreezeMon

Further steps:

146

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace board

Description

CCI4. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 320 20334 IConvFreeze_CCI4 - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon

Further steps: - Replace board CCI4. Cooling failure

Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters

321

20335

CoolingFailure_CCI4

Default reaction: - Converter TRIP

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord

Further steps: - Replace fan(s)

147

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters - Replace pressure sensor

Description

CCI4. Fan 1 Supply 1 fault

Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 322 20336 Fan1Supply1Flt_CCI4 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

148

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI4. Fan 1 Supply 2 fault

Description

Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - dirty filters

Default reaction: 323 20337 Fan1Supply2Flt_CCI4 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI4. Fan 2 Supply 1 fault

Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

324

20338

Fan2Supply1Flt_CCI4

Default reaction: - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps:

149

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace fan

Description

- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace preasure sensor

CCI4. Fan 2 Supply 2 fault

Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

Default reaction: 325 20339 Fan2Supply2Flt_CCI4 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

150

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Fan Supply Miniature Circuit Breaker 1 fault

Possible reasons: - Fan 1 defective

Default reaction: - Converter Redundancy fault 326 20340 MCB1Fault_CCI4 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI4. Fan Supply Miniature Circuit Breaker 2 fault

Possible reasons: - Fan 2 defective

Default reaction: - Converter Redundancy fault 327 20341 MCB2Fault_CCI4 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

151

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 328 20342 ThyrTemp1Lev1Fl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI4. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 329 20343 ThyrTemp2Lev1Fl_CCI4 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

152

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI4. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 330 20344 ThyrTemp3Lev1Fl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

153

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 331 20345 ThyrTemp4Lev1Fl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI4. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 332 20346 ThyrTemp5Lev1Fl_CCI4 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

154

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI4. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 333 20347 ThyrTemp6Lev1Fl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

155

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 334 20348 AirTemp1Lev1Flt_CCI4 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI4. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

335

20349

AirTemp2Lev1Flt_CCI4

Default reaction: - Converter alarm

Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

156

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Further steps:

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI4. Thyristor Rp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 336 20350 ThyrTemp1SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

157

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Thyristor Tn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 337 20351 ThyrTemp2SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI4. Thyristor Sp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 338 20352 ThyrTemp3SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

158

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Thyristor Rn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 339 20353 ThyrTemp4SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI4. Thyristor Tp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 340 20354 ThyrTemp5SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

159

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Thyristor Sn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 341 20355 ThyrTemp6SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI4. Air Temperature 1 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 342 20356 AirTemp1SensFlt_CCI4 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit

160

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Air Temperature 2 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 343 20357 AirTemp2SensFlt_CCI4 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit CCI4. Snubber Switch fault

Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch

Default reaction: N-1 344 20358 SnubberSwiFlt_CCI4 - Converter alarm TWIN - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord

Further steps: - Re-check sensor circuit

161

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI4. Snubber Fuse fault

Description

Possible reasons: ----

Default reaction: 345 20359 SnubberFuseFlt_CCI4 ----

Related parameters: ----

Further steps: ---CCI4. Thyristor Fuse fault

Possible reasons: - Digital input for fuse supervision activated

Default reaction: 346 20360 ThyristorFuseFl_CCI4 - Converter alarm

Related parameters: ----

Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI4. Converter cabinet Door fault

Possible reasons: - Digital input for open door activated 347 20361 DoorFlt_CCI4

Default reaction: - Converter alarm

Related parameters: ----

162

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Close converter cabinet door

CCI4. Software Version fault

Possible reasons: - Wrong converter interface SW version

Default reaction: 348 20362 VersionFlt_CCI4 - Converter Trip

Related parameters: ----

Further steps: - Download required software version CCI4. NegConvFault_CCI4

Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration

Default reaction: 349 20363 NegConvFault_CCI4 - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord

Further steps: - Re-check HW input

163

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. PulseBlock_CCI4 by hardware

Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive

350

20364

PulseBlockFault_CCI4

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Re-check HW input 351 352 20365 20366 TestPosition_CCI4 Event2_31_CCI4 CCI4. Thyristor Rp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

353

20367

ThyrTemp1Lev2Fl_CCI4

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

164

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Thyristor Tn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

354

20368

ThyrTemp2Lev2Fl_CCI4

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI4. Thyristor Sp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 355 20369 ThyrTemp3Lev2Fl_CCI4

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

165

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

1'345

20370

ForceChannel1 CCI4. Thyristor Rn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

356

20371

ThyrTemp4Lev2Fl_CCI4

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

166

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Thyristor Tp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

357

20372

ThyrTemp5Lev2Fl_CCI4

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI4. Thyristor Sn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 358 20373 ThyrTemp6Lev2Fl_CCI4

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

167

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

CCI4. Air Temperature 1 ( Thyristor Cooler Input ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 359 20374 AirTemp1Lev2Flt_CCI4

Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

168

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4. Air Temperature 2 ( Air outlet chimney ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: - Converter alarm 360 20375 AirTemp2Lev2Flt_CCI4 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters 361 362 363 364 365 366 367 368 369 370 371 372 373 374 20376 20377 20378 20379 20380 20381 20382 20383 20384 20385 20386 20387 20388 20389 Event3_08_CCI4 Event3_09_CCI4 Event3_10_CCI4 Event3_11_CCI4 Event3_12_CCI4 Event3_13_CCI4 Event3_14_CCI4 Event3_15_CCI4 Event3_16_CCI4 Event3_17_CCI4 Event3_18_CCI4 Event3_19_CCI4 Event3_20_CCI4 Event3_21_CCI4

169

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
375 376 377 378 379 380 381 382 383 384

ID
20390 20391 20392 20393 20394 20395 20400 20401 20402 20403

Name
Event3_22_CCI4 Event3_23_CCI4 Event3_24_CCI4 Event3_25_CCI4 Event3_26_CCI4 Event3_27_CCI4 Event3_28_CCI4 Event3_29_CCI4 Event3_30_CCI4 Event3_31_CCI4

Events

Description

CCI5. Thyristor Rp Fault: The monitoring of Converter 5 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 385 20404 ThyrFlt_Rp_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

170

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Thyristor Tn Fault: The monitoring of Converter 5 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 386 20405 ThyrFlt_Tn_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

171

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Thyristor Sp Fault: The monitoring of Converter 5 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 387 20406 ThyrFlt_Sp_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

172

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Thyristor Rn Fault: The monitoring of Converter 5 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 388 20407 ThyrFlt_Rn_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

173

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Thyristor Tp Fault: The monitoring of Converter 5 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 389 20408 ThyrFlt_Tp_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

174

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Thyristor Sn Fault: The monitoring of Converter 5 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 390 20409 ThyrFlt_Sn_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI5. Fuse Rp Fault: Branch Fuse Rp blown

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 391 20410 FuseFlt_Rp_CCI5

Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters:

175

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

CCI5. Fuse Tn Fault: Branch Fuse Tn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 392 20411 FuseFlt_Tn_CCI5 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

176

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Fuse Sp Fault: Branch Fuse Sp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 393 20412 FuseFlt_Sp_CCI5 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI5. Fuse Rn Fault: Branch Fuse Rn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 394 20413 FuseFlt_Rn_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

177

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
TFFDnumOfPeriods

Description

Further steps: ----

CCI5. Fuse Tp Fault: Branch Fuse Tp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 395 20414 FuseFlt_Tp_CCI5 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

178

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Fuse Sn Fault: Branch Fuse Sn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 396 20415 FuseFlt_Sn_CCI5 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI5. Overcurrent in Phase R detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 397 20416 TOCD_R_CCI5 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

179

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Further steps:

Description

CCI5. Overcurrent in Phase S detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 398 20417 TOCD_S_CCI5 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---1'346 20418 ForceChannel2

180

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Overcurrent in Phase T deteced

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 399 20419 TOCD_T_CCI5 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---CCI5. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: N-1 400 20420 UfOpCeil_CCI5 - Converter alarm Twin - Converter alarm

Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon

Further steps: ----

181

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI5. Device Type Error

Description

Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 5

401

20421

DevTypeErr_CCI5

Default reaction: - Converter Trip

Related parameters: ----

Further steps: ---CCI5. Address Error

Possible reasons: - Wrong HEX Switch setting at CCI 5

Default reaction: 402 20422 AddressErr_CCI5 - Converter Trip

Related parameters: ----

Further steps: ----

182

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Link Fault detected by AC 800PEC

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

403

20423

LinkFault_CCI5

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to CCI CCI5. Redundant Power 1 fail

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 404 20424 RedPwrFail1_CCI5 - Converter Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply CCI5. Redundant Power 2 fail

Possible reasons: - Power supply fault at input 2 (X2:1-2) 405 20425 RedPwrFail2_CCI5 Default reaction: - Converter Redundancy Fault

Related parameters:

183

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

CCI5. Precision Power fail

Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing

Default reaction: 406 20426 PrciPwrFail_CCI5 - Converter Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board CCI5. CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

407

20427

CPUWatchdog_CCI5

Default reaction: - Converter Trip

Related parameters: ----

Further steps:

184

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Reboot device

Description

- Download installer archive - Replace board

CCI5. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

408

20428

UfFreeze_CCI5

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UfEnaADCFreezeMon

Further steps: - Replace board CCI5. Synchronous Voltage measurement failure

Possible reasons: - One Phase of the AC-connection lost

Default reaction: 409 20429 USynInPhase_CCI5 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaInPhaseMon

Further steps: - Check cabling

185

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 410 20430 USynOpCeil_CCI5 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon

Further steps: - Replace board CCI5. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

411

20431

USynFreeze_CCI5

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaADCFreezeMon

Further steps: - Replace board CCI5. Synchronous Voltage measurement failure

Possible reasons: - Two or all three connections lost 412 20432 USynAllLost_CCI5

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaAllLostMon

186

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling

CCI5. Link Fault detected by CCI

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1)

Default reaction: 413 20433 SelfTrip_CCI5 - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to AC 800PEC CCI5. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses

Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby)

Default reaction: - Converter Trip 414 20434 AdvFuseBlow_CCI5 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown

Further steps: - Check thyristors - Check fuses

187

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

415

20435

IConvOpCeil_CCI5

Default reaction: - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaADCFreezeMon

Further steps: - Replace board CCI5. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 416 20436 IConvFreeze_CCI5 - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon

Further steps: - Replace board

188

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI5. Cooling failure

Description

Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters

Default reaction: 417 20437 CoolingFailure_CCI5 - Converter TRIP

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord

Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI5. Fan 1 Supply 1 fault

Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 418 20438 Fan1Supply1Flt_CCI5 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

189

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace pressure sensor

Description

CCI5. Fan 1 Supply 2 fault

Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

Default reaction: 419 20439 Fan1Supply2Flt_CCI5 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

190

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI5. Fan 2 Supply 1 fault

Description

Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 420 20440 Fan2Supply1Flt_CCI5 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI5. Fan 2 Supply 2 fault

Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

421

20441

Fan2Supply2Flt_CCI5

Default reaction: - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps:

191

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace fan

Description

- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

CCI5. Fan Supply Miniature Circuit Breaker 1 fault

Possible reasons: - Fan 1 defective

Default reaction: - Converter Redundancy fault 422 20442 MCB1Fault_CCI5 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI5. Fan Supply Miniature Circuit Breaker 2 fault

Possible reasons: - Fan 2 defective 423 20443 MCB2Fault_CCI5 Default reaction: - Converter Redundancy fault

Related parameters:

192

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

CCI5. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 424 20444 ThyrTemp1Lev1Fl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

193

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 425 20445 ThyrTemp2Lev1Fl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI5. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 426 20446 ThyrTemp3Lev1Fl_CCI5 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

194

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI5. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 427 20447 ThyrTemp4Lev1Fl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

195

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 428 20448 ThyrTemp5Lev1Fl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI5. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 429 20449 ThyrTemp6Lev1Fl_CCI5 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

196

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI5. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 430 20450 AirTemp1Lev1Flt_CCI5 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

197

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: 431 20451 AirTemp2Lev1Flt_CCI5 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI5. Thyristor Rp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 432 20452 ThyrTemp1SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

198

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Re-check sensor circuit

Description

CCI5. Thyristor Tn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 433 20453 ThyrTemp2SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

199

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Thyristor Sp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 434 20454 ThyrTemp3SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI5. Thyristor Rn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 435 20455 ThyrTemp4SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

200

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Thyristor Tp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 436 20456 ThyrTemp5SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI5. Thyristor Sn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 437 20457 ThyrTemp6SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

201

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Air Temperature 1 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 438 20458 AirTemp1SensFlt_CCI5 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit CCI5. Air Temperature 2 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 439 20459 AirTemp2SensFlt_CCI5 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit

202

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI5. Snubber Switch fault

Description

Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch

Default reaction: N-1 440 20460 SnubberSwiFlt_CCI5 - Converter alarm TWIN - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord

Further steps: - Re-check sensor circuit CCI5. Snubber Fuse fault

Possible reasons: ----

Default reaction: 441 20461 SnubberFuseFlt_CCI5 ----

Related parameters: ----

Further steps: ----

203

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI5. Thyristor Fuse fault

Description

Possible reasons: - Digital input for fuse supervision activated

Default reaction: 442 20462 ThyristorFuseFl_CCI5 - Converter alarm

Related parameters: ----

Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI5. Converter cabinet Door fault

Possible reasons: - Digital input for open door activated

Default reaction: 443 20463 DoorFlt_CCI5 - Converter alarm

Related parameters: ----

Further steps: - Close converter cabinet door CCI5. Software Version fault

Possible reasons: - Wrong converter interface SW version 444 20464 VersionFlt_CCI5

Default reaction: - Converter Trip

Related parameters: ----

204

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Download required software version

CCI5. NegConvFault_CCI5

Possible reasons: - The DI 12 signal of Converter I/O does not match to converter configuration

Default reaction: 445 20465 NegConvFault_CCI5 - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord

Further steps: - Re-check HW input CCI5. PulseBlock_CCI5 by hardware

Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive

446

20466

PulseBlockFault_CCI5

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Re-check HW input 447 20467 TestPosition_CCI5

205

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
448

ID
20468

Name
Event2_31_CCI5

Events

Description

CCI5. Thyristor Rp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

449

20469

ThyrTemp1Lev2Fl_CCI5

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI5. Thyristor Tn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 450 20470 ThyrTemp2Lev2Fl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature

206

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

fault of the other converters (n-1) - Clean air inlet filters

CCI5. Thyristor Sp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

451

20471

ThyrTemp3Lev2Fl_CCI5

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters 1'347 20472 ForceBU

207

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Thyristor Rn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

452

20473

ThyrTemp4Lev2Fl_CCI5

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI5. Thyristor Tp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 453 20474 ThyrTemp5Lev2Fl_CCI5

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

208

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

CCI5. Thyristor Sn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

454

20475

ThyrTemp6Lev2Fl_CCI5

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

209

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5. Air Temperature 1 ( Thyristor Cooler Input ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 455 20476 AirTemp1Lev2Flt_CCI5

Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI5. Air Temperature 2 ( Air outlet chimney ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: - Converter alarm 456 20477 AirTemp2Lev2Flt_CCI5 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level

210

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474

20478 20479 20480 20481 20482 20483 20484 20485 20486 20487 20488 20489 20490 20491 20492 20493 20494 20495

Event3_08_CCI5 Event3_09_CCI5 Event3_10_CCI5 Event3_11_CCI5 Event3_12_CCI5 Event3_13_CCI5 Event3_14_CCI5 Event3_15_CCI5 Event3_16_CCI5 Event3_17_CCI5 Event3_18_CCI5 Event3_19_CCI5 Event3_20_CCI5 Event3_21_CCI5 Event3_22_CCI5 Event3_23_CCI5 Event3_24_CCI5 Event3_25_CCI5

211

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
475 476 477 478 479 480

ID
20500 20501 20502 20503 20504 20505

Name
Event3_26_CCI5 Event3_27_CCI5 Event3_28_CCI5 Event3_29_CCI5 Event3_30_CCI5 Event3_31_CCI5

Events

Description

CCI6. Thyristor Rp Fault: The monitoring of Converter 6 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 481 20506 ThyrFlt_Rp_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

212

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Thyristor Tn Fault: The monitoring of Converter 6 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 482 20507 ThyrFlt_Tn_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

213

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Thyristor Sp Fault: The monitoring of Converter 6 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 483 20508 ThyrFlt_Sp_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

214

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Thyristor Rn Fault: The monitoring of Converter 6 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 484 20509 ThyrFlt_Rn_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

215

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Thyristor Tp Fault: The monitoring of Converter 6 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 485 20510 ThyrFlt_Tp_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

216

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Thyristor Sn Fault: The monitoring of Converter 6 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 486 20511 ThyrFlt_Sn_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI6. Fuse Rp Fault: Branch Fuse Rp blown

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 487 20512 FuseFlt_Rp_CCI6

Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters:

217

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

CCI6. Fuse Tn Fault: Branch Fuse Tn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 488 20513 FuseFlt_Tn_CCI6 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

218

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Fuse Sp Fault: Branch Fuse Sp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 489 20514 FuseFlt_Sp_CCI6 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI6. Fuse Rn Fault: Branch Fuse Rn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 490 20515 FuseFlt_Rn_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

219

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
TFFDnumOfPeriods

Description

Further steps: ----

CCI6. Fuse Tp Fault: Branch Fuse Tp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 491 20516 FuseFlt_Tp_CCI6 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

220

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Fuse Sn Fault: Branch Fuse Sn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 492 20517 FuseFlt_Sn_CCI6 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI6. Overcurrent in Phase R detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 493 20518 TOCD_R_CCI6 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

221

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Further steps:

Description

CCI6. Overcurrent in Phase S detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 494 20519 TOCD_S_CCI6 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---1'348 20520 NoCHAlarmActive

222

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Overcurrent in Phase T detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 495 20521 TOCD_T_CCI6 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---CCI6. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: N-1 496 20522 UfOpCeil_CCI6 - Converter alarm Twin - Converter alarm

Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon

Further steps: ----

223

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI6. Device Type Error

Description

Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 6

497

20523

DevTypeErr_CCI6

Default reaction: - Converter Trip

Related parameters: ----

Further steps: ---CCI6. Address Error

Possible reasons: - Wrong HEX Switch setting at CCI 6

Default reaction: 498 20524 AddressErr_CCI6 - Converter Trip

Related parameters: ----

Further steps: ----

224

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Link Fault detected by AC 800PEC

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

499

20525

LinkFault_CCI6

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to CCI CCI6. Redundant Power 1 fail

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 500 20526 RedPwrFail1_CCI6 - Converter Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply CCI6. Redundant Power 2 fail

Possible reasons: - Power supply fault at input 2 (X2:1-2) 501 20527 RedPwrFail2_CCI6 Default reaction: - Converter Redundancy Fault

Related parameters:

225

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

CCI6. Precision Power fail

Possible reasons: - Internal power fail on CCI - Both pover supply inputs are missing

Default reaction: 502 20528 PrciPwrFail_CCI6 - Converter Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board CCI6. CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

503

20529

CPUWatchdog_CCI6

Default reaction: - Converter Trip

Related parameters: ----

Further steps:

226

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Reboot device

Description

- Download installer archive - Replace board

CCI6. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

504

20530

UfFreeze_CCI6

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UfEnaADCFreezeMon

Further steps: - Replace board CCI6. Synchronous Voltage measurement failure

Possible reasons: - One Phase of the AC-connection lost

Default reaction: 505 20531 USynInPhase_CCI6 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaInPhaseMon

Further steps: - Check cabling

227

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 506 20532 USynOpCeil_CCI6 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon

Further steps: - Replace board CCI6. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

507

20533

USynFreeze_CCI6

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaADCFreezeMon

Further steps: - Replace board CCI6. Synchronous Voltage measurement failure

Possible reasons: - Two or all three connections lost 508 20534 USynAllLost_CCI6

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaAllLostMon

228

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling

CCI6. Link Fault detected by CCI

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1)

Default reaction: 509 20535 SelfTrip_CCI6 - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to AC 800PEC CCI6. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses

Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby)

Default reaction: - Converter Trip 510 20536 AdvFuseBlow_CCI6 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown

Further steps: - Check thyristors - Check fuses

229

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

511

20537

IConvOpCeil_CCI6

Default reaction: - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaADCFreezeMon

Further steps: - Replace board CCI6. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 512 20538 IConvFreeze_CCI6 - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon

Further steps: - Replace board

230

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI6. Cooling failure

Description

Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters

Default reaction: 513 20539 CoolingFailure_CCI6 - Converter TRIP

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord

Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI6. Fan 1 Supply 1 fault

Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 514 20540 Fan1Supply1Flt_CCI6 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

231

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace pressure sensor

Description

CCI6. Fan 1 Supply 2 fault

Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

Default reaction: 515 20541 Fan1Supply2Flt_CCI6 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

232

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI6. Fan 2 Supply 1 fault

Description

Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 516 20542 Fan2Supply1Flt_CCI6 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI6. Fan 2 Supply 2 fault

Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

517

20543

Fan2Supply2Flt_CCI6

Default reaction: - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps:

233

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace fan

Description

- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

CCI6. Fan Supply Miniature Circuit Breaker 1 fault

Possible reasons: - Fan 1 defective

Default reaction: - Converter Redundancy fault 518 20544 MCB1Fault_CCI6 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI6. Fan Supply Miniature Circuit Breaker 2 fault

Possible reasons: - Fan 2 defective 519 20545 MCB2Fault_CCI6 Default reaction: - Converter Redundancy fault

Related parameters:

234

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

CCI6. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 520 20546 ThyrTemp1Lev1Fl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

235

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 521 20547 ThyrTemp2Lev1Fl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI6. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 522 20548 ThyrTemp3Lev1Fl_CCI6 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

236

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI6. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 523 20549 ThyrTemp4Lev1Fl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

237

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 524 20550 ThyrTemp5Lev1Fl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI6. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 525 20551 ThyrTemp6Lev1Fl_CCI6 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

238

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI6. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 526 20552 AirTemp1Lev1Flt_CCI6 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

239

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: 527 20553 AirTemp2Lev1Flt_CCI6 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI6. Thyristor Rp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 528 20554 ThyrTemp1SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

240

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Re-check sensor circuit

Description

CCI6. Thyristor Tn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 529 20555 ThyrTemp2SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

241

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Thyristor Sp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 530 20556 ThyrTemp3SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI6. Thyristor Rn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 531 20557 ThyrTemp4SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

242

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Thyristor Tp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 532 20558 ThyrTemp5SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI6. Thyristor Sn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 533 20559 ThyrTemp6SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

243

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Air Temperature 1 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 534 20560 AirTemp1SensFlt_CCI6 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit CCI6. Air Temperature 2 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 535 20561 AirTemp2SensFlt_CCI6 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit

244

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI6. Snubber Switch fault

Description

Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch

Default reaction: N-1 536 20562 SnubberSwiFlt_CCI6 - Converter alarm TWIN - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord

Further steps: - Re-check sensor circuit CCI6. Snubber Fuse fault

Possible reasons: ----

Default reaction: 537 20563 SnubberFuseFlt_CCI6 ----

Related parameters: ----

Further steps: ----

245

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI6. Thyristor Fuse fault

Description

Possible reasons: - Digital input for fuse supervision activated

Default reaction: 538 20564 ThyristorFuseFl_CCI6 - Converter alarm

Related parameters: ----

Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI6. Converter cabinet Door fault

Possible reasons: - Digital input for open door activated

Default reaction: 539 20565 DoorFlt_CCI6 - Converter alarm

Related parameters: ----

Further steps: - Close converter cabinet door CCI6. Software Version fault

Possible reasons: - Wrong converter interface SW version 540 20566 VersionFlt_CCI6

Default reaction: - Converter Trip

Related parameters: ----

246

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Download required software version

CCI6. NegConvFault_CCI6

Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration

Default reaction: 541 20567 NegConvFault_CCI6 - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord

Further steps: - Re-check HW input CCI6. PulseBlock_CCI6 by hardware

Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive

542

20568

PulseBlockFault_CCI6

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Re-check HW input 543 20569 TestPosition_CCI6

247

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
544

ID
20570

Name
Event2_31_CCI6

Events

Description

CCI6. Thyristor Rp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

545

20571

ThyrTemp1Lev2Fl_CCI6

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI6. Thyristor Tn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 546 20572 ThyrTemp2Lev2Fl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature

248

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

fault of the other converters (n-1) - Clean air inlet filters

CCI6. Thyristor Sp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

547

20573

ThyrTemp3Lev2Fl_CCI6

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

249

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Thyristor Rn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

548

20574

ThyrTemp4Lev2Fl_CCI6

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI6. Thyristor Tp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 549 20575 ThyrTemp5Lev2Fl_CCI6

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

250

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

CCI6. Thyristor Sn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

550

20576

ThyrTemp6Lev2Fl_CCI6

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

251

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6. Air Temperature 1 ( Thyristor Cooler Input ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 551 20577 AirTemp1Lev2Flt_CCI6

Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI6. Air Temperature 2 ( Air outlet chimney ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: - Converter alarm 552 20578 AirTemp2Lev2Flt_CCI6 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level

252

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570

20579 20580 20581 20582 20583 20584 20585 20586 20587 20588 20589 20590 20591 20592 20593 20594 20595 20600

Event3_08_CCI6 Event3_09_CCI6 Event3_10_CCI6 Event3_11_CCI6 Event3_12_CCI6 Event3_13_CCI6 Event3_14_CCI6 Event3_15_CCI6 Event3_16_CCI6 Event3_17_CCI6 Event3_18_CCI6 Event3_19_CCI6 Event3_20_CCI6 Event3_21_CCI6 Event3_22_CCI6 Event3_23_CCI6 Event3_24_CCI6 Event3_25_CCI6

253

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
571 572 573 574 575 576

ID
20601 20602 20603 20604 20605 20606

Name
Event3_26_CCI6 Event3_27_CCI6 Event3_28_CCI6 Event3_29_CCI6 Event3_30_CCI6 Event3_31_CCI6

Events

Description

CCI7. Thyristor Rp Fault: The monitoring of Converter 7 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 577 20607 ThyrFlt_Rp_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

254

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Thyristor Tn Fault: The monitoring of Converter 7 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 578 20608 ThyrFlt_Tn_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

255

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Thyristor Sp Fault: The monitoring of Converter 7 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 579 20609 ThyrFlt_Sp_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

256

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Thyristor Rn Fault: The monitoring of Converter 7 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 580 20610 ThyrFlt_Rn_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

257

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Thyristor Tp Fault: The monitoring of Converter 7 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 581 20611 ThyrFlt_Tp_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

258

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Thyristor Sn Fault: The monitoring of Converter 7 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 582 20612 ThyrFlt_Sn_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI7. Fuse Rp Fault: Branch Fuse Rp blown

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 583 20613 FuseFlt_Rp_CCI7

Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters:

259

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

CCI7. Fuse Tn Fault: Branch Fuse Tn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 584 20614 FuseFlt_Tn_CCI7 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

260

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Fuse Sp Fault: Branch Fuse Sp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 585 20615 FuseFlt_Sp_CCI7 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI7. Fuse Rn Fault: Branch Fuse Rn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 586 20616 FuseFlt_Rn_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

261

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
TFFDnumOfPeriods

Description

Further steps: ----

CCI7. Fuse Tp Fault: Branch Fuse Tp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 587 20617 FuseFlt_Tp_CCI7 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

262

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Fuse Sn Fault: Branch Fuse Sn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 588 20618 FuseFlt_Sn_CCI7 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI7. Overcurrent in Phase R detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 589 20619 TOCD_R_CCI7 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

263

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Further steps:

Description

CCI7. Overcurrent in Phase S detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 590 20620 TOCD_S_CCI7 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ----

264

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Overcurrent in Phase T detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 591 20621 TOCD_T_CCI7 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---CCI7. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: N-1 592 20622 UfOpCeil_CCI7 - Converter alarm Twin - Converter alarm

Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon

Further steps: ----

265

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI7. Device Type Error

Description

Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 2

593

20623

DevTypeErr_CCI7

Default reaction: - Converter Trip

Related parameters: ----

Further steps: ---CCI7. Address Error

Possible reasons: - Wrong HEX Switch setting at CCI 2

Default reaction: 594 20624 AddressErr_CCI7 - Converter Trip

Related parameters: ----

Further steps: ----

266

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Link Fault detected by AC 800PEC

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

595

20625

LinkFault_CCI7

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to CCI CCI7. Redundant Power 1 fail

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 596 20626 RedPwrFail1_CCI7 - Converter Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply CCI7. Redundant Power 2 fail

Possible reasons: - Power supply fault at input 2 (X2:1-2) 597 20627 RedPwrFail2_CCI7 Default reaction: - Converter Redundancy Fault

Related parameters:

267

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

CCI7. Precision Power fail

Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing

Default reaction: 598 20628 PrciPwrFail_CCI7 - Converter Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board CCI7. CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

599

20629

CPUWatchdog_CCI7

Default reaction: - Converter Trip

Related parameters: ----

Further steps:

268

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Reboot device

Description

- Download installer archive - Replace board

CCI7. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

600

20630

UfFreeze_CCI7

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UfEnaADCFreezeMon

Further steps: - Replace board CCI7. Synchronous Voltage measurement failure

Possible reasons: - One Phase of the AC-connection lost

Default reaction: 601 20631 USynInPhase_CCI7 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaInPhaseMon

Further steps: - Check cabling

269

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 602 20632 USynOpCeil_CCI7 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon

Further steps: - Replace board CCI7. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

603

20633

USynFreeze_CCI7

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaADCFreezeMon

Further steps: - Replace board CCI7. Synchronous Voltage measurement failure

Possible reasons: - Two or all three connections lost 604 20634 USynAllLost_CCI7

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaAllLostMon

270

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling

CCI7. Link Fault detected by CCI

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1)

Default reaction: 605 20635 SelfTrip_CCI7 - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to AC 800PEC CCI7. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses

Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby)

Default reaction: - Converter Trip 606 20636 AdvFuseBlow_CCI7 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown

Further steps: - Check thyristors - Check fuses

271

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

607

20637

IConvOpCeil_CCI7

Default reaction: - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaADCFreezeMon

Further steps: - Replace board CCI7. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 608 20638 IConvFreeze_CCI7 - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon

Further steps: - Replace board

272

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI7. Cooling failure

Description

Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters

Default reaction: 609 20639 CoolingFailure_CCI7 - Converter TRIP

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord

Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI7. Fan 1 Supply 1 fault

Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 610 20640 Fan1Supply1Flt_CCI7 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

273

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace pressure sensor

Description

CCI7. Fan 1 Supply 2 fault

Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

Default reaction: 611 20641 Fan1Supply2Flt_CCI7 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

274

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI7. Fan 2 Supply 1 fault

Description

Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 612 20642 Fan2Supply1Flt_CCI7 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI7. Fan 2 Supply 2 fault

Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

613

20643

Fan2Supply2Flt_CCI7

Default reaction: - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps:

275

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace fan

Description

- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

CCI7. Fan Supply Miniature Circuit Breaker 1 fault

Possible reasons: - Fan 1 defective

Default reaction: - Converter Redundancy fault 614 20644 MCB1Fault_CCI7 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - replace fan (HW-schematic page 410) - re-check cabling CCI7. Fan Supply Miniature Circuit Breaker 2 fault

Possible reasons: - Fan 2 defective 615 20645 MCB2Fault_CCI7 Default reaction: - Converter Redundancy fault

Related parameters:

276

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

CCI7. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 616 20646 ThyrTemp1Lev1Fl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

277

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 617 20647 ThyrTemp2Lev1Fl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI7. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 618 20648 ThyrTemp3Lev1Fl_CCI7 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

278

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI7. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 619 20649 ThyrTemp4Lev1Fl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

279

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 620 20650 ThyrTemp5Lev1Fl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI7. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 621 20651 ThyrTemp6Lev1Fl_CCI7 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

280

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI7. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 622 20652 AirTemp1Lev1Flt_CCI7 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

281

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: 623 20653 AirTemp2Lev1Flt_CCI7 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI7. Thyristor Rp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 624 20654 ThyrTemp1SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

282

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Re-check sensor circuit

Description

CCI7. Thyristor Tn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 625 20655 ThyrTemp2SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

283

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Thyristor Sp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 626 20656 ThyrTemp3SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI7. Thyristor Rn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 627 20657 ThyrTemp4SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

284

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Thyristor Tp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 628 20658 ThyrTemp5SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI7. Thyristor Sn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 629 20659 ThyrTemp6SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

285

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Air Temperature 1 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 630 20660 AirTemp1SensFlt_CCI7 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit CCI7. Air Temperature 2 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 631 20661 AirTemp2SensFlt_CCI7 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit

286

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI7. Snubber Switch fault

Description

Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch

Default reaction: N-1 632 20662 SnubberSwiFlt_CCI7 - Converter alarm TWIN - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord

Further steps: - Re-check sensor circuit CCI7. Snubber Fuse fault

Possible reasons: ----

Default reaction: 633 20663 SnubberFuseFlt_CCI7 ----

Related parameters: ----

Further steps: ----

287

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI7. Thyristor Fuse fault

Description

Possible reasons: - Digital input for fuse supervision activated

Default reaction: 634 20664 ThyristorFuseFl_CCI7 - Converter alarm

Related parameters: ----

Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI7. Converter cabinet Door fault

Possible reasons: - Digital input for open door activated

Default reaction: 635 20665 DoorFlt_CCI7 - Converter alarm

Related parameters: ----

Further steps: - Close converter cabinet door CCI7. Software Version fault

Possible reasons: - Wrong converter interface SW version 636 20666 VersionFlt_CCI7

Default reaction: - Converter Trip

Related parameters: ----

288

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Download required software version

CCI7. NegConvFault_CCI7

Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration

Default reaction: 637 20667 NegConvFault_CCI7 - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord

Further steps: - Re-check HW input CCI7. PulseBlock_CCI7 by hardware

Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive

638

20668

PulseBlockFault_CCI7

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Re-check HW input 639 20669 TestPosition_CCI7

289

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
640

ID
20670

Name
Event2_31_CCI7

Events

Description

CCI7. Thyristor Rp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

641

20671

ThyrTemp1Lev2Fl_CCI7

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI7. Thyristor Tn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 642 20672 ThyrTemp2Lev2Fl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature

290

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

fault of the other converters (n-1) - Clean air inlet filters

CCI7. Thyristor Sp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

643

20673

ThyrTemp3Lev2Fl_CCI7

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

291

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Thyristor Rn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

644

20674

ThyrTemp4Lev2Fl_CCI7

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI7. Thyristor Tp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 645 20675 ThyrTemp5Lev2Fl_CCI7

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

292

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

CCI7. Thyristor Sn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

646

20676

ThyrTemp6Lev2Fl_CCI7

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

293

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7. Air Temperature 1 ( Thyristor Cooler Input ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 647 20677 AirTemp1Lev2Flt_CCI7

Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI7. Air Temperature 2 ( Air outlet chimney ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: - Converter alarm 648 20678 AirTemp2Lev2Flt_CCI7 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level

294

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666

20679 20680 20681 20682 20683 20684 20685 20686 20687 20688 20689 20690 20691 20692 20693 20694 20695 20700

Event3_08_CCI7 Event3_09_CCI7 Event3_10_CCI7 Event3_11_CCI7 Event3_12_CCI7 Event3_13_CCI7 Event3_14_CCI7 Event3_15_CCI7 Event3_16_CCI7 Event3_17_CCI7 Event3_18_CCI7 Event3_19_CCI7 Event3_20_CCI7 Event3_21_CCI7 Event3_22_CCI7 Event3_23_CCI7 Event3_24_CCI7 Event3_25_CCI7

295

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
667 668 669 670 671 672

ID
20701 20702 20703 20704 20705 20706

Name
Event3_26_CCI7 Event3_27_CCI7 Event3_28_CCI7 Event3_29_CCI7 Event3_30_CCI7 Event3_31_CCI7

Events

Description

CCI8. Thyristor Rp Fault: The monitoring of Converter 8 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 673 20707 ThyrFlt_Rp_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

296

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Thyristor Tn Fault: The monitoring of Converter 8 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 674 20708 ThyrFlt_Tn_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

297

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Thyristor Sp Fault: The monitoring of Converter 8 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 675 20709 ThyrFlt_Sp_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

298

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Thyristor Rn Fault: The monitoring of Converter 8 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 676 20710 ThyrFlt_Rn_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

299

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Tp Fault: The monitoring of Converter 2 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 677 20711 ThyrFlt_Tp_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

300

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2. Thyristor Sn Fault: The monitoring of Converter 2 has detected a non conducting thyristor

Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)

Default reaction: 678 20712 ThyrFlt_Sn_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI8. Fuse Rp Fault: Branch Fuse Rp blown

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 679 20713 FuseFlt_Rp_CCI8

Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters:

301

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

CCI8. Fuse Tn Fault: Branch Fuse Tn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 680 20714 FuseFlt_Tn_CCI8 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

302

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Fuse Sp Fault: Branch Fuse Sp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 681 20715 FuseFlt_Sp_CCI8 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI8. Fuse Rn Fault: Branch Fuse Rn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 682 20716 FuseFlt_Rn_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

303

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
TFFDnumOfPeriods

Description

Further steps: ----

CCI8. Fuse Tp Fault: Branch Fuse Tp faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 683 20717 FuseFlt_Tp_CCI8 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ----

304

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Fuse Sn Fault: Branch Fuse Sn faulty

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: N-1 684 20718 FuseFlt_Sn_CCI8 - Converter redundancy fault Twin - Converter Trip

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods

Further steps: ---CCI8. Overcurrent in Phase R detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 685 20719 TOCD_R_CCI8 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

305

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Further steps:

Description

CCI8. Overcurrent in Phase S detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 686 20720 TOCD_S_CCI8 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ----

306

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Overcurrent in Phase T detected

Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)

Default reaction: 687 20721 TOCD_T_CCI8 N-1 - Converter alarm Twin - Converter alarm

Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Further steps: ---CCI8. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: N-1 688 20722 UfOpCeil_CCI8 - Converter alarm Twin - Converter alarm

Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon

Further steps: ----

307

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI8. Device Type Error

Description

Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 8

689

20723

DevTypeErr_CCI8

Default reaction: - Converter Trip

Related parameters: ----

Further steps: ---CCI8. Address Error

Possible reasons: - Wrong HEX Switch setting at CCI 8

Default reaction: 690 20724 AddressErr_CCI8 - Converter Trip

Related parameters: ----

Further steps: ----

308

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Link Fault detected by AC 800PEC

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

691

20725

LinkFault_CCI8

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to CCI CCI8. Redundant Power 1 fail

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 692 20726 RedPwrFail1_CCI8 - Converter Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply CCI8. Redundant Power 2 fail

Possible reasons: - Power supply fault at input 2 (X2:1-2) 693 20727 RedPwrFail2_CCI8 Default reaction: - Converter Redundancy Fault

Related parameters:

309

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

CCI8. Precision Power fail

Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing

Default reaction: 694 20728 PrciPwrFail_CCI8 - Converter Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board CCI8. CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

695

20729

CPUWatchdog_CCI8

Default reaction: - Converter Trip

Related parameters: ----

Further steps:

310

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Reboot device

Description

- Download installer archive - Replace board

CCI8. Field Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

696

20730

UfFreeze_CCI8

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UfEnaADCFreezeMon

Further steps: - Replace board CCI8. Synchronous Voltage measurement failure

Possible reasons: - One Phase of the AC-connection lost

Default reaction: 697 20731 USynInPhase_CCI8 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaInPhaseMon

Further steps: - Check cabling

311

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 698 20732 USynOpCeil_CCI8 - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon

Further steps: - Replace board CCI8. Synchronous Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

699

20733

USynFreeze_CCI8

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaADCFreezeMon

Further steps: - Replace board CCI8. Synchronous Voltage measurement failure

Possible reasons: - Two or all three connections lost 700 20734 USynAllLost_CCI8

Default reaction: - Converter Alarm

Related parameters: Prot_Protection \ UsynEnaAllLostMon

312

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling

CCI8. Link Fault detected by CCI

Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1)

Default reaction: 701 20735 SelfTrip_CCI8 - Converter Trip

Related parameters: ----

Further steps: - Check optical link cabling to AC 800PEC CCI8. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses

Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby)

Default reaction: - Converter Trip 702 20736 AdvFuseBlow_CCI8 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown

Further steps: - Check thyristors - Check fuses

313

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

703

20737

IConvOpCeil_CCI8

Default reaction: - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaADCFreezeMon

Further steps: - Replace board CCI8. Converter Current measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 704 20738 IConvFreeze_CCI8 - Converter TRIP

Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon

Further steps: - Replace board

314

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI8. Cooling failure

Description

Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters

Default reaction: 705 20739 CoolingFailure_CCI8 - Converter TRIP

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord

Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI8. Fan 1 Supply 1 fault

Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 706 20740 Fan1Supply1Flt_CCI8 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

315

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace pressure sensor

Description

CCI8. Fan 1 Supply 2 fault

Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

Default reaction: 707 20741 Fan1Supply2Flt_CCI8 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

316

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI8. Fan 2 Supply 1 fault

Description

Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters

Default reaction: 708 20742 Fan2Supply1Flt_CCI8 - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI8. Fan 2 Supply 2 fault

Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters

709

20743

Fan2Supply2Flt_CCI8

Default reaction: - Converter Redundancy fault

Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps:

317

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace fan

Description

- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

CCI8. Fan Supply Miniature Circuit Breaker 1 fault

Possible reasons: - Fan 1 defective

Default reaction: - Converter Redundancy fault 710 20744 MCB1Fault_CCI8 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI8. Fan Supply Miniature Circuit Breaker 2 fault

Possible reasons: - Fan 2 defective 711 20745 MCB2Fault_CCI8 Default reaction: - Converter Redundancy fault

Related parameters:

318

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord

Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

CCI8. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 712 20746 ThyrTemp1Lev1Fl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

319

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 713 20747 ThyrTemp2Lev1Fl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI8. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 714 20748 ThyrTemp3Lev1Fl_CCI8 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

320

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI8. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 715 20749 ThyrTemp4Lev1Fl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

321

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 716 20750 ThyrTemp5Lev1Fl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI8. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: 717 20751 ThyrTemp6Lev1Fl_CCI8 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

322

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

CCI8. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 718 20752 AirTemp1Lev1Flt_CCI8 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

323

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: 719 20753 AirTemp2Lev1Flt_CCI8 - Converter alarm

Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI8. Thyristor Rp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 720 20754 ThyrTemp1SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps:

324

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Re-check sensor circuit

Description

CCI8. Thyristor Tn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 721 20755 ThyrTemp2SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

325

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Thyristor Sp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 722 20756 ThyrTemp3SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - re-check sensor circuit CCI8. Thyristor Rn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 723 20757 ThyrTemp4SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

326

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Thyristor Tp Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 724 20758 ThyrTemp5SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit CCI8. Thyristor Sn Case Temperature Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 725 20759 ThyrTemp6SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Re-check sensor circuit

327

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Air Temperature 1 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 726 20760 AirTemp1SensFlt_CCI8 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit CCI8. Air Temperature 2 Sensor fault

Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C

Default reaction: - Converter alarm 727 20761 AirTemp2SensFlt_CCI8 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Re-check sensor circuit

328

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI8. Snubber Switch fault

Description

Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch

Default reaction: N-1 728 20762 SnubberSwiFlt_CCI8 - Converter alarm TWIN - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord

Further steps: - Re-check sensor circuit CCI8. Snubber Fuse fault

Possible reasons: ----

Default reaction: 729 20763 SnubberFuseFlt_CCI8 ----

Related parameters: ----

Further steps: ----

329

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI8. Thyristor Fuse fault

Description

Possible reasons: - Digital input for fuse supervision activated

Default reaction: 730 20764 ThyristorFuseFl_CCI8 - Converter alarm

Related parameters: ----

Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI8. Converter cabinet Door fault

Possible reasons: - Digital input for open door activated

Default reaction: 731 20765 DoorFlt_CCI8 - Converter alarm

Related parameters: ----

Further steps: - Close converter cabinet door CCI8. Software Version fault

Possible reasons: - Wrong converter interface SW version 732 20766 VersionFlt_CCI8

Default reaction: - Converter Trip

Related parameters: ----

330

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Download required software version

CCI8. NegConvFault_CCI8

Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration

Default reaction: 733 20767 NegConvFault_CCI8 - Converter Trip

Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord

Further steps: - Re-check HW input CCI8. PulseBlock_CCI8 by hardware

Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive

734

20768

PulseBlockFault_CCI8

Default reaction: - Converter Trip

Related parameters: ----

Further steps: - Re-check HW input 735 20769 TestPosition_CCI8

331

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
736

ID
20770

Name
Event2_31_CCI8

Events

Description

CCI8. Thyristor Rp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

737

20771

ThyrTemp1Lev2Fl_CCI8

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI8. Thyristor Tn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 738 20772 ThyrTemp2Lev2Fl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature

332

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

fault of the other converters (n-1) - Clean air inlet filters

CCI8. Thyristor Sp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

739

20773

ThyrTemp3Lev2Fl_CCI8

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

333

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Thyristor Rn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

740

20774

ThyrTemp4Lev2Fl_CCI8

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI8. Thyristor Tp Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip 741 20775 ThyrTemp5Lev2Fl_CCI8

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

334

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

CCI8. Thyristor Sn Case Temperature above trip level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter Trip

742

20776

ThyrTemp6Lev2Fl_CCI8

Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas

Conv_ConverterModule1 \ EnaThyrTempMeas

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

335

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8. Air Temperature 1 ( Thyristor Cooler Input ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature

Default reaction: - Converter alarm 743 20777 AirTemp1Lev2Flt_CCI8

Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI8. Air Temperature 2 ( Air outlet chimney ) above fault level

Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working

Default reaction: - Converter alarm 744 20778 AirTemp2Lev2Flt_CCI8 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas

Conv_ConverterModule1 \ EnaCabinetTempMeas

Further steps: - Reduce excitation current to prevent overtemperature fault level

336

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Clean air inlet filters

Description

745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762

20779 20780 20781 20782 20783 20784 20785 20786 20787 20788 20789 20790 20791 20792 20793 20794 20795 21000

Event3_08_CCI8 Event3_09_CCI8 Event3_10_CCI8 Event3_11_CCI8 Event3_12_CCI8 Event3_13_CCI8 Event3_14_CCI8 Event3_15_CCI8 Event3_16_CCI8 Event3_17_CCI8 Event3_18_CCI8 Event3_19_CCI8 Event3_20_CCI8 Event3_21_CCI8 Event3_22_CCI8 Event3_23_CCI8 Event3_24_CCI8 Event3_25_CCI8

337

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
763 764 765 766 767 768

ID
21001 21002 21003 21004 21005 21006

Name
Event3_26_CCI8 Event3_27_CCI8 Event3_28_CCI8 Event3_29_CCI8 Event3_30_CCI8 Event3_31_CCI8

Events

Description

Field Current instantaneous overcurrent fault

Possible reasons: - Short circuit either on converter AC or DC-side

Default reaction: - Trip 769 21007 OvrCurrInstFlt Related parameters: ProtOvercurrentMon \ Ifskal Ifinst InstDelay

Further steps: ---Field Current inverse time Overcurrent fault

Possible reasons: - Overload either on AC or DC-side

Related parameters: ProtOvercurrentMon / Ifskal 770 21008 OvrCurrInvFlt Ifstart SelCurve k FixInvDelay ThermalDownTime

Further steps:

338

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

P/Q Protection fault

Possible reasons: - Loss of Excitation - FCB Tripped from external

Default reaction: - Trip

771

21009

PQProtFlt

Related parameters: Prot_PQMon \ Characteristic_QP10 Characteristic_QP08 Characteristic_QP06 Characteristic_QP04 Characteristic_QP02 Characteristic_QP00 DelayTime

Further steps: ----

339

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
V/Hz Protection fault

Description

Possible reasons: - The machine voltage was higher than the V/Hz protection characteristic

Default reaction: - Trip

772

21010

VHzProtFlt

Related parameters: Prot_VHzMon \ Gradient Vfn ThermalDownTime DelayTime DelayFuncSelect DelayFactor

Further steps: ---External short-circuit Trip: Short-circuit on converter DC side

Possible reasons: - Short circuit on DC side which was not possible to clear due to a 200ms pulse blocking period

Default reaction: - Trip

773

21011

DCSCTrip

Related parameters: Prot_ConvFaultDetect \ ExtSCIfFaultLevel ExtSCUfFaultLevel ExtSCIfClearingFaultLevel ExtSCUfClearingFaultLevel ExtSCReleaseFaultClearing TFCDthreshold

Prot_Protection \ EnableIConvMon

340

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
EnableConvFaultDetection

Description

Further steps: ----

S800 Watchdog

Possible reasons: - Connection to optional I/O of S800 module (OM1 Link 5)

Default reaction: 774 21012 S800Watchdog - Alarm

Related parameters: Prot_protection \ EnableS800Mon

Further steps: - Check optical link Other Channel Hardware fault

Possible reasons: - Powerfail or FPGA freeze on other Channel detected 775 21013 OtherCHHWFlt Default reaction: - Immediate changeover to this channel

Related parameters:

341

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: - Check power supply - Replace hardware

Backup Channel Hardware fault

Possible reasons: - Powerfail or FPGA freeze on other Channel detected

Default reaction: 776 21014 BUHWFlt - Changeover to back-up channel blocked

Related parameters: ----

Further steps: - Check power supply - Replace hardware Other Channel Link fault detected by AC 800PEC

Possible reasons: - Optical link cabling to other AC 800PEC interrupted (OM1 Link 1&2) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) 777 21015 OtherCHLinkFlt

Default reaction: - Alarm

Related parameters: ----

Further steps:

342

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Check optical links cabling to other AC 800PEC

CCM Backup Channel Link fault detected by AC 800PEC

Possible reasons: - Optical link cabling to CCM Backup Channel interrupted (OM1 Link 3) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

778

21016

BUCHLinkFlt

Default reaction: - Channel to back-up link loss

Related parameters: ----

Further steps: - Check optical link cabling to CCM

343

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCM Link fault detected by AC 800PEC

Possible reasons: - Optical link cabling to CCM interrupted (OM1 Link 4) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

779

21017

CCMLinkFlt

Default reaction: - Channel fault

Related parameters: ----

Further steps: - Check optical link cabling to CCM Other Channel Software version fault

Possible reasons: - Wrong Channel SW version in other regulator channel

Default reaction: 780 21018 OtherCHVerFlt - Alarm

Related parameters: ----

Further steps: - Download required software version

344

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Backup Channel Software version fault

Possible reasons: - Wrong SW version in back-up channel

Default reaction: 781 21019 BUCHVersionFlt - Alarm

Related parameters: ----

Further steps: - Download required software version CCM Software version fault

Possible reasons: - Wrong SW version in CCM measuring board

Default reaction: 782 21020 CCMVersionFlt - Alarm

Related parameters: ----

Further steps: - Download required software version Other Channel Redundant Link 1 Address Error Link fault detected by AC 800PEC

Possible reasons: - Optical link cabling to other AC 800PEC connected to wrong optical port (Link 1 to Link 1 ) - CCM Hex switch setting not correct

783

21021

OtherCHAddrErr1

Default reaction: - Alarm

345

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Related parameters:

Description

Further steps: - Check optical link cabling to other channel

Other Channel Redundant Link 2 Address Error Link fault detected by AC 800PEC

Possible reasons: - Optical link cabling to other AC 800PEC connected to wrong optical port (OM1 Link 2 to OM1 Link 2 ) - CCM Hex switch setting not correct

784

21022

OtherCHAddrErr2

Default reaction: - Alarm

Related parameters: ----

Further steps: - Check optical link cabling to other channel Backup Channel Address Error

Possible reasons: - Wrong HEX Switch setting at back-up CCM

785

21023

BUCHAddressErr

Default reaction: - Channel fault

Related parameters: ----

346

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Further steps:

Description

CCM Address Error

Possible reasons: - Wrong HEX Switch setting at CCM

Default reaction: 786 21024 CCMAddressErr - Channel fault

Related parameters: ----

Further steps: ---Other Channel Device Type Error on Redundant Link 1 Device Type Error detected by AC 800PEC

Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 1) - Wrong installer archive loaded to other AC 800PEC

787

21025

OtherCHDevType1

Default reaction: - Alarm

Related parameters: ----

Further steps: ----

347

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Other Channel Device Type Error on Redundant Link 2 Device Type Error detected by AC 800PEC

Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 2) - Wrong installer archive loaded to other AC 800PEC

788

21026

OtherCHDevType2

Default reaction: - Alarm

Related parameters: ----

Further steps: ---Backup Device Type Error

Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 3) - Wrong installer archive loaded to CCM BU

Default reaction: 789 21027 BUDevTypeErr - Channel to back-up link loss - Alarm

Related parameters: ----

Further steps: ----

348

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCM Device Type Error

Description

Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 4) - Wrong installer archive loaded to CCM 1

790

21028

CCMDevTypeErr

Default reaction: - Channel fault

Related parameters: ----

Further steps: ---Power fail

Possible reasons: - Internal power fail on AC 800PEC - Both power supply inputs are missing

Default reaction: 791 21029 PowerFail - channel fault, if possible channel transfer

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board

349

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Backup CCM Redundant Power 1 fail

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 792 21030 BURedPwrFail1 - Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply CCM Redundant Power 1 fail

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 793 21031 CCMRedPwrFail1 - Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply Backup CCM Redundant Power 2 fail

Possible reasons: - Power supply fault at input 2 (X2:3-4)

794

21032

BURedPwrFail2

Default reaction: - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

350

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Further steps:

Description

- Check cabling and power supply

CCM Redundant Power 2 fail

Possible reasons: - Power supply fault at input 2 (X2:3-4)

Default reaction: 795 21033 CCMRedPwrFail2 - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply BU Precision Power fail

Possible reasons: - Internal power fail on CCM - BU - Both power supply inputs are missing

Default reaction: 796 21034 BUPrciPwrFail - BU channel HW-Fault

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board

351

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCM Precision Power fail

Description

Possible reasons: - Internal power fail on CCM - Both power supply inputs are missing

Default reaction: 797 21035 CCMPrciFail - Channel Fault

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 798 21036 CPUWatchdog - Channel Fault

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board

352

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Backup Channel CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 799 21037 BUCPUWatchdog - Back-up channel HW-fault

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board CCM CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 800 21038 CCMCPUWatchdog - Channel fault

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board

353

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI1 Trip: Pulses Blocked on CCI1

Possible reasons: - Optical link cabling to CCI1 interrupted (OM2 Link 1) - CCI1 CPU failure - Internal power fail on CCI1 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI1 - Wrong HEX Switch setting at CCI1 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 801 21039 CCI1Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match converter configuration

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

354

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI2 Trip: Pulses Blocked on CCI2

Possible reasons: - Optical link cabling to CCI2 interrupted (OM2 Link 1) - CCI2 CPU failure - Internal power fail on CCI2 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI2 - Wrong HEX Switch setting at CCI2 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 802 21040 CCI2Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 2 signal of Converter I/O does not match to converter configuration

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

355

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI3 Trip: Pulses Blocked on CCI3

Possible reasons: - Optical link cabling to CCI3 interrupted (OM2 Link 1) - CCI3 CPU failure - Internal power fail on CCI3 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI3 - Wrong HEX Switch setting at CCI3 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 803 21041 CCI3Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

356

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI4 Trip: Pulses Blocked on CCI4

Possible reasons: - Optical link cabling to CCI4 interrupted (OM2 Link 1) - CCI4 CPU failure - Internal power fail on CCI4 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI4 - Wrong HEX Switch setting at CCI4 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 804 21042 CCI4Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

357

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI5 Trip: Pulses Blocked on CCI5

Possible reasons: - Optical link cabling to CCI5 interrupted (OM2 Link 1) - CCI5 CPU failure - Internal power fail on CCI5 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI5 - Wrong HEX Switch setting at CCI5 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 805 21043 CCI5Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

358

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI6 Trip: Pulses Blocked on CCI6

Possible reasons: - Optical link cabling to CCI6 interrupted (OM2 Link 1) - CCI6 CPU failure - Internal power fail on CCI6 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI6 - Wrong HEX Switch setting at CCI6 - Insufficient converter cooling - Overtemerature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 806 21044 CCI6Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

359

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI7 Trip: Pulses Blocked on CCI7

Possible reasons: - Optical link cabling to CCI7 interrupted (OM2 Link 1) - CCI7 CPU failure - Internal power fail on CCI7 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI7 - Wrong HEX Switch setting at CCI7 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 807 21045 CCI7Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

360

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CCI8 Trip: Pulses Blocked on CCI8

Possible reasons: - Optical link cabling to CCI8 interrupted (OM2 Link 1) - CCI8 CPU failure - Internal power fail on CCI8 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI8 - Wrong HEX Switch setting at CCI8 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 808 21046 CCI8Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

361

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI1 Redundancy fault

Description

Possible reasons: - Power supply fault at CCI1 input 1 (X1:1-2) - Power supply fault at CCI1 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 809 21047 CCI1RedFault Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps - See individual events CCI2 Redundancy fault

Possible reasons: - Power supply fault at CCI2 input 1 (X1:1-2) - Power supply fault at CCI2 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 810 21048 CCI2RedFault Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps - See individual events

362

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI3 Redundancy fault

Description

Possible reasons: - Power supply fault at CCI3 input 1 (X1:1-2) - Power supply fault at CCI3 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 811 21049 CCI3RedFault Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps - See individual events CCI4 Redundancy fault

Possible reasons: - Power supply fault at CCI4 input 1 (X1:1-2) - Power supply fault at CCI4 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 812 21050 CCI4RedFault Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps - See individual events

363

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI5 Redundancy fault

Description

Possible reasons: - Power supply fault at CCI5 input 1 (X1:1-2) - Power supply fault at CCI5 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 813 21051 CCI5RedFault Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps - See individual events CCI6 Redundancy fault

Possible reasons: - Power supply fault at CCI6 input 1 (X1:1-2) - Power supply fault at CCI6 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 814 21052 CCI6RedFault Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps - See individual events

364

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI7 Redundancy fault

Description

Possible reasons: - Power supply fault at CCI7 input 1 (X1:1-2) - Power supply fault at CCI7 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 815 21053 CCI7RedFault Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps - See individual events CCI8 Redundancy fault

Possible reasons: - Power supply fault at CCI8 input 1 (X1:1-2) - Power supply fault at CCI8 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 816 21054 CCI8RedFault Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps - See individual events

365

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI1 Alarm

Description

Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) 817 21055 CCI1Alarm - Converter cabinet door open - Wrong SW version

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events CCI2 Alarm

Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air 818 21056 CCI2Alarm - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version

Default reaction: - Redundancy Fault

366

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Related parameters:

Description

- Verify the listing together with the individual events

Further steps: - See individual events

CCI3 Alarm

Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) 819 21057 CCI3Alarm - Converter cabinet door open - Wrong SW version

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

367

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI4 Alarm

Description

Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) 820 21058 CCI4Alarm - Converter cabinet door open - Wrong SW version

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events CCI5 Alarm

Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) 821 21059 CCI5Alarm - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version

Default reaction: - Redundancy Fault

368

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Related parameters:

Description

Verify the listing together with the individual events

Further steps: - See individual events

CCI6 Alarm

Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) 822 21060 CCI6Alatm - Converter cabinet door open - Wrong SW version

Default reaction: - Redundancy Fault

Related parameters: Verify the listing together with the individual events

Further steps: - See individual events

369

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CCI7 Alarm

Description

Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) 823 21061 CCI7Alarm - Converter cabinet door open - Wrong SW version

Default reaction: - Redundancy Fault

Related parameters: Verify the listing together with the individual events

Further steps: - See individual events CCI8 Alarm

Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air 824 21062 CCI8Alarm - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version

Default reaction: - Redundancy Fault

370

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Related parameters:

Description

Verify the listing together with the individual events

Further steps: - See individual events

Generator Voltage measurement failure

Possible reasons: - One Phase of the AC-connection lost

Default reaction: 825 21063 PTMonInPhaseFlt - Auto fault

Related parameters: Prot_Protection \ PTEnaInPhaseMon

Further steps: - Check cabling Generator Voltage measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level 826 21064 PTMonOpampCeil

Default reaction: - Auto fault

Related parameters: Prot_Protection \ PTEnaOpAmpCeilMon

371

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Replace board

Generator Voltage measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure

827

21065

PTMonADCFreeze

Default reaction: - Auto fault

Related parameters: Prot_Protection \ PTEnaADCFreezeMon

Further steps: - Replace board Generator Voltage measurement failure

Possible reasons: - Two or all three connections lost

Default reaction: 828 21066 PTMonAllLost - Auto fault

Related parameters: Prot_Protection \ PTEnaAllLostMon

Further steps: - Check cabling

372

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Generator Current measurement failure

Possible reasons: - One or two connections lost

Default reaction: 829 21067 CTMonSumFault - Auto fault

Related parameters: Prot_Protection \ CTEnaSumMon

Further steps: - Check cabling Generator Current measurement failure

Possible reasons: - Operation amplifier blocked at ceiling level

Default reaction: 830 21068 CTMonOpampCeil - Auto fault

Related parameters: Prot_Protection \ CTEnaOpAmpCeilMon

Further steps: - Replace board Generator Current measurement failure

Possible reasons: - Operation amplifier blocked (frozen) - ADC failure 831 21069 CTMonADCFreeze Default reaction: - Auto fault

Related parameters: Prot_Protection \ CTEnaADCFreezeMon

373

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Replace board

Generator Current measurement failure

Possible reasons: - One connection lost (if only two CT-measurement circuits are used)

Default reaction: 832 21070 CTMonParaphase - Auto fault

Related parameters: Prot_Protection \ EnableMaschineMeasCTMon PTEnaParaPhaseMon

Further steps: - Check cabling CIO1 Trip

Possible reasons: - Optical link cabling to CIO1 interrupted (Link 1) - CIO1 CPU failure - Internal power fail on CIO1 833 21071 CIO1Trip - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO1 - Wrong HEX Switch setting at CIO1

Default reaction: - Redundancy Fault

Related parameters:

374

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Verify the listing together with the individual events

Further steps: - See individual events

CIO2 Trip

Possible reasons: - Optical link cabling to CIO2 interrupted (Link 3) - CIO2 CPU failure - Internal power fail on CIO2 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO2 834 21072 CIO2Trip - Wrong HEX Switch setting at CIO2

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

375

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO3 Trip

Description

Possible reasons: - Optical link cabling to CIO3 interrupted (Link 1) - CIO3 CPU failure - Internal power fail on CIO3 - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO3 835 21073 CIO3Trip - Wrong HEX Switch setting at CIO3

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events CIO4 Trip

Possible reasons: - Optical link cabling to CIO4 interrupted (Link 3) - CIO4 CPU failure - Internal power fail on CIO4 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO4 836 21074 CIO4Trip - Wrong HEX Switch setting at CIO4

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

376

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO5 Trip

Description

Possible reasons: - Optical link cabling to CIO5 interrupted (Link 1) - CIO5 CPU failure - Internal power fail on CIO5 - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO5 837 21075 CIO5Trip - Wrong HEX Switch setting at CIO5

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events CIO6 Trip

Possible reasons: - Optical link cabling to CIO6 interrupted (Link 3) - CIO6 CPU failure - Internal power fail on CIO6 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO6 838 21076 CIO6Trip - Wrong HEX Switch setting at CIO6

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

377

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO7 Trip

Description

Possible reasons: - Optical link cabling to CIO7 interrupted (Link 1) - CIO7 CPU failure - Internal power fail on CIO7 - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO7 839 21077 CIO7Trip - Wrong HEX Switch setting at CIO7

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events CIO8 Trip

Possible reasons: - Optical link cabling to CIO8 interrupted (Link 3) - CIO8 CPU failure - Internal power fail on CIO8 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO8 840 21078 CIO8Trip - Wrong HEX Switch setting at CIO8

Default reaction: - Redundancy Fault

Related parameters: - Verify the listing together with the individual events

Further steps: - See individual events

378

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO1 Redundancy fault

Description

Possible reasons: - Power supply fault at CIO1 input 1 (X1:1-2) - Power supply fault at CIO1 input 2 (X2:3-4)

841

21079

CIO1RedFault

Default reaction: - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO2 Redundancy fault

Possible reasons: - Power supply fault at CIO2 input 1 (X1:1-2) - Power supply fault at CIO2 input 2 (X2:3-4)

842

21080

CIO2RedFault

Default reaction: - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO3 Redundancy fault

Possible reasons: - Power supply fault at CIO3 input 1 (X1:1-2) 843 21081 CIO3RedFault - Power supply fault at CIO3 input 2 (X2:3-4)

Default reaction: - Redundancy Fault

379

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Related parameters:

Description

Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

CIO4 Redundancy fault

Possible reasons: - Power supply fault at CIO4 input 1 (X1:1-2) - Power supply fault at CIO4 input 2 (X2:3-4)

844

21082

CIO4RedFault

Default reaction: - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO5 Redundancy fault

Possible reasons: - Power supply fault at CIO5 input 1 (X1:1-2) - Power supply fault at CIO5 input 2 (X2:3-4)

845

21083

CIO5RedFault

Default reaction: - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

380

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO6 Redundancy fault

Description

Possible reasons: - Power supply fault at CIO6 input 1 (X1:1-2) - Power supply fault at CIO6 input 2 (X2:3-4)

846

21084

CIO6RedFault

Default reaction: - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO7 Redundancy fault

Possible reasons: - Power supply fault at CIO7 input 1 (X1:1-2) - Power supply fault at CIO7 input 2 (X2:3-4)

847

21085

CIO7RedFault

Default reaction: - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO8 Redundancy fault

Possible reasons: - Power supply fault at CIO8 input 1 (X1:1-2) 848 21086 CIO8RedFault - Power supply fault at CIO8 input 2 (X2:3-4)

Default reaction: - Redundancy Fault

381

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Related parameters:

Description

Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

CIO1 Alarm

Possible reasons: - Wrong SW version on CIO1 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)

Default reaction: - Alarm

Related parameters: Meas_CIO1 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 849 21087 CIO1Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq

Further steps: ----

382

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO2 Alarm

Description

Possible reasons: - Wrong SW version on CIO2 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)

Default reaction: - Alarm

Related parameters: Meas_CIO2 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 850 21088 CIO2Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq

Further steps: ----

383

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO3 Alarm

Description

Possible reasons: - Wrong SW version on CIO3 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)

Default reaction: - Alarm

Related parameters: Meas_CIO3 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 851 21089 CIO3Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq

Further steps: ----

384

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO4 Alarm

Description

Possible reasons: - Wrong SW version on CIO4 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)

Default reaction: - Alarm

Related parameters: Meas_CIO4 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 852 21090 CIO4Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq

Further steps: ----

385

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO5 Alarm

Description

Possible reasons: - Wrong SW version on CIO5 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)

Default reaction: - Alarm

Related parameters: Meas_CIO5 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 853 21091 CIO5Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq

Further steps: ----

386

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO6 Alarm

Description

Possible reasons: - Wrong SW version on CIO6 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)

Default reaction: - Alarm

Related parameters: Meas_CIO6 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 854 21092 CIO6Alatm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq

Further steps: ----

387

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO7 Alarm

Description

Possible reasons: - Wrong SW version on CIO7 - Temperature sensor fault at CIO temerature input 1,2 or 3 (X800)

Default reaction: - Alarm

Related parameters: Meas_CIO7 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 855 21093 CIO7Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq

Further steps: ----

388

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO8 Alarm

Description

Possible reasons: - Wrong SW version on CIO8 - Temperature sensor fault at CIO temerature input 1,2 or 3 (X800)

Default reaction: - Alarm

Related parameters: Meas_CIO8 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 856 21094 CIO8Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq

Further steps: ---Small IO deviation between Channel 1 and Channel 2

Possible reasons: - Defective I/O section on CCM Board - Wiring faults 857 21095 SmallIODev_CH Default reaction: - Alarm

Related parameters: ----

389

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check wiring - Replace device

Small IO deviation between this Channel and Backup Channel

Possible reasons: - Defective I/O section on CCM Board - Wiring faults

Default reaction: 858 21096 SmallIODev_BU - Alarm

Related parameters: ----

Further steps: - Check wiring - Replace device Other Channel Channel fault

Possible reasons: - Other channel has a channel fault event

Default reaction: 859 21097 OtherCHChannlFl - Alarm

Related parameters: ----

Further steps:

390

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Check other channel

Description

Back-up Channel Channel fault

Possible reasons: - Back-up channel has a channel fault event

Default reaction: 860 21098 BUChannelFlt - Alarm

Related parameters: ----

Further steps: - Check Back-up channel Automatic channel transfer occurred. (Channel transfer not forced by the user)

Possible reasons: - CCM link fault - CCM Address error - CCM device type error - AC 800PEC Power fail 861 21099 CHXferFlt - CCM Power fail - CCM CPU watchdog - AC 800PEC CPU watchdog - CCM link fault - CIO config word fault - Manual fault in manual mode - Auto and manual mode fault

391

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Default reaction:

Description

Related parameters: ----

Further steps: - According to individual event documentation

862 863 864

21100 21101 21102

Event3_29 Event3_30 Event3_31 Earth Fault Relay Stage 1 fault

Possible reasons: - Resistance to ground too low

Default reaction: - Alarm

865

21103

EFRStage1Flt

Related parameters: Prot_EarthFaultMon \ Level1ResponseValue SelectIRDH275 SelectCIO

Prot_Protection \ EnaEarthFaultMon

Further steps: ----

392

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Earth Fault Relay Stage 2 fault

Possible reasons: - Resistance to ground too low

Default reaction: - Trip

866

21104

EFRStage2Flt

Related parameters: Prot_EarthFaultMon \ Level2ResponseValue SelectIRDH275 SelectCIO

Prot_Protection \ EnaEarthFaultMon

Further steps: ---Earth Fault Relay Communication fault

Possible reasons: - Serial link to device IRDH275 is disturbed - Link to selected CIO failed

Default reaction: - Alarm 867 21105 EFRCommFlt Related parameters: Prot_EarthFaultMon \ SelectIRDH275 SelectCIO

Prot_Protection \ EnaEarthFaultMon

Further steps: ----

393

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Field-flashing timeout

Description

Possible reasons: - Field Flashing breaker was closed for a longer time than expected

Default reaction: 868 21106 FFTimeout - Emergency stop

Related parameters: SM-StateMashine \ FieldFlashTimeout

Further steps: ---Excitation-on timeout

Possible reasons: - The overall excitation starting time was longer than the supervision time - Converter electronics was not able to fire thyristors

Default reaction: 869 21107 ExcOnTimeout - Emergency stop

Related parameters: SM_StateMashine \ ExcOnTimeout FireAllTimeout FieldFlashTimeout

Further steps: ----

394

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Synchronous voltage over-voltage fault level reached

Possible reasons: ----

Default reaction: - Trip 870 21108 OVFlt

Related parameters: Prot_Pretecion \ Enable OverVoltageMon

Prot_OverVoltageMon \ OVDetectionLevel FaultOnDelayTime

Further steps: ---Parameter save fault

Possible reasons: - Flash defective

Default reaction: 871 21109 ParSaveFlt - Alarm

Related parameters: ----

Further steps: - Replace AC 800PEC

395

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

One or more auxiliaries are not ready

Possible reasons: - Aux not ready input (CIO1 DI09 activated) - Aux ready input (CIO3 DI06 not activated)

Default reaction: 872 21110 AuxNotReadyFlt - Alarm - Start-up inhibit

Related parameters: ----

Further steps: - Check inputs CIO configuration word is not valid

Possible reasons: - Wrong CIO Configuration

Default reaction: 873 21111 ConfigWordFlt - Channel fault - Start-up inhibit

Related parameters: MeasCIOConfig \ CIOConfigWord

Further steps: - Check configuration

396

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Field Bus External Trip

Description

Possible reasons: - Trip via fieldbus. Fieldbus control word Bit 2 (Bits 015) - Bit 2 is logic zero

874

21112

FieldBusExtTrip

Default reaction: ----

Related parameters: ----

Further steps: ---Converter Redundancy Stage fault level 1 More thyristors in the same branch as defined with stage level parameter are not conducting

Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's - Defective pulse amplifiers - Blocked Thyristors 875 21113 ConvRed1Flt - Blocked CCI

Default reaction: - Alarm

Related parameters: Conv_ConverterSystem1 \ FaultStage1Level

Further steps: ----

397

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Converter Redundancy Stage fault level 2 More thyristors in the same branch as defined with stage level parameter are not conducting

Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's - Defective pulse amplifiers - Blocked Thyristors 876 21114 ConvRed2Flt - Blocked CCI

Default reaction: - Alarm

Related parameters: Conv_ConverterSystem1 \ FaultStage2Level

Further steps: ---Converter Redundancy Stage fault level 3 More thyristors in the same branch as defined with stage level parameter are not conducting

Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's 877 21115 ConvRed3Flt - Defective pulse amplifiers - Blocked Thyristors - Blocked CCI

Default reaction: - Alarm

Related parameters: Conv_ConverterSystem1 \ FaultStage3Level

398

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: ----

Converter Redundance Stage fault level 4 More thyristors in the same branch as defined with stage level parameter are not conducting

Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's - Defective pulse amplifiers - Blocked Thyristors 878 21116 ConvRed4Flt - Blocked CCI

Default reaction: - Trip

Related parameters: Conv_ConverterSystem1 \ FaultStage4Level

Further steps: ----

399

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

PT fail during excitation on sequence

Possible reasons: - PT's not connected - CCM defective

Default reaction: 879 21117 PTFailExcOn - Auto Fault

Related parameters: Prot_Protection \ EnaUgExcOnMon

Further steps: - Check PT circuit - Check CCM Crowbar fault

Possible reasons: - Crowbar not conducting when opening fieldbreaker

Default reaction: 880 21118 CrowbarFlt - Alarm

Related parameters: ----

Further steps: ----

400

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Crowbar Over-voltage detection

Possible reasons: - The field overvoltage protection (crowbar) was responding to a positive or negative field overvoltage - Negative field overvoltage occurs if an interruption occurs in the power supply or field circuit

Default reaction: - Trip

881

21119

CrowbarOVFlt

Related parameters: ----

Further steps: - Check whether there is (or has been) a problem with the generator. If not, report the problem to ABB. - Check the function of the field breaker at the input or output of the converter. - Check connection line and insulation resistance of the field winding. - Check Positive field overvoltage, this error is usually caused by a generator fault, which induces negative field current, such as pole slip, short circuit at the generator terminals etc.

401

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Rotor Temperature level 1 fault

Possible reasons: - UNITROL 6000 monitors the rotor temperature, which is calculated from the excitation current, excitation voltage and the resulting field resistance. Alarm is triggered if this value exceeds the set temperature.

Default reaction: - Alarm

Related parameters: 882 21120 RotTempFlt1 Prot_Protection \ EnableRotTempMon

Prot_RotTempMon \ RotTempFaultLevel1 R1 T1 T0 SelectMode BrushVDrop CurrDepVDrop

Further steps: - Check whether the rotor has been overloaded for a long time and whether the rotor cooling system is working properly.

402

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Rotor Temperature Level 2 fault

Possible reasons: - UNITROL 6000 monitors the rotor temperature, which is calculated from the excitation current, excitation voltage and the resulting field resistance. Alarm is triggered if this value exceeds the set temperature.

Default reaction: - Alarm

Related parameters: 883 21121 RotTempFlt2 Prot_Protection \ EnableRotTempMon

Prot_RotTempMon \ RotTempFaultLevel2 R1 T1 T0 SelectMode BrushVDrop CurrDepVDrop

Further steps: - Check whether the rotor has been overloaded for a long time and whether the rotor cooling system is working properly. 884 885 886 887 888 21122 21123 21124 21125 21126 Event4_19 Event4_20 Event4_21 Event4_22 Event4_23

403

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Local CT OPC Communication fault

Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working

Default reaction: - Alarm 889 21127 LocalCTOPCFlt Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime

Further steps: - Check wiring - Check OPC server - Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT Remote CT1 OPC Communication fault

Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective

890

21128

RemCT1OPCFlt

Default reaction: - Alarm

Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime

Further steps: - Check wiring - Check OPC server

404

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

- Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT

Remote CT2 OPC Communication fault

Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective

Default reaction: 891 21129 RemCT2OPCFlt - Alarm

Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime

Further steps: - Check wiring - Check OPC server - Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT

405

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Remote CT3 OPC Communication fault

Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective

Default reaction: 892 21130 RemCT3OPCFlt - Alarm

Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime

Further steps: - Check wiring - Check OPC server - Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT Remote CT4 OPC Communication fault

Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective

893

21131

RemCT4OPCFlt

Default reaction: - Alarm

Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime

Further steps: - Check wiring

406

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Check OPC server

Description

- Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT

Block Startup

Possible reasons: - Digital input activated (Default not used)

Default reaction: 894 21132 BlockStartUpFlt - Startup blocked

Related parameters: ----

Further steps: ---PT fail during excitation on sequence

Possible reasons: - Converter CTs not connected - CSI defective 895 21133 ManFailExcOn - CCI defective

Default reaction: - Manual Fault

Related parameters:

407

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_Protection \ EnaIfExcOnMon

Further steps: - Check CT circuit - Check CCI

Field Bus Communication fault

Possible reasons: - Fieldbus connection disturbed

Default reaction: - Alarm 896 21134 FBCommFlt - Release of the Fieldbus operation request

Related parameters: OpSel_Fieldbus \ EnableCommMon ComFaultTime

Further steps: ---Excitation Transformer Temperature Level 1 fault

Possible reasons: - Insufficient cooling of the excitaion transformer

897

21135

ExcTrTmpFlt1

Default reaction: - Alarm

Related parameters: ExcTrafoMon \ TempFaultLevel1 EnableExcTrafoMon SelectPT100

408

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
EnaTemp1 EnaTemp2 EnaTemp3

Description

Further steps: ----

Excitation Transformer Temperature Level 2 fault

Possible reasons: - Insufficient cooling of the excitation transformer

Default reaction: - Trip

898

21136

ExcTrTmpFlt2

Related parameters: ExcTrafoMon \ TempFaultLevel2 EnableExcTrafoMon SelectPT100 EnaTemp1 EnaTemp2 EnaTemp3

Further steps: ----

409

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Excitation Transformer Temperature Sensor fault

Possible reasons: - Circuit to sensor open - Level 2 picked up without level 1 alive - Level 1 and 2 picked up within 100 ms

Default reaction: - Alarm 899 21137 ExcTrSensorFlt Related parameters: ExcTrafoMon \ dTdtDetectLevel EnableExcTrafoMon EnaTemp1 EnaTemp2 EnaTemp3

Further steps: ---Excitation Transformer Oil minimum Level fault

Possible reasons: - Digital input "Oil Level in excitation transformer below limit" activated

Default reaction: 900 21138 ExcTrOilMinFlt - Alarm

Related parameters: ExcTrafoMon \ EnableExcTrafoMon

Further steps: ----

410

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Excitation Transformer Oil maximum Level fault

Possible reasons: - Digital input "Oil Level in excitation transformer above limit " activated

Default reaction: 901 21139 ExcTrOilMaxFlt - Alarm

Related parameters: ExcTrafoMon \ EnableExcTrafoMon

Further steps: ---Excitation Transformer Oil Temperature Level 1 fault

Possible reasons: - Digital input "Oil temperature in excitation transformer above limit 1" activated

Default reaction: 902 21140 ExcTrOilTmpFlt1 - Alarm

Related parameters: ExcTrafoMon \ EnableExcTrafoMon

Further steps: ---Excitation Transformer Oil Temperature Level 2 fault

Possible reasons: - Digital input "Oil temperature in excitation transformer above limit 2" activated 903 21141 ExcTrOilTmpFlt2 Default reaction: - Trip

Related parameters: ExcTrafoMon \ EnableExcTrafoMon

411

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: ----

Exictation Transformer Buchholz fault 1

Possible reasons: - Digital input "Excitation Transformer Buchholz fault 1" activated

Default reaction: 904 21142 ExcTrBuchFlt1 - Alarm

Related parameters: ExcTrafoMon \ EnableExcTrafoMon

Further steps: ---Exictation Transformer Buchholz fault 2

Possible reasons: - Digital input "Excitation Transformer Buchholz fault 2" activated

Default reaction: 905 21143 ExcTrBuchFlt2 - Alarm

Related parameters: ExcTrafoMon \ EnableExcTrafoMon

Further steps: ----

412

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Power Supply Unit 1 Input Coupling Unit +ER-V80 Source 1 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 906 21144 PSU1ICU1Src1Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU1ICU1 \ SourceConfigWord

Further steps: ---Power Supply Unit 1 Input Coupling Unit +ER-V80 Source 2 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 907 21145 PSU1ICU1Src2Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU1ICU1 \ SourceConfigWord

Further steps: ----

413

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Power Supply Unit 1 Input Coupling Unit +ER-V80 Source 3 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 908 21146 PSU1ICU1Src3Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU1ICU1 \ SourceConfigWord

Further steps: ---Power Supply Unit 1 Input Coupling Unit +ER-V80 Signal Fault

Possible reasons: - Hardware defective - Monitoring line to I/O board interrupted

Default reaction: 909 21147 PSU1ICU1SigFlt - Alarm

Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU1ICU1 \ SourceConfigWord

Further steps: ----

414

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Power Supply Unit 1 APD 1-2 Fault

Possible reasons: - See corresponding hardware diagram - APD +ER-Q801 or +ER-Q802 defective - Monitoring line to I/O board interrupted

Default reaction: 910 21148 PSU1APD12APDFlt - Alarm

Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU1APDGrp1 \ Enable

Further steps: ---Power Supply Unit 1 Input Coupling Unit +ER-V81 Source 1 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 911 21149 PSU1ICU2Src1Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU1ICU2 \ SourceConfigWord

Further steps: ----

415

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Power Supply Unit 1 Input Coupling Unit +ER-V81 Source 2 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 912 21150 PSU1ICU2Src2Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU1ICU2 \ SourceConfigWord

Further steps: ---Power Supply Unit 1 Input Coupling Unit +ER-V81 Source 3 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 913 21151 PSU1ICU2Src3Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU1ICU2 \ SourceConfigWord

Further steps: ----

416

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Power Supply Unit 1 Input Coupling Unit +ER-V81 Signal Fault

Possible reasons: - Hardware defective - Monitoring line to I/O board interrupted

Default reaction: 914 21152 PSU1ICU2SigFlt - Alarm

Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU1ICU2 \ SourceConfigWord

Further steps: ---Power Supply Unit 1 APD 3-4 Fault

Possible reasons: - See corresponding hardware diagram - APD +ER-Q801 or +ER-Q802 defective - Monitoring line to I/O board interrupted

Default reaction: 915 21153 PSU1APD34APDFlt - Alarm

Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU1APDGrp2 \ Enable

Further steps: ----

417

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Power Supply Unit 2 Input Coupling Unit +EE-V80 Source 1 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 916 21154 PSU2ICU1Src1Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU2ICU1 \ SourceConfigWord

Further steps: ---Power Supply Unit 2 Input Coupling Unit +EE-V80 Source 2 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 917 21155 PSU2ICU1Src2Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU2ICU1 \ SourceConfigWord

Further steps: ----

418

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Power Supply Unit 2 Input Coupling Unit +EE-V80 Source 3 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 918 21156 PSU2ICU1Src3Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU2ICU1 \ SourceConfigWord

Further steps: ---Power Supply Unit 2 Input Coupling Unit +EE-V80 Signal Fault

Possible reasons: - Hardware defective - Monitoring line to I/O board interrupted

Default reaction: 919 21157 PSU2ICU1SigFlt - Alarm

Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU2ICU1 \ SourceConfigWord

Further steps: ----

419

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Power Supply Unit 2 APD 1-3 Fault

Possible reasons: - See corresponding hardware diagramm - APD +EE-Q801 or +EE-Q802 or +EE-Q803 defective - Monitoring line to I/O board interrupted

Default reaction: 920 21158 PSU2APD12APDFlt - Alarm

Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU2APDGrp1 \ Enable

Further steps: ---Power Supply Unit 2 Input Coupling Unit +EE-V81 Source 1 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 921 21159 PSU2ICU2Src1Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU2ICU2 \ SourceConfigWord

Further steps: ----

420

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Power Supply Unit 2 Input Coupling Unit +EE-V81 Source 2 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 922 21160 PSU2ICU2Src2Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU2ICU1 \ SourceConfigWord

Further steps: ---Power Supply Unit 2 Input Coupling Unit +EE-V81 Source 3 Fault

Possible reasons: - See corresponding hardware diagram

Default reaction: - Alarm 923 21161 PSU2ICU2Src3Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU2ICU2 \ SourceConfigWord

Further steps: ----

421

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Power Supply Unit 2 Input Coupling Unit +EE-V81 Signal Fault

Possible reasons: - Hardware defective - Monitoring line to I/O board interrupted

Default reaction: 924 21162 PSU2ICU2SigFlt - Alarm

Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU2ICU2 \ SourceConfigWord

Further steps: ---Power Supply Unit 2 APD 4-6 Fault

Possible reasons: - See corresponding hardware diagram - APD +EE-Q811 or +EE-Q812 or +EE-Q813 defective - Monitoring line to I/O board interrupted

Default reaction: 925 21163 PSU2APD34APDFlt - Alarm

Related parameters: Prot_Protection \ EnablePowerSupplyMon

Prot_PSU2APDGrp2 \ Enable

Further steps: ----

422

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIT software version fault

Description

Possible reasons: - The downloaded CIT software version is not compatible with M/S software version

Default reaction: 926 21164 CITVersionFlt - Alarm

Related parameters: ----

Further steps: ---ColdgasAnaInFlt

Possible reasons: - One or both analog input signals for the DE/NDE temperature signals are below the supervision level

Default reaction: 927 21165 ColdgasAnaInFlt - Alarm

Related parameters: Reg_ColdGas \ SelectAnaInputType EnableAnaInFaultDetection

Further steps: ----

423

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
ColdgasAnaInFlt

Description

Possible reasons: - One or both analog input signals for the DE/NDE temperature signals are below the supervision level

Default reaction: 928 21166 LCIAnaInFlt - Alarm

Related parameters: Reg_ColdGas / SelectAnaInputType EnableAnaInFaultDetection

Further steps: ---Channel Preselection fault

Possible reasons: - Channel 1 and Channel 2 are indicated as the active one after start-up

Default reaction: - Alarm 929 21167 PreSelectionFlt - none channel is starting as the active one

Related parameters: Sys_ExcitationSystem \ PreSelChannel1 PreSelChannel2

Further steps: ----

424

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

External Short-Circuit detected

Possible reasons: - Short-circuit on converter dc side is detected

Default reaction: - Alarm

Related parameters: 930 21168 DCSCDetected Prot_Protection \ EnableConvFaultDetection EnableExtSCMon

Prot_ConvFaultDetect \ ExtSCIfFaultLevel ExtSCUfFaultLevel ExtSCIfClearingFaultLevel ExtSCUfClearingFaultLevel TFCDthreshold

Further steps: ---External Short-Circuit clearing: Pulse block activated

Possible reasons: - Short-circuit on converter dc side is detected

Default reaction: - Alarm

931

21169

DCSCBlockPulses

Related parameters: Prot_Protection \ EnableConvFaultDetection EnableExtSCMon

Prot_ConvFaultDetec \ ExtSCIfFaultLevel ExtSCUfFaultLevel ExtSCIfClearingFaultLevel ExtSCUfClearingFaultLevel

425

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
TFCDthreshold

Description

ExtSCReleaseFaultClearing

Further steps: ----

Internal Short-Circuit clearing: Alpha min activated

Possible reasons: ----

Default reaction: - Alarm

932

21170

IntSCAlphaMin

Related parameters: Prot_Protection \ EnableConvFaultDetection EnableIntSCMon

Prot_ConvFaultDetect \ TFCDthreshold IntSCReleaseFaultClearing

Further steps: ----

426

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Internal Short-Circuit

Description

Possible reasons: ----

Default reaction: - Trip

933

21171

IntSCTrip

Related parameters: Prot_Protection \ EnableConvFaultDetection EnableIntSCMon

Prot_ConvFaultDetect \ TFCDthreshold IntSCReleaseFaultClearing

Further steps: ---Generator 3-Phase Short-Circuit detected

Possible reasons: - All 3 Phases measure less than 5% voltage and at the same time more than 140% current

934

21172

GenSC3Phase

Default reaction: - Alarm

Related parameters: ----

Further steps: ----

427

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Generator 2-Phase Short-Circuit detected

Possible reasons: - One or two Phases measure less than 5% voltage and at the same time more than 140% current

935

21173

GenSC2Phase

Default reaction: - Alarm

Related parameters: ----

Further steps: ---Distant 3-Phase Short-Circuit detected

Possible reasons: - All 3 Phases measure less than 80% voltage and at the same time more than 120% current

936

21174

DistantSC3Phase

Default reaction: - Alarm

Related parameters: ----

Further steps: ----

428

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Distant 2-Phase Short-Circuit detected

Possible reasons: - One or two Phases measure less than 80% voltage and at the same time more than 120% current

937

21175

DistantSC2Phase

Default reaction: - Alarm

Related parameters: ----

Further steps: ---Any Short-Circuit deteced This signal is followed by a signal of the range 21165 . . .21168 to get better information

Possible reasons: - High current and at the same time a low voltage detected

938

21176

AnySC

Default reaction: - Alarm

Related parameters: ----

Further steps: ---939 21177 Event6_10

429

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Generator Current measurement fault: Current out of measurable range

Possible reasons: - Sensing current > 1,53 A (7.65A) 1.53%

Default reaction: 940 21178 CTOvercurrent - Alarm - Blocking of single phase CT-Monitoring

Related parameters: Prot_Protection \ EnableMaschineMeasCTMon

Further steps: ---Active Channel fault

Possible reasons: - The active channel is faulty and there is no possibility to transfer to another channel

Default reaction: 941 21179 ActiveCHFlt - Trip

Related parameters: ----

Further steps: ---Manual fault in manual mode:

Possible reasons: - There is a Manual Fault while the Unit is running in Manual Mode 942 21180 MANFltinMAN Default reaction: - Channel fault

Related parameters:

430

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: ----

Auto and Manual fault:

Possible reasons: - Auto Mode as well as Manual Mode of the same channel are faulty

Default reaction: 943 21181 AUTOandMANFlt - Channel fault

Related parameters: ----

Further steps: ---Negative bridge fault while applying negative current

Possible reasons: - Check the Event List regarding event numbers 20700 to 20795

Default reaction: 944 21182 NegFieldCurrFlt - Trip

Related parameters: ----

Further steps: ----

431

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Converter configuration fault

Description

Possible reasons: - ConverterSystemConfigWord <1 or >8 - ConverterSystemConfigWord not equal to 2 and parameter EnableColdStandby = True - ConverterNegCurrConfigWord =1 and parameter EnableColdStandby = True

945

21183

ConverterCfgFlt

Default reaction: - All pulses blocked

Related parameters: Conv_ConverterSystem1 \ ConverterSystemConfigWord ConverterNegCurrConfigWord EnableColdStandby

Further steps: ---Channel configuration fault:

Possible reasons: - ChannelConfigWord <1 or >3

Default reaction: 946 21184 ChannelCfgFlt - System deadlocked

Related parameters: Sys_ExcitationSystem \ ChannelConfigWord

Further steps: ----

432

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
IO configuration fault

Description

Possible reasons: - CIOConfigWord <1 or >32767

Default reaction: 947 23409 IOCfgFlt - Alarm

Related parameters: Meas_CIOConfig \ CIOConfigWord

Further steps: ---Internal Short-Circit detected.

Possible reasons: - Defective Thyristor

Default reaction: - Alarm

948

23410

IntSCDet

Related parameters: Prot_Protection \ EnableConvFaultDetection EnableIntSCMon

Prot_ConvFaultDetect \ TFCDthreshold IntSCReleaseFaultClearing

Further steps: ----

433

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Other Channel Redundant Link 1 Fault.

Possible reasons: - Opt cabling interrupted - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

949

21188

OtherCHLink1Flt

Default reaction: - Alarm

Related parameters: ----

Further steps: - Check optical link cabling to other channel Other Channel Redundant Link 2 Fault.

Possible reasons: - Opt cabling interrupted - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

950

21189

OtherCHLink2Flt

Default reaction: - Alarm

Related parameters: ----

Further steps: - Check optical link cabling to other channel

434

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Other Channel CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 951 21190 OtherCHCPUWD - Other channel HW-fault

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board Other Channel Power Fail

Possible reasons: - Internal power fail on AC 800PEC of other channel - Both power supply inputs are missing

Default reaction: 952 21191 OtherCHPwrFail - Other channel HW-fault

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board

435

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
External Trip

Description

Possible reasons: - CCM I/O DI5 activated

Default reaction: 953 21192 ExternalTrip - Trip

Related parameters: ----

Further steps: ---Hot-startup fault. Channel started after: Channel fault, reset manual as soon as the Regulator deviation between channel 1 and channel 2 is zero

Possible reasons: -

957

21193

HotStartUpFlt

Default reaction: -

Related parameters: ----

Further steps: ---Hardware Fault on this channel detected by the Other Channel or the Backup Channel

Possible reasons: 958 21194 CHFltStandbyCH Default reaction: -

Related parameters:

436

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: ----

Hardware Fault on the Other Channel detected by the Backup Channel

Possible reasons: -

Default reaction: 959 21195 OtherCHHWFltBU -

Related parameters: ----

Further steps: ---Channel is not active and has a Trip

Possible reasons: -

Default reaction: 960 21196 PassiveCHTrip -

Related parameters: ----

Further steps: ----

437

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Field Circuit Breaker 1 Off-Coil 1 Fault

Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.

961

21197

FCB1Off1CoilFlt

Default reaction: - Alarm

Related parameters: Brk_FieldBreaker1 \ EmaxOff1Off2DelayTime

Further steps: ---Field Circuit Breaker 1 Off-Coil 2 Fault

Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.

962

21198

FCB1Off2CoilFlt

Default reaction: - Alarm

Related parameters: Brk_FieldBreaker1 \ EmaxOff1Off2DelayTime

Further steps: ----

438

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Field Circuit Breaker 1 Status Antivalency Fault

Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time

Default reaction: 963 21199 FCB1AntivalFlt - Alarm

Related parameters: Brk_FieldBreaker1 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime

Further steps: ---Field Circuit Breaker 1 Turn-On Fault

Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.

964

21200

FCB1TurnOnFlt

Default reaction: - Emergency Stop

Related parameters: Brk_FieldBreaker1 \ FCBOnDelayTime

Further steps: ----

439

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Field Circuit Breaker 1 Turn-Off Fault

Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.

965

21201

FCB1TurnOffFlt

Default reaction: - Trip

Related parameters: Brk_FieldBreaker1 \ FCBOffDelayTime

Further steps: ---Field Circuit Breaker 1 Manual-Off Fault

Possible reasons: - Fieldbreaker was opened without command from the fieldbreaker control module (either manually or by trip command, given directly to the OFF coil)

966

21202

FCB1ManOffFlt

Default reaction: - Trip

Related parameters: ----

Further steps: ----

440

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Isolator 1 Turn-On Fault

Description

Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.

967

21203

Iso1lTurnOnFlt

Default reaction: - Emergency Stop

Related parameters: Brk_FieldIsolator1 \ IsolatorOnDelayTime

Further steps: ---Isolator 1 Turn-Off Fault

Possible reasons: - ON command not executed within the set parameter time "is Off" feedback signal is missing.

968

21204

Iso1lTurnOffFlt

Default reaction: - Emergency Stop

Related parameters: Brk_FieldIsolator1 \ IsolatorOffDelayTime

Further steps: ----

441

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Isolator 1 Status Antivalency Fault

Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time

Default reaction: 969 21205 Iso1lAntivalFlt - Alarm

Related parameters: Brk_Fieldisolator1 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime

Further steps: ---Isolator 1 On-Load Open Fault

Possible reasons: - The Isolator was opened manually when it was on-load

Default reaction: 970 21206 Iso1OnLdOffFlt - Trip

Related parameters: ----

Further steps: ----

442

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Field Circuit Breaker 2 Off-Coil 1 Fault

Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.

971

21207

FCB2Off1CoilFlt

Default reaction: - Alarm

Related parameters: Brk_FieldBreaker2 \ EmaxOff1Off2DelayTime

Further steps: ---Field Circuit Breaker 2 Off-Coil 2 Fault

Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.

972

21208

FCB2Off2CoilFlt

Default reaction: - Alarm

Related parameters: Brk_FieldBreaker2 \ EmaxOff1Off2DelayTime

Further steps: ----

443

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Field Circuit Breaker 2 Status Antivalency Fault

Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time

Default reaction: 973 21209 FCB2AntivalFlt - Alarm

Related parameters: Brk_FieldBreaker2 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime

Further steps: ---Field Circuit Breaker 2 Turn-On Fault

Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.

974

21210

FCB2TurnOnFlt

Default reaction: - Emergency Stop

Related parameters: Brk_FieldBreaker2 \ FCBOnDelayTime

Further steps: ----

444

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Field Circuit Breaker 2 Turn-Off Fault

Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.

975

21211

FCB2TurnOffFlt

Default reaction: - Trip

Related parameters: Brk_FieldBreaker2 \ FCBOffDelayTime

Further steps: ---Field Circuit Breaker 2 Manual-Off Fault

Possible reasons: - Fieldbreaker was opened without command from the fieldbreaker control module (either manually or by trip command, given directly to the OFF coil)

976

21212

FCB2ManOffFlt

Default reaction: - Trip

Related parameters: ----

Further steps: ----

445

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Isolator 2 Turn-On Fault

Description

Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.

977

21213

Iso2lTurnOnFlt

Default reaction: - Emergency Stop

Related parameters: Brk_FieldIsolator2 \ IsolatorOnDelayTime

Further steps: ---Isolator 2 Turn-Off Fault

Possible reasons: - ON command not executed within the set parameter time "is Off" feedback signal is missing.

978

21214

Iso2lTurnOffFlt

Default reaction: - Emergency Stop

Related parameters: Brk_FieldIsolator2 \ IsolatorOffDelayTime

Further steps: ----

446

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Isolator 2 Status Antivalency Fault

Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time

Default reaction: 979 21215 Iso2lAntivalFlt - Alarm

Related parameters: Brk_Fieldisolator2 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime

Further steps: ---Isolator 2 On-Load Open Fault

Possible reasons: - The Isolator was opened manually when it was on-load

Default reaction: 980 21216 Iso2OnLdOffFlt - Trip

Related parameters: ----

Further steps: ----

447

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Field Circuit Breaker 3 Off-Coil 1 Fault

Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.

981

21217

FCB3Off1CoilFlt

Default reaction: - Alarm

Related parameters: Brk_FieldBreaker3 \ EmaxOff1Off2DelayTime

Further steps: ---Field Circuit Breaker 3 Off-Coil 2 Fault

Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.

982

21218

FCB3Off2CoilFlt

Default reaction: - Alarm

Related parameters: Brk_FieldBreaker3 \ EmaxOff1Off2DelayTime

Further steps: ----

448

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Field Circuit Breaker 3 Status Antivalency Fault

Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time

Default reaction: 983 21219 FCB3AntivalFlt - Alarm

Related parameters: Brk_FieldBreaker3 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime

Further steps: ---Field Circuit Breaker 3 Turn-On Fault

Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.

984

21220

FCB3TurnOnFlt

Default reaction: - Emergency Stop

Related parameters: Brk_FieldBreaker3 \ FCBOnDelayTime

Further steps: ----

449

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Field Circuit Breaker 3 Turn-Off Fault

Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.

985

21221

FCB3TurnOffFlt

Default reaction: - Trip

Related parameters: Brk_FieldBreaker3 \ FCBOffDelayTime

Further steps: ---Field Circuit Breaker 3 Manual-Off Fault

Possible reasons: - Fieldbreaker was opened without command from the fieldbreaker control module (either manually or by trip command, given directly to the OFF coil)

986

21222

FCB3ManOffFlt

Default reaction: - Trip

Related parameters: ----

Further steps: ----

450

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Isolator 3 Turn-On Fault

Description

Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.

987

21223

Iso3lTurnOnFlt

Default reaction: - Emergency Stop

Related parameters: Brk_FieldIsolator3 \ IsolatorOnDelayTime

Further steps: ---Isolator 3 Turn-Off Fault

Possible reasons: - ON command not executed within the set parameter time "is Off" feedback signal is missing.

988

21224

Iso3lTurnOffFlt

Default reaction: - Emergency Stop

Related parameters: Brk_FieldIsolator3 \ IsolatorOffDelayTime

Further steps: ----

451

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Isolator 3 Status Antivalency Fault

Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time

Default reaction: 989 21225 Iso3lAntivalFlt - Alarm

Related parameters: Brk_Fieldisolator3 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime

Further steps: ---Isolator 3 On-Load Open Fault

Possible reasons: - The Isolator was opened manually when it was on load

Default reaction: 990 21226 Iso3OnLdOffFlt ----

Related parameters: ----

Further steps: ---991 21227 FCBNotChgdFlt Field Circuit Breaker not charged fault

452

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Trip while system running with fire all

Possible reasons: - Too high synchronous voltage, generator voltage or field current while excitation start with fire all thyristors

Default reaction: 992 21228 FireAllTrip - Emergency stop

Related parameters: Prot_Protection \ EnableFireAllTripDet

Further steps: ---993 994 995 996 997 998 999 1'000 1'001 1'002 1'003 1'004 1'005 1'006 1'007 1'008 1'009 1'010 1'011 1'012 1'013 1'014 1'015 1'016 1'017 1'018 1'019 1'020 1'021 1'022 1'023 1'024 21229 21230 21231 21232 21233 21234 21235 21236 21237 21238 21239 21240 21241 21242 21243 21244 21245 21246 21247 21248 21249 21250 21251 21252 21253 21254 21255 22000 22001 22002 22003 22004 Event8_00 Event8_01 Event8_02 Event8_03 Event8_04 Event8_05 Event8_06 Event8_07 Event8_08 Event8_09 Event8_10 Event8_11 Event8_12 Event8_13 Event8_14 Event8_15 Event8_16 Event8_17 Event8_18 Event8_19 Event8_20 Event8_21 Event8_22 Event8_23 Event8_24 Event8_25 Event8_26 Event8_27 Event8_28 Event8_29 Event8_30 Event8_31

453

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO1. Link Fault

Description

Possible reasons: - Optical link cabling to CIO interrupted (OM2 Link 5) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

1'025

22005

LinkFault_CIO1

Default reaction: - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO1. Redundant Power fail 1

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 1'026 22006 RedPwrFail1_CIO1 - Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply CIO1. Redundant Power fail 2

Possible reasons: - Power supply fault at input 2 (X2:3-4) 1'027 22007 RedPwrFail2_CIO1 Default reaction: - Redundancy Fault

Related parameters:

454

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply

CIO1. Precision Power fail

Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing

Default reaction: 1'028 22008 PrciPwrFail_CIO1 - CIO Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board CIO1. CPU Watchdog

Possible reasons: - CPU failure - Simulink application not running

1'029

22009

CPUWatchdog_CIO1

Default reaction: - CIO Trip

Related parameters: ----

Further steps:

455

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Reboot device

Description

- Download installer archive - Replace board

CIO1. Software Version fault

Possible reasons: - Wrong converter interface SW version

Default reaction: 1'030 22010 VersionFlt_CIO1 - CIO Trip

Related parameters: ----

Further steps: - Download required software version CIO1. Address Error

Possible reasons: - Wrong HEX Switch setting at CIO

Default reaction: 1'031 22011 AddressErr_CIO1 - CIO Trip

Related parameters: ----

Further steps: - Check Hex-Switch setting on CIO

456

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO1. Device Type Error

Description

Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 5) - Wrong installer archive loaded to CIO

1'032

22012

DevTypeErr_CIO1

Default reaction: - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO1 Digital IO deviation between IO's of Channel 1 and Channel 2

Possible reasons: - Defective I/O section on CIO Board - Wiring faults

Default reaction: 1'033 22013 SigConsistFlt_CIO1 - Alarm

Related parameters: ----

Further steps: - Check wiring - Replace device

457

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CIO1. Temperature Sensor 1 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'034

22014

Temp1SnsFlt_CIO1

Default reaction: - Alarm

Related parameters: ----

Further steps: ---CIO1. Temperature Sensor 2 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'035

22015

Temp2SnsFlt_CIO1

Default reaction: - Alarm

Related parameters: ----

Further steps: ----

458

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CIO1. Temperature Sensor 3 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'036

22016

Temp3SnsFlt_CIO1

Default reaction: - Alarm

Related parameters: ----

Further steps: ---1'037 1'038 1'039 1'040 1'041 1'042 1'043 1'044 1'045 1'046 1'047 1'048 1'049 1'050 1'051 1'052 1'053 22017 22018 22019 22020 22021 22022 22023 22024 22025 22026 22027 22028 22029 22030 22031 22100 22101 Event1_12_CIO1 Event1_13_CIO1 Event1_14_CIO1 Event1_15_CIO1 Event1_16_CIO1 Event1_17_CIO1 Event1_18_CIO1 Event1_19_CIO1 Event1_20_CIO1 Event1_21_CIO1 Event1_22_CIO1 Event1_23_CIO1 Event1_24_CIO1 Event1_25_CIO1 Event1_26_CIO1 Event1_27_CIO1 Event1_28_CIO1

459

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
1'054 1'055 1'056

ID
22102 22103 22104

Name
Event1_29_CIO1 Event1_30_CIO1 Event1_31_CIO1

Events

Description

CIO2. Link Fault

Possible reasons: - Optical link cabling to CIO1 interrupted (OM6 Link 3) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)

1'057

22105

LinkFault_CIO2

Default reaction: - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO2. Redundant Power fail 1

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 1'058 22106 RedPwrFail1_CIO2 - Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply

460

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CIO2. Redundant Power fail 2

Possible reasons: - Power supply fault at input 2 (X2:3-4)

Default reaction: 1'059 22107 RedPwrFail2_CIO2 - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO2. Precision Power fail

Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing

Default reaction: 1'060 22108 PrciPwrFail_CIO2 - CIO Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board

461

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO2. CPU Watchdog

Description

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 1'061 22109 CPUWatchdog_CIO2 - CIO Trip

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board CIO2. Software Version fault

Possible reasons: - Wrong converter interface SW version

Default reaction: 1'062 22110 VersionFlt_CIO2 - CIO Trip

Related parameters: ----

Further steps: - Download required software version

462

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO2. Address Error

Description

Possible reasons: - Wrong HEX Switch setting at CIO

Default reaction: 1'063 22111 AddressErr_CIO2 - CIO Trip

Related parameters: ----

Further steps: - Check Hex-Swtich setting on CIO CIO2. Device Type Error

Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO

1'064

22112

DevTypeErr_CIO2

Default reaction: - CIO Trip Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO2. Digital IO deviation between IO's of Channel 1 and Channel 2

Possible reasons: - Defective I/O section on CIO Board - Wiring faults 1'065 22113 SigConsistFlt_CIO2 Default reaction: - Alarm

Related parameters: ----

463

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check wiring - Replace device

CIO2. Temperature Sensor 1 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'066

22114

Temp1SnsFlt_CIO2

Default reaction: - Alarm

Related parameters: ----

Further steps: ---CIO2. Temperature Sensor 2 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'067 22115 Temp2SnsFlt_CIO2 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

Default reaction: - Alarm

Related parameters: ----

464

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: ----

CIO2. Temperature Sensor 3 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'068

22116

Temp3SnsFlt_CIO2

Default reaction: - Alarm

Related parameters: ----

Further steps: ---1'069 1'070 1'071 1'072 1'073 1'074 1'075 1'076 1'077 22117 22118 22119 22120 22121 22122 22123 22124 22125 Event1_12_CIO2 Event1_13_CIO2 Event1_14_CIO2 Event1_15_CIO2 Event1_16_CIO2 Event1_17_CIO2 Event1_18_CIO2 Event1_19_CIO2 Event1_20_CIO2

465

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
1'078 1'079 1'080 1'081 1'082 1'083 1'084 1'085 1'086 1'087 1'088

ID
22126 22127 22128 22129 22130 22131 22200 22201 22202 22203 22204

Name
Event1_21_CIO2 Event1_22_CIO2 Event1_23_CIO2 Event1_24_CIO2 Event1_25_CIO2 Event1_26_CIO2 Event1_27_CIO2 Event1_28_CIO2 Event1_29_CIO2 Event1_30_CIO2 Event1_31_CIO2

Events

Description

CIO3. Link Fault

Possible reasons: - Optical link cabling to CIO interrupted (OM2 Link 6)

Default reaction: 1'089 22205 LinkFault_CIO3 - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO3. Redundant Power fail 1

Possible reasons: - Power supply fault at input 1 (X1:1-2) 1'090 22206 RedPwrFail1_CIO3

Default reaction: - Redundancy Fault

Related parameters: ----

466

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling and power supply

CIO3. Redundant Power fail 2

Possible reasons: - Power supply fault at input 2 (X2:3-4)

Default reaction: 1'091 22207 RedPwrFail2_CIO3 - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO3. Precision Power fail

Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing

Default reaction: 1'092 22208 PrciPwrFail_CIO3 - CIO Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board

467

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO3. CPU Watchdog

Description

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 1'093 22209 CPUWatchdog_CIO3 - CIO Trip

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board CIO3. Software Version fault

Possible reasons: - Wrong converter interface SW version

Default reaction: 1'094 22210 VersionFlt_CIO3 - CIO Trip

Related parameters: ----

Further steps: - Download required software version

468

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO3. Address Error

Description

Possible reasons: - Wrong HEX Switch setting at CIO

Default reaction: 1'095 22211 AddressErr_CIO3 - CIO Trip

Related parameters: ----

Further steps: - Check Hex-Swtich setting on CIO CIO3. Device Type Error

Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 6) - Wrong installer archive loaded to CIO3

1'096

22212

DevTypeErr_CIO3

Default reaction: - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO3. Digital IO deviation between IO's of Channel 1 and Channel 2

Possible reasons: - Defective I/O section on CIO Board 1'097 22213 SigConsistFlt_CIO3 - Wiring faults

Default reaction: - Alarm

Related parameters:

469

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: - Check wiring - Replace device

CIO3. Temperature Sensor 1 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'098

22214

Temp1SnsFlt_CIO3

Default reaction: - Alarm

Related parameters: ----

Further steps: ---CIO3. Temperature Sensor 2 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'099 22215 Temp2SnsFlt_CIO3 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

Default reaction: - Alarm

Related parameters: ----

470

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: ----

CIO3. Temperature Sensor 3 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'100

22216

Temp3SnsFlt_CIO3

Default reaction: - Alarm

Related parameters: ----

Further steps: ---1'101 1'102 1'103 1'104 1'105 1'106 1'107 1'108 1'109 22217 22218 22219 22220 22221 22222 22223 22224 22225 Event1_12_CIO3 Event1_13_CIO3 Event1_14_CIO3 Event1_15_CIO3 Event1_16_CIO3 Event1_17_CIO3 Event1_18_CIO3 Event1_19_CIO3 Event1_20_CIO3

471

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
1'110 1'111 1'112 1'113 1'114 1'115 1'116 1'117 1'118 1'119 1'120

ID
22226 22227 22228 22229 22230 22231 22300 22301 22302 22303 22304

Name
Event1_21_CIO3 Event1_22_CIO3 Event1_23_CIO3 Event1_24_CIO3 Event1_25_CIO3 Event1_26_CIO3 Event1_27_CIO3 Event1_28_CIO3 Event1_29_CIO3 Event1_30_CIO3 Event1_31_CIO3

Events

Description

CIO4. Link Fault

Possible reasons: - Optical link cabling to CIO3 interrupted (OM6 Link 3)

Default reaction: 1'121 22305 LinkFault_CIO4 - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO4. Redundant Power fail 1

Possible reasons: - Power supply fault at input 1 (X1:1-2) 1'122 22306 RedPwrFail1_CIO4

Default reaction: - Redundancy Fault

Related parameters: ----

472

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling and power supply

CIO4. Redundant Power fail 2

Possible reasons: - Power supply fault at input 2 (X2:3-4)

Default reaction: 1'123 22307 RedPwrFail2_CIO4 - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO4. Precision Power fail

Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing

Default reaction: 1'124 22308 PrciPwrFail_CIO4 - CIO Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board

473

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO4. CPU Watchdog

Description

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 1'125 22309 CPUWatchdog_CIO4 - CIO Trip

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board CIO4. Software Version fault

Possible reasons: - Wrong converter interface SW version

1'126

22310

VersionFlt_CIO4

Default reaction: - CIO Trip Related parameters: ----

Further steps: - Download required software version CIO4. Address Error

Possible reasons: - Wrong HEX Switch setting at CIO 1'127 22311 AddressErr_CIO4 Default reaction: - CIO Trip

Related parameters:

474

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: - Check Hex-Swtich setting on CIO

CIO4. Device Type Error

Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO

1'128

22312

DevTypeErr_CIO4

Default reaction: - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO4. Digital IO deviation between IO's of Channel 1 and Channel 2

Possible reasons: - Defective I/O section on CIO Board - Wiring faults

Default reaction: 1'129 22313 SigConsistFlt_CIO4 - Alarm

Related parameters: ----

Further steps: - Check wiring

475

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
- Replace device

Description

CIO4. Temperature Sensor 1 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'130

22314

Temp1SnsFlt_CIO4

Default reaction: - Alarm

Related parameters: ----

Further steps: ---CIO4. Temperature Sensor 2 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'131 22315 Temp2SnsFlt_CIO4 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

Default reaction: - Alarm

Related parameters: ----

476

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: ----

CIO4. Temperature Sensor 3 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'132

22316

Temp3SnsFlt_CIO4

Default reaction: - Alarm

Related parameters: ----

Further steps: ---1'133 1'134 1'135 1'136 1'137 1'138 1'139 1'140 1'141 22317 22318 22319 22320 22321 22322 22323 22324 22325 Event1_12_CIO4 Event1_13_CIO4 Event1_14_CIO4 Event1_15_CIO4 Event1_16_CIO4 Event1_17_CIO4 Event1_18_CIO4 Event1_19_CIO4 Event1_20_CIO4

477

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
1'142 1'143 1'144 1'145 1'146 1'147 1'148 1'149 1'150 1'151 1'152

ID
22326 22327 22328 22329 22330 22331 22400 22401 22402 22403 22404

Name
Event1_21_CIO4 Event1_22_CIO4 Event1_23_CIO4 Event1_24_CIO4 Event1_25_CIO4 Event1_26_CIO4 Event1_27_CIO4 Event1_28_CIO4 Event1_29_CIO4 Event1_30_CIO4 Event1_31_CIO4

Events

Description

CIO5. Link Fault

Possible reasons: - Optical link cabling to CIO interrupted (OM3 Link 5)

Default reaction: 1'153 22405 LinkFault_CIO5 - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO5. Redundant Power fail 1

Possible reasons: - Power supply fault at input 1 (X1:1-2) 1'154 22406 RedPwrFail1_CIO5

Default reaction: - Redundancy Fault

Related parameters: ----

478

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling and power supply

CIO5. Redundant Power fail 2

Possible reasons: - Power supply fault at input 2 (X2:3-4)

Default reaction: 1'155 22407 RedPwrFail2_CIO5 - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO5. Precision Power fail

Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing

Default reaction: 1'156 22408 PrciPwrFail_CIO5 - CIO Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board

479

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO5. CPU Watchdog

Description

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 1'157 22409 CPUWatchdog_CIO5 - CIO Trip Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board CIO5. Software Version fault

Possible reasons: - Wrong converter interface SW version

Default reaction: 1'158 22410 VersionFlt_CIO5 - CIO Trip

Related parameters: ----

Further steps: - Download required software version CIO5. Address Error Possible reasons: - Wrong HEX Switch setting at CIO

1'159

22411

AddressErr_CIO5

Default reaction: - CIO Trip

Related parameters: ----

480

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check Hex-Swtich setting on CIO

CIO5. Device Type Error

Possible reasons: - Wrong device connected to AC 800PEC (OM3 Link 5) - Wrong installer archive loaded to CIO

1'160

22412

DevTypeErr_CIO5

Default reaction: - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO5.Digital IO deviation between IO's of Channel 1 and Channel 2

Possible reasons: - Defective I/O section on CIO Board - Wiring faults

Default reaction: 1'161 22413 SigConsistFlt_CIO5 - Alarm

Related parameters: ----

Further steps: - Check wiring - Replace device

481

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CIO5. Temperature Sensor 1 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'162

22414

Temp1SnsFlt_CIO5

Default reaction: - Alarm

Related parameters: ----

Further steps: ---CIO5. Temperature Sensor 2 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'163

22415

Temp2SnsFlt_CIO5

Default reaction: - Alarm

Related parameters: ----

Further steps: ----

482

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CIO5. Temperature Sensor 3 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'164

22416

Temp3SnsFlt_CIO5

Default reaction: - Alarm

Related parameters: ----

Further steps: ---1'165 1'166 1'167 1'168 1'169 1'170 1'171 1'172 1'173 1'174 1'175 1'176 1'177 1'178 1'179 1'180 1'181 22417 22418 22419 22420 22421 22422 22423 22424 22425 22426 22427 22428 22429 22430 22431 22500 22501 Event1_12_CIO5 Event1_13_CIO5 Event1_14_CIO5 Event1_15_CIO5 Event1_16_CIO5 Event1_17_CIO5 Event1_18_CIO5 Event1_19_CIO5 Event1_20_CIO5 Event1_21_CIO5 Event1_22_CIO5 Event1_23_CIO5 Event1_24_CIO5 Event1_25_CIO5 Event1_26_CIO5 Event1_27_CIO5 Event1_28_CIO5

483

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
1'182 1'183 1'184

ID
22502 22503 22504

Name
Event1_29_CIO5 Event1_30_CIO5 Event1_31_CIO5

Events

Description

CIO6. Link Fault

Possible reasons: - Optical link cabling to CIO5 interrupted (OM6 Link 3)

Default reaction: 1'185 22505 LinkFault_CIO6 - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO6. Redundant Power fail 1

Possible reasons: - Power supply fault at input 1 (X1:1-2)

Default reaction: 1'186 22506 RedPwrFail1_CIO6 - Redundancy Fault

Related parameters: ----

Further steps: - Check cabling and power supply

484

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

CIO6. Redundant Power fail 2

Possible reasons: - Power supply fault at input 2 (X2:3-4)

Default reaction: 1'187 22507 RedPwrFail2_CIO6 - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO6. Precision Power fail

Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing

Default reaction: 1'188 22508 PrciPwrFail_CIO6 - CIO Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board

485

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO6. CPU Watchdog

Description

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 1'189 22509 CPUWatchdog_CIO6 - CIO Trip

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board CIO6. Software Version fault

Possible reasons: - Wrong converter interface SW version

Default reaction: 1'190 22510 VersionFlt_CIO6 - CIO Trip

Related parameters: ----

Further steps: - Download required software version

486

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO6. Address Error

Description

Possible reasons: - Wrong HEX Switch setting at CIO

Default reaction: 1'191 22511 AddressErr_CIO6 - CIO Trip

Related parameters: ----

Further steps: - Check Hex-Swtich setting on CIO CIO6. Device Type Error

Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO

1'192

22512

DevTypeErr_CIO6

Default reaction: - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO6. Temperature Sensor 1 fault

Possible reasons: PT100 PTC 1'193 22513 SigConsistFlt_CIO6 - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at senor cabling > 181.6 Ohm > --- Ohm

Default reaction: - Alarm

487

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Related parameters:

Description

Further steps: ----

CIO6. Temperature Sensor 1 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'194

22514

Temp1SnsFlt_CIO6

Default reaction: - Alarm

Related parameters: ----

Further steps: ---CIO6. Temperature Sensor 2 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'195 22515 Temp2SnsFlt_CIO6 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

Default reaction: - Alarm

Related parameters: ----

488

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: ----

CIO6. Temperature Sensor 3 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'196

22516

Temp3SnsFlt_CIO6

Default reaction: - Alarm

Related parameters: ----

Further steps: ---1'197 1'198 1'199 1'200 1'201 1'202 1'203 1'204 1'205 22517 22518 22519 22520 22521 22522 22523 22524 22525 Event1_12_CIO6 Event1_13_CIO6 Event1_14_CIO6 Event1_15_CIO6 Event1_16_CIO6 Event1_17_CIO6 Event1_18_CIO6 Event1_19_CIO6 Event1_20_CIO6

489

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
1'206 1'207 1'208 1'209 1'210 1'211 1'212 1'213 1'214 1'215 1'216

ID
22526 22527 22528 22529 22530 22531 22600 22601 22602 22603 22604

Name
Event1_21_CIO6 Event1_22_CIO6 Event1_23_CIO6 Event1_24_CIO6 Event1_25_CIO6 Event1_26_CIO6 Event1_27_CIO6 Event1_28_CIO6 Event1_29_CIO6 Event1_30_CIO6 Event1_31_CIO6

Events

Description

CIO7. Link Fault

Possible reasons: - Optical link cabling to CIO interrupted (OM3 Link 6)

Default reaction: 1'217 22605 LinkFault_CIO7 - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO7. Redundant Power fail 1

Possible reasons: - Power supply fault at input 1 (X1:1-2) 1'218 22606 RedPwrFail1_CIO7

Default reaction: - Redundancy Fault

Related parameters: ----

490

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: - Check cabling and power supply

CIO7. Redundant Power fail 2

Possible reasons: - Power supply fault at input 2 (X2:3-4)

Default reaction: 1'219 22607 RedPwrFail2_CIO7 - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO7. Precision Power fail

Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing

Default reaction: 1'220 22608 PrciPwrFail_CIO7 - CIO Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board

491

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO7. CPU Watchdog

Description

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 1'221 22609 CPUWatchdog_CIO7 - CIO Trip

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board CIO7. Software Version fault

Possible reasons: - Wrong converter interface SW version

Default reaction: 1'222 22610 VersionFlt_CIO7 - CIO Trip

Related parameters: ----

Further steps: - Download required software version

492

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO7. Address Error

Description

Possible reasons: - Wrong HEX Switch setting at CIO

Default reaction: 1'223 22611 AddressErr_CIO7 - CIO Trip

Related parameters: ----

Further steps: - Check Hex-Swtich setting on CIO CIO7. Device Type Error

Possible reasons: - Wrong device connected to AC 800PEC (OM3 Link 6) - Wrong installer archive loaded to CIO

1'224

22612

DevTypeErr_CIO7

Default reaction: - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO7. Digital IO deviation between IO's of Channel 1 and Channel 2

Possible reasons: - Defective I/O section on CIO Board 1'225 22613 SigConsistFlt_CIO7 - Wiring faults

Default reaction: - Alarm

Related parameters:

493

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: - Check wiring - Replace device

CIO7. Temperature Sensor 1 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'226

22614

Temp1SnsFlt_CIO7

Default reaction: - Alarm

Related parameters: ----

Further steps: ---CIO7. Temperature Sensor 2 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'227 22615 Temp2SnsFlt_CIO7 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

Default reaction: - Alarm

Related parameters: ----

494

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: ----

CIO7. Temperature Sensor 3 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'228

22616

Temp3SnsFlt_CIO7

Default reaction: - Alarm

Related parameters: ----

Further steps: ---1'229 1'230 1'231 1'232 1'233 1'234 1'235 1'236 1'237 22617 22618 22619 22620 22621 22622 22623 22624 22625 Event1_12_CIO7 Event1_13_CIO7 Event1_14_CIO7 Event1_15_CIO7 Event1_16_CIO7 Event1_17_CIO7 Event1_18_CIO7 Event1_19_CIO7 Event1_20_CIO7

495

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
1'238 1'239 1'240 1'241 1'242 1'243 1'244 1'245 1'246 1'247 1'248

ID
22626 22627 22628 22629 22630 22631 22700 22701 22702 22703 22704

Name
Event1_21_CIO7 Event1_22_CIO7 Event1_23_CIO7 Event1_24_CIO7 Event1_25_CIO7 Event1_26_CIO7 Event1_27_CIO7 Event1_28_CIO7 Event1_29_CIO7 Event1_30_CIO7 Event1_31_CIO7

Events

Description

CIO8. Link Fault

Possible reasons: - Optical link cabling to CIO7 interrupted (OM6 Link 3)

1'249

22705

LinkFault_CIO8

Default reaction: - CIO Trip Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO8. Redundant Power fail 1

Possible reasons: - Power supply fault at input 1 (X1:1-2)

1'250

22706

RedPwrFail1_CIO8

Default reaction: - Redundancy Fault

Related parameters: ----

496

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Further steps:

Description

- Check cabling and power supply

CIO8. Redundant Power fail 2

Possible reasons: - Power supply fault at input 2 (X2:3-4)

Default reaction: 1'251 22707 RedPwrFail2_CIO8 - Redundancy Fault

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Further steps: - Check cabling and power supply CIO8. Precision Power fail

Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing

Default reaction: 1'252 22708 PrciPwrFail_CIO8 - CIO Trip

Related parameters: ----

Further steps: - Check cabling and power supply - Replace board

497

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO8. CPU Watchdog

Description

Possible reasons: - CPU failure - Simulink application not running

Default reaction: 1'253 22709 CPUWatchdog_CIO8 - CIO Trip

Related parameters: ----

Further steps: - Reboot device - Download installer archive - Replace board CIO8. Software Version fault

Possible reasons: - Wrong converter interface SW version

Default reaction: 1'254 22710 VersionFlt_CIO8 - Alarm

Related parameters: ----

Further steps: - Download required software version

498

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
CIO8. Address Error

Description

Possible reasons: - Wrong HEX Switch setting at CIO

Default reaction: 1'255 22711 AddressErr_CIO8 - CIO Trip

Related parameters: ----

Further steps: - Check Hex-Swtich setting on CIO CIO8. Device Type Error

Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO

1'256

22712

DevTypeErr_CIO8

Default reaction: - CIO Trip

Related parameters: ----

Further steps: - Check optical link cabling to CIO CIO8. Digital IO deviation between IO's of Channel 1 and Channel 2

Possible reasons: - Defective I/O section on CIO Board 1'257 22713 SigConsistFlt_CIO8 - Wiring faults

Default reaction: - Alarm

Related parameters:

499

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: - Check wiring - Replace device

CIO8. Temperature Sensor 1 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'258

22714

Temp1SnsFlt_CIO8

Default reaction: - Alarm

Related parameters: ----

Further steps: ---CIO8. Temperature Sensor 2 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'259 22715 Temp2SnsFlt_CIO8 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

Default reaction: - Alarm

Related parameters: ----

500

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Further steps: ----

CIO8. Temperature Sensor 3 fault

Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm

1'260

22716

Temp3SnsFlt_CIO8

Default reaction: - Alarm

Related parameters: ----

Further steps: ---1'261 1'262 1'263 1'264 1'265 1'266 1'267 1'268 1'269 22717 22718 22719 22720 22721 22722 22723 22724 22725 Event1_12_CIO8 Event1_13_CIO8 Event1_14_CIO8 Event1_15_CIO8 Event1_16_CIO8 Event1_17_CIO8 Event1_18_CIO8 Event1_19_CIO8 Event1_20_CIO8

501

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr
1'270 1'271 1'272 1'273 1'274 1'275 1'276 1'277 1'278 1'279 1'280

ID
22726 22727 22728 22729 22730 22731 23000 23001 23002 23003 23004

Name
Event1_21_CIO8 Event1_22_CIO8 Event1_23_CIO8 Event1_24_CIO8 Event1_25_CIO8 Event1_26_CIO8 Event1_27_CIO8 Event1_28_CIO8 Event1_29_CIO8 Event1_30_CIO8 Event1_31_CIO8

Events

Description

Channel Fault - Group alarm

Possible reasons: - One or more events which are assigned to "Channel Fault" has (have) occurred - The signal was forced by the command "Force Channel Fault"

Default reaction: 1'281 23005 ChannelFault - Single channel -> Trip - Redundant system -> Channel transfer

Related parameters: ----

Further steps: - According to individual event description

502

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Auto Fault - Group alarm

Description

Possible reasons: - One or more events which are assigned to "Auto Fault" has (have) occurred - The signal was forced by the command "Force Auto Fault"

Default reaction: 1'282 23006 AutoFault - Single channel -> Transfer to "Manual Mode" - Redundant system -> Channel transfer, own channel transfer to "Manual Mode"

Related parameters: ----

Further steps: - according to individual event description Manual Fault - Group alarm

Possible reasons: - One or more events which are assigned to "Manual Fault" has (have) occurred - The signal was forced by the command "Force Manual Fault"

Default reaction: 1'283 23007 ManualFault - Single channel -> Trip - Redundant system -> Channel transfer

Related parameters: ----

Further steps: - According to individual event description

503

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Other Channel Hardware Fault - Group alarm

Possible reasons: - One or more events which are assigned to "Other Channel Hardware Fault" has (have) occurred - The signal was forced by the command "Force Other Channel Hardware Fault"

1'284

23008

OtherCHHWFault

Default reaction: - Blocking of channel transfer ability to "Other Channel"

Related parameters: ----

Further steps: - According to individual event description Backup Channel Hardware Fault - Group alarm

Possible reasons: - One or more events which are assigned to Auto Fault has (have) accured - The signal was forced by the command "Force Auto Fault"

Default reaction: 1'285 23009 BUCHHWFault - Single channel -> Transfer to "Manual Mode" - Reduadant system -> Channel transfer, own channel transfer to "Manual Mode"

Related parameters: ----

Further steps: - According to individual event description

504

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events

Description

Channel to Backup Link Loss - Group alarm

Possible reasons: - One or more events which are assigned to Channel to Backup Link Loss has (have) occurred - The signal was forced by the command "Channel to Backup Link Loss"

1'286

23010

CHtoBULinkLoss

Default reaction: - Blocking of channel transfer ability to Backup Channel

Related parameters: ----

Further steps: - According to individual event description Emergency Stop - Group alarm

Possible reasons: - One or more events which are assigned to "Emergency Stop" has (have) occurred - The signal was forced by the command "Emergency Stop"

Default reaction: 1'287 23011 EmergencyStop - Excitation is swiched off - Fieldbreaker is opened

Related parameters: ----

Further steps: - According to individual event description

505

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Trip 1 - Group alarm

Description

Possible reasons: - One or more events which are assigned to "Trip 1" has (have) occurred - The signal was forced by the command "Trip 1"

Default reaction: 1'288 23100 Trip1 - Trip command given to Plant Protection - Excitation is swiched off - Fieldbreaker is opened

Related parameters: ----

Further steps: - According to individual event description Trip 2 - Group alarm

Possible reasons: - One or more events which are assigned to "Trip 2" has (have) occurred - The signal was forced by the command "Trip 2"

Default reaction: - Trip request given to Plant Protection 1'289 23101 Trip2 - If accepted - Excitation is swiched off - Fieldbreaker is opened

Related parameters: ----

Further steps: - According to individual event description

506

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Startup Inhibit - Group alarm

Description

Possible reasons: - One or more events which are assigned to "Startup Inhibit" has (have) occurred - The signal was forced by the command "Force Startup Inhibit"

Default reaction: 1'290 23102 StartupInhibit - Blocking of Fieldbreaker Close command - Blocking of Excitation On command

Related parameters: ----

Further steps: - According to individual event description Redundancy Fault - Group alarm

Possible reasons: - One or more events which are assigned to "Redundancy Fault" has (have) occurred - The signal was forced by the command "Redundancy Fault"

1'291

23103

RedundancyFault

Default reaction: ----

Related parameters: ----

Further steps: - According to individual event description

507

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Alarm - Group alarm

Description

Possible reasons: - One or more events which are assigned to "Alarm" has (have) occurred - The signal was forced by the command "Alarm"

1'292

23104

Alarm

Default reaction: ----

Related parameters: ----

Further steps: - According to individual event description Force Channel Fault

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Channel Fault"

Default reaction: 1'293 23105 ForceChannelFault ----

Related parameters: ----

Further steps: ----

508

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Force Auto Fault

Description

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Auto Fault"

Default reaction: 1'294 23106 ForceAutoFault ----

Related parameters: ----

Further steps: ---Force Manual Fault

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Manual Fault"

Default reaction: 1'295 23107 ForceManualFault ----

Related parameters: ----

Further steps: ---Force Other Channel Hardware Fault

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Other Channel Hardware Fault"

1'296

23108

ForceOtherCHHWFault

Default reaction: ----

Related parameters:

509

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: ----

Force Backup Channel Hardware Fault

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Backup Channel Hardware Fault"

1'297

23109

ForceBUCHHWFault

Default reaction: ----

Related parameters: ----

Further steps: ---Force Channel to Backup Link Loss

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Channel to Backup Link Loss"

1'298

23110

ForceCHtoBULinkLoss

Default reaction: ----

Related parameters: ----

Further steps:

510

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Force Emergency Stop

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Emergency Stop"

Default reaction: 1'299 23111 ForceEmergencyStop ----

Related parameters: ----

Further steps: ---Force Trip 1

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Trip"

Default reaction: 1'300 23200 ForceTrip1 ----

Related parameters: ----

Further steps: ----

511

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Force Trip 2

Description

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "conditional Trip"

Default reaction: 1'301 23201 ForceTrip2 ----

Related parameters: ----

Further steps: ---Force Startup Inhibit

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Startup Inhibit"

Default reaction: 1'302 23202 ForceStartupInhibit ----

Related parameters: ----

Further steps: ---Force Redundancy Fault

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Redundancy Fault" 1'303 23203 ForceRedundancyFault Default reaction: ----

Related parameters:

512

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: ----

Force Alarm

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Alarm"

Default reaction: 1'304 23204 ForceAlarm ----

Related parameters: ----

Further steps: ---Force CCI1 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI1 Trip"

Default reaction: 1'305 23205 ForceCCI1Trip ----

Related parameters: ----

Further steps: ----

513

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Force CCI2 Trip

Description

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI2 Trip"

Default reaction: 1'306 23206 ForceCCI2Trip ----

Related parameters: ----

Further steps: ---Force CCI3 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI3 Trip"

Default reaction: 1'307 23207 ForceCCI3Trip ----

Related parameters: ----

Further steps: ---Force CCI4 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI4 Trip" 1'308 23300 ForceCCI4Trip Default reaction: ----

Related parameters:

514

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: ----

Force CCI5 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI5 Trip"

Default reaction: 1'309 23301 ForceCCI5Trip ----

Related parameters: ----

Further steps: ---Force CCI6 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI6 Trip"

Default reaction: 1'310 23302 ForceCCI6Trip ----

Related parameters: ----

Further steps: ----

515

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Force CCI7 Trip

Description

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI7 Trip"

Default reaction: 1'311 23303 ForceCCI7Trip ----

Related parameters: ----

Further steps: ---Force CCI8 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI8 Trip"

Default reaction: 1'312 23304 ForceCCI8Trip ----

Related parameters: ----

Further steps: ---Force CIO1 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO1 Trip" 1'313 23305 ForceCIO1Trip Default reaction: ----

Related parameters:

516

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: ----

Force CIO2 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO2 Trip"

Default reaction: 1'314 23306 ForceCIO2Trip ----

Related parameters: ----

Further steps: ---Force CIO3 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO3 Trip"

Default reaction: 1'315 23307 ForceCIO3Trip ----

Related parameters: ----

Further steps: ----

517

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Force CIO4 Trip

Description

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO4 Trip"

Default reaction: 1'316 23400 ForceCIO4Trip ----

Related parameters: ----

Further steps: ---Force CIO5 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO5 Trip"

Default reaction: 1'317 23401 ForceCIO5Trip ----

Related parameters: ----

Further steps: ---Force CIO6 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO6 Trip" 1'318 23402 ForceCIO6Trip Default reaction: ----

Related parameters:

518

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events

Description

Further steps: ----

Force CIO7 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO7Trip"

Default reaction: 1'319 23403 ForceCIO7Trip ----

Related parameters: ----

Further steps: ---Force CIO8 Trip

Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO8 Trip"

Default reaction: 1'320 23404 ForceCIO8Trip ----

Related parameters: ----

Further steps: ----

519

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Reset

Description

Possible reasons: - A Reset command was given to the Excitation System

Default reaction: 1'321 23405 Reset ----

Related parameters: ----

Further steps: ---AuxReady State

Possible reasons: - The Excitation System reached the "AuxReady" main state

Default reaction: 1'322 23406 AuxReady ----

Related parameters: ----

Further steps: ---AuxOn State

Possible reasons: - The Excitation System reached the "AuxOn" main state

1'323

23407

AuxOn

Default reaction: ----

Related parameters: ----

520

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name
----

Events
Further steps:

Description

Ready State

Possible reasons: - The Excitation System reached the "Ready" main state

Default reaction: 1'324 23408 Ready ----

Related parameters: ----

Further steps: ---Operation State

Possible reasons: - The Excitation System reached the "Operation" main State

Default reaction: 1'325 21186 Operation ----

Related parameters: ----

Further steps: ----

521

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Manual Control Active

Description

Possible reasons: - The Excitation System changed to "Manual" Mode

Default reaction: 1'326 23411 ManualControl ----

Related parameters: ----

Further steps: ---Channel Active

Possible reasons: - The Excitation System changed the control to "this Channel"

Default reaction: 1'327 21187 ChannelActive ----

Related parameters: ----

Further steps: ----

522

3BHS258033 E01 Rev. A

Unitrol 6800 Alarm and Event list

ABB
Nr ID Name

Events
Transient Recorder Trigger

Description

Possible reasons: - The Transient Recorder in the Excitation System was triggered either by a - Trip - Channel Fault - Auto Fault - Manual Fault or 1'328 23412 TRTrig - manually

Default reaction: ----

Related parameters: ----

Further steps: ---Channel Startup

Possible reasons: - The channel hardware was powered up

Default reaction: 1'329 23413 ChannelStartup ----

Related parameters: ----

Further steps: ---1'330 1'332 1'340 23414 23415 20173 ActUfMeasFlt Event6_27 Event3_09_CCI2

523

3BHS258033 E01 Rev. A