4-TERMINAL EARTH RESISTANCE TESTER AND SOIL RESISTIVITY TESTER

MANUAL

CAT.IV

The circuit from the service drop the service entrance, and to the power meter and primary overcurrent protection device(distribution panel) Primary electrical circuits of the equipment connected directly to the distribution panel, and feeders from the distribution panel to outlets. Instrument with double or reinforced insulation. User must refer to the explanations in the instruction manual.

CAT.III

Function

Range

Resolution

Measuring Range

Accuracy

3%rdg0.05W 2 W0.001 W 0.05~2.099 W Earth Resistance Re(Rg at r measurement) 20 W0.01 W 0.05~20.99 W 200 W 0.1 W 0.5~209.9 W 3%rdg5rdg 2000 W 1 W 5~2099 W 20k W 10 W 50~20.99K W 100 W 500~209.9K W 200k W 8% of Re+Rh+Rs 2W 20 W 0.3~395.6 W m 0.3~3956 W m

Auxiliary Earth Resistance Rh, Rs

200 W 0.3~39.56k W m 0.1 W m~ 1 W m Earth Resistivity r r = 2 x II x a x Rg Auto ranging 2000 W 0.3~395.6k W m 20k W 200k W
Series Interference Voltage Ust(A.C only)

0.3~1999k W m 2%rdg.2dgt (50~60Hz)

50V Autoranging

0.1V 0.5Hz

0~50.9Vrms 40Hz~500Hz

Frequency Fst

Rh,Rs limit Re<0.40 W 0.4 W R e<1.00W 1 . 0 0 W R e<2.00W 2 . 0 W R e

Accuracy 1k W 2k W 3.5k W

Accuracy

5%rdg1%fs

=Rex100+5k W (Rh,Rs<50k W )

Marks and Message BATT Batt Error Measuring...

Details Battery voltage is low. Replace the batteries.

This mark is being displayed during a measurment. Measuring range for the selected Range is exceeded. In case of Ust measurments, 50V or more is detedted. Failed to make successful mesurements Rk is exceeded the limit value;exceeding 2W at 2 Range and exceeding 9W at 20 or lower. Setting for Rk can be made at 20W or lower. Setting for Rk can be madeonly at 2w,3w,4w measurements. Ust is Regulated value or more. Rh and rs values exceed the allowable range. Correct results might not be obtained. No saved data exists. Memory is full. No more data can saved. A confirmation message before deleting the selected. A confirmation message before deleting all selected. All items have been deleted. Nxxx is a memory no.,and the left message saying 95 data have been stored.(Displayed at the Data Review Screen.) Indicating the measured result is saved with Memory NO. 003.

OL

--Rh>limit Range<=20 Only 2w/3w/4w Voltage Hight! Rh>limit Rs>limit No Saved data Memory Full Delete This Item? Delete All Item? Data Succed Delete NO03/095 No03

S005 Saved

The character S stands for Site. Selectable from 000 to 999. Data is successfully saved.

10

11

12

13

Red Yellow Green

CAT III 300V

ES

MENU TEST E NT E R S AV E ESC

Rx
Grounded Electrode to test auxiliary earth spikes 5~ 10m 5~ 10m

14

15

Red Yellow Green

ES
CAT III 300V

Black
S H

ES

MENU TEST E NT E R S AV E ESC

Rx
Grounded Electrode to test auxiliary earth spikes 5~ 10m 5~ 10m
CAT III 300V

Red Green

Secondary side Primary Side

ES

Supply Transfomer be sure to check grounded side of a commercial power supply

MENU TEST E NT E R S AV E ESC

Rx
Grounded Electrode to test

re

Where earth for mains supply is used

16

Green

Black

Yellow

Red

CAT III 300V

ES

MENU TEST E NT E R S AV E ESC