Technical Specifications
Features:
B-9201
Features and Benefits 1. 2. 3. 4. 5. 6. Re-settable (non-breaking glass) Additional volt free contact Electronically addressed Friendly installation and test Suitable for semi-flush and surface mount installation Stylish pleasing design
Protection rating: IP 30 Operating voltage: 24Vdc Loop voltage Operating current: Standby current 0.8mA Alarm Current 2mA Operating temperature: -10C to +50C N/O Output contact: 60Vdc, 0.1A Contact resistance: 100m Relative humidity: 95% Application: Indoor use Visual Indicator: LED, Red ( lit steady when alarm, 3 sec interval blinking at normal state) Material and colour: ABS, red Wiring: 1 pair non polarized Dimensions: 90x122x48.5mm
Description: Designed for the purpose of raising an alarm manually once verification of a fire or emergency condition has occurred. By pressing the non breakable glass. The I-9201 constructed of high impact red ABS and smooth shiny appearance on the surface. Stylish pleasing design and easy to install for modern building interior. Complete with terminating back box enables first fix installation and termination leaving the fascia with integral electronics to be simply plugged into pace at the time of commissioning. Non breakable glass that can be reset with the GST standard reset tool. The I-9201 operated via a micro-switch that when pressed a signal will be transmitted and the volt free contact will be latched. Contain integral LED indicator to denote operational mode. Electronic addressing can be done through Handheld Programming device (P-9910), purchased separately.
Mounting Base The manual call point should be installed in compliance with all local codes having a jurisdiction in your area or NFPA 72 National Fire Alarm Code, NFPA 70 National Electrical Code, BS 5389 and EN54. Surface mount and it is installed onto a standard one gang electrical box with a mounting hole that has 52mm~68mm spacing.
I9201
WALL
FIRE
MOUNTING BASE
SURFACE MOUNT
I9201 WALL
FIRE
10 11 12
K1 K2 Z1 Z2
LOOP IN
LOOP OUT
Programming The address of the manual call point can be programmed using GST handheld programmer (P-9910), purchased separately. Connect the two wires of the handheld programmer to Z1 and Z2 terminals of the manual call point (I-9102).
12 11 10
Z1 AND Z2 TERMINAL
MANUFACTURED IN ACCORDANCE WITH