MALLA DE PUESTA A TIERRA

SUBESTACIN DE ENERGA ELCTRICA


TRANSFORMADOR DE 630 KVA

HOSPITAL REGIONAL DEL BAJO CAUCA

MUNICIPIO DE CAUCASIA

10-02-2011
1
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

LISTA DE CONTENIDO
LISTA DE CONTENIDO .................................................................................................. 2
MALLA DE PUESTA A TIERRA HOSPITAL REGIONAL DEL BAJO CAUCA ............. 3
1.

OBJETIVO Y NATURALEZA DE LOS SISTEMAS DE TIERRA. ........................................ 3

2.

CONSTITUCIN Y DIMENSINAMIENTO DE UN SISTEMA DE TIERRA. .......................... 3

3.

CONFIGURACIN DEL SISTEMA DE TIERRAS. .............................................................. 4

3.1.
4.

SISTEMA DE TIERRAS PARA FUERZA..................................................................... 4

MEDICIONES DE RESISTIVIDAD. ..................................................................................... 5

4.1.
EL MODELO DE LAS DOS CAPAS. ............................................................................ 6
4.1.1.
RESULTADOS. ....................................................................................................... 6
5.

CARACTERSTICAS DEL SISTEMA ELCTRICO. ......................................................... 10

6.

DISEO DE LA MALLA DE PUESTA A TIERRA. ............................................................ 11

6.1.

DISTRIBUCIN DE CORRIENTES. ........................................................................... 11

7.

SELECCIN DEL CONDUCTOR DE LA MALLA. ............................................................ 13

8.

RESISTENCIA DE PUESTA A TIERRA............................................................................ 16

9.

CRITERIOS DE SEGURIDAD. .......................................................................................... 19

10.

TIEMPO DE DURACIN DE LA FALLA. ...................................................................... 19

11.

TENSIN SUPERFICIAL, TENSIN DE CONTACTO Y TENSIN DE PASO ............. 20

ANEXOS. ...................................................................................................................... 22
SIMULACIN 1......................................................................................................................... 22
GRFICOS. .............................................................................................................................. 37
GUIA PARA SOLDADURAS. ................................................................................................... 48
GUIA GRAFICA DE INSTALACIN. ........................................................................................ 50
CANTIDADES DE OBRA APROXIMADAS. ............................................................................. 51

2
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

MALLA DE PUESTA A TIERRA HOSPITAL REGIONAL DEL BAJO CAUCA


1. OBJETIVO Y NATURALEZA DE LOS SISTEMAS DE TIERRA.
Dos objetivos principales deben lograrse en el diseo de las mallas de tierra de las
subestaciones bajo condiciones normales y de fallas:
a. Proveer un medio para disipar las corrientes elctricas en la tierra sin exceder los lmites de
operacin de los equipos.
b. Debe asegurar que una persona en la vecindad de este sistema no est expuesto al peligro
de choque elctrico.
La correcta conexin a tierra de todo el sistema elctrico, es un factor de suma importancia para
la seguridad del personal y del equipo elctrico en s.
El propsito que se persigue con la existencia de los sistemas de tierra es:
a. Proteccin para el personal operativo, autorizado o no autorizado.
b. Proteccin a los equipos e instalaciones contra tensiones peligrosas.
c. Evitar que durante la circulacin de falla a tierra, se produzcan diferencias de potencial entre
distintos puntos de la instalacin, proporcionando para esto, un circuito de muy baja
impedancia para la circulacin de estas corrientes.
d. Apego a normas y reglamentos pblicos en vigor.
2. CONSTITUCIN Y DIMENSINAMIENTO DE UN SISTEMA DE TIERRA.
Para el dimensionado de la malla de tierra de la subestacin se tendrn en cuenta las
siguientes prescripciones:
a. El dimensionado de la instalacin de tierra es funcin de la intensidad que, en caso de fallo,
circula a travs de la parte afectada de la instalacin de tierra y del tiempo de duracin del
defecto.
b. El dimensionado de las instalaciones se har de forma que no se produzcan calentamientos
que puedan deteriorar sus caractersticas o aflojar elementos desmontables.
c. Los electrodos y dems elementos metlicos llevarn las protecciones precisas para evitar
corrosiones peligrosas durante la vida de la instalacin.
d. Se tendrn en cuenta las variaciones posibles de las caractersticas del suelo en pocas
secas y despus de haber sufrido corrientes de fallo elevadas.
Al proyectar una instalacin de puesta a tierra para una subestacin, se seguir el siguiente
procedimiento:

3
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

a. Investigacin de las caractersticas del suelo.


b. Determinacin de las corrientes mximas de puesta a tierra (monofsicas a tierra) y el
tiempo mximo correspondiente de eliminacin del defecto.
c. Diseo preliminar de la instalacin de tierra.
d. Clculo de la resistencia del sistema de puesta a tierra.
e. Clculo de las tensiones de paso en el exterior de la instalacin.
f.

Clculo de las tensiones de paso y contacto en el interior de la instalacin.

g. Comprobar que las tensiones de paso y contacto calculadas son inferiores a las tensiones
de paso y contacto admisibles.
h. Investigacin de las tensiones transferibles al exterior por tuberas, rieles, vallas,
conductores de neutro, blindaje de cables, circuitos de sealizacin y de los puntos
especialmente peligrosos, y estudio de formas de eliminacin o reduccin.
i.

Correccin y ajuste del diseo inicial estableciendo el definitivo.

Despus de construida la instalacin de tierra, se harn las comprobaciones y verificaciones


precisas en sitio, y se efectuarn los cambios necesarios que permitan alcanzar valores de
tensin aplicada inferiores o iguales a los mximos admitidos.
Una instalacin de puesta a tierra se compone esencialmente de electrodos, que son los
elementos que estn en ntimo contacto con el suelo (enterrados) y de conductores, utilizados
para enlazar a los electrodos entre si y a stos, con los gabinetes de los equipos y dems
instalaciones expuestas a corrientes nocivas, manteniendo al mismo tiempo, una superficie
equipotencial a su alrededor.

3. CONFIGURACIN DEL SISTEMA DE TIERRAS.


Para la correcta operacin del sistema elctrico, se construir un sistema de tierras:

Sistema de Tierras para Fuerza. Transformador de 630 kVA.

3.1.

SISTEMA DE TIERRAS PARA FUERZA.

Utilizado para conectar a tierra todos los elementos de la instalacin que en condiciones
normales de operacin no estn sujetos a tensiones, pero que pueden tener diferencia de
potencial con respecto a tierra a causa de fallas accidentales en los circuitos elctricos, as
como los puntos de la instalacin elctrica en los que es necesario establecer una conexin a
tierra para dar mayor seguridad, mejor funcionamiento y regularidad en la operacin y en fin,
todos los elementos sujetos a corrientes elctricas importantes de corto circuito y
sobretensiones en condiciones de falla.

4
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

4. MEDICIONES DE RESISTIVIDAD.
La medicin de la resistividad del terreno es la razn ms importante para los electricistas al
disear sistemas de puesta a tierra. La resistividad es un factor determinante en el valor de
resistencia a tierra que pueda tener un electrodo enterrado, puede determinar a que
profundidad debe ser enterrado el mismo para obtener un valor de resistencia bajo. La
resistividad puede variar ampliamente en terrenos que tengan las mismas caractersticas, su
valor cambia con las estaciones. La misma es determinada grandemente por el contenido de
electrolitos, el cual consiste de humedad, minerales y sales disueltas. Un suelo seco tiene un
alto valor de resistividad si no contiene sales solubles. La resistividad es tambin influenciada
por la temperatura.
El mtodo ms utilizado por los electricistas para realizar las mediciones es el de Wenner:
Para la medicin se disponen 4 electrodos en lnea recta y equidistantes una distancia "a",
simtricamente respecto al punto en el que se desea medir la resistividad del suelo, como se
muestra posteriormente, el equipo de medida es un telurmetro de cuatro terminales, los
electrodos externos son los de inyeccin de la corriente y los centrales los encargados de medir
la cada de potencial (en funcin de la resistencia).
Para realizar las medidas de resistividad se empleo el mtodo de Wenner, recomendado por la
norma ANSI/IEEE Std 81 IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and
Earth Surface potentials of a Ground System .
En el mtodo de Wenner los electrodos se disponen en lnea recta espaciados uniformemente y
la resistividad aparente del suelo a una profundidad dada es la resistividad medida para un
espaciamiento entre electrodos igual a dicha profundidad.
En la Figura 1 se muestra el esquema de conexin para los dos mtodos.

5
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

4.1.

EL MODELO DE LAS DOS CAPAS.

El diseo del sistema de puesta a tierra se realiza con base en el RETIE y luego se detalla,
utilizando para los clculos, un programa de computador basado en el mtodo de las dos capas
y la teora de las imgenes.
El mtodo de las dos capas consiste en la modelacin del suelo en dos capas de resistividad
uniforme con base en los valores de resistividad tomados en el terreno. Este modelo sirve para
estudiar el comportamiento del sistema de puesta a tierra frente a fallas originadas por
condiciones atmosfricas o en el sistema de potencia. En la Figura 2 se ilustra el modelo de las
capas.

Figura 2. Modelo de las dos capas del terreno


Donde:
1: Resistividad de la capa superior del terreno
2: Resistividad de la capa inferior del terreno

4.1.1. RESULTADOS.
Para las medidas a 1 m, 2 m, 4 m, 6 m y 8 m de profundidad se sigui el mtodo de Wenner. En
la Tabla 1 se muestra los valores de resistividad aparente.

6
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Tabla 1. Resistividad aparente calculada [


m]
PROFUNDIDAD [m]

RUTA

PROMEDIO

1022.00

1043.00

1032.50

14.85

764.00

753.00

758.50

7.78

415.00

398.00

406.50

12.02

254.30

236.70

245.50

12.45

166.40

155.90

161.15

7.42

DESVIACIN ESTANDAR

520.83

Figura 3. Resistividad aparente calculada [


m]

7
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

8
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

A partir de los datos de resistividad, se obtuvo un modelo del terreno de dos capas con los
resultados indicados en la Tabla 2.

9
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Tabla 2. Resultados modelo de las capas del terreno


Resistividad [
m]
Capa superior (
1)
1023.62

Capa inferior
(
2)
123.25

Profundidad capa
superior [m]

Coeficiente de
reflexin

2.17

-0.78

5. CARACTERSTICAS DEL SISTEMA ELCTRICO.


La red primaria que alimenta la subestacin, proviene del circuito R25-04 de la subestacin del
O.R local. De acuerdo con la informacin suministrada por el operador de red, se tiene la
siguiente informacin tcnica en el punto de conexin de la subestacin.
La informacin tcnica del transformador de distribucin que se instalara en la subestacin
elctrica se indica en la tabla 3.
Tabla 3. Caractersticas nominales del transformador
Potencia [kVA]
630

Tensin primaria [kV]


13.2

Tensin secundaria [V]


208/120

10
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

6. DISEO DE LA MALLA DE PUESTA A TIERRA.


El diseo de la malla de puesta a tierra contempla la verificacin de la distribucin de
corrientes a tierra, la seleccin del conductor, el clculo de la resistencia de puesta a
tierra y el anlisis de las tensiones de contacto y de paso, producidas durante fallas a
tierra.
El piso de concreto que cubre la zona donde se colocar la malla de puesta a tierra, se
simul como una capa de triturado de 20 cm de espesor y con una resistividad de 2500
*m.
Los niveles de corto circuito en el punto de conexin del circuito (R25-04) del proyecto
HOSPITAL REGIONAL DEL BAJO CAUCA, proporcionado por Empresas Pblicas de
Medelln son los siguientes:

Corriente de falla trifsica simtrica: 1.24 kA.


Corriente de falla monofsica simtrica: 0.95 kA.
Corriente de falla trifsica asimtrica: 1.92 kA.
Corriente de falla monofsica asimtrica: 1.40 kA
Relacin X/R trifsica: 1.18
Relacin X/R monofsica: 0.80

La informacin sobre el calibre y la longitud de los conductores del circuito (R25-04)


hasta el punto de conexin, suministrada por EEPPM fue la siguiente:
Tipo de cable:

km:

18.920
0.077
0.634
0.887
0.333
0.000

350 kCM, XLPE, 15kV, 133% Aislamiento


266.8 AWG, ACSR
4/0 AWG, ACSR
1/0 AWG, ACSR
2 AWG, ACSR
4 AWG, ACSR

6.1.

DISTRIBUCIN DE CORRIENTES.

En la figura 4 con la informacin suministrada por el O.R local y de acuerdo a la configuracin


de la red de distribucin, se simul mediante el programa ATP una falla monofsica a tierra
utilizando los valores pico entregados por el O.R local, presentando una inyeccin de corriente
por la malla de 220.65 A(pico) 156 A(rms) y un retorno por neutro de 729.35 A (pico) 515.6
A(rms) ambas en estado estable.

11
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 4. Sistema modelado para hallar la corriente por las mallas


En la Figura 5 se ilustra el grfico con los resultados de la simulacin de distribucin de
corrientes a tierra.

12
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 5. Resultados de la simulacin de distribucin de corrientes a tierra


La corriente de diseo de la malla de puesta a tierra es de 156 A(rms) y fue calculada siguiendo
las directrices de la norma IEEE80-2000.

7. SELECCIN DEL CONDUCTOR DE LA MALLA.


Teniendo en cuenta que las protecciones acten en un tiempo inferior a 200 ms, tal como lo
estima la norma ANSI/IEEE Std. 242 IEEE Recommended Practice for Protection and
Coordination of Industrial and Commercial Power Systems y dado que la distribucin de la
corriente por la malla se efecta por las retculas; El cableado de la malla debe realizarse en
cable 4/0 AWG Cu desnudo (seccin mnima), este se selecciono de la siguiente expresin
siguiendo las directrices de la norma ANSI/IEEE 80.

13
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

De donde:
Amm2 : Seccin del conductor en mm2
I : Corriente de falla a tierra, suministrada por el OR (rms en kA)
Kf : Constante del material empleado ( =7 para el cobre)
Tc : tiempo de despeje de la falla a tierra en segundos.
Se concluye, Para una corriente de cortocircuito mxima (corriente de falla trifsica asimtrica)
de 1.92 kA, de acuerdo a los niveles de corto circuito entregados por el operador de red, con
uniones en soldadura exotrmica y un tiempo de despeje de la falla de 0.5s, el rea calculada
es de 4,81 mm2.
Donde se concluye que el rea del cable recomendado para la malla de puesta a tierra en la
subestacin es de 67.40 mm2, que corresponde a un No. 2/0 AWG, que es el calibre mnimo
para mallas de puesta a tierra segn recomendaciones de la norma IEEE 80, para obtener el
valor de la resistencia de puesta a tierra buscado por debajo de 10.
Se debe colocar la malla a una profundidad de 50 cm, medidos a partir de la superficie del suelo
(tierra fsica).
Para la conexin a tierra de los equipos, celdas, gabinetes y estructuras de la edificacin, es
necesario emplear una cola en cable de cobre No. 2/0 AWG con borne terminal.
Adems de los transformadores, se debe conectar a tierra el neutro de la acometida primaria, y
los gabinetes, al igual que todo equipo elctrico o metlico en el cuarto de la subestacin. Los
equipos de la subestacin por ningn motivo pueden quedar por fuera de la malla de puesta a
tierra.
Se debe construir mnimo una caja de inspeccin de 30x30 cm libres, para efectos de medida e
inspeccin de la malla de la subestacin.
Todas las uniones de la malla se deben realizar con soldadura exotrmica (mirar anexo).
Algunas medidas realizadas sobre lozas de concreto (teniendo en cuenta el hierro de la
estructura) y estando secas, nos mostraron valores superiores a 50 k; este valor sumado a la
resistencia de contacto de los pies y del calzado, permite aumentar las tensiones de paso y de
toque permisibles en el rea de la subestacin, debido a la alta resistividad del concreto seco
(entre 106 y 109 W*m).

14
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Teniendo en cuenta todo lo anterior, la corriente que circulara por el cuerpo de una persona
descalza y con los pies secos en el cuarto de la subestacin sera de 35 mA(rms) durante 500
ms (bajo una eventual condicin de falla), valor que est en la zona segura de las grficas
mostradas en la norma IEC 479-1. Adems la corriente mxima sin riesgo de fibrilacin
ventricular que permite la norma IEEE80-2000 para personas de 50 kg es de 164 mA(rms)
durante 500 ms.
La corriente mxima sin riesgo de fibrilacin ventricular se calcula como:

Con:
k=0.116 para peso humano de 50 kg
k=0.157 para peso humano de 70 kg
Y donde:
ts: Duracin de la corriente [s]
If: Corriente mxima sin riesgo de fibrilacin ventricular.
La tensin de contacto permisible es 712.50 voltios y se calcula como:

Siendo RC la resistencia del cuerpo; Rp la resistencia de contacto o de puesta a tierra de un pie;


Rmp la resistencia mutua entre los pies.
La tensin de paso permisible es 2357.87 voltios y se calcula como:

Para el clculo de la resistencia de contacto de los pies, se consideran stos como discos
metlicos de radio Rp, separados una distancia d, colocados en la superficie del suelo.
Asumiendo resistividad uniforme r para el suelo, lo que incluso sera vlido en un suelo de dos
capas, considerando entonces slo la capa superior ya que para las dimensiones del pie es
suficiente considerar esta capa, se tiene:

15
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Las tensiones de contacto son inferiores al GPR (1490.06V) de la malla de puesta a tierra y Las
tensiones de paso permisibles para la zona de la subestacin son superiores al GPR
(1490.06V) de la malla de puesta a tierra (mirar simulacin), y se demuestra que se cumplen
con las condiciones de seguridad en cuanto a tensiones de contacto y de paso se refiere.

8. RESISTENCIA DE PUESTA A TIERRA.


Este sistema de puesta a tierra propuesto contempla la instalacin de una malla en cable de
cobre embebida en el piso de concreto del rea de la subestacin, consta de una serie de
electrodos 15, de 5/8 x 2.40 m, enlazados entre s, formando un rectangulo de 16 x 7 metros y
unido por la mitad en ambas direcciones; Todo con cable 2/0 AWG Cu desnudo.
Adems de los transformadores, se debe conectar a tierra el neutro de la acometida primaria, y
los gabinetes, al igual que todo equipo elctrico o metlico en el cuarto de la subestacin y/o
malla eslabonada exterior.
Para determinar la resistencia de puesta a tierra de la malla, se utiliz el programa de
computador, los distintos mtodos, hiptesis y teoras en que se fundamentan los clculos de
esta aplicacin son:
a. La ecuacin fundamental en el clculo del sistema de puesta a tierra es la ecuacin de
Laplace, que establece que en determinadas condiciones el laplaciano del potencial
elctrico es nulo.
b. Expondremos mtodos fsicos, como el de Wenner, para medir la resistividad de un terreno
y fundamentaremos el clculo de potenciales debidos al flujo de corriente por un conductor
cilndrico en suelos uniformes o de dos capas.
c. Tambin se desarrollarn los mtodos numricos utilizados para el clculo de los
parmetros de un modelo de dos capas (Marquardt-Levenberg), resolucin de sistemas de
ecuaciones de grandes dimensiones (gradiente biconjugado) e interpolacin para ajuste de
perfiles de corriente o tensin (Spline).
d. El clculo del sistema de puesta a tierra se basa en una serie de hiptesis fundamentales de
partida y en la segmentacin de los conductores que forman el sistema.
El mtodo aqu expuesto es vlido nicamente para electrodos de puesta a tierra formados por
conductores cilndricos orientados en el espacio en cualquier direccin (paralelos,
perpendiculares o inclinados con respecto a la superficie del terreno), es decir, no es vlido por
ejemplo para electrodos hemisfricos, placas macizas, anillos circulares, etc., aunque algunos
de estos se pueden simular con conductores cilndricos.
En la Tabla 4 se muestran los datos de entrada al programa.

16
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Se debe construir mnimo una caja tipo distribucin de 30x30cm libres, para efectos de medida
e inspeccin de la malla de la subestacin.
La malla de puesta a tierra construida, se debe someter a revisin por parte del interventor del
O.R local, o el inspector RETIE, antes de cubrirla, para verificar su tamao y profundidad de
enterramiento, se debe tambin medir su resistencia (sin tenerla unida con el neutro del
sistema) despus de cubierta y posteriormente ponerla en servicio.
Tabla 4. Datos de entrada del programa
Magnitud
Resistividad capa superior del suelo [
m]
Resistividad capa inferior del suelo [
m]
Resistividad de la capa de cascajo o
concreto [
m]
Espesor de la capa de cascajo o concreto [m]
Profundidad de la primera capa [m]
Profundidad de enterramiento de la malla [m]
GPR [V]
Tiempo de aclaracin de la falla [s]
Radio del conductor [cm]
Nmero de varillas [Un]
Radio de la varilla [cm]
Longitud de la varilla [m]

Valor
Malla Enterrada
1023.62
123.25
2.500
0.2
2.17
0.5
1490.06
0.5
0.525
15
0.7937
2,4

17
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

18
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

La resistencia del sistema de puesta a tierra determinada con el programa, es de 9.55, cuyo
valor se considera adecuado y cumple con las recomendaciones del RETIE.

9. CRITERIOS DE SEGURIDAD.
Los principales criterios de seguridad en el diseo de una malla de puesta a tierra corresponden
a la limitacin de los potenciales de contacto y potenciales de paso.
El programa de computador permite obtener las tensiones superficiales, tensiones de contacto y
tensiones de paso para un perfil seleccionado.

10. TIEMPO DE DURACIN DE LA FALLA.


La mayor parte de las fallas de un sistema de potencia son aclaradas entre 30 ms y 200 ms,
dependiendo del tiempo de operacin y de la coordinacin establecida para la operacin de las
protecciones. Con el propsito de ser conservativos para la verificacin de las tensiones de

19
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

contacto y de paso al interior de la malla, se asumi un tiempo de despeje de 500 ms, como lo
recomienda la norma ANSI/IEEE Std. 80 IEEE Guide for Safety in A.C. Substation Grounding.

11. TENSIN SUPERFICIAL, TENSIN DE CONTACTO Y TENSIN DE PASO


Para el control de las tensiones de contacto y de paso se consider un G.P.R. en la malla
puesta a tierra con un valor de 1490.06V.
Se analizo el perfil en la malla embebida en el cuarto de la subestacin, tal como se indica en la
Figura 6 y 7.

Figura 6. Perfil de tensin evaluado en la malla embebida.

20
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 7. Perfil de tensin evaluado en la malla embebida.


Del anlisis del perfil se concluye que las tensiones de contacto y de paso han sido controladas
en el interior del cuarto de la subestacin y el rea de la puerta.
Ver resultados anexos, simulaciones y grficos.

21
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

ANEXOS.
SIMULACIN 1.

Informe de resultados del sistema de puesta a tierra


Proyecto
Configuracin

MALLA DE PUESTA A TIERRA HOSPITAL REGIONAL DEL BAJO CAUCA


MALLA DE 16 X 7 METROS - 2/0

Caractersticas del terreno


Modelo de terreno
Resistividad de modelo uniforme
Resistividad de la capa superior
Resistividad de la capa inferior
Espesor de la capa superior
Factor de reflexin

DOS CAPAS
1023.62923374522 Ohmios-metro
123.256877704494 Ohmios-metro
2.17302953554178 metros
-0.785058208528322

Configuracin geomtrica
Clave
Nmero de conductores horizontales
Nmero de conductores verticales
Nmero de conductores inclinados
Longitud total del electrodo activo
Longitud total del electrodo pasivo

M8H15V (MALLA RETICULADA)


8
15
0
119.000 metros
0.000 metros

------------------------------------------------------------------------------------------------------------------------------| N/T/H |
X (metros)
|
Y (metros)
|
Z (metros)
|
Radio
|
Longitud
|
ngulo ()
|
|
|
Inicial
Final
|
Inicial
Final
|
Inicial
Final
| (centmetros) |
(metros)
|
X
Z
------------------------------------------------------------------------------------------------------------------------------|
1/A/S |
-8.0000
8.0000 |
-3.5000
-3.5000 |
0.5000
0.5000 |
0.5250
|
16.0000 |
0.00
------------------------------------------------------------------------------------------------------------------------------|
2/A/S |
-8.0000
8.0000 |
0.0000
0.0000 |
0.5000
0.5000 |
0.5250
|
16.0000 |
0.00
------------------------------------------------------------------------------------------------------------------------------|
3/A/S |
-8.0000
8.0000 |
3.5000
3.5000 |
0.5000
0.5000 |
0.5250
|
16.0000 |
0.00
------------------------------------------------------------------------------------------------------------------------------|
4/A/S |
-8.0000
-8.0000 |
-3.5000
3.5000 |
0.5000
0.5000 |
0.5250
|
7.0000 |
90.00
------------------------------------------------------------------------------------------------------------------------------|
5/A/S |
-4.0000
-4.0000 |
-3.5000
3.5000 |
0.5000
0.5000 |
0.5250
|
7.0000 |
90.00
------------------------------------------------------------------------------------------------------------------------------|
6/A/S |
0.0000
0.0000 |
-3.5000
3.5000 |
0.5000
0.5000 |
0.5250
|
7.0000 |
90.00
------------------------------------------------------------------------------------------------------------------------------|
7/A/S |
4.0000
4.0000 |
-3.5000
3.5000 |
0.5000
0.5000 |
0.5250
|
7.0000 |
90.00
------------------------------------------------------------------------------------------------------------------------------|
8/A/S |
8.0000
8.0000 |
-3.5000
3.5000 |
0.5000
0.5000 |
0.5250
|
7.0000 |
90.00
------------------------------------------------------------------------------------------------------------------------------|
9/A/S |
-8.0000
-8.0000 |
-3.5000
-3.5000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 10/A/S |
-4.0000
-4.0000 |
-3.5000
-3.5000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 11/A/S |
0.0000
0.0000 |
-3.5000
-3.5000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 12/A/S |
4.0000
4.0000 |
-3.5000
-3.5000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 13/A/S |
8.0000
8.0000 |
-3.5000
-3.5000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 14/A/S |
-8.0000
-8.0000 |
0.0000
0.0000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 15/A/S |
-4.0000
-4.0000 |
0.0000
0.0000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 16/A/S |
0.0000
0.0000 |
0.0000
0.0000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 17/A/S |
4.0000
4.0000 |
0.0000
0.0000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 18/A/S |
8.0000
8.0000 |
0.0000
0.0000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 19/A/S |
-8.0000
-8.0000 |
3.5000
3.5000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 20/A/S |
-4.0000
-4.0000 |
3.5000
3.5000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 21/A/S |
0.0000
0.0000 |
3.5000
3.5000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 22/A/S |
4.0000
4.0000 |
3.5000
3.5000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
------------------------------------------------------------------------------------------------------------------------------| 23/A/S |
8.0000
8.0000 |
3.5000
3.5000 |
0.3000
2.7000 |
0.7370
|
2.4000 |
90.00
-------------------------------------------------------------------------------------------------------------------------------

22
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Segmentacin
Tipo de segmentacin
CONDUCTOR
Nmero total de segmentos
Segmentos por conductor horizontal
EJE Y
Segmentos por conductor vertical
Segmentos por conductor inclinado

SEGMENTOS DE LA MISMA LONGITUD EN CADA


52
4 EN PARALELOS AL EJE X / 2 EN PARALELOS AL
1
0

Magnitudes del sistema


Intensidad a disipar
Sobretensin de tierra en el electrodo
electrodo pasivo
Resistencia de puesta a tierra

156.00000 Amperios
1,490.06488 Voltios (activo) / No hay
9.5516980 Ohmios

Seguridad
Mtodo de clculo de tensiones mximas
Tiempo de despeje de la falta
Capa superficial de alta resistividad
Resistividad de la capa superficial
Espesor de la capa superficial
Peso estimado para clculo de tensiones
Factor de correccin
Mxima tensin de paso admisible
SOBRETENSIN DE TIERRA)
Mxima tensin de contacto admisible
DE TIERRA)

IEEE STD 80-2000


0.5 segundos
S
2500 Ohmios-metro
20 centmetros
50 kilogramos
0.89153194370373
2,357.87 Voltios (158.24% DE LA
712.50 Voltios (47.82% DE LA SOBRETENSIN

Informe de resultados del modelo de dos capas


Medidas de resistividad
--------------------------------------------------| N/H |
Espaciado
|
Resistividad
|
|
|
(metros)
|
(Ohmios-metro)
|
--------------------------------------------------|
1/S |
1.0000
|
1032.5000
|
|
2/S |
2.0000
|
758.5000
|
|
3/S |
4.0000
|
406.5000
|
|
4/S |
6.0000
|
245.5000
|
|
5/S |
8.0000
|
161.1500
|
---------------------------------------------------

Valores iniciales
Resistividad de la capa superior
Anchura de la capa superior
Resistividad de la capa inferior
Factor de reflexin

1200 Ohmios-metro
2 metros
150 Ohmios-metro
-0.777777777777778

Resultados del modelo


Resistividad de la capa superior
Anchura de la capa superior
Resistividad de la capa inferior
Factor de reflexin

1023.62923374522 Ohmios-metro
2.17302953554178 metros
123.256877704494 Ohmios-metro
-0.785058208528322

------------------------------------------------------------------------------------------------------------------------

23
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

| N |
Espaciado
|
Resistividad medida
|
Resistividad calculada
|
Diferencia
|
Diferencia
|
|
|
(metros)
|
(Ohmios-metro)
|
(Ohmios-metro)
| (Ohmios-metro) |
(%)
|
-----------------------------------------------------------------------------------------------------------------------|
1 |
1.0000
|
1032.5000
|
979.2282
|
53.27182
|
5.15950
|
|
2 |
2.0000
|
758.5000
|
799.2262
|
-40.72616
|
-5.36930
|
|
3 |
4.0000
|
406.5000
|
413.2493
|
-6.74927
|
-1.66034
|
|
4 |
6.0000
|
245.5000
|
231.3349
|
14.16515
|
5.76992
|
|
5 |
8.0000
|
161.1500
|
165.8179
|
-4.66786
|
-2.89659
|
-----------------------------------------------------------------------------------------------------------------------Error cuadrtico medio = 30.8690777686309 (4.4696471450006%)

24
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Tabla 5. Segmentacin.
SEGMENTACIN
INDICE
GLOBAL

ELECTRODO

HABILITADO

ORIENTACION

SEGMENTO

X
INICIAL
(m)

Y
INICIAL
(m)

Z
INICIAL
(m)

X
FINAL
(m)

Y
FINAL
(m)

Z
FINAL
(m)

RADIO
(m)

Activo

Horizontal

-8

-3.5

0.5

-4

-3.5

0.5

0.525

Activo

Horizontal

-4

-3.5

0.5

-3.5

0.5

0.525

2.3646202

0.591155

Activo

Horizontal

-3.5

0.5

-3.5

0.5

0.525

2.3646202

0.591155

Activo

Horizontal

-3.5

0.5

-3.5

0.5

0.525

2.5625612

0.6406403

Activo

Horizontal

-8

0.5

-4

0.5

0.525

2.0172801

0.50432

Activo

Horizontal

-4

0.5

0.5

0.525

1.8275113

0.4568778

Activo

Horizontal

0.5

0.5

0.525

1.8275113

0.4568778

Activo

Horizontal

0.5

0.5

0.525

2.0172801

0.50432

Activo

Horizontal

-8

3.5

0.5

-4

3.5

0.5

0.525

2.5625612

0.6406403

Activo

Horizontal

-4

3.5

0.5

3.5

0.5

0.525

2.3646202

0.591155

Activo

Horizontal

3.5

0.5

3.5

0.5

0.525

2.3646202

0.591155

Activo

Horizontal

3.5

0.5

3.5

0.5

0.525

2.5625612

0.6406403

Activo

Horizontal

-8

-3.5

0.5

-8

0.5

0.525

3.5

90

2.2715482

0.6490138

Activo

Horizontal

-8

0.5

-8

3.5

0.5

0.525

3.5

90

2.2715482

0.6490138

Activo

Horizontal

-4

-3.5

0.5

-4

0.5

0.525

3.5

90

1.7396707

0.4970488

Activo

Horizontal

-4

0.5

-4

3.5

0.5

0.525

3.5

90

1.7396707

0.4970488

Activo

Horizontal

-3.5

0.5

0.5

0.525

3.5

90

1.7012731

0.486078

Activo

Horizontal

0.5

3.5

0.5

0.525

3.5

90

1.7012731

0.486078

Activo

Horizontal

-3.5

0.5

0.5

0.525

3.5

90

1.7396707

0.4970488

Activo

Horizontal

0.5

3.5

0.5

0.525

3.5

90

1.7396707

0.4970488

Activo

Horizontal

-3.5

0.5

0.5

0.525

3.5

90

2.2715482

0.6490138

Activo

Horizontal

0.5

3.5

0.5

0.525

3.5

90

2.2715482

0.6490138

Activo

Vertical

-8

-3.5

0.3

-8

-3.5

2.173

0.737

1.87303

90

1.8418952

0.9833776

LONGITUD ANGULO
(m)
EJE X ()
4

ANGULO
EJE Z ()

INTENSIDAD
(A)

DENSIDAD
(A/m)

2.5625612

0.6406403

Activo

Vertical

-8

-3.5

2.17303

-8

-3.5

2.7

0.737

0.52697

90

6.1181753

11.6100916

10

Activo

Vertical

-4

-3.5

0.3

-4

-3.5

2.173

0.737

1.87303

90

1.5597849

0.8327604

10

Activo

Vertical

-4

-3.5

2.17303

-4

-3.5

2.7

0.737

0.52697

90

5.6420801

10.7066344

11

Activo

Vertical

-3.5

0.3

-3.5

2.173

0.737

1.87303

90

1.5302272

0.8169798

11

Activo

Vertical

-3.5

2.17303

-3.5

2.7

0.737

0.52697

90

5.537775

10.508701

12

Activo

Vertical

-3.5

0.3

-3.5

2.173

0.737

1.87303

90

1.5597849

0.8327604

12

Activo

Vertical

-3.5

2.17303

-3.5

2.7

0.737

0.52697

90

5.6420801

10.7066344

13

Activo

Vertical

-3.5

0.3

-3.5

2.173

0.737

1.87303

90

1.8418952

0.9833776

13

Activo

Vertical

-3.5

2.17303

-3.5

2.7

0.737

0.52697

90

6.1181753

11.6100916

14

Activo

Vertical

-8

0.3

-8

2.173

0.737

1.87303

90

1.5920084

0.8499644

14

Activo

Vertical

-8

2.17303

-8

2.7

0.737

0.52697

90

5.8065174

11.0186771

15

Activo

Vertical

-4

0.3

-4

2.173

0.737

1.87303

90

1.304434

0.69643

25
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

15

Activo

Vertical

-4

2.17303

-4

2.7

0.737

0.52697

90

5.2675828

9.9959734

16

Activo

Vertical

0.3

2.173

0.737

1.87303

90

1.2752416

0.6808444

16

Activo

Vertical

2.17303

2.7

0.737

0.52697

90

5.1541964

9.780807

17

Activo

Vertical

0.3

2.173

0.737

1.87303

90

1.304434

0.69643

17

Activo

Vertical

2.17303

2.7

0.737

0.52697

90

5.2675828

9.9959734

18

Activo

Vertical

0.3

2.173

0.737

1.87303

90

1.5920084

0.8499644

18

Activo

Vertical

2.17303

2.7

0.737

0.52697

90

5.8065174

11.0186771

19

Activo

Vertical

-8

3.5

0.3

-8

3.5

2.173

0.737

1.87303

90

1.8418952

0.9833776

19

Activo

Vertical

-8

3.5

2.17303

-8

3.5

2.7

0.737

0.52697

90

6.1181753

11.6100916

20

Activo

Vertical

-4

3.5

0.3

-4

3.5

2.173

0.737

1.87303

90

1.5597849

0.8327604

20

Activo

Vertical

-4

3.5

2.17303

-4

3.5

2.7

0.737

0.52697

90

5.6420801

10.7066344

21

Activo

Vertical

3.5

0.3

3.5

2.173

0.737

1.87303

90

1.5302272

0.8169798

21

Activo

Vertical

3.5

2.17303

3.5

2.7

0.737

0.52697

90

5.537775

10.508701

22

Activo

Vertical

3.5

0.3

3.5

2.173

0.737

1.87303

90

1.5597849

0.8327604

22

Activo

Vertical

3.5

2.17303

3.5

2.7

0.737

0.52697

90

5.6420801

10.7066344

23

Activo

Vertical

3.5

0.3

3.5

2.173

0.737

1.87303

90

1.8418952

0.9833776

23

Activo

Vertical

3.5

2.17303

3.5

2.7

0.737

0.52697

90

6.1181753

11.6100916

26
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Tabla 6. Potencial, intensidad y densidad de corriente en los conductores.


POTENCIAL, INTENSIDAD Y DENSIDAD DE CORRIENTE EN LOS CONDUCTORES
CONDUCTOR

ELECTRODO

ORIENTACION

SEGMENTO

INICIO SEGMENTO(m)

Horizontal

-8

-3.5

0.5

-4

-3.5

0.5

1490.06485

2.562561198

0.640640299

Horizontal

-4

-3.5

0.5

-3.5

0.5

1490.064914

2.364620179

0.591155045

Horizontal

-3.5

0.5

4.00E+00

-3.5

0.5

10

1490.064914

2.364620179

0.591155045

Horizontal

-3.5

0.5

-3.5

0.5

14

1490.06485

2.562561198

0.640640299

Horizontal

-8

0.5

-4

0.5

1490.064891

2.01728011

0.504320028

Horizontal

-4

0.5

0.5

1490.064873

1.827511327

0.456877832

Horizontal

0.5

0.5

10

1490.064873

1.827511327

0.456877832

Horizontal

0.5

0.5

14

1490.064891

2.01728011

0.504320028

Horizontal

-8

3.5

0.5

-4.00E+00

3.5

0.5

1490.06485

2.562561198

0.640640299

Horizontal

-4.00E+00

3.5

0.5

0.00E+00

3.5

0.5

1490.064914

2.364620179

0.591155045

Horizontal

3.5

0.5

3.5

0.5

10

1490.064914

2.364620179

0.591155045

Horizontal

3.5

0.5

3.5

0.5

14

1490.06485

2.562561198

0.640640299

Horizontal

-8

-3.5

0.5

-8

0.5

1.75

1490.064887

2.271548176

0.649013765

Horizontal

-8

0.5

-8

3.5

0.5

5.25

1490.064887

2.271548176

0.649013765

Horizontal

-4

-3.5

0.5

-4.00E+00

0.5

1.75

1490.064889

1.739670656

0.497048759

Horizontal

-4.00E+00

0.5

-4.00E+00

3.5

0.5

5.25

1490.064889

1.739670656

0.497048759

Horizontal

-3.5

0.5

5.65E-15

0.5

1.75

1490.064859

1.701273085

0.486078024

Horizontal

5.65E-15

0.5

1.13E-14

3.5

0.5

5.25

1490.064859

1.701273085

0.486078024

Horizontal

-3.5

0.5

0.5

1.75

1490.064889

1.739670656

0.497048759

Horizontal

0.5

3.5

0.5

5.25

1490.064889

1.739670656

0.497048759

Horizontal

-3.5

0.5

8.00E+00

0.5

1.75

1490.064887

2.271548176

0.649013765

Horizontal

8.00E+00

0.5

8.00E+00

3.5

0.5

5.25

1490.064887

2.271548176

0.649013765

Vertical

-8

-3.5

0.3

-8

-3.5

2.17303

0.936514768

1490.064884

1.841895237

0.983377572

Vertical

-8

-3.5 2.17303

-8

-3.5

2.7

2.136514768

1490.064893

6.118175341

11.61009156

10

Vertical

-4

-3.5

-4

-3.5

2.17303

0.936514768

1490.06488

1.559784915

0.832760448

10

Vertical

-4

-3.5 2.17303

-4

-3.5

2.7

2.136514768

1490.064876

5.642080116

10.70663443

11

Vertical

-3.5

-3.5

2.17303

0.936514768

1490.064883

1.530227226

0.816979763

11

Vertical

-3.5 2.17303

-3.5

2.7

2.136514768

1490.06487

5.53777504

10.50870099

12

Vertical

-3.5

-3.5

2.17303

0.936514768

1490.06488

1.559784915

0.832760448

12

Vertical

-3.5 2.17303

-3.5

2.7

2.136514768

1490.064876

5.642080116

10.70663443

13

Vertical

-3.5

-3.5

2.17303

0.936514768

1490.064884

1.841895237

0.983377572

13

Vertical

-3.5 2.17303

-3.5

2.7

2.136514768

1490.064893

6.118175341

11.61009156

14

Vertical

-8

0.3

-8

2.17303

0.936514768

1490.064882

1.592008383

0.849964378

14

Vertical

-8

2.17303

-8

2.7

2.136514768

1490.064863

5.806517401

11.01867712

15

Vertical

-4

0.3

-4

2.17303

0.936514768

1490.064881

1.304434008

0.696430026

15

Vertical

-4

2.17303

-4

2.7

2.136514768

1490.064905

5.267582761

9.99597343

0.3

0.3

0.3

0.3

FIN SEGMENTO (m)

DISTANCIA (m)

POTENCIA (V) INTENSIDAD (A)

27
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

DENSIDAD (A/m)

16

Vertical

0.3

2.17303

0.936514768

1490.064884

1.275241617

0.680844372

16

Vertical

2.17303

2.7

2.136514768

1490.064883

5.154196424

9.780807032

17

Vertical

0.3

2.17303

0.936514768

1490.064881

1.304434008

0.696430026

17

Vertical

2.17303

2.7

2.136514768

1490.064905

5.267582761

9.99597343

18

Vertical

0.3

2.17303

0.936514768

1490.064882

1.592008383

0.849964378

18

Vertical

2.17303

2.7

2.136514768

1490.064863

5.806517401

11.01867712

19

Vertical

-8

3.5

0.3

-8

3.5

2.17303

0.936514768

1490.064884

1.841895237

0.983377572

19

Vertical

-8

3.5

2.17303

-8

3.5

2.7

2.136514768

1490.064893

6.118175341

11.61009156

20

Vertical

-4

3.5

0.3

-4

3.5

2.17303

0.936514768

1490.06488

1.559784915

0.832760448

20

Vertical

-4

3.5

2.17303

-4

3.5

2.7

2.136514768

1490.064876

5.642080116

10.70663443

21

Vertical

3.5

0.3

3.5

2.17303

0.936514768

1490.064883

1.530227226

0.816979763

21

Vertical

3.5

2.17303

3.5

2.7

2.136514768

1490.06487

5.53777504

10.50870099

22

Vertical

3.5

0.3

3.5

2.17303

0.936514768

1490.06488

1.559784915

0.832760448

22

Vertical

3.5

2.17303

3.5

2.7

2.136514768

1490.064876

5.642080116

10.70663443

23

Vertical

3.5

0.3

3.5

2.17303

0.936514768

1490.064884

1.841895237

0.983377572

23

Vertical

3.5

2.17303

3.5

2.7

2.136514768

1490.064893

6.118175341

11.61009156

28
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Tabla 7. Potencial y tensin de contacto y paso en los puntos de la malla.


POTENCIAL Y TENSION DE CONTACTO Y PASO EN LOS PUNTOS DE LA MALLA
PUNTO X (m)

Y (m)

POTENCIAL (V) POTENCIAL (%PSPT) T.CONTACTO (V) T.CONTACTO (%PSPT) T.PASO (V) T.PASO (%PSPT)

-8

-3.5

1083.99982

72.7485

406.06506

27.2515

23.07329

1.5485

-8

-2.33333

1055.10516

70.8093

434.95972

29.1907

50.31575

3.3767

-8

-1.16667

1094.95871

73.484

395.10617

26.516

163.28835

10.9585

-8

1271.65991

85.3426

218.40497

14.6574

101.63613

6.8209

-8

1.16667

1094.95871

73.484

395.10617

26.516

163.28835

10.9585

-8

2.33333

1055.10516

70.8093

434.95972

29.1907

50.31575

3.3767

-8

3.5

1083.99982

72.7485

406.06506

27.2515

23.07329

1.5485

-6.4

-3.5

1036.07216

69.532

453.99272

30.468

45.30406

3.0404

-6.4

-2.33333

960.58762

64.4662

529.47726

35.5338

89.8127

6.0274

10

-6.4

-1.16667

989.48016

66.4052

500.58472

33.5948

140.22239

9.4105

11

-6.4

1130.26573

75.8535

359.79915

24.1465

95.72729

6.4244

12

-6.4

1.16667

989.48016

66.4052

500.58472

33.5948

140.22239

9.4105

13

-6.4

2.33333

960.58762

64.4662

529.47726

35.5338

89.8127

6.0274

14

-6.4

3.5

1036.07216

69.532

453.99272

30.468

45.30406

3.0404

15

-4.8

-3.5

1150.03083

77.1799

340.03405

22.8201

112.68582

7.5625

16

-4.8

-2.33333

1071.21937

71.8908

418.84552

28.1092

189.51571

12.7186

17

-4.8

-1.16667

1100.90263

73.8829

389.16226

26.1171

240.64913

16.1502

18

-4.8

1262.63157

84.7367

227.43332

15.2633

142.50461

9.5637

19

-4.8

1.16667

1100.90263

73.8829

389.16226

26.1171

240.64913

16.1502

20

-4.8

2.33333

1071.21937

71.8908

418.84552

28.1092

189.51571

12.7186

21

-4.8

3.5

1150.03083

77.1799

340.03405

22.8201

112.68582

7.5625

22

-3.2

-3.5

1154.66216

77.4907

335.40273

22.5093

108.23314

7.2637

23

-3.2

-2.33333

1085.47335

72.8474

404.59153

27.1526

175.89132

11.8043

24

-3.2

-1.16667

1115.15418

74.8393

374.9107

25.1607

227.07721

15.2394

25

-3.2

1267.68393

85.0758

222.38095

14.9242

137.44217

9.2239

26

-3.2

1.16667

1115.15418

74.8393

374.9107

25.1607

227.07721

15.2394

27

-3.2

2.33333

1085.47335

72.8474

404.59153

27.1526

175.89132

11.8043

28

-3.2

3.5

1154.66216

77.4907

335.40273

22.5093

108.23314

7.2637

29

-1.6

-3.5

1084.42787

72.7772

405.63701

27.2228

106.6232

7.1556

30

-1.6

-2.33333

1017.44049

68.2816

472.62439

31.7184

118.44087

7.9487

31

-1.6

-1.16667

1044.36773

70.0887

445.69715

29.9113

159.53202

10.7064

32

-1.6

1173.8932

78.7813

316.17169

21.2187

138.62897

9.3036

33

-1.6

1.16667

1044.36773

70.0887

445.69715

29.9113

159.53202

10.7064

34

-1.6

2.33333

1017.44049

68.2816

472.62439

31.7184

118.44087

7.9487

35

-1.6

3.5

1084.42787

72.7772

405.63701

27.2228

106.6232

7.1556

36

-3.5

1283.41085

86.1312

206.65403

13.8688

80.1187

5.3769

29
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

37

-2.33333

1191.37436

79.9545

298.69052

20.0455

106.66266

7.1583

38

-1.16667

1222.71353

82.0577

267.35135

17.9423

189.99381

12.7507

39

1427.55514

95.8049

62.50974

4.1951

183.19821

12.2946

40

1.16667

1222.71353

82.0577

267.35135

17.9423

189.99381

12.7507

41

2.33333

1191.37436

79.9545

298.69052

20.0455

106.66266

7.1583

42

3.5

1283.41085

86.1312

206.65403

13.8688

80.1187

5.3769

43

1.6

-3.5

1084.42787

72.7772

405.63701

27.2228

106.6232

7.1556

44

1.6

-2.33333

1017.44049

68.2816

472.62439

31.7184

118.44087

7.9487

45

1.6

-1.16667

1044.36773

70.0887

445.69715

29.9113

159.53202

10.7064

46

1.6

1173.8932

78.7813

316.17169

21.2187

138.62897

9.3036

47

1.6

1.16667

1044.36773

70.0887

445.69715

29.9113

159.53202

10.7064

48

1.6

2.33333

1017.44049

68.2816

472.62439

31.7184

118.44087

7.9487

49

1.6

3.5

1084.42787

72.7772

405.63701

27.2228

106.6232

7.1556

50

3.2

-3.5

1154.66216

77.4907

335.40273

22.5093

108.23314

7.2637

51

3.2

-2.33333

1085.47335

72.8474

404.59153

27.1526

175.89132

11.8043

52

3.2

-1.16667

1115.15418

74.8393

374.9107

25.1607

227.07721

15.2394

53

3.2

1267.68393

85.0758

222.38095

14.9242

137.44217

9.2239

54

3.2

1.16667

1115.15418

74.8393

374.9107

25.1607

227.07721

15.2394

55

3.2

2.33333

1085.47335

72.8474

404.59153

27.1526

175.89132

11.8043

56

3.2

3.5

1154.66216

77.4907

335.40273

22.5093

108.23314

7.2637

57

4.8

-3.5

1150.03083

77.1799

340.03405

22.8201

112.68582

7.5625

58

4.8

-2.33333

1071.21937

71.8908

418.84552

28.1092

189.51571

12.7186

59

4.8

-1.16667

1100.90263

73.8829

389.16226

26.1171

240.64913

16.1502

60

4.8

1262.63157

84.7367

227.43332

15.2633

142.50461

9.5637

61

4.8

1.16667

1100.90263

73.8829

389.16226

26.1171

240.64913

16.1502

62

4.8

2.33333

1071.21937

71.8908

418.84552

28.1092

189.51571

12.7186

63

4.8

3.5

1150.03083

77.1799

340.03405

22.8201

112.68582

7.5625

64

6.4

-3.5

1036.07216

69.532

453.99272

30.468

45.30406

3.0404

65

6.4

-2.33333

960.58762

64.4662

529.47726

35.5338

89.8127

6.0274

66

6.4

-1.16667

989.48016

66.4052

500.58472

33.5948

140.22239

9.4105

67

6.4

1130.26573

75.8535

359.79915

24.1465

95.72729

6.4244

68

6.4

1.16667

989.48016

66.4052

500.58472

33.5948

140.22239

9.4105

69

6.4

2.33333

960.58762

64.4662

529.47726

35.5338

89.8127

6.0274

70

6.4

3.5

1036.07216

69.532

453.99272

30.468

45.30406

3.0404

71

-3.5

1083.99982

72.7485

406.06506

27.2515

23.07329

1.5485

72

-2.33333

1055.10516

70.8093

434.95972

29.1907

50.31575

3.3767

73

-1.16667

1094.95871

73.484

395.10617

26.516

163.28835

10.9585

74

1271.65991

85.3426

218.40497

14.6574

101.63613

6.8209

75

1.16667

1094.95871

73.484

395.10617

26.516

163.28835

10.9585

76

2.33333

1055.10516

70.8093

434.95972

29.1907

50.31575

3.3767

77

3.5

1083.99982

72.7485

406.06506

27.2515

23.07329

1.5485

30
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

78

-8

-3.5

1083.99982

72.7485

406.06506

79

-6.4

-3.5

80

-4.8

-3.5

81

-3.2

82

-1.6

27.2515

23.07329

1.5485

1036.07216

69.532

453.99272

30.468

45.30406

3.0404

1150.03083

77.1799

340.03405

22.8201

112.68582

7.5625

-3.5

1154.66216

77.4907

335.40273

22.5093

108.23314

7.2637

-3.5

1084.42787

72.7772

405.63701

27.2228

106.6232

7.1556

83

-3.5

1283.41085

86.1312

206.65403

13.8688

80.1187

5.3769

84

1.6

-3.5

1084.42787

72.7772

405.63701

27.2228

106.6232

7.1556

85

3.2

-3.5

1154.66216

77.4907

335.40273

22.5093

108.23314

7.2637

86

4.8

-3.5

1150.03083

77.1799

340.03405

22.8201

112.68582

7.5625

87

6.4

-3.5

1036.07216

69.532

453.99272

30.468

45.30406

3.0404

88

-3.5

1083.99982

72.7485

406.06506

27.2515

23.07329

1.5485

89

-8

-2.33333

1055.10516

70.8093

434.95972

29.1907

50.31575

3.3767

90

-6.4

-2.33333

960.58762

64.4662

529.47726

35.5338

89.8127

6.0274

91

-4.8

-2.33333

1071.21937

71.8908

418.84552

28.1092

189.51571

12.7186

92

-3.2

-2.33333

1085.47335

72.8474

404.59153

27.1526

175.89132

11.8043

93

-1.6

-2.33333

1017.44049

68.2816

472.62439

31.7184

118.44087

7.9487

94

-2.33333

1191.37436

79.9545

298.69052

20.0455

106.66266

7.1583

95

1.6

-2.33333

1017.44049

68.2816

472.62439

31.7184

118.44087

7.9487

96

3.2

-2.33333

1085.47335

72.8474

404.59153

27.1526

175.89132

11.8043

97

4.8

-2.33333

1071.21937

71.8908

418.84552

28.1092

189.51571

12.7186

98

6.4

-2.33333

960.58762

64.4662

529.47726

35.5338

89.8127

6.0274

99

-2.33333

1055.10516

70.8093

434.95972

29.1907

50.31575

3.3767

100

-8

-1.16667

1094.95871

73.484

395.10617

26.516

163.28835

10.9585

101

-6.4

-1.16667

989.48016

66.4052

500.58472

33.5948

140.22239

9.4105

102

-4.8

-1.16667

1100.90263

73.8829

389.16226

26.1171

240.64913

16.1502

103

-3.2

-1.16667

1115.15418

74.8393

374.9107

25.1607

227.07721

15.2394

104

-1.6

-1.16667

1044.36773

70.0887

445.69715

29.9113

159.53202

10.7064

105

-1.16667

1222.71353

82.0577

267.35135

17.9423

189.99381

12.7507

106

1.6

-1.16667

1044.36773

70.0887

445.69715

29.9113

159.53202

10.7064

107

3.2

-1.16667

1115.15418

74.8393

374.9107

25.1607

227.07721

15.2394

108

4.8

-1.16667

1100.90263

73.8829

389.16226

26.1171

240.64913

16.1502

109

6.4

-1.16667

989.48016

66.4052

500.58472

33.5948

140.22239

9.4105

110

-1.16667

1094.95871

73.484

395.10617

26.516

163.28835

10.9585

111

-8

1271.65991

85.3426

218.40497

14.6574

101.63613

6.8209

112

-6.4

1130.26573

75.8535

359.79915

24.1465

95.72729

6.4244

113

-4.8

1262.63157

84.7367

227.43332

15.2633

142.50461

9.5637

114

-3.2

1267.68393

85.0758

222.38095

14.9242

137.44217

9.2239

115

-1.6

1173.8932

78.7813

316.17169

21.2187

138.62897

9.3036

116

1427.55514

95.8049

62.50974

4.1951

183.19821

12.2946

117

1.6

1173.8932

78.7813

316.17169

21.2187

138.62897

9.3036

118

3.2

1267.68393

85.0758

222.38095

14.9242

137.44217

9.2239

31
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

119

4.8

1262.63157

84.7367

227.43332

15.2633

142.50461

120

6.4

1130.26573

75.8535

359.79915

24.1465

95.72729

6.4244

121

1271.65991

85.3426

218.40497

14.6574

101.63613

6.8209

122

-8

1.16667

1094.95871

73.484

395.10617

26.516

163.28835

10.9585

123

-6.4

1.16667

989.48016

66.4052

500.58472

33.5948

140.22239

9.4105

124

-4.8

1.16667

1100.90263

73.8829

389.16226

26.1171

240.64913

16.1502

125

-3.2

1.16667

1115.15418

74.8393

374.9107

25.1607

227.07721

15.2394

126

-1.6

1.16667

1044.36773

70.0887

445.69715

29.9113

159.53202

10.7064

127

1.16667

1222.71353

82.0577

267.35135

17.9423

189.99381

12.7507

128

1.6

1.16667

1044.36773

70.0887

445.69715

29.9113

159.53202

10.7064

129

3.2

1.16667

1115.15418

74.8393

374.9107

25.1607

227.07721

15.2394

130

4.8

1.16667

1100.90263

73.8829

389.16226

26.1171

240.64913

16.1502

131

6.4

1.16667

989.48016

66.4052

500.58472

33.5948

140.22239

9.4105

132

1.16667

1094.95871

73.484

395.10617

26.516

163.28835

10.9585

9.5637

133

-8

2.33333

1055.10516

70.8093

434.95972

29.1907

50.31575

3.3767

134

-6.4

2.33333

960.58762

64.4662

529.47726

35.5338

89.8127

6.0274

135

-4.8

2.33333

1071.21937

71.8908

418.84552

28.1092

189.51571

12.7186

136

-3.2

2.33333

1085.47335

72.8474

404.59153

27.1526

175.89132

11.8043

137

-1.6

2.33333

1017.44049

68.2816

472.62439

31.7184

118.44087

7.9487

138

2.33333

1191.37436

79.9545

298.69052

20.0455

106.66266

7.1583

139

1.6

2.33333

1017.44049

68.2816

472.62439

31.7184

118.44087

7.9487

140

3.2

2.33333

1085.47335

72.8474

404.59153

27.1526

175.89132

11.8043

141

4.8

2.33333

1071.21937

71.8908

418.84552

28.1092

189.51571

12.7186

142

6.4

2.33333

960.58762

64.4662

529.47726

35.5338

89.8127

6.0274

143

2.33333

1055.10516

70.8093

434.95972

29.1907

50.31575

3.3767

144

-8

3.5

1083.99982

72.7485

406.06506

27.2515

23.07329

1.5485

145

-6.4

3.5

1036.07216

69.532

453.99272

30.468

45.30406

3.0404

146

-4.8

3.5

1150.03083

77.1799

340.03405

22.8201

112.68582

7.5625

147

-3.2

3.5

1154.66216

77.4907

335.40273

22.5093

108.23314

7.2637

148

-1.6

3.5

1084.42787

72.7772

405.63701

27.2228

106.6232

7.1556

149

3.5

1283.41085

86.1312

206.65403

13.8688

80.1187

5.3769

150

1.6

3.5

1084.42787

72.7772

405.63701

27.2228

106.6232

7.1556

151

3.2

3.5

1154.66216

77.4907

335.40273

22.5093

108.23314

7.2637

152

4.8

3.5

1150.03083

77.1799

340.03405

22.8201

112.68582

7.5625

153

6.4

3.5

1036.07216

69.532

453.99272

30.468

45.30406

3.0404

154

3.5

1083.99982

72.7485

406.06506

27.2515

23.07329

1.5485

32
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Tabla 8. Resistencias propias y mutuas entre segmentos en ohmios.


RESISTENCIAS PROPIAS Y MUTUAS ENTRE SEGMENTOS EN OHMIOS
Rij

10

11

12

13

14

15

16

286.14

13.60

3.03

1.74

12.39

6.21

2.61

1.66

3.46

2.84

1.99

1.47

25.61

5.14

25.61

5.14

13.60

286.14

13.60

3.03

6.21

12.39

6.21

2.61

2.84

3.46

2.84

1.99

4.75

2.95

25.61

5.14

3.03

13.60

286.14

13.60

2.61

6.21

12.39

6.21

1.99

2.84

3.46

2.84

2.13

1.86

4.75

2.95

1.74

3.03

13.60

286.14

1.66

2.61

6.21

12.39

1.47

1.99

2.84

3.46

1.45

1.36

2.13

1.86

12.39

6.21

2.61

1.66

286.14

13.60

3.03

1.74

12.39

6.21

2.61

1.66

25.61

25.61

25.61

25.61

6.21

12.39

6.21

2.61

13.60

286.14

13.60

3.03

6.21

12.39

6.21

2.61

4.75

4.75

25.61

25.61

2.61

6.21

12.39

6.21

3.03

13.60

286.14

13.60

2.61

6.21

12.39

6.21

2.13

2.13

4.75

4.75

1.66

2.61

6.21

12.39

1.74

3.03

13.60

286.14

1.66

2.61

6.21

12.39

1.45

1.45

2.13

2.13

3.46

2.84

1.99

1.47

12.39

6.21

2.61

1.66

286.14

13.60

3.03

1.74

5.14

25.61

5.14

25.61

10

2.84

3.46

2.84

1.99

6.21

12.39

6.21

2.61

13.60

286.14

13.60

3.03

2.95

4.75

5.14

25.61

11

1.99

2.84

3.46

2.84

2.61

6.21

12.39

6.21

3.03

13.60

286.14

13.60

1.86

2.13

2.95

4.75

12

1.47

1.99

2.84

3.46

1.66

2.61

6.21

12.39

1.74

3.03

13.60

286.14

1.36

1.45

1.86

2.13

13

23.93

4.22

2.06

1.42

23.93

4.22

2.06

1.42

5.72

2.90

1.82

1.33

#####

17.40

9.77

5.98

14

5.72

2.90

1.82

1.33

23.93

4.22

2.06

1.42

23.93

4.22

2.06

1.42

17.40

321.01

5.98

9.77

15

23.93

23.93

4.22

2.06

23.93

23.93

4.22

2.06

5.72

5.72

2.90

1.82

9.77

5.98

#####

17.40

16

5.72

5.72

2.90

1.82

23.93

23.93

4.22

2.06

23.93

23.93

4.22

2.06

5.98

9.77

17.40

321.01

5.984

9.771

2.507

4.216

23.933

23.93

4.216

4.216

23.93

23.93

4.216

2.895

5.716

5.716

2.895

2.818

2.507

9.771

5.984

321

#####

9.771

2.895

5.716

5.716

2.895

4.216

23.93

23.93

4.216

4.216

23.93

23.93

4.216

2.507

2.818

5.984

9.771

#####

321

5.984

2.056

4.216

23.93

23.93

2.056

4.216

23.93

23.93

1.817

2.895

5.716

5.716

1.69

1.616

2.818

2.507

9.771

5.984

1.817

2.895

5.716

5.716

2.056

4.216

23.93

23.93

2.056

4.216

23.93

23.93

1.616

1.69

2.507

2.818

5.984

1.416

2.056

4.216

23.93

1.416

2.056

4.216

23.93

1.332

1.817

#####

5.716

1.239

1.209

1.69

1.616

1.332

1.817

2.895

5.716

1.416

2.056

4.216

23.93

1.416

2.056

4.216

23.93

1.209

1.239

1.616

#####

26.51

4.174

2.061

1.416

8.318

3.329

1.926

1.371

3.11

2.273

1.643

1.258

31.81

5.212

7.207

8.543

3.425

1.997

1.407

5.088

2.936

1.879

1.363

2.794

2.175

1.621

1.254

9.128

3.931

26.51

26.511

4.174

2.061

8.318

8.318

3.329

1.926

3.11

#####

2.273

1.643

7.207

8.543

8.543

3.425

1.997

5.088

5.088

2.936

1.879

2.794

2.794

2.175

1.621

4.719

4.174

26.511

26.51

4.174

3.329

8.318

8.318

3.329

2.273

3.11

3.11

2.273

3.425

8.543

8.543

3.425

2.936

5.088

5.088

2.936

2.175

2.794

2.794

2.061

4.174

26.51

26.51

1.926

3.329

8.318

8.318

1.643

2.273

1.997

3.425

8.543

8.543

1.879

2.936

5.088

5.088

1.621

1.416

2.061

4.174

26.51

1.371

1.926

3.329

8.318

1.258

1.407

1.997

3.425

8.543

1.363

1.879

2.936

5.088

8.318

3.329

1.926

1.371

26.511

4.174

2.061

5.088

2.936

1.879

1.363

8.543

3.425

8.318

8.318

3.329

1.926

26.511

26.51

5.088

5.088

2.936

1.879

8.543

8.543

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36

17

18

19

20

21

22

23

24

25

4.748

2.946

2.131

1.857

1.448

1.358

39.84

8.689

39.84

25.61

5.142

4.748

2.946

2.131

1.857

4.719

3.566

39.84

25.61

5.142

25.61

5.142

4.748

2.946

2.137

2.036

4.719

4.748

2.946

25.61

5.142

25.61

5.142

1.453

1.426

2.137

4.748

4.748

2.131

2.131

1.448

1.448

8.489

5.015

8.489

25.61

25.61

4.748

4.748

2.131

2.131

3.537

2.999

8.489

25.61

25.61

25.61

25.61

4.748

4.748

1.985

1.909

3.537

4.748

4.748

25.61

25.61

25.61

25.61

1.406

1.381

1.985

2.946

4.748

1.857

2.131

1.358

1.448

3.121

2.775

3.121

5.142

25.61

2.946

4.748

1.857

2.131

2.319

2.19

#####

5.142

25.61

5.142

25.61

#####

4.748

1.679

1.638

2.319

2.946

4.748

5.142

25.61

5.142

25.61

1.288

1.268

1.679

2.818

2.507

1.69

1.616

1.239

1.209

44.11

9.152

7.265

2.507

2.818

1.616

1.69

1.209

1.239

5.915

4.076

3.751

9.771

5.984

2.818

2.507

1.69

1.616

7.265

4.657

44.11

2.818

1.616

#####

3.751

3.142

5.915

5.984

2.818

2.507

2.646

2.459

7.265

9.771

2.507

2.818

2.189

2.1

#####

321

17.4

9.771

5.984

1.658

1.636

2.646

9.771

17.4

321

5.984

9.771

1.528

1.514

2.189

2.818

2.507

9.771

5.984

321

#####

1.227

1.225

1.658

2.507

2.818

5.984

9.771

#####

321

1.171

1.171

1.528

3.594

2.645

2.172

1.654

1.521

1.222

1.165

455.8

21.49

7.361

4.719

3.099

2.466

2.092

1.632

1.507

1.219

1.164

16.68

175.6

5.038

3.594

31.81

5.212

7.207

#####

2.645

2.172

1.654

1.521

7.361

5.02

455.8

3.099

9.128

3.931

4.719

3.099

2.466

2.092

1.632

1.507

5.038

4.767

16.68

2.645

2.172

7.207

3.594

31.81

5.212

7.207

3.594

2.645

2.172

2.656

2.501

7.361

2.175

2.466

2.092

4.719

3.099

9.128

3.931

4.719

3.099

2.466

2.092

2.499

2.439

5.038

3.11

3.11

1.654

1.521

2.645

2.172

7.207

3.594

31.81

5.212

7.207

3.594

1.662

1.648

2.656

2.175

2.794

2.794

1.632

1.507

2.466

2.092

4.719

3.099

9.128

3.931

4.719

3.099

1.642

1.634

2.499

1.643

2.273

3.11

1.222

1.165

1.654

1.521

2.645

2.172

7.207

3.594

31.81

5.212

1.225

1.229

1.662

1.254

1.621

2.175

2.794

1.219

1.164

1.632

1.507

2.466

2.092

4.719

3.099

9.128

3.931

1.223

1.227

1.642

1.416

8.318

3.329

1.926

1.371

31.81

31.81

7.207

7.207

2.645

2.645

1.654

1.654

1.222

1.222

9.135

5.679

4.695

1.997

1.407

5.088

2.936

1.879

1.363

9.128

9.128

4.719

4.719

2.466

2.466

1.632

1.632

1.219

1.219

5.702

5.408

3.811

4.174

2.061

8.318

8.318

3.329

1.926

7.207

7.207

31.81

31.81

7.207

7.207

2.645

2.645

1.654

1.654

4.695

3.803

9.135

3.425

1.997

5.088

5.088

2.936

1.879

4.719

4.719

9.128

9.128

4.719

4.719

2.466

2.466

1.632

1.632

3.811

3.632

5.702

33
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52

3.329

8.318

8.318

3.329

4.174

26.51

26.51

4.174

3.329

8.318

8.318

3.329

2.645

2.645

7.207

7.207

31.81

31.81

7.207

7.207

2.645

2.645

2.385

2.285

4.695

2.936

5.088

5.088

2.936

3.425

8.543

8.543

3.425

2.936

5.088

5.088

2.936

2.466

2.466

4.719

4.719

9.128

9.128

4.719

4.719

2.466

2.466

2.282

2.238

3.811

1.926

3.329

8.318

8.318

2.061

4.174

26.51

26.51

1.926

3.329

8.318

8.318

1.654

1.654

2.645

2.645

7.207

7.207

31.81

31.81

7.207

7.207

1.591

1.58

2.385

1.879

2.936

5.088

5.088

1.997

3.425

8.543

8.543

1.879

2.936

5.088

5.088

1.632

1.632

2.466

2.466

4.719

4.719

9.128

9.128

4.719

4.719

1.574

1.569

2.282

1.371

1.926

3.329

8.318

1.416

2.061

4.174

26.51

1.371

1.926

3.329

8.318

1.222

1.222

1.654

1.654

2.645

2.645

7.207

7.207

31.81

31.81

1.196

1.201

1.591

1.363

1.879

2.936

5.088

1.407

1.997

3.425

8.543

1.363

1.879

2.936

5.088

1.219

1.219

1.632

1.632

2.466

2.466

4.719

4.719

9.128

9.128

1.194

1.199

1.574

3.11

2.273

1.643

1.258

8.318

3.329

1.926

1.371

26.51

4.174

2.061

1.416

5.212

31.81

3.594

7.207

2.172

2.645

1.521

1.654

1.165

1.222

3.159

2.871

2.63

2.794

2.175

1.621

1.254

5.088

2.936

1.879

1.363

8.543

3.425

1.997

1.407

3.931

9.128

3.099

4.719

2.092

2.466

1.507

1.632

1.164

1.219

2.872

2.781

2.479

3.11

3.11

2.273

1.643

8.318

8.318

3.329

1.926

26.51

26.51

4.174

2.061

3.594

7.207

5.212

31.81

3.594

7.207

2.172

2.645

1.521

1.654

2.63

2.481

3.159

2.794

2.794

2.175

1.621

5.088

5.088

2.936

1.879

8.543

8.543

3.425

1.997

3.099

4.719

3.931

9.128

3.099

4.719

2.092

2.466

1.507

1.632

2.479

2.421

2.872

2.273

3.11

3.11

2.273

3.329

8.318

8.318

3.329

4.174

26.51

26.51

4.174

2.172

2.645

3.594

7.207

5.212

31.81

3.594

7.207

2.172

2.645

1.899

1.866

2.63

2.175

2.794

2.794

2.175

2.936

5.088

5.088

2.936

3.425

8.543

8.543

3.425

2.092

2.466

3.099

4.719

3.931

9.128

3.099

4.719

2.092

2.466

1.861

1.843

2.479

1.643

2.273

3.11

3.11

1.926

3.329

8.318

8.318

2.061

4.174

26.51

26.51

1.521

1.654

2.172

2.645

3.594

7.207

5.212

31.81

3.594

7.207

1.421

1.419

1.899

1.621

2.175

2.794

2.794

1.879

2.936

5.088

5.088

1.997

3.425

8.543

8.543

1.507

1.632

2.092

2.466

3.099

4.719

3.931

9.128

3.099

4.719

1.413

1.413

1.861

1.258

1.643

2.273

3.11

1.371

1.926

3.329

8.318

1.416

2.061

4.174

26.51

1.165

1.222

1.521

1.654

2.172

2.645

3.594

7.207

5.212

31.81

1.119

1.125

1.421

1.254

1.621

2.175

2.794

1.363

1.879

2.936

5.088

1.407

1.997

3.425

8.543

1.164

1.219

1.507

1.632

2.092

2.466

3.099

4.719

3.931

9.128

1.118

1.125

1.413

34
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Tabla 9. Sistema de ecuaciones e intensidad de corriente.


SISTEMA DE ECUACIONES E INTENSIDAD DE CORRIENTE
SEGMENTO ELECTRODO HABILITADO LAMBDA VECTOR {1} DIFERENCIA CORRIENTE (A) CORRIENTE TOTAL (A)
1
Activo
S
1.72E-03 0.999999979 2.14E-08
2.562561198
2.562561198
2
Activo
S
1.59E-03 1.000000021 -2.14E-08 2.364620179
4.927181377
3
Activo
S
1.59E-03 1.000000021 -2.14E-08 2.364620179
7.291801556
4
Activo
S
1.72E-03 0.999999979 2.14E-08
2.562561198
9.854362754
5
Activo
S
1.35E-03 1.000000006 -5.89E-09
2.01728011
11.87164286
6
Activo
S
1.23E-03 0.999999994 5.82E-09
1.827511327
13.69915419
7
Activo
S
1.23E-03 0.999999994 5.82E-09
1.827511327
15.52666552
8
Activo
S
1.35E-03 1.000000006 -5.89E-09
2.01728011
17.54394563
9
Activo
S
1.72E-03 0.999999979 2.14E-08
2.562561198
2.01E+01
10
Activo
S
1.59E-03 1.00E+00
-2.14E-08 2.364620179
2.25E+01
11
Activo
S
1.59E-03 1.000000021 -2.14E-08 2.364620179
24.83574718
12
Activo
S
1.72E-03 0.999999979 2.14E-08
2.562561198
27.39830838
13
Activo
S
1.52E-03 1.000000003 -2.95E-09 2.271548176
29.66985656
14
Activo
S
1.52E-03 1.000000003 -2.95E-09 2.271548176
31.94140473
15
Activo
S
1.17E-03 1.000000004 -4.27E-09 1.739670656
3.37E+01
16
Activo
S
1.17E-03 1.00E+00
-4.27E-09 1.739670656
3.54E+01
17
Activo
S
1.14E-03 0.999999985 1.54E-08
1.701273085
37.12201913
18
Activo
S
1.14E-03 0.999999985 1.54E-08
1.701273085
38.82329222
19
Activo
S
1.17E-03 1.000000004 -4.27E-09 1.739670656
40.56296287
20
Activo
S
1.17E-03 1.000000004 -4.27E-09 1.739670656
42.30263353
21
44.5741817
Activo
S
1.52E-03 1.000000003 -2.95E-09 2.271548176
22
46.84572988
Activo
S
1.52E-03 1.000000003 -2.95E-09 2.271548176
23
Activo
S
1.24E-03 1.000000001 -1.48E-09 1.841895237
48.68762512
24
Activo
S
4.11E-03 1.000000007 -6.98E-09 6.118175341
54.80580046
25
Activo
S
1.05E-03 0.999999999 1.43E-09
1.559784915
56.36558537
26
Activo
S
3.79E-03 0.999999996 4.24E-09
5.642080116
62.00766549
27
Activo
S
1.03E-03
1
-2.78E-10 1.530227226
63.53789272
28
Activo
S
3.72E-03 0.999999992 8.03E-09
5.53777504
69.07566776
29
Activo
S
1.05E-03 0.999999999 1.43E-09
1.559784915
70.63545267
30
5.642080116
76.27753279
Activo
S
3.79E-03 0.999999996 4.24E-09
31
Activo
S
1.24E-03 1.000000001 -1.48E-09 1.841895237
78.11942803
32
Activo
S
4.11E-03 1.000000007 -6.98E-09 6.118175341
84.23760337
33
Activo
S
1.07E-03
1
1.95E-10
1.592008383
85.82961175
34
Activo
S
3.90E-03 0.999999987 1.31E-08
5.806517401
91.63612915
35
Activo
S
8.75E-04 0.999999999 5.90E-10
1.304434008
92.94056316
36
Activo
S
3.54E-03 1.000000016 -1.56E-08 5.267582761
98.20814592

35
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52

Activo
Activo
Activo
Activo
Activo
Activo
Activo
Activo
Activo
Activo
Activo
Activo
Activo
Activo
Activo
Activo

S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S

8.56E-04
3.46E-03
8.75E-04
3.54E-03
1.07E-03
3.90E-03
1.24E-03
4.11E-03
1.05E-03
3.79E-03
1.03E-03
3.72E-03
1.05E-03
3.79E-03
1.24E-03
4.11E-03

1.000000001
1.000000001
0.999999999
1.000000016
1
0.999999987
1.000000001
1.000000007
0.999999999
0.999999996
1
0.999999992
0.999999999
0.999999996
1.000000001
1.000000007

-9.75E-10
-5.63E-10
5.89E-10
-1.56E-08
1.95E-10
1.31E-08
-1.48E-09
-6.98E-09
1.43E-09
4.24E-09
-2.78E-10
8.03E-09
1.43E-09
4.24E-09
-1.48E-09
-6.98E-09

1.275241617
5.154196424
1.304434008
5.267582761
1.592008383
5.806517401
1.841895237
6.118175341
1.559784915
5.642080116
1.530227226
5.53777504
1.559784915
5.642080116
1.841895237
6.118175341

99.48338754
104.637584
105.942018
111.2096007
112.8016091
118.6081265
120.4500218
126.5681971
128.127982
133.7700621
135.3002893
140.8380644
142.3978493
148.0399294
149.8818247
156

36
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

GRFICOS.

Figura 8. Malla de puesta a tierra vista en planta.

37
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 9. Malla de puesta a tierra vista en perspectiva.

38
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 10. Malla de puesta a tierra vista lateral.


Convenciones:
Conductor Desnudo calibre 2/0 AWG Cu.
Varilla de 2.4 m y 5/8.
Caja de inspeccin 30 x 30 cm
NOTA1: Los datos de las coordenadas de la malla estn dados en metros.

39
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 11. Perfiles de Potenciales sobre el suelo

40
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 12. Superficie 3D de potencial

41
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 13. Perfil de Tensin de contacto.

42
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 14. Superficie 3D de tensin de contacto

43
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 15. Perfil de Tensin de paso.

44
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 16. Superficie 3D de tensin de paso

45
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 17. Perfiles de potencial, Tensin de paso y Tensin de contacto.

46
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Figura 18. Potencial y Tensiones de contacto y paso en los puntos de la malla.

47
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

GUIA PARA SOLDADURAS.


GRAMOS DE SOLDADURA DE ACUERDO AL TIPO DE UNION Y CALIBRE DE
CONDUCTORES

TIPOS DE UNIONES

Unin de Cable con Varilla de 5/8

Unin de Cable con Varilla de 5/8 en T

48
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

Unin de Cable con Cable en T

Unin de Cuatro Cables en Cruz

Unin de Cable con Cable

Unin de Cuatro Cables con Varilla de 5/8

49
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

GUIA GRAFICA DE INSTALACIN.


Excavacin para instalacin de cables del SPT.

Caja de inspeccin SPT.

50
ALEJANDRO JOSE ARROYAVE MONSALVE, Ingeniero Electricista
Contactos: 3113112743, Email: aleyave25@gmail.com

CANTIDADES DE OBRA APROXIMADAS.


PUESTA A TIERRA
Cable N 4/0 Cu AWG
Cable N 2/0 Cu AWG
Electrodo de cobre 5/8 x
2.40m
Soldadura Exotrmica 150g
Caja de Inspeccin 30 x 30
Favigel
Terminales N 2/0
TOTAL

UNIDAD CANTIDAD VALOR UN


M
M

0
122

Un

15

Un
Un
Un
Un

41
1
0
26

VALOR
TOTAL

__________________________________
ALEJANDRO ARROYAVE MONSALVE
INGENIERO ELECTRICISTA
MATRICULA AN205-42794
51