Termix BTD

Direct substation for single-family houses or apartments


District heating substation for direct heating with tank for domestic hot water preparation and with thermostatic or electronic control.
Application The Termix BTD substation is a complete solution for hot water and heating systems with differential pressure control. The Termix BTD is applicable for single-family houses or apartments. District heating (DH) The substation is prefabricated with a differential pressure controller, fitting piece and sensor pockets for insertion of a heat meter as well as a strainer and ball valves. Heating (HE) The heating circuit is designed for direct generation of heat. The differential pressure control sets the optimal operation conditions for radiator thermostatic valves in order to enable individual temperature control in each room. Furthermore the station can be delivered with a mixing loop including a pump, control valve, electronic controller and non-return valve. Domestic hot water (DHW) The domestic hot water circuit consists of a hot water tank with coil and selfacting thermostatic control valve or electronic controller. The hot water tank and coil are enamelled and the tank contains a magnesium anode. The substation is delivered with a built-in non-return valve and safety valve mounted in the cold water supply. Options The Termix BTD can also be supplied with a thermostatic circulation valve. Construction All pipes are made of stainless steel. The connections are made with nuts and gaskets. The Termix BTD is completed by a white steel cover in modern design with door and including external thermometers.

FEATURES AND BENEFITS


Substation for single-family houses or apartments Direct heating and DHW regulation with a thermostatic control valve or electronic controller Mixing loop with thermostatic or electronic controller (optional) 100 or 150 ltr. tank for DHW Operates independently of differential pressure and ow temperature Suitable in cases of low district heating capacity Pipes made of stainless steel

VC.KE.N1.02 Danfoss 06/2009

Termix BTD
Circuit diagram - example
E 1 6 7 9 14 18 20 21 31 41 42 DHW tank with coil Ball valve Thermostatic/non-return valve Thermostatic valve Strainer Sensor pocket, heat meter Thermometer Filling/drain valve To be ordered separately Dierential pressure controller Fitting piece, heat meter Safety valve/non-return valve

DHW

DCW Circ.

DH supply

HE supply

DH return

HE return

Technical parameters: Nominal pressure: PN 10 (16) DH supply temperature: Tmax = 120 C Brazing material (HEX): Copper Weight incl. cover: Cover: 90-130 kg White lacquered steel sheet

Connections: The connections are situated underneath the hot water tank Connections sizes: DH supply + HE: G (int. thread) DCW + DHW + DH return: G (ext. thread)

Dimensions (mm): With cover: H 1720 x W 540 x D 645 (type BTD-1) H 1870 x W 540 x D 645 (type BTD-2)

Options: Booster pump (increases DH flow) Electronic controller for heating in connection with a mixing loop Electronic controller for heating and DHW in connection with a mixing loop Thermostatic circulation set Room thermostat Zone valve with actuator Air screw (DH supply) Fitting piece for wall mounting

DHW: Capacity examples, 10 C/50 C


Substation type BTD-1 BTD-2 Tank volume l 100 150 Coil supply/return temp. C 80/40 70/30 60/30 80/40 70/30 60/30 DHW constant output l/h 486 245 172 486 245 172 DHW output first hour* l/h 546 305 232 576 335 262 DHW constant output kW 22,6 11,4 8,0 22,6 11,4 8,0

* Output first hour = constant output + 60% of tank volume