10.1 Aeropropellers
A propeller, or airscrew, converts the torque of an engine (piston engine or turboprop) into thrust. Propeller blades have an airfoil section that becomes more circular towards the hub. The torque of a rotating propeller imparts a rotational motion to the air flowing through it. Pressure is reduced in front of the blades and increased behind them, creating a rotating slipstream. Large masses of air pass through the propeller, but the velocity rise is small compared to that in turbojet and turbofan engines.
264
where D = drag L = lift dF = thrust force acting on blade element dQ = corresponding torque force r = radius The value of that makes b a maximum is termed the optimum advance angle opt.
Draught Plant
265
Performance characteristics
The pitch and angle have different values at different radii along a propeller blade. It is common to refer to all parameters determining the overall characteristics of a propeller to their values at either 0.7r or 0.75r. Lift coefficient CL is a linear function of the angle of attack up to the point where the blade stalls, while drag coefficient CD is a quadratic function of . Figure 10.2 shows broad relationships between blading efficiency, pitch angle, and L/D ratio.
Propeller coefficients
It can be shown, neglecting the compressibility of the air, that f(Vo, n, dp, , F) = 0 Using dimensional analysis, the following coefficients are obtained for expressing the performances of propellers having the same geometry F = n2d 4pCF Q = n2d 5pCQ P = n3d 5pCp
CF, CQ, and CP are termed the thrust, torque, and power coefficients. These
266
Torque coefficient CQ
= Q n 2d 5
Power coefficient CP
= P n 3d 4
where d = propeller diameter (ft) n = speed in revs/s Q = torque (ft.lbs) F = thrust (lbf) P = power (ft.lbs/s) = air density (lb.s2/ft4)
Activity factor
Activity factor (AF) is a measure of the power-absorbing capabilities of a propeller, and hence a measure of its solidity. It is defined as
AF = 100 000 r / R =1 c r r d 16 r h / R d P R R
3
Draught Plant
267
268
Figure 10.4 shows a typical fan operating characteristic. Note how the characteristic reflects the amount of pressure it takes to push air through the system. Inlet control vanes are often used to help locate the operating point. The system resistance line shows how the fan efficiency reduces as the air flow and pressure decrease. An alternative method of control is by using variable speed drive motors or variable speed hydraulic couplings.
Stall conditions
Every fan has a stable and unstable operating range. Stable flow is defined as the condition under which enough air flows through the fan wheel to provide a constant static pressure output for a given flow. As pressure is increased and flow reduced, the fan follows the curve to the left of the original operating point. At some point, the airflow is reduced to a point where individual fan blades, and then all the blades, enter a stalled condition, causing the flow regime to break down.
Draught Plant
269
Critical speeds
Operation of a fan too near its critical speed will make it very sensitive to out-of-balance forces and resulting vibration. As a rule of thumb, the normal operating speed of a fan should be at least 20 per cent below the first critical speed.
Useful standards
Table 10.1 shows some published technical standards relating to draught fans and similar equipment. Table 10.1 Technical standards fans
Standard BS 848-1: 1997, ISO 5801: 1997 BS 848-2: 1985 Title Status Fans for general purposes. Current Performance testing using standardized airways. Fans for general purposes. Methods of noise testing. Current, partially replaced
BS 848-4: 1997, ISO 13351: 1996 BS 848-5: 1999, ISO 12499: 1999 BS 848-6: 1989 BS 848-8: 1999, ISO 13349: 1999 BS 848-10: 1999, ISO 13350: 1999 BS 5060: 1987, IEC 60879: 1986 BS EN 25136: 1994, ISO 5136: 1990 BS EN 45510-4-3: 1999 88/72307 DC
Fans for general purposes. Dimensions. Current Fans for general purposes. Special for mechanical safety (guarding). Fans for general purposes. Method of measurement of fan vibration. Fans for general purposes. Vocabulary and definition of categories. Fans for general purposes. Performance testing of jet fans. Specification for performance and construction of electric circulating fans and regulators. Acoustics. Determination of sound power radiated into a duct by fans. In-duct method. Guide for the procurement of power station equipment. Boiler auxiliaries. Draught plant. General purpose industrial fans. Fan size designation (ISO/DIS 8171). Current Current, work in hand Current Current Current, confirmed Current, work in hand Current
270
89/76909 DC
BS 848. Part 8. Fan terminology and classification. Machines for underground mines. Safety requirements for mining ventilation machinery. Electrically driven fans for underground use (prEN 1872). Ventilation for buildings. Air handling units. Ratings and performance for components and sections (prEN 13053).
Current, draft for public comment Current, draft for public comment Current, draft for public comment
95/704659 DC
97/719334 DC
98/704585 DC
Current, draft Ventilation for buildings. Performance for public testing of components/products for residential ventilation. Part 4. Fans used comment in residential ventilation systems (prEN 13141-4). Industrial fans. Performance testing in situ (ISO/DIS 5802). Acoustics. Determination of sound power radiated into a duct by fans and other air-moving devices. In-duct method (ISO/DIS 5136). ISO/DIS 14694. Industrial fans. Specification for balance quality and vibration levels. Current, draft for public comment Current, draft for public comment Current, draft for public comment
98/718875 DC
00/561592 DC
00/704961 DC
Construction
Figure 10.5 shows a basic fin-fan cooler design; they vary very little between manufacturers. The main design points are outlined below.
Draught Plant
271
272
The cooling matrix This consists of a matrix of extruded carbon steel or stainless steel finned tubes arranged in a complex multi-pass flow path. The matrix is often divided into discrete banks of tubes, extending horizontally between a set of headers. The fins consist of a continuous spiral-wound, thin steel strip that is resistance-welded into a thin slot machined in a close helix around the tubes outer surface. The extended surface of the fins adds significantly to the effective surface area, thereby increasing the overall thermal transfer. A typical tube bank is between six and ten tubes deep in order to achieve the necessary heat transfer in as small a (horizontal) area as possible. The headers Each end of the tube banks are stub-welded into heavy-section cast and welded headers. These contain internal division plates and baffles that give the desired multi-pass pattern through the system. Each header also contains stub pieces and small access hatches for inspection, cleaning, and bleeding off unwanted air during commissioning. In most designs, the headers are designed and built to an accepted pressure vessel standard. The air fans Primary cooling effect is provided by a bank of axial-flow cooling fans that blow air vertically upwards through the tube nest. Fans are generally beltdriven for simplicity, and have variable incidence blades positioned by a pneumatic actuator arrangement. The electric motors are often two-speed (typically 300 r/min and 600 r/min), to allow operating current and power consumption to be reduced when air temperature is low. In a typical unit, each fan will be located about 2 m off the ground and will be protected by an expanded metal safety guard. Tip speed of the fan is normally kept below 60 m/s to avoid over-stressing the aluminium blades.
Draught Plant
273
Static pressure versus blade angle The performance of the fan does not keep on improving as blade incidence is increased. There is a welldefined cut-off point, above which the blades start to become aerodynamically inefficient and will actually produce less, rather than more, cooling effect. Blade angle versus motor current This places a limitation on the fitnessfor-purpose of the fan. Maximum motor design currents usually have a design margin of about 30 per cent (to keep the cost of the motors down). A well-designed unit should reach full operating current before the static pressure curve levels off. Vibration Axial fans are normally smooth-running units and rarely experience vibration problems. A maximum Vrms level of about 2.5 mm/s is acceptable, using the principles of VDI 2056. Mechanical integrity: points to check blade locking arrangements, including the fitted clevis, used to locate the blades accurately in position on the hub; the pneumatic positioner and diaphragm that move the blade angle; the blades themselves (usually aluminium): check for length and any obvious mechanical damage; all locknuts and lockwashers fitted to the rotating components.
274