MicroLogix 1200 System Expansion Worksheet

Use the worksheet below to account for the amount of 5V dc and 24V dc current consumed by your controller, expansion I/O, and user supplied equipment. Current consumed by the Controller, Memory Modules, and Real Time Clock Modules has already been factored into the calculations below. A system is valid if the current and power requirements are satisfied, and if all expansion I/O modules are mounted no further than 6 modules away from the power supply. This version of the MicroLogix 1200 system qualifier is an interactive version which utilizes user input to calculate system current and power. The qualifier then determines if the chosen system is acceptable or if it violates any of the MicroLogix 1200 requirements and/or rules. Blue cells represent directions for user input and cells colored in yellow represent where the user enters that input. Red cells represent any errors the user input has caused or any MicroLogix 1200 requirements and/or rules that have been violated .

MicroLogix 1200 Controller Configuration


Controller Type (Required: Only one maximum) Catalog Number (Click below and use drop-down menu to select a controller)
Select SelectController Controller

Embedded I/O Configuration Controller Line Power Input

AC Inputs

DC Inputs

DC Outputs

Relay Outputs

Select Controller Select Controller Select Controller Select Controller Select Controller

Communication / Display Devices (Optional:only one maximum) Catalog Number (Click below and use drop-down menu to select a device) Select SelectDevice Device
(1) (2) (1)(2)

Device Current Draw 5V dc (mA) Select Device 24V dc (mA) Select Device

These are optional accessories. Current is consumed only if the accessory is installed.

Current for the 1761-NET-AIC or 1761-NET-ENI may be supplied from the controller communications port or from an external 24V dc source. No current is consumed from the controller when a user supplied external source is used. The current for a 2707-MVH232 or 2707-MVP232 MicroView Operator Interface is always supplied from the controller's communication port, if directly connected. 5V dc (mA) Device Current Draw Subtotal: Select Controller 24V dc (mA) Select Controller

Catalog Number

Expansion Modules Number of Modules


(3)

Expansion Modules (Optional: See restrictions below) 1762-IA8 1762-IF2OF2 1762-IF4 1762-IQ8 1762-IQ16 1762-IR4 1762-IT4 1762-OA8 1762-OB8 1762-OB16 1762-OF4 1762-OW8 1762-OW16 1762-OX6I Total Modules
(3)

Module Current Requirements 5V dc (mA) 50 40 40 50 60 40 40 115 115 175 40 80 120 110 24V dc (mA) 0 105 50 0 0 50 50 0 0 0 165 90 140 110

Number of Number of Modules * A Modules * B + subtotal = + subtotal = Select Controller Calculated Controller Current Required 5V dc (mA) 24V dc (mA)

Module Current Subtotal:

Select Controller Select Controller

Select Controller Select Controller

Total Controller Current Consumed:


(3)

A maximum of 6 modules are addressable, provided the sum of the current consumed is within the limit for your controller. All modules must be used within their specified "Power Supply Distance Rating". All modules have a rating of 6.

Validating System Power Loading on MicroLogix 1200 Controllers


After you have calculated the amount of current consumed by your system, use the tables below to verify that the total power loading is less than the maximum allowed. If the Controller current or the Controller power loading is exceeded; you will have to reconfigure your system. For 1762-L24AWA, -L24AWAR, -L24BXB or -L24BXBR; and 1762-L40AWA, -L40AWAR, -L40BXB or 1762-L40BXBR Current Loading Maximum Current Calculated Current Maximum Power Calculated Power Select Controller Total 5V dc Current Consumed (mA) Select Controller Total 24V dc Current Consumed (mA) Select Controller Total Watts

Select Controller

Select Controller

Select Controller

Select Controller

Select Controller

Select Controller

For 1762-L24BWA, -L24BWAR and 1762-L40BWA, -L40BWAR Add any User 24V sensor current for applications with dc input sensors Current Loading User 24V Sensor Current (Max. = 250 mA) Maximum Current Calculated Current Maximum Power Calculated Power Select Controller Select Controller Select Controller Total 5V dc Current Consumed (mA) Total 24V dc Current Consumed (mA) Total Watts

Select Controller

Select Controller

Select Controller

Select Controller

Select Controller

Select Controller

MicroLogix 1200 System Expansion Worksheet


Use the worksheet below to account for the amount of 5V dc and 24V dc current consumed by your controller, expansion I/O, and user supplied equipment. Current consumed by the Controller, Memory Modules, and Real Time Clock Modules has already been factored into the calculations below. A system is valid if the current and power requirements are satisfied, and if all expansion I/O modules are mounted no further than 6 modules away from the power supply. This version of the MicroLogix 1200 system qualifier is a printable version which allows the user to print the qualifier and fill out a hard copy for their records. The user must determine if their system is acceptable or not using the guidelines below.

MicroLogix 1200 Controller Configuration


Controller Type (Required: Only one maximum) Catalog Number 1762-L24AWA 1762-L24AWAR 1762-L24BWA 1762-L24BWAR 1762-L24BXB 1762-L24BXBR 1762-L40AWA 1762-L40AWAR 1762-L40BWA 1762-L40BWAR 1762-L40BXB 1762-L40BXBR Communication / Display Devices (Optional:only one maximum) Catalog Number
(1)(2)

Embedded I/O Configuration AC Inputs 14 14 24 24 DC Inputs 14 14 14 14 24 24 24 24 DC Outputs 5 5 8 8 Relay Outputs 10 10 10 10 5 5 16 16 16 16 8 8 Controller Line Power Input 120 / 240V ac 120 / 240V ac 120 / 240V ac 120 / 240V ac 24V dc 24V dc 120 / 240V ac 120 / 240V ac 120 / 240V ac 120 / 240V ac 24V dc 24V dc

Maximum Load Current


5V dc 400 mA 400 mA 400 mA 400 mA 400 mA 400 mA 600 mA 600 mA 600 mA 600 mA 600 mA 600 mA 24V dc 350 mA 350 mA 350 mA 350 mA 350 mA 350 mA 500 mA 500 mA 500 mA 500 mA 500 mA 500 mA

Maximum Load Power


10.4 W 10.4 W 12 W 12 W 10.4 W 10.4 W 15 W 15 W 16 W 16 W 15 W 15 W

Device Current Draw 5V dc (mA) 0 0 0 0 24V dc (mA) 120 100 80 80

1761-NET-AIC 1761-NET-ENI 2707-MVH232 2707-MVP232


(1) (2)

These are optional accessories. Current is consumed only if the accessory is installed.

Current for the 1761-NET-AIC or 1761-NET-ENI may be supplied from the controller communications port or from an external 24V dc source. No current is consumed from the controller when a user supplied external source is used. The current for a 2707-MVH232 or 2707-MVP232 MicroView Operator Interface is always supplied from the controller's communication port, if directly connected. 5V dc (mA) Device Current Draw Subtotal: 24V dc (mA)

Catalog Number

Expansion Modules Number of Modules


(3)

Expansion Modules (Optional: See restrictions below) 1762-IA8 1762-IF2OF2 1762-IF4 1762-IQ8 1762-IQ16 1762-IR4 1762-IT4 1762-OA8 1762-OB8 1762-OB16 1762-OF4 1762-OW8 1762-OW16 1762-OX6I Total Modules
(3)

Module Current Requirements 5V dc (mA) 50 40 40 50 60 40 40 115 115 175 40 80 120 110 24V dc (mA) 0 105 50 0 0 50 50 0 0 0 165 90 140 110

Number of Number of Modules * A Modules * B + subtotal = + subtotal = mA Max mA Max Calculated Controller Current Required 5V dc 24V dc (mA) (mA)

Module Current Subtotal:

Total Controller Current Consumed:


(3)

A maximum of 6 modules are addressable, provided the sum of the current consumed is within the limit for your controller. All modules must be used within their specified "Power Supply Distance Rating". All modules have a rating of 6.

Validating System Power Loading on MicroLogix 1200 Controllers


After you have calculated the amount of current consumed by your system, use the tables below to verify that the total power loading is less than the maximum allowed. If the Controller current or the Controller power loading is exceeded; you will have to reconfigure your system. For 1762-L24AWA, -L24AWAR, -L24BXB or -L24BXBR; and 1762-L40AWA, -L40AWAR, -L40BXB or 1762-L40BXBR Current Loading Maximum Current Calculated Current Maximum Power Calculated Power W Total 5V dc Current Consumed (mA) mA Total 24V dc Current Consumed (mA) mA Total Watts

mA

mA

For 1762-L24BWA, -L24BWAR and 1762-L40BWA, -L40BWAR Add any User 24V sensor current for applications with dc input sensors Current Loading User 24V Sensor Current (Max. = 250 mA) Maximum Current Calculated Current Maximum Power Calculated Power W mA Total 5V dc Current Consumed (mA) Total 24V dc Current Consumed (mA) mA Total Watts

mA

mA

mA