WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

TABLE 17 - 33 / 33 KV (UE) HT XLPE SINGLE CORE ALUMINIUM CONDUCTOR CABLE


POLYCAB SINGLE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING
TO IS: 7098 PART-2/1985:
UNARMOURED CABLE
Nominal
Nominal
Nominal Approx. Approx.
Size Thickness Thickness Overall Weight of
of XLPE of PVC Diaeter Cable.
of
Conductor Insulation Outer of Cable
Sheath
Sq.mm.
120
150
185
240
300
400
500
630
800
1000

mm
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5

mm
2.2
2.4
2.4
2.4
2.6
2.6
2.8
3.0
3.0
3.2

mm
40
41.5
43.5
46
48.5
51
54.5
58
62
67

Kg/Km
1700
1900
2100
2350
2650
3100
3600
4200
4850
5700

ALUMINIUM STRIP ARMOURED CABLE

ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY

Minimum Nominal Minimum Approx. Approx. Nominal Minimum


Thickness Dimesion Thickness Overall Weight of Dimesion Thickness
of Inner
of
of PVC Diameter Cable
of
of PVC
Sheath
Strip
Outer of Cable
Round Outer
Sheath
Wire
Sheath
mm
0.40
0.40
0.50
0.50
0.50
0.50
0.60
0.60
0.60
0.70

mm
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

mm
1.72
1.72
1.72
1.88
1.88
2.04
2.04
2.2
2.36
2.52

mm
42
43.5
45
48
50
53.5
56.5
60
64
69

Kg/Km
2000
2150
2400
2700
3000
3450
3950
4550
5300
6250

mm
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
3.15
3.15

mm
1.72
1.88
1.88
2.04
2.04
2.2
2.2
2.36
2.52
2.68

Approx. Approx.
In In Duct at In Air at *Normal
Overall Weight of Ground at 30 C.
40 C. Delivery
Diameter Cable
30 C.
Length
of Cable
mm
45.5
47.5
49.5
53.0
55.0
58.5
62.0
65.5
71.0
76.0

Kg/Km
2250
2500
2700
3200
3500
4000
4550
5200
6200
7250

Amps.
230
260
290
335
380
430
485
550
610
660

Amps.
200
225
255
290
325
370
420
470
520
560

Amps.
310
350
400
470
540
630
730
840
950
1060

Mtrs.
500
500
500
500
500
500
500
500
500
500

TABLE 18 - 33 / 33 KV (UE) HT XLPE SINGLE CORE COPPER CONDUCTOR CABLE


POLYCAB SINGLE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING
TO IS: 7098 PART-2/1985:
Nominal
Size
of
Conductor

UNARMOURED CABLE
Nominal Nominal Approx. Approx.
Thickness Thickness Overall Weight of
of XLPE of PVC Diaeter Cable
Insulation Outer of Cable
Sheath

ALUMINIUM STRIP ARMOURED CABLE


Minimum Nominal Minimum Approx. Approx.
Thickness Dimesion Thickness Overall Weight of
of Inner
of
of PVC Diameter Cable
Sheath
Strip
Outer of Cable
Sheath

ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY


Nominal
Dimesion
of
Round
Wire

Minimum
Thickness
of PVC
Outer
Sheath

Approx. Approx.
In In Duct at In Air at *Normal
Overall Weight of Ground at 30 C.
40 C. Delivery
Diameter Cable
30 C.
Length
of Cable

Sq.mm.
120

mm
9.5

mm
2.2

mm
41.5

Kg/Km
2450

mm
0.40

mm
0.8

mm
1.72

mm
43.0

Kg/Km
2750

mm
2.0

mm
1.72

mm
45.5

Kg/Km
3000

Amps.
300

Amps.
260

Amps.
400

Mtrs.
500

150
185
240
300
400
500
630
800
1000

9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5

2.4
2.4
2.4
2.6
2.6
2.8
3.0
3.0
3.2

43.0
45.0
47.5
50.0
53.0
56.5
60.0
64.0
69.0

2850
3250
3850
4550
5600
6700
8100
9800
11900

0.40
0.50
0.50
0.50
0.50
0.60
0.60
0.60
0.70

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.72
1.72
1.88
1.88
2.04
2.04
2.2
2.36
2.52

44.5
46.5
49.5
51.5
55.0
58.0
61.5
66.0
71.0

3050
3500
4200
4850
5950
7050
8450
10250
12450

2.0
2.0
2.5
2.5
2.5
2.5
2.5
3.15
3.15

1.88
1.88
2.04
2.04
2.2
2.2
2.36
2.52
2.68

47.5
49.5
53.0
55.0
58.5
62.0
65.5
71.0
76.0

3400
3850
4650
5350
6500
7650
9100
11200
13450

330
375
430
480
540
600
660
720
760

290
325
370
415
465
520
570
620
660

450
510
600
690
790
910
1020
1140
1240

500
500
500
500
250
250
250
250
200

The above data is approximate and subject to manufacturing tolerance.