33/11kV DISTRIBUTION POWER SYSTEM PROTECTION

FUNDAMENTAL OF PROTECTION

1
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

OBJECTIVES
At the end of the session, the participant will be able: To show the concept and application of protection system To explain the role of protection system in TNB To show the types of protection relay used in TNB system To show the application of the relays in TNB system

2
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

WHY WE NEED PROTECTION?

3
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

Role of Protection
Protect power system against any faults Detect Fault Isolate faulty plant Minimize damage Minimize danger to people Minimize supply interruption
4
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

PMU 132/33 kV

IDEAL PROTECTION SYSTEM FOR TNB PPU SYSTEM


33/11 kV PE 11/0.415 kV x x x x X X X

-bus bar protection -cable/line protection -transformer protection


5
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

All TNB equipment has to be protected!

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

PROTECTION PRINCIPLES
Criteria
1. Fast

Definition
Fast fault clearance Minimize the system interruptions or duration of system disturbance Improve system stability Safety of Human & Equipment

2.Dependable Must operate for faults in the protected zone / Reliable Will operate correctly for all the faults for which it is designed to operate 3. Secure / Stable 4. Selective Must not operate/ stable for faults outside the protected zone, power system disturbance Will not mal-operate if no fault in the protected zone Able to identify the faulty section and/or phase(s) of a power system Operate as much of the system as necessary to de-energize only distressed components of power system
6
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

PROTECTION PRINCIPLES (continued)


Criteria Definition
Sensitive enough to operate under minimum fault condition To consider minimum fault level Low Level Fault may lead to more severe fault Utilise minimal hardware and software logic to perform intended function Increase in hardware components may reduce the system reliability

5. Sensitive

6. Simple

7.Economical The cost commensurate with the intended function and power system risk assessment

7
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

PROTECTION DESIGN PHILOSOPHY


Fault Clearing System (FCS)
Protection System
CT Protection Equipment/ Relay

Circuit Breaker
Trip Coil CB Mechanism

VT

TE

TE

DC System

DC System

CT Current Transformer VT Voltage Transformer TE Telecommunication Equipment CB Circuit Breaker

Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

Fault Clearing Requirements


Maximum Fault Clearing Time (MFCT)
Main Protection Function

Voltage Level (kV) Equipment

33/22/11 150ms 600ms

Substation Circuit

9
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

BASIC COMPONENT
SENSING DEVICE
CURRENT TRANSFORMER VOLTAGE TRANSFORMER

RELAY
DECISION MAKER - TRIP OR NOT ?

CIRCUIT BREAKER
FAULT ISOLATION
10
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

PROTECTION ISOLATION COMPONENTS

CIRCUIT BREAKER

SENSING DEVICE

TRIP

RELAY

11
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

TYPE OF PROTECTION
Unit Protection
- operates on differential principle - has defined zone protection determined by CT - must be stable during external fault

Non-unit Protection
Simpler and cheaper Requires time coordination between various stages Long clearance time for faults close to source
12
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

UNIT PROTECTION
CB SS1 TRIP
Discrimination by zone!

CT

ZOP

CT CB TRIP SS2

Fault

RELAY
13
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

NON-UNIT PROTECTION
SS3 SS1 1.5sec 0.5sec 0 sec SS4
Fault
14
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

SS2

1.0sec

Discrimination by time factor!

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

LIST OF UNIT AND NON UNIT PROTECTION Unit Protection


Current Differential / Pilot wire relay (7SJ610, Solkor Rf, Solkor N) TX Differential (SEL 587, 7UT512) TX REF (SPAE 010, 7VH600)

Non Unit Protection


OCEF (7SJ602, P123) SBEF (7SJ602, CAU) Directional OCEF (SEL351A)
15
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

MAIN & BACK UP PROTECTION


Main protection Back up protection

Transformer

-TX Diff -TX REF -TX Guard -Current Differential / Solkor Rf - High Set OCEF - Low/High impedance - Arc protection

-OCEF - SBEF -OCEF -SBEF -OCEF

Cable/line

Bus bar

16
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

RELAY OPERATING TIME


OCEF 1.2 s (outgoing feeder PMU) 0.4 s (outgoing feeder PPU) 0.8 s (incomer TX 33/11 kV PPU) SBEF - 2 to 2.5 s for 1st stage - 5 s for 2nd stage REF 50 ms TX Diff 50 ms Current Diff 12 ms Arc protection 7 ms
17
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

PILOT WIRE / CURRENT DIFFERENTIAL RELAY Use circulating current principle (Solkor Rf) Use voltage balance priciple (Translay H04) Is a unit protection Need communication channel Operation by comparing the current magnitude of both end
18
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

BASIC OF DIFFERENTIAL SCHEME


FLOW OF FAULT CURRENT OUT OF ZONE

CB

CT 600/1

CT 600/1 CB

5A

5A

5A 5A 5A

5A

0A

FAULT 3000A
19

5A
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

5A

TNB Integrated Learning Solution Sdn Bhd - ILSAS

BASIC OF DIFFERENTIAL SCHEME


FLOW OF FAULT CURRENT IN ZONE

CB

CT 600/1 FAULT 3000A

CT 600/1 CB

5A

5A

0A

5A

0A

0A

5A

5A
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

0A

20

TNB Integrated Learning Solution Sdn Bhd - ILSAS

TRANSLAY BALANCE VOLTAGE


SSA CB CT F CT CB 1 SOURCE

SSB

T OPERATE

T NO OPERATION
21

Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

OCEF
The cheapest protection relay Available in 3 OC, 1 EF and 2OC, 1 EF Use Standard Inverse Definite Minimum Time characteristics

22
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

23
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

OCEF BASIC DIAGRAM


2 O/C 1 E/F
R Y B

O/C

2 OC and 1 EF is sufficient to cover fault for all 3 phases O/C


EARTH BONDING

E/F

24
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

OC OPERATION 2 Phase fault


R Y B

OC

OC

CT R Y Fault

EF

25
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

OC OPERATION 2 Phase fault


X X X

CT CT CT OC R B Fault

R Y B

OC EF

26
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

EF OPERATION Single phase fault


X X X

VCB

EARTH OC EF OC B E Fault

27
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

STANDBY EARTH FAULT (SBEF)


Use Definite Time Characteristics Set normally between 2-2.5 s for 1st stage and 5 s for 2nd stage, depending on coordination studies Is a back up protection

28
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

SBEF CHARACTERISTICS

29
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

BASIC OVERALL TRANSFORMER PROTECTION

POWER TRANSFORMER BREAKER CT CT BREAKER

REF SBEF
STAR

INTERPOSING CT
DELTA

DIFF

30
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

Power Transformer (132/33kV or 132/11kV) - HV


Protection Classification Main Protection Backup Protection Device Designation 87T 64REF/HV 51OC TXG Protection Device Transformer Biased Differential Protection Transformer Restricted Earth Fault Overcurrent Protection Transformer Guards Bucholz (Main & OLTC Tanks) 63B Winding Temperature (HV/LV) 26WT Oil Temperature - 26OT Pressure Relief Device 63PRD Circuit Breaker Failure Protection Circuit Breaker Failure Protection

* 50BF/1 * 50BF/2

Requirement in TNB COP Ed.2 Note* : For Gas Insulated Switchgear (GIS) Substation Only
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

31

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

Power Transformer (132/33kV or 132/11kV) - LV


Protection Classification Main Protection Backup Protection Device Designation 64REF/LV 51OC+51EF 64SBEF Protection Device Transformer Restricted Earth Fault Overcurrent & Earth Fault Protection Transformer Standby Earth Fault

32
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

TX Differential
Is a unit protection Usually located at 33 kV CRP Use current circulating method Operated by comparing the magnitude of current of both ends

33
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

BASIC OF DIFFERENTIAL SCHEME (through fault)


CB 2000 CT 200/1 33/11 kV 6000A CT 600/1 CB

10A

10A

10A

10A 10A

10A

0A - relay stable 10A

FAULT 6000A
34

10A
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

BASIC OF DIFFERENTIAL SCHEME (in zone fault)


CB 2000 CT 200/1 33/11 kV 0A CT 600/1 CB

6000A 10A 10A 10A 0A

0A

0A

10A relay operates


DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

10A
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

0A

35

TNB Integrated Learning Solution Sdn Bhd - ILSAS

RESTRICTED EARTH FAULT (REF)


Is a unit protection Usually located at 11 kV CRP Has 2 types
Voltage operated Current operated

36
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

RESTRICTED EARTH FAULT SCHEME FOR STAR WINDING

REF protected zone

37
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

REF (OUT ZONE FAULT)


4A

CT 600/1

2400A

4A EARTH FAULT OUTSIDE ZOP 2400A RELAY STABLE CT 600/1 4A 4A 4A 4A

0A

2400A

earth
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

38
DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

REF (IN ZONE FAULT) 2400A


0A

CT 600/1

0A 2400A EARTH FAULT INSIDE ZOP 2400A RELAY OPERATES CT 600/1 4A 4A 0A 4A

4A

earth
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

39
DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

REF (PH-PH FAULT) 2400A


2400A 4A

CT 600/1

4A

PH - PH FAULT OUTSIDE ZOP 2400A RELAY NO OPERATION/STABLE CT 600/1

earth
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

40
DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

REF (PH-PH FAULT) 2400A


2400A

CT 600/1

PH - PH FAULT INSIDE ZOP 2400A RELAY NO OPERATION/STABLE CT 600/1

earth
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

41
DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

DIRECTIONAL OCEF
Directional Control at C and D
I1 + I2 I1 C I2

51 A

67

LOAD

51 B

67

Relay D does not operate due to current flow in the reverse direction.
42

Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

ARC PROTECTION
Input from light sensor and current transformer Light input coming from flashover Current input coming from fault current magnitude Tripped if both conditions existed Tripping time 7 ms
43
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

ARC protection Two incomers


VAMP 221
Ib> VX010 VX010 T2 T2

VAMP 221

CB1

T1

CB2

T1

CB3

X1

X2

44
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

TNBD PRACTICE
TX 33 /11 kV Protection
Main protection
TX DIFF, REF (>5MVA TX) TX Guard
Bucholz Main Tank & OLTC Pressure Relief Device HV and LV winding temperature Oil temperature

Back up protection
OCEF SBEF
45
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

TNBD PRACTICE
Cable Protection
Main protection
Current Differential / Pilot wire relay Directional relay

Back up protection
OCEF SBEF

46
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

TNBD PRACTICE
Overhead Line Protection
Main protection
OCEF High Set with A/Reclose

Back up protection
OCEF IDMT SBEF

47
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

TNBD PRACTICE
Bus bar Protection
Main protection
Recently used Arc Protection Reverse blocking scheme (not yet widely used)

Back up protection
OCEF

48
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

PROTECTION SYSTEM USED IN TNB SYSTEM


PMU 132/33 kV PPU 33/11 kV PE 11/0.415 kV x x x x X TX 33 / 11 kV > 5 MVA Main and back up protection used/available TX 33/11 kV < 5 MVA Used quenchol fuses Local TX Used OCEF
49
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

X X X

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

PROTECTION SYSTEM USED IN TNB SYSTEM


PMU 132/33 kV PPU 33/11 kV PE 11/0.415 kV x x x x X
Underground cable 33 kV Main protection are active unless pilot wire is not available Back up protection used (OCEF) Underground cable 11 kV Main protection translay H04 not widely used. Directional OCEF used for parallel feeders Only used back up OCEF Overhead line 33 kV Used OCEF with reclose / Auto recloser

X X X

50
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

PROTECTION SYSTEM USED IN TNB SYSTEM


PMU 132/33 kV PPU 33/11 kV PE 11/0.415 kV x x x x X Bus bar Arc protection only recently used Most TNB sub station no arc protection installation/available Only depends on back up OCEF as solely protection
51
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

X X X

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

Protection Relay Location


Solkor R/RF OC/EF Master Trip

33kV
Tx Differential Tx Guard OC/EF Master Trip NER OC/EF REF Master Trip 31 Bus Section 32 OC/EF REF Master Trip 1HO 2HO

33kV Outgoing
Tx Differential Tx Guard OC/EF Master Trip

Tx1

Tx2

11kV
OC/EF Translay Master Trip
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

SBEF Tx1 11kV Outgoing SBEF Tx2 Master Trip

52
DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009

TNB Integrated Learning Solution Sdn Bhd - ILSAS

53
Sharul Amri Ismail & Sahari Abdullah (Sep 2008) 33/11kV Distribution Power System Protection For ST

DISTRIBUTION POWER SYSTEM PROTECTION Ir. Azizuddin Zakaria 2833/11kV Dec 2009