Unitron UC16PG/UC16IP

UC Controllers

UC16PG / UC16IP
MECHANICAL Size:225 x 130 x 45 mm (8.86 x 5.12 x 1.78") Enclosure:Injection moulded ABS Mounting:DIN rail Environment:- 0 - 50 DegC (32-122 DegF) Ambient 0 - 90% Rh non condensing Note:This equipment is intended for field installation within the enclosure of another product. WIRING

Termination:-

Note:ELECTRICAL Power Requirements:Transformer Rating:-

PCB mounted plug terminal connections Conductor Area: Max: AWG 12 (3.09mm2) Min: AWG 22 (0.355 mm2) Use Copper or Copper Clad Aluminium Conductors only. 24V AC +/- 20% 50/60 Hz 10VA

PROCESSOR VLSI Motorola 68HC11 8 MHz 128K Operating System Memory 32K RAM Battery backed for 2 years minimum INPUTS 8 Universal Inputs NiCd1000, PT1000, 1K7A1, 2-2K3A1, 3K3A1, 5K3A1, 10K3A1, 10K4A1, 20K6A1, 30K6A1, 50K6A1, 100K6A1, S7K6, UUT43J1, UUT45J1 Passive Detectors within the range 30 to 4M . 0 - 10V @ 134K 0 - 20 mA @ 120 Digital Volt Free Contact Pulse up to 12 Hz 8 Digital Inputs (UC16IP only) Volt Free Contact OUTPUTS (UC16PG only) 8 Analog 0-10V @ 10mA COMMUNICATIONS Local RS232 TTL port @ 1200 or 9600 Baud

Cylon Controls Limited Clonshaugh Industrial Estate Clonshaugh Dublin 17 Ireland Tel: +353 (0) 1 2450 500 Fax: +353 (0) 1 2450 501 Email: askus@cylon.ie

Cylon Controls UK Limited 50 Centenary Business Centre Hammond Close Attleborough Fields Nuneaton Warwickshire CV11 6RY Tel: (024) 7632 7777 Fax: (024) 7632 7878 Email: askus@cylon.ie

Due to Cylon's policy of continuous improvements these specifications may be upgraded without notice.

UCDS-0001 Rev 4.00

Cylon Controls Limited

8 Universal Input Ports


8 Universal Input Ports
A B

UC ID Selector Switches RS485 Network Port RS485 Network Terminator RS232 Port
Input Selection Jumpers

UC ID Selector Switches

2 3

7 8

9 10 11 12 13 14 15 16

35 36

Input Selection Jumpers

RS485 Network Port RS485 Network Terminator RS232 Port

WatchDog LED (Green) Power On LED (Red) Quick Connector


17 18 19 20 21 22 23 24 25 26 27 28 29 30 3132

Fuse 33b 34 24 VAC GND


WatchDog LED (Green)

Power On LED (Red)

8 0-10V outputs
8 Digital Inputs

Input Point Selection Jumpers (Pins come covered by jumpers)


Volt free contacts 0-10V 0-20 mA Passive

Pin Open Pin covered by jumper

RS485 Network Terminator

Input Point Selection Jumpers (Pins come covered by jumpers)


Volt free contacts 0-10V 0-20 mA Passive

Pin Open Pin covered by jumper

RS485 Network Terminator

ON

ON

Important Earth this controller by connecting the 0V wire (Go), on the secondary side of the 24V AC transformer to Earth (green / yellow wire, terminal 33b) at one point.

UC Address Switch RS485 Network Port RS485 Network Terminator RS232 Port (PL4)

Important Earth this controller by connecting the 0V wire (Go), on the secondary side of the 24V AC transformer to Earth (green / yellow wire, terminal 33b) at one point.

UC Address Switch

RS485 Network Port RS485 Network Terminator RS232 Port (PL4)

UCDS-0001 Rev 4.00

Cylon Controls Limited

24 VAC