UC Controllers
UC16PG / UC16IP
MECHANICAL Size:225 x 130 x 45 mm (8.86 x 5.12 x 1.78") Enclosure:Injection moulded ABS Mounting:DIN rail Environment:- 0 - 50 DegC (32-122 DegF) Ambient 0 - 90% Rh non condensing Note:This equipment is intended for field installation within the enclosure of another product. WIRING
Termination:-
PCB mounted plug terminal connections Conductor Area: Max: AWG 12 (3.09mm2) Min: AWG 22 (0.355 mm2) Use Copper or Copper Clad Aluminium Conductors only. 24V AC +/- 20% 50/60 Hz 10VA
PROCESSOR VLSI Motorola 68HC11 8 MHz 128K Operating System Memory 32K RAM Battery backed for 2 years minimum INPUTS 8 Universal Inputs NiCd1000, PT1000, 1K7A1, 2-2K3A1, 3K3A1, 5K3A1, 10K3A1, 10K4A1, 20K6A1, 30K6A1, 50K6A1, 100K6A1, S7K6, UUT43J1, UUT45J1 Passive Detectors within the range 30 to 4M . 0 - 10V @ 134K 0 - 20 mA @ 120 Digital Volt Free Contact Pulse up to 12 Hz 8 Digital Inputs (UC16IP only) Volt Free Contact OUTPUTS (UC16PG only) 8 Analog 0-10V @ 10mA COMMUNICATIONS Local RS232 TTL port @ 1200 or 9600 Baud
Cylon Controls Limited Clonshaugh Industrial Estate Clonshaugh Dublin 17 Ireland Tel: +353 (0) 1 2450 500 Fax: +353 (0) 1 2450 501 Email: askus@cylon.ie
Cylon Controls UK Limited 50 Centenary Business Centre Hammond Close Attleborough Fields Nuneaton Warwickshire CV11 6RY Tel: (024) 7632 7777 Fax: (024) 7632 7878 Email: askus@cylon.ie
Due to Cylon's policy of continuous improvements these specifications may be upgraded without notice.
UC ID Selector Switches RS485 Network Port RS485 Network Terminator RS232 Port
Input Selection Jumpers
UC ID Selector Switches
2 3
7 8
9 10 11 12 13 14 15 16
35 36
8 0-10V outputs
8 Digital Inputs
ON
ON
Important Earth this controller by connecting the 0V wire (Go), on the secondary side of the 24V AC transformer to Earth (green / yellow wire, terminal 33b) at one point.
UC Address Switch RS485 Network Port RS485 Network Terminator RS232 Port (PL4)
Important Earth this controller by connecting the 0V wire (Go), on the secondary side of the 24V AC transformer to Earth (green / yellow wire, terminal 33b) at one point.
UC Address Switch
24 VAC
GND