Exercise Objectives
After completing this exercise, you should be able to do the following: Identify differential settings and protection requirements. Define settings recommendations for transformer differential protection. Calculate effective settings for system examples. Validate relay settings.
In this exercise, the instructor will introduce the SEL-387A Current Differential and Overcurrent Relay differential protection settings and demonstrate how to calculate these settings. You will then perform your own calculations and enter protection settings into ACSELERATOR QuickSet SEL-5030 Software. After sending your settings to the relay, you will validate the settings and verify the proper assertion of the elements.
You can also refer to the SEL-387A Instruction Manual (available at http://www.selinc.com) for further information about protection and logic functions.
Page 1 of 9
20120723
Protection Schemes
The SEL-387A allows you to choose transformer differential protection with harmonic blocking, harmonic restraint, or both, providing stability during transformer inrush conditions. Even-numbered harmonics (second and fourth) provide security during energization, while fifth-harmonic blocking provides security for overexcitation conditions.
The SEL-387A has three percentage differential elements: 87R1, 87R2, and 87R3. These elements employ operate (IOP) and restraint (IRT) quantities that the relay calculates from the winding input currents. Tripping occurs if the operate quantity is greater than the curve value for that particular restraint quantity. A minimum pickup level for the operate quantity must also be satisfied. For added security during transformer energization, Slope 2 is used in place of Slope 1 for 10 cycles. The four settings that define the characteristic are as follows: O87P is the minimum IOP level required for operation. SLP1 is the initial slope, beginning at the origin and intersecting O87P at IRT = O87P (100/SLP1). IRS1 is the limit of IRT for SLP1 operation, intersecting where SLP2 begins. SLP2 is the second slope, which must be greater than or equal to SLP1.
With careful selection of these settings, you can closely duplicate the characteristics of existing differential relays that have been in use for many years. The SEL-387A also has three unrestrained differential elements: 87U1, 87U2, and 87U3. The unrestrained elements detect very high differential current that clearly indicates an internal fault. These elements compare the IOP quantity to a setting value (U87P)typically about 10 times TAPand trip if this level is exceeded.
Page 2 of 9
20120723
The unrestrained elements respond only to the fundamental frequency component of the differential current and are not affected by the percentage restraint, harmonic blocking, or harmonic restraint functions.
Transformer Differential
For transformer current differential applications similar to the one illustrated in Figure 2, the SEL-387A offers differential protection that can correctly compensate for the ratio and phase shift of the power transformer.
H1 H3 200:5 A B C H2 H1 H2 H3 X3 X0 X1 X2 X3 X0 X1
X2 2000:5
Figure 2 defines the required connections for a basic transformer differential protection scheme. The CTs located at the high side of the power transformer are connected to relay inputs IAW1, IBW1, and ICW1. The CTs located at the low-side terminals of the power transformer are connected to relay inputs IAW2, IBW2, and ICW2.
205 206
203 204
211 212
209 210
207 208
Transformer Data
Rated 50 MVA Rated high side, 161 kV (DAB) Rated low side, 14.4 kV (wye) High-side bushing CT ratio (wye connected) Low-side bushing CT ratio (wye connected) Neutral bushing CT ratio
Differential (87) Element Settings Page 3 of 9 20120723
Step 1
In the Transformer Differential Elements settings, enable differential protection. E87 = _________________ The relay automatically calculates the Tap 1 and Tap 2 settings based on the transformer MVA data obtained from the transformer nameplate. If the MVA setting is set to OFF, you must calculate the Tap 1 and Tap 2 settings. The following equations are used to calculate the Winding 1 and Winding 2 tap settings and the CT primary currents:
Ipri = MVA 1000 kV 3
TAP =
Step 2
Determine and enter the Restrained Element Operating Current PU in multiples of tap. O87P = __________________ Set high enough to avoid operation because of steady-state CT errors and transformer magnetizing current. The typical O87P range is 0.3 to 0.5. For this example, use the relay default setting O87P = 0.3. Set to approximately 50 percent of the O87P setting. Set longer than the maximum clearing time for external faults.
Step 3
Determine and enter the Restraint Slope 1 Percentage. SLP1 = __________________ To determine the maximum error for setting the percentage of the differential element, consider the following: Relay tap mismatch (this can be 0 with the proper CT ratio selection). Power transformer ratio (nominal tap to minimum tap). No-load taps can be up to 5 percent, and autotransformers are typically 10 percent. Protective relay error (up to 5 percent). CT ratio error (3 to 5 percent). Magnetizing inrush (up to 5 percent).
Page 4 of 9
20120723
Step 4
Determine and enter the Restraint Slope 2 Percentage. SLP2 = __________________ Set Slope 2 in the range of 50 to 70 percent to avoid problems with CT saturation for high fault currents.
Step 5
Determine and enter the Restraint Current Slope 1 Limit. IRS1 = __________________ The suggested IRS1 setting, expressed as a percentage of winding current, is 3.0.
Step 6
Determine and enter the Unrestrained Element Current PU in multiples of tap. U87P = __________________ The instantaneous unrestrained current element is intended to react quickly to very heavy current levels that clearly indicate an internal fault. The typical setting range is from 8.0 to 10.0.
Step 7
Determine and enter the Second-Harmonic Blocking Percentage. PCT2 = __________________ Transformer simulations show that magnetizing inrush current usually yields more than 30 percent of IF2/IF1 (compensated second-harmonic differential current/compensated fundamental differential current) in the first cycle of the inrush. The typical setting range is 12 to 15 percent. A setting of 15 percent usually provides a margin for security.
Step 8
Determine and enter the Fourth-Harmonic Blocking Percentage. PCT4 = __________________ Relays typically use even harmonics to detect inrush conditions and to prevent misoperations resulting from inrush. The largest even-harmonic current component is usually the second harmonic, followed by the fourth harmonic. Use fourth-harmonic blocking to provide additional security against inrush conditions; set PCT4 to less than PCT2.
Step 9
Determine and enter the Fifth-Harmonic Blocking Percentage. PCT5 = _________________ Fourier analysis of transformer currents during overexcitation indicates that a 35 percent fifth-harmonic setting is adequate to block the percentage differential element. To disable fifth-harmonic blocking, set PCT5 to OFF.
Differential (87) Element Settings Page 5 of 9 20120723
Step 10
Determine and enter the Fifth-Harmonic Alarm Threshold. TH5P = __________________ Use the presence of the fifth-harmonic differential current to assert an alarm output during startup. This alarm indicates that the rated transformer excitation current has been exceeded. At full load, a TH5P setting of 0.1 corresponds to 10 percent of the fundamental current.
Step 11
Determine and enter the Fifth-Harmonic Alarm Delay. TH5D = __________________ The TH5D delay setting prevents the relay from indicating the transient presence of fifth-harmonic currents. When TH5P = OFF, TH5D is hidden. Consider triggering an event report if the transformer excitation current exceeds the fifth-harmonic threshold.
Step 12
Determine the need for the dc ratio blocking setting. DCRB = ___________________ Some magnetizing inrush cases contain very little harmonic content but a dc offset. The SEL-387A can detect the dc offset and use it in the blocking (not restraint) logic. The dc ratio blocking feature applies to inrush cases with little harmonic content, but a high dc offset. The measurement principle is that of waveshape recognition, distinguishing between the time constants for inrush current that typically are longer than the time constants for an internal fault. Elements DCBL1, DCBL2, and DCBL3 are combined to form Relay Word bit DCBL, which sets the threshold of the dc ratio blocking function. The factory default is DCRB = N.
Step 13
Determine whether your application requires harmonic restraint and/or harmonic blocking features. Enable Harmonic Restraint and/or Harmonic Blocking accordingly. HRSTR = __________________ Restrained elements (87R1, 87R2, and 87R3) determine whether the IOP quantity is greater than the restraint quantity. This characteristic is modified by increasing the restraint current as a function of the second- and fourth-harmonic content in the input currents for the harmonic restraint elements (87HR1, 87HR2, and 87HR3). Set HRSTR to Y to activate the harmonic restraint element 87HR. A setting of Y defeats common harmonic blocking. IHBL = __________________ While the restrained differential elements are making decisions, a parallel blocking decision process occurs with specific harmonic magnitudes in the IOP quantities. When IHBL is set to N, any differential element will prevent tripping of any restrained differential element.
Page 6 of 9
20120723
Step 14
Verify the trip logic. Relay Word bits 87R and 87U are assigned to the trip TR3 equation. The factory default setting OUT103 is assigned to TRIP3.
Step 15
When you are finished, your settings will be verified in a class discussion.
Figure 4 illustrates the location of the CT for a transformer phase differential protection scheme. The IAW1, IBW1, and ICW1 relay inputs measure the load current on the transformer high side. The IAW2, IBW2, and ICW2 relay inputs measure the load current on the transformer low side.
Page 7 of 9
20120723
For 1.0 per unit (pu) of load flowing through, the primary currents measured by the relay inputs are as follows: IAW1 = 179.3 at 0.00 IBW1 = 179.3 at 120 ICW1 = 179.3 at 120 IAW2 = 2000 at 150.00 IBW2 = 2000 at 30.00 ICW2 = 2000 at 90.00
Step 1 Reset the relay targets by pushing the {TARGET RESET} pushbutton on the relay front panel. Step 2 Clear the Sequential Events Recorder (SER) entries by communicating directly with the relay as follows: Select Communications > Terminal. Establish relay communications, and then issue the SER C command. OR Select Tools > HMI > HMI to access the human-machine interface (HMI) menu in ACSELERATOR QuickSet.
Step 3 After the instructor uses the SEL-AMS to inject current into the relay, verify the following: The relay is correctly measuring the primary values of the currents and voltages. The differential element is stable (IOP values are very small, and IRT values are close to 2.0). There are no targets or SER entries related to the phase differential element.
Page 8 of 9
20120723
Step 1
Reset the relay targets by pushing the {TARGET RESET} pushbutton on the relay front panel.
Step 2
Clear the SER entries. You can perform this task by using either the SER C serial port command or the ACSELERATOR QuickSet HMI.
Step 3
After the instructor uses the SEL-AMS to inject current into the relay, do the following: Issue the MET DIF serial command, or select Meter Differential from the ACSELERATOR QuickSet HMI menu options. Verify that (IOP/IRT) 100 = the SLP1 setting 5 percent.
SEL-387A IOP1 0.37 IRT1 2.37 IOP1F2 0.00 IOP1F4 0.26 IOP1F5 0.26 IOP2 0.37 IRT2 2.38 IOP2F2 0.26 IOP2F4 0.26 IOP2F5 0.00 IOP3 0.37 IRT3 2.37 IOP3F2 0.00 IOP3F4 0.00 IOP3F5 0.00
Operate
(pu)
Restraint
(pu)
Page 9 of 9