Supply fault rms current level (KVA) 8970 (taken from Harmonic calculations)
% Reactance 1
Protective device Moeller NZM…A160
Range 125 160
Short circuit rating 25 kA
Short circuit release 10 * Range max
Max energy let through 75 KA2s
Max short circuit setting 1600 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 1108 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
50 479972 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
25 188989 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
16 151191 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
35 151191 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
4 76795 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
10 34640 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
4 22170 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
2.5 22170 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 38398 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 38398 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 6000 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 6000 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 6000 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 15119 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 15119 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 5542 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 5542 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed
Note device OK
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 2771 Passed Passed
Note device OK