Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
ENGINEERING ADVANTAGE
World's energy consumption 40% of the world's energy consumption is used in buildings*
(*) Sources: European Commission EPBD (point 6, pp1) & US Department of Energys Buildings Energy Data Book
2
ENGINEERING ADVANTAGE
Building structure
(insulation, double glazing, )
HVAC installation
Use of new technologies System approach of hydronic design Shorter pay-back times
Human factor
Avoid interferences with the HVAC system Educate tenants and maintenance team Never-ending task
Best way to save energy Larger energy savings Long pay-back times
Building modifications require adaptation or modernization of the HVAC installation to take into account new heat gains/losses
3
When modifying a HVAC installation one must take into account the capabilities of people using the installation
ENGINEERING ADVANTAGE
ENGINEERING ADVANTAGE
12
Chillers
Coefficient of Performance (COP) is used to indicate chiller efficiency:
Condenser
COP =
Pevaporator Pcompressor
2.5K 4K6
Tr
Ts
Evaporator Chilled water
Heat transfer (and thus COP) is good when Log Mean Temperature Difference between water and refrigerant is kept high
Evaporator refrigerant temperature remains constant Supply water temperature Ts is usually kept constant Thus return water temperature Tr must be kept "high" to keep LMTD high
Tr
Ts
Refrigerant saturated suction temp.
Keeping a high Tr (thus a high T = Ts-Tr) provides higher COP at partial load
ENGINEERING ADVANTAGE
24
Effect of a decrease of the return water temp. on COP Example : Chiller: 200 tons (703 kW) Water condenser temperatures: 29,5/35C Supply temperature of chilled water Ts : 7C
COP
5,2 5 4,8 4,6 4,4 4,2
Copyright TA Hydronics SA. All rights reserved.
4,6 4,4
4,2 4 10,5
11
11,5
12
12,5
13
15%
A reduction of return temperature of chilled water can lead to a 15% drop of the COP
25
ENGINEERING ADVANTAGE
The T through a terminal unit increases when the flow reduces. Thus the return water temperature increases when the flow reduces. Cooling All benefits for chiller COP.
Return temp. Tr
26,0 24,0 22,0 20,0 18,0 16,0 14,0 12,0 10,0 8,0 6,0 0% 20% 40%
60%
80%
100%
ENGINEERING ADVANTAGE
The T through a terminal unit increases when the flow reduces. But the flow through the terminal unit is reduced by bypassing an increasing fraction of the primary flow (at temperature Ts). Thus the return water temperature decreases when the flow reduces !!!
STAD-P
Constant flow
Variable flow
26,0 24,0 22,0 20,0 18,0 16,0 14,0 12,0 10,0 8,0 6,0 0% 20% 40%
Return temp. Tr
Cooling
Variable flow circuit Constant flow circuit
60% 80% 100%
ENGINEERING ADVANTAGE
> qd
open open shut
0 qd
open
> qd
0 qd
Copyright TA Hydronics SA. All rights reserved.
> qd
open
>qd
open shut
open
28
ENGINEERING ADVANTAGE
System load
At 50% load, the total flow in system reaches 73% of the total design flow. This is a 46% increase w.r.t. the required flow (50%) at 50% load. Seasonal flow increase lead to an estimated increased pumping energy consumption equal to +3% of total plant energy consumption
29
3%
ENGINEERING ADVANTAGE
At flow that is near design flow, emitted power does not increase much with the flow Control signal switches on/off when room temperature deviates much beyond the thermostat differential
Room t
Emission
100%
80%
60%
40%
20%
Flow
Design set-point 24 C
q qdesign
P Pdesign
q T P= k
T Tdesign
30
ENGINEERING ADVANTAGE
System load
Below 50% of the load, which represents typically 70% of the cooling season, the return water temperature is degraded by 1.5 to 2C. This will result approximately in a 3 to 4% increase in seasonal chiller energy consumption
31
3%
ENGINEERING ADVANTAGE
On-off control
Return temp. Tr
Return temp. Tr
System load
32
ENGINEERING ADVANTAGE
Renovation of 2 University buildings with a total of 9840 m2 Installed cooling capacity: Building 1 : 1452 tons refrig. Building 2 : 1730 tons refrig. Work performed during summer 2010 Results compared for Oct.-Nov. 2009 vs 2010 DP controllers paired with manual balancing valves installed
33
ENGINEERING ADVANTAGE
2009 2010
Dp controllers at on-off control FCU groups and PAU/AHUs and re-balanced Annualized 22% chiller energy saving
22%
34
ENGINEERING ADVANTAGE
2009
2010
Addition of Dp controllers at FCU groups zones and pressure independent control valves for PAU/AHU and re-balanced Annualized 16.5% chiller energy saving
16%
35
ENGINEERING ADVANTAGE
ENGINEERING ADVANTAGE
3 DP stabilization against large Dp fluctuations in part load 1 Balanced chiller plant 2 Proper fail-safe bypass valve sizing and characteristic
ENGINEERING ADVANTAGE
ENGINEERING ADVANTAGE
ENGINEERING ADVANTAGE
ENGINEERING ADVANTAGE
> Locate VSP sensor at index circuit and adjust set-point to the DP of the most demanding stablized circuit potentially up to 40% pump energy saving > Make use of computerized balancing method and instrument to produce balancing report without manual record of measurements and verfications
ENGINEERING ADVANTAGE
Conclusion
Important energy savings can be achieved by taking care of:
Maintaining cold/warm return water temperature to condensing boilers/chillers (~15%), Having an adequate pressurisation avoiding scaling/fouling in boilers/evaporators (~5-10%).
Stable and accurate room t control gives (~5-20%) energy savings by:
Copyright TA Hydronics SA. All rights reserved.
Avoiding oversizing in on-off systems, Using state-of-the-art thermostatic radiator valves, Sizing of modulating control valves for good minimum authority.
ENGINEERING ADVANTAGE
garry.chui@tahydronics.com tom.pak@tahydronics.com
93
ENGINEERING ADVANTAGE