TECHNICAL DATA CABLE GLAND TYPE INGRESS PROTECTION PROCESS CONTROL SYSTEM : A2F/M & A2F/MF : IP66, NEMA 4X : BS EN ISO 9001

HAZARDOUS AREA CLASSIFICATION GLAND ATEX CERTIFICATION No : SIRA06ATEX1097X, SIRA07ATEX4326X ATEX CERTIFICATION CODE : I M2 Ex d I / Ex e I IEC Ex CERTIFICATION No : IEC Ex SIR.06.0039X IEC Ex CERTIFICATION CODE : Ex d I / Ex e I MA/FT ATEX CERTIFICATION No : SIRA 09ATEX1034U ATEX CERTIFICATION CODE : IM2 Ex d I Mb IEC Ex CERTIFICATION No : IEC Ex SIR.09.0024U IEC Ex CERTIFICATION CODE : Ex d I Mb

ASSEMBLY FITTING INSTRUCTIONS FOR INSTALLATION FOR A2F/M & A2F/MF CABLE GLANDS
CABLE GLAND FOR USE WITH UNARMOURED AND BRAID ARMOURED CABLES IN MINING APPLICATIONS

INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC

INSTALLATION INSTRUCTIONS Installation should only be performed by a competent person using the correct tools. Read all instructions before beginning installation.

SPECIAL CONDITIONS FOR SAFE USE The A2F/M and A2F/MF shall only be used where the temperature, at the point of entry, is between -60C and +130C. The entry component threads may need additional sealing to maintain the ingress protection rating as applicable to the associated equipment to which it will be attached. ACCESSORIES The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer

CABLE GLAND TYPES A2F/M & A2F/MF

20S/16 20S 20 25 32 50S 63S 75S 75 90 63 50 40

16

M16 M20 M20 M20 M25 M32 M40 M50 M50 M63 M63 M75 M75 M90

1/2 1/2 1/2 1/2 3/4 1-1/4 1-1/2 2 2 1

3/4 3/4 3/4 3/4 1-1/4 1-1/2 2-1/2 2-1/2 3 3 2 1

15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0

3.2 3.2 6.1 6.5

8.1 8.7

22.0 24.0 24.0 36.0 41.0 50.0 55.0 60.0 70.0 75.0 79.0 108.0 122.0 138.0 154.0 84.0 27.0

23.8 25.9 25.9 29.2 38.9 44.3 54.0 64.8

18.0 21.0 21.0 26.0 28.0 29.0 30.0 30.0 30.0 32.0 32.0 48.0 55.0 62.0 44.0 27.0 24.0

11.1 23.5 31.0 35.6 41.5 54.0 47.2 17.0

20.0 26.3 32.2 38.2 50.0 56.0 62.0 68.0 80.0 91.0 115.0 98.0 44.1

14.0

11.7

20S16A2F/M1RA 20SA2F/M1RA 20A2F/M1RA 25A2F/M1RA 32A2F/M1RA 50SA2F/M1RA 63SA2F/M1RA 75SA2F/M1RA 75A2F/M1RA 90A2F/M1RA 63A2F/M1RA 50A2F/M1RA 40A2F/M1RA

16A2F/M1RA

20S16A2F/MF1RA 20SA2F/MF1RA 20A2F/MF1RA 25A2F/MF1RA 32A2F/MF1RA 50SA2F/MF1RA 63SA2F/MF1RA 75SA2F/MF1RA 75A2F/MF1RA 90A2F/MF1RA 63A2F/MF1RA 50A2F/MF1RA 40A2F/MF1RA

16A2F/MF1RA

0.051 0.054 0.054 0.059 0.112 0.128 0.168 0.224 0.231 0.360 0.344 0.466 0.395 1.346 1.575 2.322 3.400

Cable Gland Selection Table

Cable Gland Size

Metric

Standard

Entry Threads NPT

Option NPT

Min Thread Length

Diameter of Cable Min Max

Across Flats Max

Across Corners Max

Nominal Protrusio n Length

Ordering Reference A2F/M (Brass Metric)

Ordering Reference A2F/MF (Brass Metric)

Cable Gland A2F/M Weight (Kgs)

59.4 75.6 81.0 85.3 116.6 131.8 149.0 166.3 90.7

A2F/M

2-1/2 2-1/2 3 3 4 -

3-1/2 3-1/2 -

61.1 61.6 76.0 86.0 97.0

100 115 130

M100 M115 M130

100A2F/M1RA 115A2F/M1RA 130A2F/M1RA

100A2F/MF1RA 115A2F/MF1RA 130A2F/MF1RA

All dimensions in millimeters

A2F/M
I, the undersigned, hereby declare that the equipment referred to herein conforms to 94/9/EC directive. Dr Geof Mood - Technical Director - (Authorised Person)

A2F/MF

- A2F Gland for Mining Applications - A2F/M Assembly with Flange Mount Type MA/FT

Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.

0518

Registered Office: Glasshouse Street St. Peters Newcastle upon Tyne NE6 1BS Tel: +44 191 265 7411 Fax: +44 191 265 0581 E-Mail: cmp@cmp-products.co.uk Web: www.cmp-products.com Company Number:

CMP PRODUCTS

www.cmp-products.com

Logos shown for illustration purposes only. Please check certification for details

CMP Document No. FI443 Issue 1 07/11

A2F/MF

INSTALLATION INSTRUCTIONS FOR CMP GLAND TYPE A2F/M & A2F/MF


CABLE GLAND COMPONENTS
1. 2. 3. 4. Entry Item Seal Seal Nut Optional Flange Mount
1 2 3

DUBAI HOUSTON NEWCASTLE SINGAPORE SHANGHAI PUSAN PERTH

www.cmp-products.com
3. Determine the conductor length required to suit the installation and prepare the cable accordingly, removing part of the outer sheath where required to reveal the insulated conductors.

4. Slacken the seal nut (3) to relax the seal (2).

PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION

1. It is not necessary to dismantle the gland any further than illustrated below.

A2F/M

A2F/MF 5. Pass the cable through the gland to the desired position, then tighten the seal nut by hand until resistance is felt (when the seal contacts the cable). Tighten with a spanner one further turn.

2. Fit the gland into the equipment and fully tighten the entry item (1). (Bolt flange to equipment on the A2F/MF version).

A2F/M

A2F/MF

www.cmp-products.com