CONTENTS
06 Clean Room 07 Details 08 Reliability 09 Technical Details 10 Test 11 Installation and Maintenance
General
We provide excellent solutions for our customers requirements all around the world with a wide variety of SF6 Gas Circuit Breaker technologies. Our experience in the field of Gas Circuit Breaker technology, innovative design, certified comprehensive quality management with ISO 9001 and exemplary clean-room manufacturing ensure that our circuit-breakers satisfy the customers highest demands while achieving the required levels of economic efficiency and environmental compatibility. Our current range of products includes high voltage GCBs from 145kV to 362kV with short circuit ratings up to 63KA.
Special Features
High Reliability
Enhanced insulating properties by means of sealed metal enclosure filled with SF6 gas
Compact dimensions significantly reduce space requirements Safety oriented design with hermetically sealed enclosure
Environmental Compatibility
Prevention & reduction of SF6 emission with HICOs superb technology and process
Clean Room
Details
A : Nozzle & Arcing Contact Arc Quenching is carried out under highly-pressured SF6 gas compressed by Puffer System. The excellent endurance anti-arc performance and simple structure of interrupter enable it to interrupt the rated peak currents more than 20 times. B : Main Contact The stationary & moving contacts consisting of single body structure assembly reduces the number of parts and make maintenance & inspection simple.
C~D : Preventing Particle Contamination Heli-Coils inserted into screw tap of inner parts eliminate particles during assembly. E ~ F : Convenience of Maintenance & Inspection Supporting point of stationary part of interrupter is separated from the cover to facilitate checking of interior parts.
Standard
Below RH 65 203 Below 100,000/ft3(0.5)
Interrupting Analysis
6/7
Reliability
Technical Details
Interrupter
The interrupter of the HICO Gas Circuit Breaker has high reliability for all interrupting duties and satisfies the latest standards of IEC and IEEE. Arc quenching takes place under 71PSIG of SF6 gas pressure.
SF6 GAS Live Parts BCT Insulators Dead Parts
362kV 50/63kA
Adopting SINGLE PUFFER System reduces the number of parts and makes the interrupter simple and reliable. Closing resistor can be provided initially and removed as requirements change.
362HCBP50
362 1300 555 2000 / 3000 / 4000 50 2 1680 43000 / 19500 617 / 280
362HCBP63
362 1300 555 2000 / 3000 / 4000 63 2 1680 43000 / 19500 617 / 280
Operating Mechanism
Technical Data
Dimension in inches
A 105-1/2 F 276 B 135-3/4 G 102-3/4 C 169 H 69 D 203-1/4 K 216-1/2 E 218 L 183-1/2
Features
Dead tank type Three tank construction Porcelain or Composite bushings Two-cycle interrupting time Exterior bushing current transformers Separated SF6 gas systems per phase Single interrupter per phase ASME pressure vessel certification for unfired pressure vessels Shipped fully assembled except bushing
Proof
Tested and verified for 90% short line fault Tested and verified to meet IEEE standard Fully factory tested before shipment
Options
High-creep and high-altitude bushings Tank heater for low temperature applications Pre-insertion resistors Synchronous switching Condition monitoring Capacitors only 63kA
Operating mechanism of the 362kV GCB is of the pneumatic type with proven capability and reliable operation history. It satisfies the operating duty O-0.3s-CO-3m-CO required by IEC and IEEE. It is designed and manufactured to interrupt in less than two cycles. Interrupter is opened using compressed air and is closed using energy stored in coil-spring charged by open operation. It can be opened and closed manually and safely by using a simple jacking system.
Mechanical operations
Pneumatic operating mechanism Duty cycle O-0.3sec-CO-3min-CO
8/9
Test
All Circuit Breakers are designed, built, and tested in accordance with the latest versions of ANSI & IEEE Standards C37.04, C37.06, C37.09. HICO seeks to exceed all established testing criteria by carrying out additional tests we consider essential in producing a higher reliability product.
1. Professional maintenance system ensures life-long reliability. 2. HICOs comprehensive service offerings, prompt response time and efficient & professional support are in place around the clock all around the world. 3. Following factory assembly and testing, the Gas Circuit Breaker is disassembled for packing and shipment. 4. All breakers supplied to North American sites are inspected, assembled, and tested at HICO Americas U.S. facility. Where possible, breakers are shipped assembled on conventional low-bed trucks to the customers site. HICO America also provides installation assistance and field support. The equipment is designed to minimize the number of disassembled parts, while considering performance, maintenance, ease of installation and transportation. The disassembled parts are packed as complete units whenever possible to lower the construction costs at the sites. To maintain the highest criteria of operating reliability, a routine inspection and maintenance schedule may be recommended.
HICO GCB in Garland, USA
Testing Laboratory
Transportation in USA
10/11