Electrical diagrams
D-2
0
D-4
0
Masterpact NT and NW
Communications of the 24 V DC External power supply AD module Communications option 24 V DC external power supply Earth-fault and earth-leakage protection Neutral protection Zone selective interlocking Additional characteristics Catalogue numbers and order form
D-1
Electrical diagrams
The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in normal position.
Power
DB101401
Control unit
Remote operation
Control unit
Terminal block marking Com
E5 E6 E3 E4 E1 E2
Remote operation
UC2 UC3
F2+ VN F1
UC1
SDE2 /
184 182 181 / /
Res
K2
SDE1
84 82
MN
D2
/ MX2
/ C12
MX1
C2 C3
XF
A2 A3 A1
PF
254 252 251
MCH
B2 B3 B1
Z5 M1 M2 M3 Z3 Z4 Z1 Z2 T3 T4 T1 T2
K1
81
D1
C11
C1
A
b b
P
b b
H
b b
Control unit Com : E1-E6 communication UC1 : Z1-Z5 zone selective interlocking Z1 = ZSI OUT SOURCE Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M1 = Vigi module input (Micrologic 7) UC2 : T1, T2, T3, T4 = external neutral M2, M3 = Vigi module input (Micrologic 7) UC3 : F2+, F1 external 24 V DC power supply VN external voltage connector (must be connected to the neutral with a 3P circuit breaker) UC4 : External Voltage Connector (PTE option)
or
Remote operation SDE2 : fault-trip indication contact or Res : remote reset SDE1 : fault-trip indication contact (supplied as standard) MN : undervoltage release or MX2 : shunt release MX1 : shunt release (standard or communicating) XF : PF : closing release (standard or communicating) ready-to-close contact
b b b b
b b b b b
b b b b b
b b
b b
M6C : 6 programmable contacts to be connected to the external module M6C) ext. 24 V DC power supply required.
D-2
Electrical diagrams
Indication contacts
DB101406 DB101407
Chassis contacts
Indication contacts
OF4
44 42 41
Chassis contacts
OF1
14 12 11
OF3
34 32 31
OF2
24 22 21
CD2
824 822 821
CD1
814 812 811
CE3
334 332 331
CE2
324 322 321
CE1
314 312 311
CT1
914 912 911
Chassis contacts
CD2 : disconnected position CD1 contacts CE3 : CE2 CE1 connected position contacts CT1 : test position contacts
DB117043
Key: drawout device only. XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard. interconnected connections (only one wire per connection point).
D-3
Electrical diagrams
The diagram is shown with circuits deenergised, all devices open, connected and charged and relays in normal position.
Power
DB101401
Control unit
Remote operation
Control unit
Terminal block marking Com
E5 E6 E3 E4 E1 E2
Remote operation
UC2 UC3
F2+ VN F1
UC1
UC4
V3 V2 V1
M2C / M6C
484 474 471 / / / Q3 Q2 Q1
SDE2 /
184 182 181 / /
Res
K2
SDE1
84 82
MN
D2
/ MX2
/ C12
MX1
C2 C3
XF
A2 A3 A1
PF
254 252 251
MCH
B2 B3 B1
Z5 M1 M2 M3 Z3 Z4 Z1 Z2 T3 T4 T1 T2
K1
81
D1
C11
C1
A
b b
P
b b
H
b b
Control unit Com : E1-E6 communication UC1 : Z1-Z5 zone selective interlocking Z1 = ZSI OUT SOURCE Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M1 = Vigi module input (Micrologic 7) UC2 : T1, T2, T3, T4 = external neutral M2, M3 = Vigi module input (Micrologic 7) UC3 : F2+, F1 external 24 V DC power supply VN external voltage connector (must be
Remote operation SDE2 : fault-trip indication contact or Res : remote reset SDE1 : fault-trip indication contact (supplied as standard) MN : undervoltage release or MX2 : shunt release MX1 : shunt release (standard or communicating) XF : PF : closing release (standard or communicating) ready-to-close contact
b b b b
b b b b b
b b b b b
b b
b b
connected to the neutral UC4 : External Voltage Connector (PTE option) M2C : 2 programmable contacts (internal relay) ext. 24 V DC power supply required
or
M6C : 6 programmable contacts (to be connected to the external module M6C) ext. 24 V DC power supply required
D-4
Electrical diagrams
Indication contacts
DB101409
Chassis contacts
Indication contacts
OF4 44 42 41 OF3 34 32 31 OF2 24 22 21 OF1 14 12 11 OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 244 242 241 234 232 231 224 222 221 214 212 211 144 142 141 134 132 131 124 122 121 114 112 111
Chassis contacts
CD3 834 832 831 CE6 364 362 361 CD2 824 822 821 CD1 814 812 811 CE4 344 342 341 CE3 334 332 331 CE2 324 322 321 CE1 314 312 311 CT3 934 932 931 CE9 394 392 391 CT2 924 922 921 CT1 914 912 911 CE7 374 372 371
or
or
or
or
or
or
or
or
or
CE5 354 352 351
or
CE8 384 382 381
EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 248 246 245 238 236 235 228 226 225 218 216 215 148 146 145 138 136 135 128 126 125 118 116 115
Indication contacts
OF4 : OF3 OF2 OF1 ON/OFF indication contacts OF24 or EF24 OF23 or EF23 OF22 or EF22 OF21 or EF21 OF14 or EF14 OF13 or EF13 OF12 or EF12 OF11 or EF11 Combined connected-deconnected indication contacts
Chassis contacts
CD3 CD2 CD1 or CE6 CE5 CE4 disconnected CE3 position CE2 contacts CE1 connected position contacts connected position contacts CT3 CT2 CT1 or CE9 CE8 CE7 or CD6 CD5 CD4 test position contacts
Key: drawout device only. XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard. interconnected connections (only one wire per connection point).
D-5
Electrical diagrams
Masterpact NT and NW
Communications of the 24 V DC External power supply AD module
None of the control-unit protection functions require an auxiliary source. However, the 24 V DC external power-supply (AD module) is required for certain operating congurations as indicated in the table below. Circuit breaker Voltage measurement inputs Closed Powered Open Powered Not powered
Yes No Yes Yes (3) No Yes
M2C, M6C programmable contacts option Yes Yes Protection function No No No (2) Display function No (1) Time-stamping function No No Circuit-breaker status indications No No and control via communications bus Identication, settings, operation No (2) No (1) and maintenance aids via communications bus (1) Except for Micrologic A control units (if current < 20 % In). (2) Except for Micrologic A control units. (3) Time setting is manual and can be carried out automatically by the supervisor via the communications bus.
DB117190
Note: In case of using the 24 V DC external power supply (AD module), maximum cable length between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters. The BAT battery module, mounted in series upstream of the AD module, ensures an uninterrupted supply of power if the AD module power supply fails. The voltage measurement inputs are standard equipment on the downstream connectors of the circuit breaker. External connections are possible using the PTE external voltage measurement input option. With this option, the internal voltage measurement inputs are disconnected and terminals VN, V1, V2, V3 are connected only to the control unit (Micrologic P and H only). The PTE option is required for voltages less than 220 V and greater than 690 V (in which case a voltage transformer is compulsory). For three-pole devices, the system is supplied with terminal VN connected only to the control unit (Micrologic P and H). When the PTE option is implemented, the voltage measurement input must be protected against short-circuits. Installed as close as possible to the busbars, this protection function is ensured by a P25M circuit breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117). This voltage measurement input is reserved exclusively for the control unit and must not ever be used to supply other circuits outside the switchboard.
D-6
Electrical diagrams
Masterpact NT and NW
Communications of the 24 V DC External power supply AD module
Wiring diagrams
DB114653 DB1145230
Power supply wiring for Micrologic trip unit and M6C module.
Connection
The maximum length for each conductor supplying power to the trip unit or M6C module is 10 m. Do not ground F2+, F1-, or power supply output: b the positive terminal (F2+) on the trip unit must not be connected to earth ground b the negative terminal (F1-) on the trip unit must not be connected to earth ground b the output terminals (- and +) of the 24 V DC power supply must not be grounded. Reduce electromagnetic interference: b the input and output wires of the 24 V DC power supply must be physically separated as much as possible b if the 24 V DC power supply wires cross power cables, they must cross perpendicularly. If this is not physically possible, the power supply conductors must be twisted together b Power supply conductors must be cut to length. Do not loop excess conductor. Use only one 24 V DC power supply for each Micrologic trip unit. Connect external 24 V DC power supply only per the following wiring diagrams.
D-7
Electrical diagrams
Masterpact NT and NW
DB101417
(1) Drawout device equipped with Modbus chassis COM. (2) Drawout device equipped with Digipact chassis COM.
D-8
Electrical diagrams
Masterpact NT and NW
Communicating switchboard
This conguration provides remote display and control of Masterpacts equipped with the Modbus or Digipact COM module. The Digipact bus can be combined with the Modbus bus.
DB117191
D-9
Electrical diagrams
Masterpact NT and NW
Earth-fault and earth-leakage protection Neutral protection Zone selective interlocking
D-10
Electrical diagrams
Masterpact NT and NW
Earth-fault and earth-leakage protection Neutral protection Zone selective interlocking
Earth-leakage protection
DB101415 DB101420
Connection of the rectangular-sensor secondary circuit Use the cable shipped with the rectangular sensor.
Neutral protection
b three pole circuit breaker: v neutral protection is impossible with Micrologic A v Masterpact equipped with Micrologic P or H v the current transformer for external neutral is necessary (the wiring diagram is identical to the one used for the residual earth-fault protection) b four pole circuit breaker: v Masterpact equipped with Micrologic A, P or H v the current transformer for external neutral is not necessary.
Note: the maximum permissible distance between two devices is 3000 m. A downstream circuit breaker can control up to ten upstream circuit breakers.
D-11