Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
, Chatham House
Calculation/Sketch
CV2 FACILITIES UPGRADE
MP306
Project
Project No.
Designed by
ND
Date
Sheet
25 SEPTEMBER 2004
Circ:
of
FN/OR/AGR/ND
DUCT
SECTION
CFM
SIZE (MM)
LENGTH
DIA.
FT.
800
E
FT.
FITTINGS
B
Br
R
FT.
FT.
FT.
EQUIV.
TOTAL
AIR
FRICTION
EQUIV. VELOCITYDROP/100 FT
fpm
IN W.G.
AC SUPPLY DUCT
1
28,000
800
874.5
2.0
6.6
5.0
5.0
11.6
4195
0.48
28,000
1.5
4.9
0.0
4.9
1193
0.02
28,000
2000
600
1147
49.4
162.1
75.0
237.1
2437
0.13
22,400
1800
600
1096
5.0
16.4
30.0
5.0
35.0
51.4
2137
0.11
16,800
1400
600
980.3
5.0
16.4
30.0
5.0
35.0
51.4
2003
0.11
11,200
1000
600
840
5.0
16.4
30.0
5.0
35.0
51.4
1819
0.11
5,600
600
600
655.9
5.0
16.4
30.0
5.0
35.0
51.4
1492
0.10
3,360
500
500
546.6
3.0
9.8
45.0
54.8
1289
0.10
2,240
500
350
455.5
5.5
18.0
15.0
5.0
20.0
38.0
1237
0.12
10
1,120
350
300
354
5.5
18.0
15.0
5.0
20.0
38.0
1024
0.11
11
1,120
350
300
354
2.0
6.6
30.0
36.6
1024
0.11
12
1,120
350
300
354
2.0
6.6
0.0
6.6
1024
0.25
75.0
15.0
30.0
30.0
AC RETURN DUCT
12
5,000
760
500
670.2
4.0
13.1
15.0
30.0
13
5,000
760
500
670.2
5.0
16.4
15.0
14
10,000
1100
600
878.1
5.0
16.4
15.0
15
15,000
1500
600
1011
20.5
67.3
60.0
45.0
58.1
1276
0.08
5.0
20.0
36.4
1276
0.08
5.0
20.0
36.4
1486
0.07
60.0
127.3
1681
0.08
Abbreviations:
15 Ft.
VOLUME DAMPER ( x 3 )
30 Ft.
BACKDRAFT DAMPER
15 Ft.
FIRE DAMPER
5 Ft.
S:\MPI\MP408\2 AHUS-2\178420635.xls.ms_office\ND
Date: 25 September 2004
/File
FRICTION
DROP
IN W.G.
0.056
0.001
0.304
0.055
0.056
0.057
0.053
0.055
0.044
0.042
0.041
0.016
0.779
0.044
0.028
0.026
0.097
0.195
0.779
0.375
0.400
0.200
0.150
0.195
0.250
0.200
0.150
2.700
0.135
2.835
S:\MPI\MP408\2 AHUS-2\178420635.xls.ms_office\ND
Date: 25 September 2004
S:\MPI\MP408\2 AHUS-2\178420635.xls.ms_office\ND
Date: 25 September 2004