Transformer
Load Short Circuit Calculator
Simple Calculations
Detailed Calculations
Transformer Tables
X/R1 =
20000
10
Transformer Data
Capacity:
kVA=
Transformer Impedance:
%Z=
Impedance Tolerance:
%=
X/Rt=
5.75
12
I(xfrmr)=
4558 Amps
Calculated
%Z1=
kVAt X 100%
SCkVA1
478046 kVA
0.62755 %Z
%Z1 x sin[arctan(X/R1)] =
%R1 =
%X1
X/R1
0.62444
0.06244
%Zt x sin[arctan(X/Rt)] =
%Rt =
%Xt
X/Rt
5.65540
0.47128
6.27984
0.53373
%Ztot =
6.30248
100
%Ztot
x I(xfrmr) =
Resistance/Reactance Ratio:
72,321 Amps
X/R2 =
11.77
Calculated
Calculated
2279
Amps =
9,116 Amps
Calculated
SC Amps2 + SCAmps(motor) =
81,437 Amps
Calculated
Transformer
Load Current and Short Circuit Calculator
Go To Detailed Calculations
Go to Main Sheet
Click above if you wish to include X/R ratios and better Utility information.
Choose from the drop down menue or fill in the blnk were required.
Red triangles indicate additional comments.
Transformer Type
Transformer KVA
kVA
Secondary Voltage
Volts
Impedance Tolerance
Motor load
% of xfmr kVA
3,007 Amps
Calculated
Maximum SC Current
56,218 Amps
Calculated
68,247 Amps
Calculated
133 %
Calculated
3,999 Amps
Calculated
Revision 2
July 2 ,1996
kVA
40000
25000
20000
15000
10000
7500
5000
4000
3750
3000
2500
2000
1500
1000
750
500
300
Amps = kVA X
kVA
10000
7500
5000
4000
3750
3000
2500
2000
1500
1000
750
524
393
262
209
196
157
131
96
72
48
36
kVA
10000
7500
5000
4000
3750
3000
2500
2000
1500
1000
750
GE Industrial Systems
Page 4
1.25 X FA
1.25
1.25
1.25
1.25
1.25
1.25
6,392
1.15
4,794
1.15
3,196
1.15
2,397
1.15
fan rating
5,324
3,918
2,939
1,959
1,469
1.25 X FA
1.25
1.25
1.25
1.25
1.25
1.25
1.15
5,369
1.15
3,579
1.15
2,685
1.15
Revision 2
July 2 ,1996
g
kVA
5000
4000
3750
3000
2500
2000
1500
1000
750
500
300
kVA
5000
4000
3750
3000
2500
2000
1500
1000
750
500
300
kVA
5000
4000
3750
3000
2500
2000
1500
1000
750
500
300
380 V
208 V
6,069
5,058
4,046
3,035
2,023
1,517
1,012
607
5,544
3,696
2,772
1,848
1,109
5,816
4,653
3,490
2,327
1,745
1,163
698
6,376
4,251
3,188
2,125
1,275
5,260
3,945
2,630
1,973
1,315
789
7,207
4,805
3,604
2,402
1,441
GE Industrial Systems
Page 5
Revision 2
July 2 ,1996
g
kVA
5000
4000
3750
3000
2500
2000
1500
1000
750
500
300
13,800 V
235
188
176
141
117
94
70
47
35
23
14
12,470 V
260
208
195
156
130
104
78
52
39
26
16
12,000 V
270
216
202
162
135
108
81
54
40
27
16
4,160 V
778
622
584
467
389
311
233
156
117
78
47
480 V
380 V
208 V
5,395
5,058
4,046
3,372
2,697
2,023
1,349
1,012
674
405
5,111
4,259
3,407
2,556
1,704
1,278
852
511
6,225
4,669
3,112
2,334
1,556
934
Dry type
Fans = 133%
115deg rise = 115%
80deg rise = 130%
Cast coil
Fans = 140%
For some manufacturers can vary from 133% to 150%.
Liquid fill primary substation 12MVA and larger
Two levels of fans are available each 33% of base kVA., 166% max.
55/65 deg rise rating provides an additional 12% for a maximum of 186%.
Notes:
*Padmount transformers larger than 2500 kVA are not specifically described in the ANSI standards
neither are fan cooled ratings. Installation of fans would specifically contravene the tamper resistant requirements of the ANSI standards. Fans are not recommended for Padmounted transformers.
*Padmount transfomers loadbreak separable connectors are limited to 200 amperes maximum.
*Padmount transfomers dead front primary bushings are limited to 600 amperes maximum.
*Padmount primary under oil switches are limited to 400 amperes maximum.
*Padmount transformer's internal fuses are very limited above 1500kVA, separate protection is often
required.
All transformer secondaries are, generally, limited to 5000 amperes maximum.
For all 480V transformers 3000 kVA & larger take consideration of secondary short circuit current
as it could exceed 65,000 amperes and hence require special secondary distribution equipment.
Motor contribution not included !
GE Industrial Systems
Page 6
Revision 2
July 2 ,1996
(Transformer nominal full load current/%Z) X 100 X 1.075 = Short circuit current.
with infinite short circuit kVA available on primary.
Example:
1
nominal current 2500kVA at 480V is 3,011 amps, nominal Z% is 5.75
SCA = (3,011/5.75) X 100 X 1.075 = 56,293 amps symmetrical RMS
2
If primary short circuit current is limited it can be incorporated into the calculations
as follows:
SSCA = TFLC/((TkVA/PSCkVA)+(Z% X 0.925/100))
SSCA = Secondary short circuit amps.
TFLC = Transformer full load current, secondary.
TkVA = Transformer kVA.
PSCkVA = Primary short circuit kVA. (In medium and high voltage parlance
short circuit currents are expressed in MVA or kVA)
Example:
1
Above 2500kVA with 400MVA available at medium voltage primary.
SSCA = 3,011/((2500/400,000) +(5.75 X 0.925/100)
SSCA = 3,011/((25/4,000) + (0.0532))
SSCA = 3,011/0.05945
SSCA = 50,650 A RMS symetrical
2
An additional consideration are motor loads connected on the low voltage side of the transformer.
The conservative way to take motor contribution into consideration is to use the full load current of
all the motors connected, multiply by 4 and add to the transformer supplied short circuit current.
Note that above 2500 kVA you can easily have more than 65 kAIC!
GE Industrial Systems
Page 7