GUtech _ Main Building Mechanical Services

1. HVAC air ducts running without sufficient supports, not acceptable.

2. HVAC air ducts with poor

quality cladding works, not acceptable.

3. HVAC large ducts supported

on the AHU with Polyurethane foam (Thermocole) , not acceptable.

4. AHU flexible connection

seems to be twisted, not acceptable.

5. HVAC duct supported on

Polyurethane foam Thermocole) , not acceptable.

6. Unprofessional non-

standard way of duct work supporting, not acceptable.

7. Unprofessional non-

standard way of duct work supporting, not acceptable.

8. HVAC large ducts running without sufficient supports, not acceptable.

9. Damaged HVAC duct and thermal insulation, not acceptable.

10. Volume control damper penetrated into the GI duct and its thermal insulation, not acceptable.

11. Poor way of site management, not acceptable.

12. Electrical cables are not properly tied, not acceptable.

13. AHU flexible connection

seems to be twisted and damaged, not acceptable.

14. HVAC Duct and thermal

insulation got cut and damaged by its supports, not acceptable.

15. Chilled water pipes supported on the duct works and the duct supported on the masonry block, poor way of installation, not acceptable.

16. Chilled water pipes

supported ineffectively, not acceptable.

17. Unprofessional way of equipment / ductwork installations, not acceptable.

18. Chilled water pipes sitting

on the HVAC duct, not acceptable.

19. Fresh air intake duct on the

roof with no sand trap louver or temporary protection arrangement, not acceptable.

20. HVAC Duct and thermal

insulation got cut and damaged by its supports, not acceptable.

21. AHU flexible connection got

pressed and damaged due to insufficient supports, not acceptable.

22. Chilled water pipes with no

sufficient supports, not acceptable.

23. Chilled water pipes with no

sufficient supports. Duct end damaged by support, not acceptable.

24. Inconsistency in providing

chilled water pipe supports, not acceptable.

25. Duct and thermal insulation

damaged by supports, not acceptable.

26. Application of sealant with

no care or quality check, not acceptable.

27. Fresh air intake with no

louver or protection, not acceptable.

28. HVAC Duct sitting on the

AHU and not properly aligned or supported, not acceptable.

29. HVAC duct support

penetrated in to the insulation, unprofessional way of duct work installation, not acceptable.

30. Large HVAC duct sagging

due to no supports, not acceptable.

31. Unprofessional way of

services installation, not acceptable.

32. Undersized supporting

elements, not acceptable.

33. Thermal insulation got cut,

no quality check observed at site, not acceptable.

34. Installation of equipment and fresh air intake arrangement, absolutely not acceptable.

35. Large HVAC ducts running

with insufficient / undersized supports, not acceptable.

36. HVAC duct supported by

fire sprinkler pipe, not acceptable.

37. HVAC duct work and its

thermal insulation damaged, not acceptable.

38. HVAC duct work and

insulation damaged and supported on the AHU, not acceptable.

39. Chilled water insulation got

damaged and accessories start rusting, not acceptable.

40. Chilled water insulation got

damaged and flanges start rusting, not acceptable. Thermal insulation to be replaced with new.

41. Chilled water insulation got

damaged and flanges start rusting, not acceptable. Thermal insulation to be replaced with new.

42. AHU condensates drain pipe

termination, not acceptable.

43. Undersized (thin and

smaller) anti vibration pads, not acceptable.

44. Unprofessional way of duct

work installation, not acceptable.

45. Unprofessional way of duct

work supports, not acceptable.

46. Unprofessional way of duct

work supports, not acceptable.

47. Unprofessional way of duct

work supports, not acceptable.

48. Unprofessional way of duct

work supports, not acceptable.

49. Unprofessional way of duct

work supports, not acceptable.

50. Unprofessional way of duct

work supports, not acceptable.

51. Unprofessional way of

equipment/duct work supports, not acceptable.

52. Unprofessional way of

equipment/pipes supports, not acceptable.

53. Damaged thermal insulation

and regulating valve, not acceptable and to be replaced with new.

54. Damaged thermal insulation

and regulating valve, not acceptable and to be replaced with new.

55. Damaged thermal insulation

and regulating valve, not acceptable and to be replaced with new.

56. Rain water outlet not

protected as required, not acceptable.

57. Fresh air intake duct

supported with Thermocole, unprofessional way of site supervision not acceptable.