KVA no of batteries
X X
X X
250kva
250 48
X X
1000 0.95
X X
0.8 6
200000 = 273.6
730.9942 watts
refering the battery chart there is no single 12V battery block which can support 730 watts ,therefore divide it by 2 ie 730.99/2 = 365 watts . Now refering the battery chart @ 1.75V end cell voltage for 30 min backup verses ESC 200 12 (200AH block) gives you 399 watts which is nearest available watts that give you 30min backup Backup achieved = wattage as per chart X backup time actual wattage achieved = 399 X 30 = 365 2 strings of 200AH gives you 32.73 min backup 80kva 32.79452 min
80 X 48 X
1000 x 0.95 X
0.8 = 6
64000 = 273.6
233.9181
Now refering the battery chart @ 1.75V end cell voltage for 30 min backup verses ESC 120 12 (120AH block) gives you 238 watts which is nearest available watts that give you 30min backup Backup achieved = 238 X 30 = 233.91 1 strings of 120AH gives you 30.52 min backup 40kva 30.52456 min
40 48
1000 0.95
0.8 6
32000 = 273.6
116.9591
Now refering the battery chart @ 1.75V end cell voltage for 30 min backup verses ES 65 12 (65AH block) gives you 132 watts which is nearest available watts that give you 30min backup
Backup achieved
132 X 116.95
30 =
33.86062 min
X X
250KVA
250 1.75
X X
refer the cable sizing chart for 415Amp (nearest available to achieved discharge current 41 difficult to terminate.Therefore divide 417/2 = 208.5Amps.Now again refering a chart we n As we are connecting 2 strings of battery we need 8 runs of 70 sqmm cable for 250kva ups
80KVA
80 1.75
X X
refer the cable sizing chart for 138Amp (nearest available to achieved discharge current 13
40KVA
40 X 1.75 X
refer the cable sizing chart for 62Amp (nearest available to achieved discharge current 66.8
X X
0.8 no of 2V cells
1000 0.95
X X
0.8 288
200000 = 478.8
417.7109 amps
to achieved discharge current 417.7 Amps) we require 185sq mm cable which becomes more thicker and s.Now again refering a chart we need 2x70sqmm 2 run per battery bank ( 4 runs of 70sqmm per battery bank) s of 70 sqmm cable for 250kva ups.
1000 0.95
X X
0.8 288
64000 = 478.8
133.6675 amps
to achieved discharge current 133.66 Amps) we require 50sq mm cable 2 runs per battery bank
1000 X 0.95 X
0.8 = 288
32000 = 478.8
66.83375 amps
to achieved discharge current 66.88 Amps) we require 16sq mm cable 2 runs per battery bank