SPP- 43
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 1/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Contents
Preface ................................................................................................. 3 1. Customer or Operator Services ..................................................... 6 2. Alcatel Services............................................................................... 8 3. General specifications of product ............................................... 10 4. Site preparation and supply requirements for Customer or Operator ............................................................................................. 15 5. Installation and supply requirements for Alcatel ....................... 24 Appendix A: Installation help: Site cabling raised floor configuration with 1 A925 TC rack, 1 power supply, 1 DDF, 1 PC tool, 1 ground plate ..................................................................... 26 Appendix B. Installation help: Site cabling cable tray configuration with 2 x A925 TC racks, 2 power distribution box, 2 DDF, 1 PC tool, 1 OMC-R, X25 switch, 1 ground plate ........ 28 Abbreviations .................................................................................... 30
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 2/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Preface
Purpose The document defines the conditions regarding site preparation, for installing
EVOLIUM A925 Transcoder and activities to be handled by Customers and Alcatel Services .
Handover of site For documents relating to handover of RCD site before installation of RCD
equipment see SPG-07.
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 3/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
History
Date 00/03/22 Edition 01 Comments Released. Remarks from G. Crassin, J. Fischle, G. Lefebvre, D. Renaudeau. 00/03/10 01 Second proposal. Remarks from G. Crassin, D. Crehan, JP. Degremont, K. El Naggar, G. Lefebvre, D. Renaudeau. Introduction of X25 switch. 00/01/13 01 Creation , first proposal
Audience
Alcatel Staff (Intermediate level) Installers Customer and Alcatel services
Assumed knowledge
You must have a basic understanding of the following BSS Alcatel operations Site Engineering methods
Related documents
Sigle SPG-07 Title of document Specification of documents relating to handover of RCD site before installation of RCD equipment SPG-10 All-in-One Alcatel Service for Site Engineering. 8BL 00703 0010 DRZZA Alcatel number 8BL 00703 0006 DRAGA
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 4/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Document Structure
This section provides a summary of the contents of every chapter. Chapter 1 : Chapter 2 : Chapter 3 : Chapter 4 : Operator Chapter 5 : Installation and supply requirements for Alcatel Customer or Operator Services Alcatel Services General specifications of product Site preparation and supply requirements for Customer or
Appendix A : Installation help, site cabling raised floor configuration with 1 A925 TC rack, 1 power supply, 1 DDF, 1 PC tool, 1 ground plate Appendix B : Installation help, site cabling cable tray configuration with 2xA925 TC racks, 2 power distribution box, 2 DDF, 1 PC tool, 1OMC-R, X25 switch, 1 ground plate Abbreviations : Acronyms encountered within the document.
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 5/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 6/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
1.1 - Services to be The customer or operator is responsible for choosing the site and for all performed preparation work. The main services are as follows:
Site Preparation of site. (refer to SPG-10) (all-in-One Service: Environment) Qualification and checking Power supply (all-in-One Service: Environment) Earth
Qualification and checking PCM links (all-in-One Service: Cable) Main supplies Lighting (all-in-One Service: Environment) Circuit breaker Lightning protection Power distribution box : 48 or 60 V and 220VAC Ground bar/plate Main supplies DC power and ground cable (all-in-One Service: Cable) Cable way runs from the infrastructure to each TC PCM network termination (NTL) upline if necessary PCM distributor (DDF) Installation Of main supplies, (all-in-One Service: Environment) (all-in-One Service: Environment) Installation Of main supplies, (all-in-One Service: Cable) (all-in-One Service: Cable)
All services not provided by Customer or Operator shall be treated as additional Alcatel services.
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 7/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
2. Alcatel Services
This chapter describes the services to be supplied by Alcatel. 2.1 - Services to be performed
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 8/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
2.1 - Services to be Alcatel installs the rack . The main services are listed hereafter: performed
Supplying installation kits Basic installation kit. (All-in-One Service: Assemble) PCM cable from Alcatel equipment to DDF, optional. Power and ground cables, optional. X21 cable for X25 extraction in case of collocated OMC-R. DDF (contact to insert), optional. Installation Installation of A925 TC rack. (All-in-One Service: Assemble) Installation of PCM cable. Installation of power and ground cable cables, optional. Installation of DDF, optional. Commissioning Commissioning of A925TC. (All-in-One Service: Acceptance of A925TC. Commissioning)
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 9/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 10/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
3.2 - The environmental conditions define the climatic requirements (air temperature, Environmental humidity, etc.) that apply to the unit in normal storage and operation. They also specifications specify requirements concerning contaminating products and electromagnetic
considerations. Climatic requirements The EVOLIUM A925 Transcoder is compliant with the following requirements: - For storage ETS 300 019-1-1 class 1.1
Conditions are valid for the non-packed equipment (rack). Icing and frosting are not allowed. - For operation ETS 300 019-1-3 class 3.1
Heat and solar radiation are not allowed. Acoustic noise Compliant to ETS 300 753 : Acoustic noise emitted by Telecommunication equipment Electromagnetic environment Compliant to ETS 300-386-1, edition October 1994, for equipment in telecommunication centres and high priority of service
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 11/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Environmental conditions for EVOLIUM A925 Transcoder (ETS 300 019) Environmental parameter Low air temperature High air temperature Relative humidity High relative humidity Low absolute humidity High absolute humidity Low air pressure High air pressure Sand Dust (suspension) Dust (sedimentation) Stationary vibration, sinusoidal: - Peak-displacement amplitude - Peak-acceleration amplitude - Frequency range Non-stationary vibration including shock: - Shock-response spectrum type L, peak acceleration - Shock-response spectrum type II, peak acceleration rack with EMC protection. 3.3 - Dimensions Standard 19 and weight Back and front access by locked doors. specifications TC rack Width (mm) Total height (mm) Useful height (U) Depth (mm) Max. weight (kg)
File A70457A1.doc V7 Reference 8BL 00704 0057 DRZZA Edition 01 Status Released
mm m/s Hz
2
0.3 1
1.5 5
2 to 9 9 to 2 to 9 9 to 200 200
m/s
40
40
m/s
---
---
Alcatel
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
3.6 - Lightning and The lightning protections on external interfaces are not implemented in the over voltage A925TC protection on equipment specifications
Not necessary. DC lightning protection If necessary, must be installed at the DDF by Customer. PCM lightning protection
3.7 - X21 interface These link is applicable if the A925TC and the OMC-R are co-located.
X21 link, length of cable from A925TC to OMC-R max. 30m
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 13/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
8 pairs or 8 coaxs, Specification of 2 Mbit/s cable Network impedance L 907 / 8 pairs / 4 twisted quads 120 Ohms Core: copper = Diam. 0,5 mm Jacket = Diam. 7.8 mm FLEX3 / 8 coax Core and drain : copper = Diam. 0,4 mm 75 Ohms Insulation = Diam. 2 mm Sheath = Diam. 3,55 mm Jacket = Diam. 16.1 mm Number of multi PCM cables 2 Mbit/s cable type L907 / 8 pairs FLEX 3 / 8 coaxs Nber of cable, per subrack 16 16 16 x 4 = 64 16 x 4 = 64 Nber of cable, per rack Inserting Inserting Type of cable Connection DDF side recommended
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 14/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 4: Site preparation and supply requirements for the Customer or the Operator
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 15/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 4: Site preparation and supply requirements for Customer or Operator
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 16/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 4: Site preparation and supply requirements for Customer or Operator
The site shall be handed over with the leased lines in operation.
Alcatel
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 4: Site preparation and supply requirements for Customer or Operator
Environment of the equipment Cable are fed in through the top or the botom of the rack. The cables from DC distribution box to TC equipment should not exceed 20 meters with 16mm power cable and 40 meters with 35mm power cable. The cables from DDF to TC equipment must not exceed 20m Lighting and wall sockets The lighting in the room must have an intensity of 300 Lux at 1 m above the floor. No more than 500 Lux. The lamps should be of the electronic ballast type. A "home-purpose" wall socket network must be provided with the room (one socket about every 3 m; 2 poles and ground, 16 A). Sockets providing a 220 V emergency backup source must be provided for the operating equipment (LMT, switch X25).
2 2
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 18/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 4: Site preparation and supply requirements for Customer or Operator
4.5 - Computer LMT computer (labtop) is optional, but necessary during the installation. Length of requirements cables from A925TC to LMT terminal shall not exceed 15 meters.
Dimensions (mm): (Width x Depth x Height) ; 300 x 300 x 400 Maximum weight (kg): < 5 kg Maximum power cosumption: 110-220VAC / 50Hz ; 100W Gauge (A): earth leakage protection 30mA, 6A. Clearance: Side clearance = 0,7 m (only one side is necessary) Front clearance = 1 m Rear clearance = 0,2 m
4.6 - X21 If OMC-R collocated connection requirements Depending of the number of BSC connected to the A925TC.
Signal type X21 Number 2 per BSC Length max. 30 m
4.7 X25 switch If more than one BSC are connected to the A925TC, the use of a X25 switch is requirements mandatory for OMC-R connection. Length of cables from A925TC to X25 switch
shall not exceed 30 meters. X25 switch recommended: 36110- 20 MainStreet Maximum number of ports: from 2 to 20 lines Dimensions (mm): (Width x Depth x Height) ; 440 x 340 x 140 Rack- mountable option available - For 19 inchs rack mounting: 3 units Maximum weight (kg): 9 to 12 kg Maximum power cosumption: 110-240VAC / 50-60Hz ; < 100W Gauge (A): earth leakage protection 30mA, 6A. Operating environment: 5 to 40 C; 20% to 80% relative humidity, non condensing. Clearance: Side clearance = 0,7 m (only one side is necessary) Front clearance = 1 m Rear clearance = 0,7 m Safety standards compliance: EN 60950; UL 950; CSA 950. EMC standards compliance: EN 50022-B; EN 50082-A; FCC Class A Part 15.
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 19/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 4: Site preparation and supply requirements for Customer or Operator
4.8 - Power system The customer shall install all cables at the position of first rack. requirements
Power supply system The TC power plant should include standard backup batteries for emergency power. The TC can be powered either -48VDC or -60VDC nominal voltages: -48VDC, nominal range: -38,4VDC to 57,6VDC -60VDC, nominal range: -48VDC to 72VDC
Each TC rack must operate with two - 48V/60V (BAT A/BAT B) wires with redundancy between the two and one 0V (BATRET) wire. A power distributing box must be provided as part of the room preparations. It must include marked fuses for each output, and a grounding bus bar for the power cables. The box or power station must be marked. Power cable recommended Lugs are necessary at cable end on TC side. Double sheathing. Multi strand flexible copper core. Strand composition 0,41 mm max. class 5 (IEC 60 228) . Cable type to be compliant with local legislation and standard for electrical installation in technical site. 4 cables per TC rack are necessary : Signal 48 or 60 V DC, A 48 or 60 V DC, B 0V DC Ground Section of cable for one TC rack 16 mm / 35 mm 16 mm / 35 mm 16 mm / 35 mm 16 mm / 35 mm 20 m / 40 m 20 m / 40 m 20 m / 40 m 20 m / 40 m Length
Distribution box The distribution should be define for using lugs of system 8 mm for BAT RET (0V), 8 mm for BAT A / BAT B (-48/60V), 8 mm for electrical earth.
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 20/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 4: Site preparation and supply requirements for Customer or Operator
Breakers recommendations The customer provides the following gauges (with lightning protection if necessary): - The gauges should be calculated to operate with ETS300132-2 standard (-40,5VDC). - The gauges are only on BAT A and BAT B wires. - On first approach, the gauge is calculated like: I max. + 1/3 I max. (Imax at 38,4VDC or 48VDC) It is wished to put the gauge in agreement with the final A925TC configuration to avoid an interruption of service during an extension. Gauges estimated with standard values Number of fuses per A925TC Gauge (A) for each rack fully equipped 2 (BAT A and BAT B) 48VDC voltage 60VDC voltage 80 A 63A
Grounding distribution A ground plate directly connected to the ground box of the building must be available in the room. The grounding system is composed of a metallic grounding network, formed of iron flooring .The grounds are respectively connected to grounding plate, and to the metallic ground of the power distributing box. The ground wire circuit resistance must be less than 3 Ohms
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 21/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 4: Site preparation and supply requirements for Customer or Operator
4.9 - Leased line The following shall also be handed over: requirements
a diagram of the distribution frame, identifying the lines, a wiring diagram, the technical and commercial references of each line, the lines connected to the line terminal blocks, the looped Tx/Rx lines on the cable side in the GSM room, the quality tested lines of the local GSM distribution frame to the remote GSM distribution frame.
The equipment terminal block must be remote of customer terminal block (DDF) at maximum 1m. The customer must indicate to Alcatel the connector type equipment terminal block (only for 2Mbit/s cables 75 Ohms). The pins of terminal block to wrap, 120 Ohms supplied by the customer must have a diameter between 1 and 1,5 mm The DDF should be foreseen for one A925TC rack (each rack has 192 A and 48 Ater-mux links: 64 terminal blocks 10 pairs)
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 22/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 4: Site preparation and supply requirements for Customer or Operator
4.11 - Site The customer shall produce an overall drawing for each unit site. information requirements
General site information The drawing shall be submitted to Alcatel, after the initial requirements site inspection, or in preliminary project documentation concerning the site supplied by the customer. The drawing shall indicate the position of the unit with its connections, relative to a reference point. The GSM site data sheet must be completed based on data provided by the client or during site inspection. The GSM site information procedure document (see document SPG-07) should be completed by the customer or during a site inspection visit with Alcatel. PCM site information The operator shall hand over to the constructor, with the requirements preliminary study document or on the occasion of the site inspection: A drawing of the distribution frame locating the links with technical and commercial numbers of each link. The links with transmit/receive loops set up on the cable side at the unit.. Links qualified as far as the unit. Layout The client shall draw up a layout map for each site. That map will indicate the location of: - racks, - power supplies, - air-conditioning system, - cable ways, - collector rod system, - grounding plate, - distribution frame (positioning of the terminal blocks), - furniture for the operating and maintenance tools. That plan is submitted to the manufacturer, either after an initial inspection of the site or in a preliminary project file for the site provided by the client.
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 23/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 5: Installation and supply requirements for Alcatel
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 24/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Chapter 5: Installation and supply requirements for Alcatel
and are detailed in ALCATEL documents: A925TC / Installation manual: 3BK 17251 0001 RJZZA Commissioning of A925TC A925TC powering up and running in accordance with system ALCATEL documents: Commissioning manual: 3BK 17251 0002 RJZZA Acceptance of A925TC system Customer agrees that A925TC has been installed, commissioned and is running in accordance with ALCATEL documents: Acceptance manual: 3BK 17251 0004 RJZZA
Alcatel
File A70457A1.doc V7
Edition 01
Status Released
Date 00/03/22
Page 25/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Appendix A: Installation help: Site cabling raised floor configuration with 1 A925 TC rack, 1 power supply, 1 DDF, 1 PC tool, 1 ground plate
Appendix A: Installation help: Site cabling raised floor configuration with 1 A925 TC rack, 1 power supply, 1 DDF, 1 PC tool, 1 ground plate
220V
AC Box
Power cables
Wire braid
TX- Ater
RX- Ater
Equipment DDF
Alcatel
File A70457A1.doc V7
Customer DDF
RX- A
TX- A
Edition 01
Status Released
LMT
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
2000 mm (40U)
Ground Plate
Date 00/03/22
Page 26/30
SPP-43, A925 Transcoder Appendix A: Installation help: Site cabling raised floor configuration with 1 A925 TC rack, 1 power supply, 1 DDF, 1 PC tool, 1 ground plate
Clearance
AC Box
Ground Plate
Power
1000 mm
Length of cables : 15 m
1000 mm
600 mm
TC1
Equipment DDF
Alcatel
File A70457A1.doc V7
Edition 01
Customer DDF
Status Released
LMT
Date 00/03/22
Page 27/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Appendix B: Installation help: Site cabling cable tray configuration with 2 x A925 TC racks, 2 power distribution box, 2 DDF, 1 PC tool, 1 OMC-R, X25 switch, 1 ground plate
Appendix B. Installation help: Site cabling cable tray configuration with 2 x A925 TC racks, 2 power distribution box, 2 DDF, 1 PC tool, 1 OMC-R, X25 switch, 1 ground plate
DC BOX 48V/60V
DC BOX 48V/60V
Wire braid
Ground Plate
TC1
TC2
TC1 TC2
TC2
X25 SWITCH
Equipment DDF
Alcatel
File A70457A1.doc V7
Customer DDF
Edition 01
Status Released
TC1
LMT
Date 00/03/22
Page 28/30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-43, A925 Transcoder Appendix B: Installation help: Site cabling cable tray configuration with 2 x A925 TC racks, 2 power distribution box, 2 DDF, 1 PC tool, 1 OMC-R, X25 switch, 1 ground plate
Clearance
Ground Plate
DC Box TC1
DC Box TC2
Length of cables : 15 m
1000 mm
600 mm
LMT
600 mm
1000 mm
TC2
< 25 m
OMC-R
Alcatel
File A70457A1.doc V7
Edition 01
Customer DDF
Status Released
Date 00/03/22
X25 SWITCH
TC1
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Equipment DDF
Page 29/30
Abbreviations
Sigle AC BSC BSS DC DDF GSM MSC MFS NTL OMC-R PCM PE RCD TC U Alternative Current Base Station Controller Base Station System Direct Current Digital Distribution Frame Global System for Mobile communication Mobile Service Switching Center (GSM) Multi-BSS Fast packet Server Network Termination Line Operation and Maintenance Center - Radio Pulse Code Modulation Protective Earth Residual Current operated circuit Disrupter TransCoder Standard Unit 1U = 44,45mm Description
END OF DOCUMENT