Earth Resistance
Attach a layout sketch of the Transformer earth mat if not standard and location of additional earthing
Instrument Number: Location HV Earth Ohms Location LV Earth Instrument Number A to B+C+E B to A+C+E C to A+B+E Ohms
Insulation Resistance
Results in Megohms
A+B+C (side 1) to A+B+C (other side) A+B+C (side 1) to A+B+C (other side) A+B+C (side 1) to A+B+C (other side) @ 1 min @ 5 min @ 10 min
Transformer
Winding HV to LV+E HV to E LV to E
Voltage 5 kV 5 kV 2.5 kV
All switches / circuit breakers closed Switch 1 open (or fuse removed) Switch 2 open (or fuse removed) Switch 3 open (or fuse removed) Switch 4 open (or fuse removed) Switch 5 open (or fuse removed) Switch 6 open (or fuse removed)
A to B+C+E
B to A+C+E
C to A+B+E
A+B+C (side 1) to A+B+C (other side) A+B+C (side 1) to A+B+C (other side) A+B+C (side 1) to A+B+C (other side) A+B+C (side 1) to A+B+C (other side) A+B+C (side 1) to A+B+C (other side) A+B+C (side 1) to A+B+C (other side)
Page 1 of 2 Form SP0406C01 Ver 3
Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
Phase Rotation
Phase Rotation: A-B-C C-B-A Instrument Number:
Polarity
Location Tested: Test Method Used: Polarity Correct: ________________________ ________________________ Yes No Instrument Number:
Load Measurements
Instrument Number: Location Transformer Load LV feeder 1 LV feeder 2 LV feeder 3 LV feeder 4 LV feeder 5 LV feeder 6 A phase amps B phase Amps C phase Amps N amps
Check Items
Operational Nameplates in place Safety signs in place Yes Yes No No No No No No No No No No No NA NA Interlocks to stop paralleling feeders No Yes functional Physical inspection of equipment complete Yes No transport bracing removed, connections tight, buswork and cabling installed correctly Functional test of operation including Yes No interlocks okay HV and LV fuses correct size and installed Yes No correctly Fuse size marked on switchgear No Yes Spare fuses on site No Yes Locks in place and operational No Yes Phasing Out facility on Switchgear No Yes Fault Indicator Installed on Switchgear No Yes If Yes to the above Fault Indicator is connected to circuit
Access to switchgear clear of Yes obstructions Emergency exit marked and unobstructed Yes Surge diverters correct voltage rating HV earth connections checked LV earth connections checked CMEN bonding in place Neutral to Main Earth link in place HV cable test SP0407C01 completed LV cable test SP0405C01 completed Yes Yes Yes Yes Yes Yes Yes
NA
Page 2 of 2