DERBY WALL MOUNTED SPLIT SYSTEM

SERVICE MANUAL


Complete System Name Item Numbers Models
DWM-Z26 857601/2 Derby Wall Split 2.6kW
DWM-Z35 857603/4 Derby Wall Split 3.5kW
DWM-Z50 857605/6 Derby Wall Split 5.0kW
DWM-Z60 857607/8 Derby Wall Split 6.0kW
DWM-Z70 857609/10 Derby Wall Split 7.0kW

TABLE OF CONTENTS
1. Precaution 1
2. Function 3
3. Dimension 5
3.1 Indoor Unit 5
3.2 Outdoor Unit 5
4. Specification 6
5. Refrigerant cycle diagram 7
6. Operation limits 7
6.1 Cooling Operation 7
6.2 Heating Operation 7
7. Wiring Diagrams 8
7.1 DWM-Z26 8
7.2 DWM-Z35 9
7.3 DWM-Z50 10
7.4 DWM-Z60 11
7.5 DWM-Z70 12
8. Installation Details 13
8.1 Wrench torque sheet for installation 13
8.2 Minimum Electrical Rating 13
8.3 Pipe length and the elevation 13
8.4 Pipe Constraints 13
8.5 Air purging of the piping and indoor unit 14
8.6 Pumping down (Re-installation) 15
8.7 Re-air purging (Re-installation) 16
8.8 Balancing refrigerant of the 2-way,3-way valves 17
8.9 Evacuation 18
8.10 Gas Charging 19
9. Capacity Table 20
9.1 DWM-Z26 20
9.2 DWM-Z35 21
9.3 DWM-Z50 22
9.4 DWM-Z60 23
9.5 DWM-Z70 24
10. Electronic Function 25
10.1 Electronic control working environment 25
10.2 Proper symbols and their meaning 25
10.3 Function 25
10.4 Protection 26
10.5 Fan only mode 26
10.6 Cooling mode 26
10.7 Auto fan at cooling mode 27
10.8 Anti-freezing control to indoor evaporator at cooling mode 27
10.9 De-humidifying mode 27
10.10 Heating mode 28
10.11 Indoor fan actions at heating mode 28
10.12 Anti-cold wind control function at heating mode 28
10.13 Auto wind at heating mode 28
10.14 Indoor evaporator high temperature protection at heating mode 28
10.15 Defrosting mode 29
10.16 Auto mode 30
10.17 Forced cooling function 30
10.18 Forced Auto function 30
10.19 Sleep mode 30
10.20 Cooling 30
10.21 Heating 31
10.22 Auto 31
10.23 Auto restart function 31
11. Model and Parameters 32
12. Display board 33
13. Troubleshooting 33
13.1 Self Diagnostic failure indication 33
13.2 Diagnostic chart 34
13.3 Resetting phenomenon often occurs during operation 35
13.4 Operation lamp flashes and Timer lamp off 35
13.5 Operation lamp flashes and Timer lamp on 35
13.6 Operation lamp off and Timer lamp flashes 36
13.7 Operation lamp on and Timer lamp flashes 36
13.8 Operation lamp flashes and Timer lamp flashes 36
14. Characteristic of temperature sensor 37
15. Explosion Diagram 38
15.1 DWMG-Z26 Indoor Unit 38
15.2 DWMZ-Z26 Outdoor Unit 39
15.3 DWMG-Z35 Indoor Unit 40
15.4 DWMZ-Z35 Outdoor Unit 41
15.5 DWMG-Z50 Indoor Unit 42
15.6 DWMZ-Z50 Outdoor Unit 43
15.7 DWMG-Z60 Indoor Unit 44
15.8 DWMZ-Z60 Outdoor Unit 45
15.9 DWMG-Z70 Indoor Unit 46
15.10 DWMZ-Z70 Outdoor Unit 47





1 Precaution
1.1 Safety Precaution
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage.
Before service unit, be sure to read this service manual at first.

1.2 Warning
Installation
Do not use a defective or underrated circuit breaker. Use
this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified
electrician, or an Authorized service center.
Do not disassemble or repair the product, there is
risk of fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or
electric shock.
Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
Do not modify or extend the power cable.
There is risk of fire or electric shock.
Do not install, remove, or reinstall the unit by yourself
(customer).
There is risk of fire, electric shock, explosion, or
injury.
Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially
careful of the case edges and the fins on the
condenser and evaporator.
For installation, always contact the dealer or an
Authorized service center.
There is risk of fire, electric shock, explosion, or
injury.
Do not install the product on a defective installation
stand.
It may cause injury, accident, or damage to the
product.
Be sure the installation area does not deteriorate with
age.
If the base collapses, the air conditioner could fall
with it, causing property damage, product failure,
and personal injury.
Do not let the air conditioner run for a long time when the
humidity is very high and a door or a windows is left
open.
Moisture may condense and wet or damage
furniture.
Take care to ensure that power cable could not be pulled
out or damaged during operation.
There is risk of fire or electric shock.
Do not place anything on the power cable.
There is risk of fire or electric shock.
Do not plug or unplug the power supply plug during
operation.
There is risk of fire or electric shock.
Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
Do not place a heater or other appliance near the power
cable.
There is risk of fire and electric shock.
Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric
shock.
Do not store or use flammable gas or combustible near
the product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a
long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and open a
window for ventilation before turn the product on.
Do not use the telephone or turn switches on or off.
There is risk of explosion or fire.
If strange sounds, or small or smoke comes from
product. Turn the breaker off or disconnect the power
supply cable.
There is risk of electric shock or fire.
Stop operation and close the window in storm or
hurricane. If possible, remove the product from the
window before the hurricane arrives.
1




There is risk of property damage, failure of product,
or electric shock.
Do not open the inlet grill of the product during operation.
(Do not touch the electrostatic filter, if the unit is so
equipped.)
There is risk of physical injury, electric shock, or
product failure.
When the product is soaked (flooded or submerged),
contact an Authorized service center.
There is risk of fire or electric shock.
Be caution that water could not enter the product.
There is risk of fire, electric shock, or product
damage.
Ventilate the product from time to time when operating it
together with a stove, etc.
There is risk of fire or electric shock.
Turn the main power off when cleaning or maintaining
the product.
There is risk of electric shock.
When the product is not be used for a long time,
disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or
unintended operation.
Take care to ensure that nobody could step on or fall
onto the outdoor unit.
This could result in personal injury and product
damage.


CAUTION
Always check for gas (refrigerant) leakage after
installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained
away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration of water leakage.
Do not install the product where the noise or hot air from
the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
Avoid personal injury.
Do not install the product where it will be exposed to sea
wind (salt spray) directly.
It may cause corrosion on the product. Corrosion,
particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient
operation.


Operational
Do not expose the skin directly to cool air for long
periods of time. (Do not sit in the draft).
This could harm to your health.
Do not use the product for special purposes, such as
preserving foods, works of art, etc. It is a consumer air
conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents,
solvents, etc.
There is risk of fire, electric shock, or damage to the
plastic parts of the product.
Do not touch the metal parts of the product when
removing the air filter. They are very sharp.
There is risk of personal injury.
Do not step on pr put anything on the product. (outdoor
units)
There is risk of personal injury and failure of
product.
Always insert the filter securely. Clean the filter every
two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air
conditioner and could cause product malfunction or
damage.
Do not insert hands or other object through air inlet or
outlet while the product is operated.
There are sharp and moving parts that could cause
personal injury.
Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining
the product.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with new
ones of the same type. Do not mix old and mew batteries
or different types of batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the batteries. Do not
dispose of batteries in a fire.
They may burn of explode.
If the liquid from the batteries gets onto your skin or
clothes, wash it well with clean water. Do not use the
remote of the batteries have leaked.
The chemical in batteries could cause burns or
other health hazards.

2




2 Function

The function will be
operate in any operation
mode.
Indoor unit

Operation ON/OFF by remote controller

Room temperature sensor.
Pipe temperature sensor.

Sensing by room temperature

Maintain the room temperature in accordance with the setting temperature.
Room temperature control

Indoor fan is delayed for 5 sec at the starting.
Starting temperature control

Restarting is for approx. 3 minutes..
Time Delay Safety control

High, med, low, breeze.
Indoor fan speed control

Light up in the LED (LCD) for each operation mode.
The unit will decide the louver direction according to operation mode.
Two-direction air vane

The fan is turn to low speed (cooling/heating).
The unit will be turn off after seven hours.
Economic mode auto control

The function is usually used in rainy days in
springtime or damp areas.
Independent dehumidification

Operation indication Lamps (LED)

The louver can be set at the desired position or swing up
and down automatically
Air flow Direction control
The unit can be change by the room temperature.
Auto mode

Easy clean panel

Flexible wiring connection

Defrost mode

Temp. Compensation

Prevent the cold wind at
the beginning of unit
start.
Anti-cold function

Auto-restart function

Self-diagnostic. function

3
mode




The unit can operate in cooling mode at low ambient temperature conditions.
The unit has 3 mins delay between continuously ON/OFF operations.

Outdoor unit

Power relay control

Low ambient kit

Bird tail propeller fan makes the outdoor unit run more quietly.
Low noise air flow system

The hydrophilic fin can improve the heating efficiency at operation mode.
Hydrophilic aluminum fin

It is only operated in the heating operation mode except defrosting operation.
Discharge pipe temperature protect

Anti-rust cabinet

4 way valve control

Made from electrolytic zinc steel sheet and anti-rust coated components.
It protects the valves and prevents water from dripping.
Valve protection
cover
4
3. Dimension
3.1 Indoor Unit

Model Name W (mm) H (mm) D (mm)
DWMG-Z26 815 280 195
DWMG-Z35 906 286 235
DWMG-Z50 906 286 235
DWMG-Z60 1080 330 228
DWMG-Z70 1080 330 228

3.2 Outdoor Unit


Model Name W (mm) H (mm) D (mm) L1 (mm) L2 (mm)
DWMZ-Z26 780 540 276 549 300
DWMZ-Z35 780 540 276 549 300
DWMZ-Z50 845 695 335 560 360
DWMZ-Z60 895 860 333 590 355
DWMZ-Z70 895 860 333 590 355






5
DWM-Z26 DWM-Z35 DWM-Z50 DWM-Z60 DWM-Z70
DWMG-Z26 DWMG-Z35 DWMG-Z50 DWMG-Z60 DWMG-Z70
DWMZ-Z26 DWMZ-Z35 DWMZ-Z50 DWMZ-Z60 DWMZ-Z70
2010,2011, QLD &SA 2010,2011, QLD &SA 2010,2011, QLD &SA 2010,2011, QLD &SA 2010,2011, QLD &SA
857601 857603 857605 857607 857609
857602 857604 857606 857608 857610
Ph-V-Hz 1Ph, 220-240V, 50Hz 1Ph, 220-240V, 50Hz 1Ph, 220-240V, 50Hz 1Ph, 220-240V, 50Hz 1Ph, 220-240V, 50Hz
Capacity W 2800 3400 5200 6300 7200
Input W 760 920 1600 1940 2200
Rated current A 3.4 4.1 7.2 8.7 9.9
EER W/W 3.68 3.70 3.25 3.25 3.27
Capacity W 2800 3300 5500 6500 7700
Input W 720 890 1650 1930 2300
Rated current A 3.2 4.0 7.4 8.7 10.3
COP W/W 3.89 3.71 3.33 3.37 3.35
L/h 0.52 0.50 1.95 1.95 2.50
W 1200 1300 2300 2700 3300
A 6.7 7.0 11.5 13.0 16.0
A 30 30 38 34 34
Model PA98M1C-4DZDE1 PA118M1C-4FZ2 PA200M2CS-4KU2 PA225M2CS-4KU PA270X3CS-4MU1
Type ROTARY ROTARY ROTARY ROTARY ROTARY
Brand TOSHIBA TOSHIBA TOSHIBA TOSHIBA TOSHIBA
Capacity Btu/h 8018/8052 9495/9605 16581 18868/19073 22758/22928
Input W 785/815 955/995 1605 1875/1960 2280/2350
Rated current(RLA) A 3.6/3.5 4.5/4.4 7.45 8.8/8.7 10.70/10.70
Locked rotor Amp(LRA) A ----- 19.2 31.8 ----- 45
Thermal protector ----- ----- --- ----- UP14RE5245
Thermal protector position EXTERNAL INTERNAL INTERNAL INTERNAL INTERNAL
Capacitor uF 25 25 45 50+90+90 50+90+90
Refrigerant oil/oil charge ml ESTER OIL VG74/350 ESTER OIL VG74/350 ESTER OIL VG74 750cc ESTER OIL VG74/750 ESTER OIL VG74/950
Model RPG20D RPG25 RPG25 YDK36-4G YDK36-4G
Brand Welling Welling Welling Welling Welling
Input W 43.3 55 55 71/63/60 71/63/60
Capacitor uF 1.5 1.5 1.5 3 3
Speed(Hi/Mi/Lo) r/min 1250/1000/750 1280/1105/1000 1280/1105/1000 1150/1060/960 1150/1060/960
a Number of rows 2 2 2 2 2
4. Specifications
MEPS Compliance Level
SAGE CODE
Indoor
Outdoor
Max. current
Starting current
Compressor
Indoor fan motor
Model
Indoor
Outdoor
Power supply
Cooling
Heating
Moisture Removal
Max. input consumption
a.Number of rows 2 2 2 2 2
b.Tube pitch(a)x row pitch(b) mm 21x13.37 21x13.37 21x13.37 21x13.37 21x13.37
c. Fin Spacing mm 1.3 1.3 1.3 1.3 1.3
d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm 7, innergroove tube 7, innergroove tube 7, innergroove tube 7, innergroove tube 7, innergroove tube
f.Coil length x height x width mm 653x315x26.74 660x357x26.74 660x357x26.74 810x357x26.74 810x357x26.74
g.Number of circuits 2 3 3 4 4
m3/h 600/450/340 700/580/480 730/610/500 1000/900/800 1080/980/880
dB(A) 39/34/28 42/36/30 44/38/32 45/42/40 47/44/41
Dimension(W*D*H) mm 815x195x280 906x235x286 906x235x286 1080x228x330 1080x228x330
Packing (W*D*H) mm 915x275x360 1020x328x381 1020x328x381 1165x445x320 1165x445x320
Net/Gross weight Kg 9/11 11.5/14.5 11.5/14.5 14/21 14/21
Model YDK24-6F YDK36-6 YDK55-6H YDK53-6C YDK100-6
Brand Welling Welling Board ocean Welling Welling
Input W 58 70 105 136 168
Capacitor uF 2.5 2.5 3 3 5
Speed r/min 800 900 865 800 900
a.Number of rows 2.5 2 2 2.5 3
b.Tube pitch(a)x row pitch(b) mm 19.5x11.6 2113.37 21x13.37 2113.37 21x13.37
c.Fin spacing mm 1.2 1.5 1.4 1.4 1.4
d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm 5, innergroove tube 7,Innergroove tube 7, innergroove tube 7,Innergroove tube 7, innergroove tube
f.Coil length x height x width mm 750x507x23.2+370x507x11.6 755x504x26.74 785x651x26.74 773x798x26.74+384x798x13.37 776x798x40.11
g.Number of circuits 6 3 4 6 6
m3/h 1800 1800 2500 3500 3500
dB(A) 53 53 56 57 60
Dimension(W*D*H) mm 780x300x540 780x300x540 845x360x695 895x355x860 895x355x860
Packing (W*D*H) mm 910x335x575 910x335x575 965x395x755 1043x395x915 1043x395x915
Net/Gross weight Kg 27/29 30/34 48.5/52.5 58/62 68/73
g R410A/800g R410A/1130g R410A/1380g R410A/2000g R410A/2180g
MPa 4.2/1.5 4.2/1.5 4.2/1.5 4.2/1.5 4.2/1.5
Liquid side/ Gas side mm(inch) 6.35/9.53(1/4"/3/8") 6.35/12.7(1/4"/1/2") 6.35/12.7(1/4"/1/2") 9.53/16.0(3/8"/5/8") 9.53/16.0(3/8"/5/8")
Max. refrigerant pipe length m 20 20 20 25 25
Max. difference in level m 8 8 8 10 10
m2 1.5 2.5 2.5 2.5 2.5
10 10 No No No
Remote control Remote control Remote control Remote control Remote control
17-30 17-30 17-30 17-30 17-30
18-43/-7-24 18-43/-7-24 18-43/-7-24 18-43/-7-24 18-43/-7-24
m2 13-22 18-29 26-44 31-51 35-58
110/229/263 99/203/231 70/148/164 51/109/118 51/109/118
dB(A) 60 60 63 65 68
Design pressure
Refrigerant piping
Outdoor unit
Refrigerant type
Indoor coil
Indoor air flow (Hi/Mi/Lo)
Outdoor air flow
Outdoor noise level
Qtyper 20 /40 /40'HQ
Outside sound power level
Connection wiring
Plug type
Thermostat type
Operation temp
Ambient temp (cooling/heating)
Application area
Outdoor fan motor
Outdoor coil
Indoor noise level (Hi/Mi/Lo)
Indoor unit
The above design and specifications are subject to change without prior notice for product development.
6
5. Refrigerant cycle diagram
Heat Pump Mode


6. Operation Limits
6.1 Cooling Operation 6.2 Heating Operation

Note: The chart is the result from the continuous operation under constant air
temperature conditions. However, excludes the initial pull-down stage.

7
7. Wiring Diagram
7.1. DWM-Z26
DWMG-Z26 (Indoor Unit)


DWMZ-Z26 (Outdoor Unit)




8
7.2. DWM-Z35
DWMG-Z35 (Indoor Unit)


DWMZ-Z35 (Outdoor Unit)


9
7.3. DWM-Z50
DWMG-Z50 (Indoor Unit)


DWMZ-Z50 (Outdoor Unit)



10
7.4. DWM-Z60
DWMG-Z60 (Indoor Unit)


DWMZ-Z60 (Outdoor Unit)






11
7.5. DWM-Z70
DWMG-Z70 (Indoor Unit)


DWMZ-Z70 (Outdoor Unit)






12
13

8. Installation Details
8.1 Wrench Torque sheet for Installation
Pipe Outside Diameter Torque
mm Inch Kg.m
6.35 1/4 2.0
9.53 3/8 3.5
12.7 1/2 5.5
16.0 5/8 8.0

8.2 Minimum Electrical Ratings
Model Maximum Run
Current (A)
Rated Run current (A) Start
Current (A)
Circuit Breaker
Type D (A)
Minimum Conductor
size (mm
2
) Heating Cooling
DWM-Z26 6.7 3.2 3.4 30 10 1.5
DWM-Z35 7.0 4.0 4.1 30 10 1.5
DWM-Z50 11.5 7.4 7.2 38 20 2.5
DWM-Z60 13.0 8.7 8.7 34 20 2.5
DWM-Z70 16.0 10.3 9.9 34 20 2.5

Interconnecting cable requirements
Models Inter-connecting supply to Minimum conductor size mm
2
Remarks
DWM-Z26
Compressor+Neutral+Earth 2x1.5mm
2
+Earth Power supply to
indoor first. 4 way valve+Outdoor fan 2x1.0mm
2

DWM-Z35
Compressor+Neutral+Earth 2x1.5mm
2
+Earth Power supply to
indoor first. 4 way valve+Outdoor fan 2x1.0mm
2

DWM-Z50
Compressor+Neutral+Earth 2x2.5mm
2
+Earth Power supply to
indoor first. 4 way valve+Outdoor fan 2x1.0mm
2

DWM-Z60
Compressor+Neutral+Earth 2x2.5mm
2
+Earth
Power supply to
indoor first.
4 way valve+Outdoor fan+Comp Signal 3x1.0mm
2

Sensor 2x1.0mm
2

DWM-Z70
Compressor+Neutral+Earth 2x2.5mm
2
+Earth
Power supply to
indoor first.
4 way valve+Outdoor fan+Comp Signal 3x1.0mm
2

Sensor 2x1.0mm
2

Note: The supply voltage should be consistent with the rated voltage of the air conditioner

8.3 Pipe Length and the elevation
Model Name
Pipe Size (mm) Standard
Length (m)
Max Elevation
B (m)
Max Length
A (m)
Additional Refrigerant
(g/m) Gas Liquid
DWM-Z26 9.53 6.35 5 8 20 20
DWM-Z35 12.7 6.35 5 8 20 20
DWM-Z50 12.7 6.35 5 8 20 20
DWM-Z60 16.0 9.53 5 10 25 40
DWM-Z70 16.0 9.53 5 10 25 40

8.4 Pipe constraints

Fig 1 Fig 2
Caution
1. Oil traps must be fitted to vertical suction risers where outdoor unit is above indoor unit. Oil traps must
be placed at 5m (maximum intervals)
2. If the outdoor unit is installed below the indoor unit (Fig 1) no trap is required in such installation.
3. If the units are installed at the same level no trap is required in such installation.





8.5 Air purging of the piping and indoor unit
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will
affect the compressor, reduce the cooling capacity, and could lead to a malfunction of unit.
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it
prevents the gas leakage from the refrigeration cycle.

Procedure
1. Recheck the piping connections.
2. Open the valve stem of the 2-way valve
counterclockwise approximately 90, wait 10
seconds, and then set it to closed position.
Be sure to use a hexagonal wrench to
operate the valve stem
3. Check for gas leakage.
Check the flare connection for gas leakage
4. Purge the air from the system.
Set the 2-way valve to the open position
and remove the cap from the 3-way valves
service port.
Using the hexagonal wrench to press the
valve core pin, discharge for three
seconds and then wait for one minute.
5. Use torque wrench to tighten the service port
cap to a torque of 1.8 kg.m. (18n.m)
6. Set the 3-way valve to the opened position.
7. Mount the valve stem nuts to the 2-way
and 3-way valves.
8. Check for gas leakage.
At this time, especially check for gas
leakage from the 2-way and 3-way stem
nuts, and from the service port.

Caution:
If gas leakage is discovered in step (3) above,
take the following measures.
If the leaks stop when the piping connections
are tightened further, continue working from
step (4).
If the gas leaks do not stop when the
connections are retightened, repair the
location of the leak, discharge all of the gas
through the service port, and then recharge
with the specified amount of gas from a gas
cylinder.
14




8.6 Pumping down (Re-installation)



Procedure
1. Confirm that both the 2-way and 3-way valves are set to the opened position.
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way
valve.
Connect the charge hose with the push pin to the gas service port.
4. Air purging of the charge hose.
Open the low-pressure valve on the charge set slightly to purge air from the charge hose.
5. Set the 2-way valve to the close position.
6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
7. Immediately set the 3-way valve to the closed position.
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
8. Disconnect the charge set, and amount the 2-way and 3-way valves stem nuts and service port
caps.
Use a torque wrench to tighten the service port cap to a torque of 1.8 kg.m.
Be sure to check for gas leakage.
15





8.7 Re-air purging (Re-installation)

Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the closed position.
2. Connect the charge set and a charging cylinder to the service port of the 3-way valve.
Leave the valve on the charging cylinder closed.
3. Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the
flare nut on the 2-way valve approximately 45 for 3 seconds then closing it for 1 minutes;
repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut to on the 2-way valve.
4. Check the gas leakage.
Check the flare connections for gas leakage.
5. Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant until the gauge
indicate 0.3 to 0.5 Mpa.
6. Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the
open position.
Be sure to use a hexagonal wrench to operate the valve stems.
7. Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
16





8.8 Balance refrigerant of the 2-way, 3-way valves

Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the 3-way valves service port.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates
0.05 to 0.1 Mpa.
If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running
is higher than 0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If
this is the case, it will not be necessary to apply a evacuation.
Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil will
be discharged.
17





8.9 Evacuation

Procedure:
1. Connect the vacuum pump to the charge sets centre hose.
2. Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or
less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needed.
18




8.10 Gas charging

Procedure:
1. Connect the charge hose to the charging cylinder.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the
bottom of the cylinder.
2. Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to
purge the air (be careful of the liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
If the system cannot be charged with the specified amount of refrigerant, charge little by
little over time (approximately 150g each time while operating the air conditioner in the
cooling cycle; however, one time is not sufficient), wait approximately 1 minute and then
repeat the procedure.(pumping down-pin).
4. Immediately disconnect the charge hose from the 3-way valves service port.
Stopping partway will allow the refrigerant to be discharged.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn
off the air conditioner before disconnecting the hose.
5. Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
19

9. Capacity table
9.1 DWM-Z26
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25C 30C 35C 40C 45C 50C
21C D Total capacity W 2487 2365 2200 2021 1855 1730
15C W Sensitive capacity W 1836 1781 1703 1616 1533 1468
Input W. 622 675 728 781 834 888
24C D Total capacity W 2666 2547 2403 2250 2102 1976
17C W Sensitive capacity W 1948 1891 1823 1756 1705 1682
Input W. 622 680 738 795 853 911
27C D Total capacity W 2853 2800 2649 2443 2223 2032
19C W Sensitive capacity W 2111 2066 1988 1892 1795 1713
Input W. 635 694 753 812 871 931
32C D Total capacity W 2906 2953 2911 2810 2679 2547
23C W Sensitive capacity W 2000 2025 2008 1974 1950 1960
Input W. 628 698 767 837 906 975


WINTER OUTDOOR CONDITIONS
Indoor
Conditions

12C D
11C W
7C D
6C W
4C D
3C W
0C D
-1C W
-4C D
-6C W
-7C D
-8C W
15C
Capacity W 3107 2764 2444 1580 1321 1273
Input W. 783 699 627 540 502 530
18C
Capacity W 2926 2624 2365 1502 1387 1225
Input W. 802 699 638 575 555 582
20C
Capacity W 2910 2650 2345 1427 1283 1253
Input W. 823 724 654 575 544 572
22C
Capacity W 2706 2578 2237 1211 1296 1210
Input W. 762 719 655 573 548 600


20
9.2 DWM-Z35
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25C 30C 35C 40C 45C 50C
21C D
15C W
Total capacity W 3050 2900 2698 2478 2275 2122
Sensitive capacity W 2399 2327 2225 2112 2003 1917
Input W. 754 819 883 948 1013 1077
24C D
17C W
Total capacity W 3269 3123 2947 2759 2578 2423
Sensitive capacity W 2545 2470 2381 2295 2228 2198
Input W. 755 825 895 965 1035 1105
27C D
19C W
Total capacity W 3499 3434 3249 2996 2727 2492
Sensitive capacity W 2758 2699 2597 2472 2346 2238
Input W. 770 842 914 985 1057 1129
32C D
23C W
Total capacity W 3564 3621 3570 3447 3286 3123
Sensitive capacity W 2613 2646 2623 2580 2547 2560
Input W. 762 847 931 1015 1099 1184


WINTER OUTDOOR CONDITIONS
Indoor
Conditions

12C D
11C W
7C D 6C
W
4C D 3C
W
0C D
-1C W
-4C D
-6C W
-7C D
-8C W
15C
Capacity W 3810 3390 2998 1938 1620 1561
Input W. 968 864 775 668 620 655
18C
Capacity W 3588 3218 2901 1842 1701 1503
Input W. 991 864 788 711 686 719
20C
Capacity W 3569 3250 2876 1750 1573 1536
Input W. 1018 895 808 711 673 708
22C
Capacity W 3318 3161 2744 1486 1589 1483
Input W. 941 889 809 709 678 742


21
9.3 DWM-Z50
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25C 30C 35C 40C 45C 50C
21C D
15C W
Total capacity W 4786 4551 4234 3889 3570 3330
Sensitive capacity W 3691 3580 3424 3249 3082 2950
Input W. 1384 1503 1621 1740 1858 1977
24C D
17C W
Total capacity W 5130 4901 4624 4330 4046 3803
Sensitive capacity W 3915 3801 3664 3530 3427 3381
Input W. 1386 1514 1643 1771 1900 2028
27C D
19C W
Total capacity W 5490 5388 5098 4702 4279 3910
Sensitive capacity W 4243 4153 3996 3804 3609 3444
Input W. 1413 1545 1677 1808 1940 2072
32C D
23C W
Total capacity W 5593 5683 5603 5409 5156 4901
Sensitive capacity W 4021 4070 4036 3968 3919 3939
Input W. 1399 1554 1708 1863 2017 2172


WINTER OUTDOOR CONDITIONS
Indoor
Conditions

12C D
11C W
7C D
6C W
4C D
3C W
0C D
-1C W
-4C D
-6C W
-7C D
-8C W
15C
Capacity W 6214 5529 4889 3161 2642 2546
Input W. 1806 1612 1445 1245 1157 1221
18C
Capacity W 5852 5247 4730 3004 2773 2450
Input W. 1849 1612 1470 1326 1280 1341
20C
Capacity W 5821 5300 4689 2854 2566 2505
Input W. 1899 1670 1507 1326 1255 1320
22C
Capacity W 5412 5155 4474 2423 2591 2419
Input W. 1756 1658 1510 1322 1264 1383



22
9.4 DWM-Z60
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25C 30C 35C 40C 45C 50C
21C D
15C W
Total capacity W 5771 5488 5105 4689 4305 4016
Sensitive capacity W 4522 4385 4194 3980 3776 3613
Input W. 1666 1809 1951 2094 2236 2379
24C D
17C W
Total capacity W 6187 5910 5577 5221 4879 4585
Sensitive capacity W 4796 4656 4488 4325 4199 4142
Input W. 1668 1822 1977 2132 2286 2441
27C D
19C W
Total capacity W 6621 6497 6148 5670 5160 4715
Sensitive capacity W 5198 5087 4895 4660 4421 4219
Input W. 1701 1859 2018 2177 2335 2494
32C D
23C W
Total capacity W 6745 6853 6756 6522 6218 5910
Sensitive capacity W 4925 4986 4944 4861 4801 4825
Input W. 1684 1870 2056 2242 2428 2614


WINTER OUTDOOR CONDITIONS
Indoor
Conditions

12C D
11C W
7C D
6C W
4C D
3C W
0C D
-1C W
-4C D
-6C W
-7C D
-8C W
15C
Capacity W 7504 6677 5904 3817 3191 3075
Input W. 2176 1942 1741 1500 1394 1471
18C
Capacity W 7066 6336 5712 3628 3349 2959
Input W. 2227 1942 1771 1597 1542 1616
20C
Capacity W 7029 6400 5663 3446 3098 3025
Input W. 2287 2012 1816 1597 1512 1590
22C
Capacity W 6535 6225 5403 2926 3129 2921
Input W. 2116 1997 1819 1592 1523 1667



23
9.5 DWM-Z70
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25C 30C 35C 40C 45C 50C
21C D
15C W
Total capacity W 6569 6246 5811 5338 4900 4571
Sensitive capacity W 5260 5101 4878 4630 4392 4203
Input W. 1898 2060 2223 2385 2548 2710
24C D
17C W
Total capacity W 7042 6727 6347 5943 5553 5219
Sensitive capacity W 5579 5416 5221 5031 4884 4818
Input W. 1900 2076 2252 2429 2605 2781
27C D
19C W
Total capacity W 7536 7395 6998 6454 5873 5367
Sensitive capacity W 6047 5918 5694 5420 5143 4907
Input W. 1937 2118 2299 2480 2661 2841
32C D
23C W
Total capacity W 7677 7800 7690 7424 7077 6727
Sensitive capacity W 5729 5800 5751 5655 5585 5613
Input W. 1918 2130 2342 2554 2766 2979


WINTER OUTDOOR CONDITIONS
Indoor
Conditions

12C D
11C W
7C D
6C W
4C D
3C W
0C D
-1C W
-4C D
-6C W
-7C D
-8C W
15C
Capacity W 8559 7615 6734 4354 3639 3507
Input W. 2481 2214 1985 1710 1590 1677
18C
Capacity W 8060 7227 6516 4138 3820 3375
Input W. 2539 2214 2019 1821 1758 1842
20C
Capacity W 8017 7300 6459 3930 3534 3451
Input W. 2608 2294 2070 1821 1724 1813
22C
Capacity W 7454 7101 6162 3337 3569 3332
Input W. 2412 2277 2073 1815 1736 1900

24
10. Electronic function
10.1. Electronic control working environment
Input voltage: 198~253V
Input power frequency: 50HZ
Ambient temperature: -7C+43C
Indoor fan normal working amp is less than 1A
Outdoor fan normal working amp is less than 1.5A
Four-way valve normal working amp is less than 1A
Swing motor: DC12V
Compressor: single-phase power supply. Its normal working amp is less than 15A

10.2. Proper symbols and their meaning
T1: Indoor ambient temperature
T2: Indoor evaporator temperature
T3: Outdoor condenser temperature.
TS: Setting temperature through the remote controller
I3
sec
: Self-protection amp of compressor, continue three seconds until turns off the
compressor.
I5
MIN
: Self-protection amp of compressor, continue five minutes until turns off the
compressor.
I
FAN
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to
lower wind.
I
RESTORE
: Amp self-protection returns value
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
TE10: Condenser high temperature protection, compressor off temperature.
TE11: Condenser high temperature protection, restoring temperature.
TE14: The indoor restoring temperature when the compressor is off on the heating mode.
TE16: The indoor evaporator temperature after the defrost action, fan on temperature.
TC1: Outdoor condenser sensor temperature for the defrost condition 1.
TC2: Condenser sensor temperature after defrost.
TC3: Outdoor condenser sensor temperature for the defrost condition 2.

10.3. Function
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at cooling mode


25
10.4. Protection
Minutes delay at restart for compressor.
Sensor protection at open circuit and breaking disconnection
Fan Speed is out of control. When Indoor Fan Speed is too high (higher than High
Fan+300RPM) or too low (lower than 400RPM), the unit stops and LED displays failure
information and cannot return to normal operation automatically.
Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit
stops and
LED displays failure information and cannot return to normal operation automatically.
The current protection of the compressor.

If compressor turns off for continuously 4 times due to current protection in 5 minutes from
compressor On, t he unit stops and LED di splays failure information and cannot return to
normal operation automatically.

10.5. Fan only mode
Fan speed is high/mid/low/ Auto

10.6. Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan: (T=indoor temperature).



26
10.7. Auto fan at cooling mode

10.8. Anti-freezing control to indoor evaporator at cooling mode (T: evaporator temp)

10.9. Dehumidifying mode
The 4-way valve is off in dehumidifying mode
Compressor and Indoor Fan actions in dehumidifying mode

Block
Indoor
Fan
Compressor and Outdoor Fan
A
LOW ON 6minutes
BREEZE OFF 4minutes
B
LOW ON 5minutes
BREEZE OFF 5minutes
C
LOW ON 4minutes
BREEZE OFF 6minutes

Low room temperature protection:
When room temperature decreases to below 10C, compressor and outdoor fan will stop
(indoor fan is Breeze). Dehumidifying operation will be resumed when room temperature
restores to over 13C.
At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the
same as that of cooling mode.
At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.
27
10.10. Heating Mode
Generally, t he 4-way valve i s open in heating mode, but it is closed i n defrosting mode.
4-way valve must delay 2 minutes compared with compressor if the compressor changed
into non-heating mode or turned off. 4-way valve doesn't delay in dehumidifying mode
Generally, the outdoor fan is turned off with the on-off action of compressor i n heating
mode, except for the defrosting mode or the end of defrost
Action of compressor and outdoor fan motor at heating mode: compressor must run for 7
minutes after starting and then judge temperature. Meanwhile other protections are still
valid.
* This parameter can be changed from 0 to 3
10.11. Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but
Anti-cold wind function prevails.

10.12. Anti-cold wind control function at heating mode (T=indoor exchanger temp.)

10.13. Auto wind at heating mode (T=indoor temp)

10.14. Indoor evaporator high temperature protection at heating mode ( T= indoor exchanger
temp.)

The louver opens to Standard Angle ANGLHEAT when power is on for the first time.
28
10.15. Defrosting mode (available for heating mode)
Defrosting condition: Defrosting starts when either (1) or (2)
(1) A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the
following:

(2) Calculate from the end of latest defrost, evaporator high temp. Protection only closes
outdoor fan with the compressor still running. Add up to 90 minutes.

Defrosting time
At condition (1), If item B is satisfied before item A, it would be regarded as severe frosting
and the defrosting time is 10 minutes. If item B is satisfied after item A, the defrosting time
is 6minutes.
At condition (2), the defrosting time is 10 minutes.

After three times continuous 6-minute defrost, the fourth defrost time should be 10 minutes.
The circulation is as following:


Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 6 or 10 minutes.
B. The compressor current has reached to IDEFROST or above, IDEROST differs in
different models

Defrosting Actions


29
10.16. Auto mode
The air conditioner automatically selects one of t he following operation modes: cooling,
heating or fan only according t o t he t emperature di fference between room temperature
(TA) and set temperature (TS).

The indoor fan blows automatically in corresponding selected mode
The motion of indoor fans blade should accord with the selected operation mode
One mode should be carried out for at least 15 minutes once selected. If the compressor
cannot start for 15 minutes, reselect the operation mode according to the room temp. and
set temp., or reselect when the set temp. varies.

10.17. Force cooling function
Select forced cooling function with the forced
The compressor is unconditionally turned on, after 30 minutes cooling oper ation whose
fan mode is set as low, the A/C operates at the DRY mode with a set temp. of 24C
All protections of remote control cooling are available at forced cooling operation

10.18. Forced Auto function
Select forced auto function with the forced auto button or the switch. In forced auto status
the A/C operates at remote control mode with a set temp. of 24C.
Manual operation is controlled by touching buttons and divided into force cooling and
forced auto mode. It transfer between these two modes by pressing the buttons, the
cycling order of the button press is as below graph show to you.


10.19. Sleep mode
The sleep function is available at cooling, heating or auto mode

10.20. Cooling:
The set temperature rise 1 C per hour. Two hours later, the set temperature will maintain
as a constant and the fan speed is kept at low speed.

30
10.21. Heating:
The set temperature decrease 1 C per hour. Two hours later, the set temperature will
maintain as a constant and the air circulation is kept at low speed (Anti-cold function takes
precedence over all).

10.22. Auto
After an hour running under economic mode, the set temp will rise 1,if it is under cooling
mode; the set temp will decrease 1 ,if it is under heating mode; the set temp will be
changeless, if it is under fan-only mode; the condition will be the same after the air
conditioner running under economic mode after 2 hours, and during the next time the set
temp do not change. The total time is 7 hours, after 7 hours the unit stops.

10.23. Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous
settings before the power failure when power returns.
31
11. Model and Parameters
1PH, 198V-253V, 50Hz
Model DWM-Z26 DWM-Z35 DWM-Z50 DWM-Z60 DWM-Z70
PDELAYCOUNT 50SEC 50SEC 50SEC 127SEC 127SEC
DT1 / / / 6MIN 6MIN
I3SEC 10A 12A 17A 22A 26A
I5MIN 8.5A 8.5A 16A 20A 24A
IFAN 7.5A 7A 14A 16A 20A
IRESTORE 5A 6A 12A 14A 18A
IDEFROST 4.5A 4.5A 9A 0A 0A
TE1 28 34 34 25 25
TE2 32 36 36 32 32
TE3 30 30 30 30 30
TE4 20 20 20 20 20
TE5 2 3 3 2 2
TE6 7 10 10 12 12
TE7 60 64 64 63 63
TE8 53 56 56 54 54
TE9 50 50 50 50 50
THDEFROST/TC1 12 13 16 0 0
TMDEFROST/TC2 13 14 17 25 20
TLDEFROST/TC3 14 15 18 -3 -3
ANGLRANGE 210 143 143 155 155
ANGLOFF 96 0 0 0 0
ANGLCOOL 40 50 50 130 130
ANGLHEAT 197 105 105 100 100
ANGLCSL 0 50 50 117 117
ANGLCSH 40 75 75 143 143
ANGLHSL 157 80 80 87 87
ANGLHSH 197 105 105 113 113
ANGLDL 40 50 50 87 87
ANGLDH 197 105 105 143 143
ANGLFL 197 105 105 117 117
ANGLFH 197 105 105 117 117
CSPEEDH 1250 RPM 1280 RPM 1280 RPM 1150 RPM 1220 RPM
CSPEEDM 1000 RPM 1105 RPM 1105 RPM 1000 RPM 1100 RPM
CSPEEDL 750 RPM 1000 RPM 1000 RPM 800 RPM 1000 RPM
HSPEEDH 1100 RPM 1100 RPM 1265 RPM 1120 RPM 1250 RPM
HSPEEDM 1000 RPM 1000 RPM 1105 RPM 950 RPM 1150 RPM
HSPEEDL 850 RPM 900 RPM 1000 RPM 800 RPM

32
1120 RPM
12. Display board

Operation
The indicator flashes once every second after power is on and illuminates when the air
conditioner is in operation.
Timer indicator:
The indicator illuminates when TIMER is set ON.
PRE-DEF. indicator (For cooling & heating mode only)
The air conditioner starts defrosting automatically if outdoor unit frosts in heating
operating. At this time, PRE-DEF. indicator illuminates.
Auto indicator:
This indicator flashes when the air conditioner is in AUTO operation.
ECON indicator
This indicator illuminates while the air conditioner is in economic operation.

13. Troubleshooting
13.1 Self Diagnostic Failure Indications:
Failure phenomenon
Operation
lamp
Timer
lamp
Defrosting
lamp
Over current protection of the compressor occurs 4 times X
Indoor fan speed has been out of control for over 1 minute X
No over-zero signal
Temp. sensor on indoor evaporator is open circuit or short
circuit
X X
Indoor room temp. sensor is open circuit or short circuit X X
EEPROM error On X
Extinguish
Flash at 5Hz
33

13.2 Diagnostic chart
After energizing, no indicator is lighted and the air conditioner cannot be operated.


34


13.3 Resetting phenomenon often occurs during operation.
(That is automatically entering to the status when power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the
following procedure:




13.4 Operation lamp flashes and Timer lamp off.



12.12
13.5 Operation lamp flashes and Timer lamp on.


35


13.6 Operation lamp off and Timer lamp flashes


13.7 Operation lamp on and Timer lamp flashes
EEPROM error, indoor PCB is defective.
13.8 Operation lamp flashes, Timer lamp flashes .
This is alarm signal when the main chip cannot detect over-zero signal. When such failure occurs, the
main control board must have fault.
36


14. Characteristic of temperature sensor (T1, T2,T3)

Temp.

Resistance
K
Temp.

Resistance
K
Temp.

Resistance
K
Temp.

Resistance
K
-20 115.266 20 12.6431 60 2.35774 100 0.62973
-19 108.146 21 12.0561 61 2.27249 101 0.61148
-18 101.517 22 11.5 62 2.19073 102 0.59386
-17 96.3423 23 10.9731 63 2.11241 103 0.57683
-16 89.5865 24 10.4736 64 2.03732 104 0.56038
-15 84.219 25 10 65 1.96532 105 0.54448
-14 79.311 26 9.55074 66 1.89627 106 0.52912
-13 74.536 27 9.12445 67 1.83003 107 0.51426
-12 70.1698 28 8.71983 68 1.76647 108 0.49989
-11 66.0898 29 8.33566 69 1.70547 109 0.486
-10 62.2756 30 7.97078 70 1.64691 110 0.47256
-9 58.7079 31 7.62411 71 1.59068 111 0.45957
-8 56.3694 32 7.29464 72 1.53668 112 0.44699
-7 52.2438 33 6.98142 73 1.48481 113 0.43482
-6 49.3161 34 6.68355 74 1.43498 114 0.42304
-5 46.5725 35 6.40021 75 1.38703 115 0.41164
-4 44 36 6.13059 76 1.34105 116 0.4006
-3 41.5878 37 5.87359 77 1.29078 117 0.38991
-2 39.8239 38 5.62961 78 1.25423 118 0.37956
-1 37.1988 39 5.39689 79 1.2133 119 0.36954
0 35.2024 40 5.17519 80 1.17393 120 0.35982
1 33.3269 41 4.96392 81 1.13604 121 0.35042
2 31.5635 42 4.76253 82 1.09958 122 0.3413
3 29.9058 43 4.5705 83 1.06448 123 0.33246
4 28.3459 44 4.38736 84 1.03069 124 0.3239
5 26.8778 45 4.21263 85 0.99815 125 0.31559
6 25.4954 46 4.04589 86 0.96681 126 0.30754
7 24.1932 47 3.88673 87 0.93662 127 0.29974
8 22.5662 48 3.73476 88 0.90753 128 0.29216
9 21.8094 49 3.58962 89 0.8795 129 0.28482
10 20.7184 50 3.45097 90 0.85248 130 0.2777
11 19.6891 51 3.31847 91 0.82643 131 0.27078
12 18.7177 52 3.19183 92 0.80132 132 0.26408
13 17.8005 53 3.07075 93 0.77709 133 0.25757
14 16.9341 54 2.95896 94 0.75373 134 0.25125
15 16.1156 55 2.84421 95 0.73119 135 0.24512
16 15.3418 56 2.73823 96 0.70944 136 0.23916
17 14.6181 57 2.63682 97 0.68844 137 0.23338
18 13.918 58 2.53973 98 0.66818 138 0.22776
19 13.2631 59 2.44677 99 0.64862 139 0.22231
37
15. EXPLOSION DIAGRAMS
Exploded View Parts for DWMG-Z 26 - INDOOR
SAGE CODE : 857601
Power Supply: 220-240V, 50Hz, 1Ph
No. Sage Code Sage Description Part Name Quantity BOM code Remark
1 868450 Front panel and Panel frame assy G-Z26 Front panel and Panel frame assy 1 201132690088
2 Air filter G-Z26 Air filter 2 201131320312
3 Air cleaner G-Z26,35,50 Air cleaner 1 201130100212
4 Air cleaner holder G-Z26,35,50 Air cleaner holder 1 201130100217
6 Window cover for repairing G-Z26 Window cover for repairing 1 201131390182
7 Screw cap G-Z26 Screw cap 3 201132600045
9 Air out frame assy G-Z26 Air out frame assy 1 201132690066
9.1 Vertical grille G-Z26 Vertical grille 11 201131320336
9.2 Louver holder G-Z26 Louver holder 1 201131320337
9.3 868451 Horizontal louver G-Z26 Horizontal louver 1 201132600050
10 868456 Louver motor G-Z26 Louver motor 1 202400200012
11 Drain hose G-Z26 Drain hose 1 201130000011
14 Breakwater G-Z26 Breakwater 1 201130510509
15 Evaporator,assy G-Z26 Evaporator,assy 1 201532390079
16 Motor cover G-Z26 Motor cover 1 201131320316
17 868453 Motor G-Z26 Motor 1 202400300215
18 Bearing holder G-Z26 Bearing holder 1 202730100201
19 868452 Cross flow fan G-Z26 Cross flow fan 1 201100200008
20 Chassis G-Z26 Chassis 1 201132600055
21 Connecting pipe clamp G-Z26 Connecting pipe clamp 1 201130100204
23 Installation plate G-Z26 Installation plate 1 201232400000
24 Electronic control box,indoor unit G-Z26 Electronic control box,indoor unit 1 203332690050
24.1 E-Parts box's cover G-Z26 E-Parts box's cover 1 201131390179
24.2 E-Parts box G-Z26 E-Parts box 1 201131390178
24.3 868454 Main control board G-Z26 Main control board 1 201332690053
24.3.1 868455 Wires capacitor G-Z26 Wires capacitor 1 202401200020
24.4 868489 Indoor temp sensor G-Z26,35,50 Indoor temp sensor 1 202432390005
24.5 868513 Evaporator temp sensor G-Z26,60,70 Evaporator temp sensor 1 202301300080
24.6 Wire join G-Z26 Wire join 1 202301450124 JXZ-AD5ZG1-A
25 868493 Remote Controller G-Z26,35,50,60,70 Remote Controller 1 203355091296
26 Holder,Remote Controller G-Z26,35,50,60,70 Holder,Remote Controller 1 201155091083
27 Seal G-Z26,35,50,60,70 Seal 1 202720090001
28 Connector watering G-Z26,35,50,60,70 Connector for watering 1 201101020011
29.1 Copper nut - Liquid G-Z26,35,50 Copper nut - Liquid 1 201600320000 TLM-A01
29.2 Copper nut - Gas G-Z26,60,70 Copper nut - Gas 1 201600320001 TLM-B02
32 Sensor fix clamp G-Z26,35,50,60,70 Sensor fix clamp 1 201102000305
38
Exploded View Parts for DWMZ-Z 26 - OUTDOOR
SAGE CODE : 857602
Power Supply: 220-240V, 50Hz, 1Ph
No. Sage Code Sage Description Part Name Quantity BOM code Remark
1 Support Board Z-Z26,35 Support Board 1 201237400055
2 Rear net Z-Z26,35 Rear net 1 2011374G0001
3 Condenser coil assembly Z-Z26 Condenser coil assembly 1 201537390114
4 Valve plate Z-Z26,35,50 Valve plate 1 201235000018
5 Base pan assembly Z-Z26 Base pan assembly 1 20123739G011
6 Partition plate Z-Z26,35 Partition plate 1 2012374G0008
7 Right clapboard Z-Z26,35 Right clapboard 1 20123739G003
8 Big handle Z-Z26,35,50 Big handle 1 201145500005
9 Water collector Z-Z26,35,50 Water collector 1 201135290005
10 Front net Z-Z26 Front net 1 201235290030
11 Front panel Z-Z26,35 Front panel 1 2012374G0005
12 Clamp for front net Z-Z26,35,50,60,70 Clamp for front net 6 201135110801
13 868460 Axial flow fan Z-Z26,35 Axial flow fan 1 201100300502
14 868461 Motor Z-Z26 Motor 1 202400400465
15 Motor mounting bracket assembly Z-Z26 Motor mounting bracket assembly 1 201237700002
16 Left supporter Z-Z26,35 Left supporter 1 201237400054
17 Top cover assembly Z-Z26,35 Top cover assembly 1 2012374G0024
18 Clip,capacitor Z-Z26 Clip,capacitor 1 201200100026
19 868462 Capacitor,Compressor Z-Z26 Capacitor,Compressor 1 202401000415
20 868463 Wires capacitor Z-Z26,35 Wires capacitor 1 202401190019
21 Terminal Z-Z26 Terminal 1 202301450130
23 Insulation plate Z-Z26,35,50,60,70 Insulation plate 1 201135000004
24 Installation board for E-parts Z-Z26,35 Installation board for E-parts 1 201235000034
25 4-way valve assembly Z-Z26 4-way valve assembly 1 201637390402
25.1 868465 Gas valve Z-Z26 Gas valve 1 201600720094
25.2 868466 4-Ways valve Z-Z26 4-Ways valve 1 201600690010
26 Liquid valve assembly Z-Z26 Liquid valve assembly 1 201637390817
26.1 868498 Liquid valve Z-Z26,35,50 Liquid valve 1 201600740522
27 868464 Compressor Z-Z26 Compressor 1 201400620860
28 Little handler Z-Z26,35,50 Little handler 1 201150290006
39
No. Sage Code Sage Description Part Name Quantity BOM code Remark
1 Indoor unit plastic assembly G-Z35,50 Indoor unit plastic assembly 1 201132890441
1.1 Indoor unit plastic assembly G-Z35,50 Indoor unit plastic assembly 1 201132890440
1.1.1 868480 Front panel and Panel frame assy G-Z35,50 Front panel and Panel frame assy 1 P0000629163
1.1.1.1 Front panel G-Z35,50 Front panel 1 201132890520
1.1.1.2 Panel frame assy G-Z35,50 Panel frame assy 1 P0000628928
1.1.2 Air out frame assy G-Z35,50 Air out frame assy 1 201132800119
Exploded View Parts for DWMG-Z 35 - INDOOR
SAGE CODE : 857603
Power Supply: 220-240V, 50Hz, 1Ph
1.1.2 Air out frame assy G-Z35,50 Air out frame assy 1 201132800119
1.1.2.1 Vertical grille G-Z35,50 Vertical grille 10 201132800083
1.1.2.2 Louver holder G-Z35,50 Louver holder 2 201132800091
1.1.2.3.1 868481 Horizontal louver Up G-Z35,50 Horizontal louver UP 1 201132800131
1.1.2.3.2 868482 Horizontal louver Down G-Z35,50 Horizontal louver DOWN 1 201132800132
1.1.3 Chassis G-Z35,50 Chassis 1 P0000624791
2 Air filter G-Z35,50 Air filter 2 201131010402
3 Air cleaner G-Z26,35,50 Air cleaner 1 201130100212
4 Air cleaner holder G-Z26,35,50 Air cleaner holder 1 201130100217
5 868483 Display board assy G-Z35,50 Display board assy 1 203331390240
10 868484 Louver motor G-Z35,50 Louver motor 1 202400100022
11 Drain hose G-Z35,50 Drain hose 1 201101020012
14 Breakwater G-Z35,50 Breakwater 1 201131010409
15 Evaporator,assy G-Z35,50 Evaporator,assy 1 201532890055
16 Motor cover G-Z35,50 Motor cover 1 201131010403
17 868485 Motor G-Z35,50 Motor 1 202400300413
18 Bearing holder G-Z35,50 Bearing holder 1 202731010401
19 868486 Cross flow fan G-Z35,50 Cross flow fan 1 201131010401
21 Connecting pipe clamp G-Z35,50 Connecting pipe clamp 1 201131010405
23 Installation plate G-Z35,50 Installation plate 1 201232790009
24 Electronic control box,indoor unit G-Z35 Electronic control box,indoor unit 1 203332490164
24.1 E-Parts box's cover G-Z35,50 E-Parts box's cover 1 201131390181
24.2 E-Parts box G-Z35,50 E-Parts box 1 201131010411
24.3 868470 Main control board G-Z35 Main control board 1 201332490162
24.3.1 868488 Wires capacitor G-Z35,50 Wires capacitor 1 202401200001
24.4 868489 Indoor temp sensor G-Z26,35,50 Indoor temp sensor 1 202432390005
24.5 868490 Evaporator temp sensor G-Z35,50 Evaporator temp sensor 1 202301300426
24.6 Wire join G-Z35,50 Wire join 1 202301450119 JXZ-AD5Z-A
24.10 868491 Relay G-Z35,50 Relay 1 202300800071
24.11 868492 Switch board G-Z35,50 Switch board 1 201332890157
25 868493 Remote Controller G-Z26,35,50,60,70 Remote Controller 1 203355091296
26 Holder,Remote Controller G-Z26,35,50,60,70 Holder,Remote Controller 1 201155091083
27 Seal G-Z26,35,50,60,70 Seal 1 202720090001
28 Connector for watering G-Z26,35,50,60,70 Connector for watering 1 201101020011
29.1 Copper nut Liquid G-Z26,35,50 Copper nut Liquid 1 201600320000 TLM-A01
29.2 Copper nut Gas G-Z35,50 Copper nut Gas 1 201600320002 TLM-C03
31 Protection box for relay G-Z35,50 Protection box for relay 1 201230200705
32 Sensor fix clamp G-Z26,35,50,60,70 Sensor fix clamp 1 201102000305
40
Exploded View Parts for DWMZ-Z 35 - OUTDOOR
SAGE CODE : 857604
Power Supply: 220-240V, 50Hz, 1Ph
No. Sage code Sage description Part Name Quantity BOM code Remark
1 Support Board Z-Z26,35 Support Board 1 201237400055
2 Rear net Z-Z26,35 Rear net 1 2011374G0001
3 Condenser coil assembly Z-Z35 Condenser coil assembly 1 201537490054
4 Valve plate Z-Z26,35,50 Valve plate 1 201235000018
5 Base pan assembly Z-Z35 Base pan assembly 1 201237590032
6 Partition plate Z-Z26,35 Partition plate 1 2012374G0008
7 Right clapboard Z-Z26,35 Right clapboard 1 20123739G003
8 Big handle Z-Z26,35,50 Big handle 1 201145500005
9 Water collector Z-Z26,35,50 Water collector 1 201135290005
10 Front net Z-Z35 Front net 1 201235100023
11 Front panel Z-Z26,35 Front panel 1 2012374G0005
12 Clamp for front net Z-Z26,35,50,60,70 Clamp for front net 6 201135110801
13 868460 Axial flow fan Z-Z26,35 Axial flow fan 1 201100300502
14 868475 Motor Z-Z35 Motor 1 202400400723
15 Motor mounting bracket assembly Z-Z35 Motor mounting bracket assembly 1 201237400051
16 Left supporter Z-Z26,35 Left supporter 1 201237400054
17 Top cover assembly Z-Z26,35 Top cover assembly 1 2012374G0024
18 Clip,capacitor Z-Z35,50 Clip,capacitor 1 201200100025
19 868477 Capacitor,Compressor Z-Z35 Capacitor,Compressor 1 202401000410
20 868463 Wires capacitor Z-Z26,35 Wires capacitor 1 202401190019
21 Terminal Z-Z35,50 Terminal 1 202301450114
23 Insulation plate Z-Z26,35,50,60,70 Insulation plate 1 201135000004
24 Installation board for E-parts Z-Z26,35 Installation board for E-parts 1 201235000034
25 4-way valve assembly Z-Z35 4-way valve assembly 1 201637490471
25.1 868499 Gas valve Z-Z35,50 Gas valve 1 201600720194
25.2 868500 4-Ways valve Z-Z35,50 4-Ways valve 1 201600690011
26 Liquid valve assembly Z-Z35 Liquid valve assembly 1 201637490475
26.1 868498 Liquid valve Z-Z26,35,50 Liquid valve 1 201600740522
27 868476 Compressor Z-Z35 Compressor 1 201400600450
28 Little handler Z-Z26,35,50 Little handler 1 201150290006
41
No. Sage Code Sage Description Part Name Quantity BOM code Remark
1 Indoor unit plastic assembly G-Z35,50 Indoor unit plastic assembly 1 201132890441
1.1 Indoor unit plastic assembly G-Z35,50 Indoor unit plastic assembly 1 201132890440
1.1.1 868480 Front panel and Panel frame assy G-Z35,50 Front panel and Panel frame assy 1 P0000629163
1.1.1.1 Front panel G-Z35,50 Front panel 1 201132890520
1.1.1.2 Panel frame assy G-Z35,50 Panel frame assy 1 P0000628928
1.1.2 Air out frame assy G-Z35,50 Air out frame assy 1 201132800119
1 1 2 1 Vertical grille G Z35 50 Vertical grille 10 201132800083
Exploded View Parts for DWMG-Z 50 - INDOOR
SAGE CODE : 857605
Power Supply: 220-240V, 50Hz, 1Ph
1.1.2.1 Vertical grille G-Z35,50 Vertical grille 10 201132800083
1.1.2.2 Louver holder G-Z35,50 Louver holder 2 201132800091
1.1.2.3.1 868481 Horizontal louver Up G-Z35,50 Horizontal louver Up 1 201132800131
1.1.2.3.2 868482 Horizontal louver Down G-Z35,50 Horizontal louver Down 1 201132800132
1.1.3 Chassis G-Z35,50 Chassis 1 P0000624791
2 Air filter G-Z35,50 Air filter 2 201131010402
3 Air cleaner G-Z26,35,50 Air cleaner 1 201130100212
4 Air cleaner holder G-Z26,35,50 Air cleaner holder 1 201130100217
5 868483 Display board assy G-Z35,50 Display board assy 1 203331390240
10 868484 Louver motor G-Z35,50 Louver motor 1 202400100022
11 Drain hose G-Z35,50 Drain hose 1 201101020012
14 Breakwater G-Z35,50 Breakwater 1 201131010409
15 Evaporator,assy G-Z35,50 Evaporator,assy 1 201532890055
16 Motor cover G-Z35,50 Motor cover 1 201131010403
17 868485 Motor G-Z35,50 Motor 1 202400300413
18 Bearing holder G-Z35,50 Bearing holder 1 202731010401
19 868486 Cross flow fan G-Z35,50 Cross flow fan 1 201131010401
21 Connecting pipe clamp G-Z35,50 Connecting pipe clamp 1 201131010405
23 Installation plate G-Z35,50 Installation plate 1 201232790009
24 Electronic control box,indoor unit G-Z50 Electronic control box,indoor unit 1 203332890258
24.1 E-Parts box's cover G-Z35,50 E-Parts box's cover 1 201131390181
24.2 E-Parts box G-Z35,50 E-Parts box 1 201131010411
24.3 868487 Main control board G-Z50 Main control board 1 201332890219
24.3.1 868488 Wires capacitor G-Z35,50 Wires capacitor 1 202401200001
24.4 868489 Indoor temp sensor G-Z35,50 Indoor temp sensor 1 202432390005
24.5 868490 Evaporator temp sensor G-Z35,50 Evaporator temp sensor 1 202301300426
24.6 Wire join G-Z35,50 Wire join 1 202301450119 JXZ-AD5Z-A
24.10 868491 Relay G-Z35,50 Relay 1 202300800071
24.11 868492 Switch board G-Z35,50 Switch board 1 201332890157
25 868493 Remote Controller G-Z26,35,50,60,70 Remote Controller 1 203355091296
26 Holder,Remote Controller G-Z26,35,50,60,70 Holder,Remote Controller 1 201155091083
27 Seal G-Z26,35,50,60,70 Seal 1 202720090001
28 Connector for watering G-Z26,35,50,60,70 Connector for watering 1 201101020011
29.1 Copper nut Liquid G-Z26,35,50 Copper nut Liquid 1 201600320000 TLM-A01
29.2 Copper nut Gas G-Z35,50 Copper nut Gas 1 201600320002 TLM-C03
31 Protection box for relay G-Z35,50 Protection box for relay 1 201230200705
32 Sensor fix clamp G-Z26,35,50,60,70 Sensor fix clamp 1 201102000305
42
Exploded View Parts for DWMZ-Z 50 - OUTDOOR
SAGE CODE : 857606
Power Supply: 220-240V, 50Hz, 1Ph
No. Sage Code Sage Description Part Name Quantity BOM code Remark
1 Rear net Z-Z50 Rear net 1 2011481G0001
2 Condenser coil assembly Z-Z50 Condenser coil assembly 1 201537990000 CE-KFR61W/W-211.ZL.3
3 Valve plate Z-Z26,35,50 Valve plate 1 201235000018
4 Base pan assembly Z-Z50 Base pan assembly 1 201248100080
5 Big handle Z-Z26,35,50 Big handle 1 201145500005
6 Water collector Z-Z26,35,50 Water collector 1 201135290005
7 Rear right clapboard assembly Z-Z50 Rear right clapboard assembly 1 201237890012
8 Front right clapboard assembly Z-Z50 Front right clapboard assembly 1 201248100246
9 Partition plate assembly Z-Z50 Partition plate assembly 1 201238090014
10 Front panel Z-Z50 Front panel 1 20124810G002
11 Front net Z-Z50,60,70 Front net 1 201235390011
12 Clamp for front net Z-Z26,35,50,60,70 Clamp for front net 8 201135110801
13 Motor mounting bracket assembly Z-Z50 Motor mounting bracket assembly 1 201237990029
14 868495 Asynchronism motor Z-Z50 Asynchronism motor 1 202400410864 YDK55-6H
15 868496 Axial flow fan Z-Z50 Axial flow fan 1 201100320622
16 Left supporter Z-Z50 Left supporter 1 201248100070
17 Foam, Motor Holder Z-Z50 Foam, Motor Holder 1 202245500001
18 Support board for motor holder Z-Z50 Support board for motor holder 1 201248100076
19 Small handle Z-Z26,35,50 Small handle 1 201150290006
20 Top cover assembly Z-Z50 Top cover assembly 1 201245500031
21 868497 Compressor Z-Z50 Compressor 1 201400600351
22 liquid valve assembly Z-Z50 liquid valve assembly 1 201637890472
22.1 868498 Liquid valve Z-Z26,35,50 Liquid valve 1 201600740522
23 4-Ways valve assembly Z-Z50 4-Ways valve assembly 1 201637790258
23.1 868499 Gas pipe valve Z-Z35,50 Gas pipe valve 1 201600720194
23.2 868500 4-Ways valve Z-Z35,50 4-Ways valve 1 201600690011
24 Electrical box assembly Z-Z50 Electrical box assembly 1 203337890222
24.1 Installation board for E-parts Z-Z50 Installation board for E-parts 1 201245500039
24.2 Clip, capacitor Z-Z35,50 Clip, capacitor 1 201200100025 KC-20-03-04(38)(G)
24.3 868501 Capacitor, compressor Z-Z50 Capacitor, compressor 1 202401090055 45uF/450V
24.4 Terminal Z-Z50 Terminal 1 202301450114 JXZ-AZ5HG1-A
24.6 Insulation plate Z-Z26,35,50,60,70 Insulation plate 1 201135000004
24.7 868502 Fan motor capacitor Z-Z50,60 Fan motor capacitor 1 202401100353
43
No. Sage Code Sage Description Part Name Quantity BOM code Remark
1 868505 Front panel and Panel frame assyassy G-Z60,70 Front panel and Panel frame assyassy 1 201133090672
Exploded View Parts for DWMG-Z 60 - INDOOR
SAGE CODE : 857607
Power Supply: 220-240V, 50Hz, 1Ph
2 Air filter G-Z60,70 Air filter 2 201130790047 CE-KFR70G/I1Y.1-3
3 Air cleaner G-Z60,70 Air cleaner 1 201130790097
6 Window cover for repairing G-Z60,70 Window cover for repairing 1 201130790487
7 Screw cap G-Z60,70 Screw cap 3 201133090423
9 Air out frame assy G-Z60,70 Air out frame assy 1 201133090472
9.1 Vertical grille G-Z60,70 Vertical grille 15 201130790144 CE-KFR70G/I1Y.2-4
9.2 Louver holder G-Z60,70 Louver holder 3 201130790145 CE-KFR70G/I1Y.2-5
9.3 868506 Horizontal louver,up G-Z60,70 Horizontal louver,up 1 201133090762
9.4 868507 Horizontal louver,down G-Z60,70 Horizontal louver,down 1 201133090763
10 868508 Louver motor G-Z60,70 Louver motor 1 202400200004
11 Drain hose G-Z60,70 Drain hose 1 201101090005
15 Evaporator,assy G-Z60,70 Evaporator,assy 1 201533090067
16 Motor cover G-Z60,70 Motor cover 1 201130790483
17 868509 Motor G-Z60,70 Motor 1 202400400721
18 Bearing holder G-Z60,70 Bearing holder 1 202730790001
19 868510 Cross flow fan G-Z60,70 Cross flow fan 1 201100290010
20 Chassis G-Z60,70 Chassis 1 201133090473
21 Connecting pipe clamp G-Z60,70 Connecting pipe clamp 1 201233090031
23 Installation plate G-Z60,70 Installation plate 1 20123309G010
24 Electronic control box,indoor unit G-Z60 Electronic control box,indoor unit 1 203332990164
24.2 E-Parts box G-Z60,70 E-Parts box 1 201133090446
24.3 868511 Main control board G-Z60 Main control board 1 201332990143
24.4 868512 Indoor temp sensor G-Z60,70 Indoor temp sensor 1 202433190000
24.5 868513 Evaporator temp sensor G-Z26,60,70 Evaporator temp sensor 1 202301300080
24.6.1 Wire join 6T G-Z60,70 Wire join 6 Terminals 1 202301450125 JXZ-AD6Z-A
24.6.2 Wire join 3T G-Z60,70 Wire join 3 Terminals 1 202301450121 JXZ-AD3ZG1-A
24.6.3 Wire join 3TPower G-Z60,70 Wire join 3 Terminals-Power 1 202301450120 JXZ-AZ3HG1-B
24.7 wires capacitor G-Z60 wires capacitor 1 202401190033
24.9 Power module assy G-Z60,70 Power module assy 1 201333090405
24.11 868514 Display board assy G-Z60,70 Display board assy 1 201330790156
25 868493 Remote Controller G-Z26,35,50,60,70 Remote Controller 1 203355091296
26 Holder,Remote Controller G-Z26,35,50,60,70 Holder,Remote Controller 1 201155091083
27 Seal G-Z26,35,50,60,70 Seal 1 202720090001
28 Connector for watering G-Z26,35,50,60,70 Connector for watering 1 201101020011
29.1 Copper nut - Liquid G-Z26,60,70 Copper nut Liquid 1 201600320001 TLM-B02
29.2 Copper nut - Gas G-Z60,70 Copper nut Gas 1 201600320003 TLM-D04
38 E-Parts box's cover G-Z60,70 E-Parts box's cover 1 201130790478
41 Sensor fix clamp G-Z26,35,50,60,70 Sensor fix clamp 1 201102000305 41 Sensor fix clamp G Z26,35,50,60,70 Sensor fix clamp 1 201102000305
44
No. Sage Code Sage Description Part Name Quantity BOM code Remark
G
DERBY AIR CONDITIONING DWM-Z 60
Exploded View Parts for DWMZ-Z 60 - OUTDOOR
SAGE CODE : 857608
Power Supply: 220-240V, 50Hz, 1Ph
1 Rear net Z-Z60,70 Rear net 1 2011482G0001
2 Condenser coil assembly Z-Z60 Condenser coil assembly 1 201537990043 AU-KFR61W/N1PW-310(C2).ZL.1
3 Valve plate Z-Z60,70 Valve plate 1 201245370923
4 Base pan assembly Z-Z60,70 Base pan assembly 1 2012483G0007
5 Big handle Z-Z60,70 Big handle 1 201145320903
6 Water collector Z-Z60,70 Water collector 1 201135490001
7 Rear right clapboard assembly Z-Z60,70 Rear right clapboard assembly 1 201238190015
8 Front right clapboard assembly Z-Z60,70 Front right clapboard assembly 1 201245320903
9 Partition plate assembly Z-Z60,70 Partition plate assembly 1 201248200030
10 Front panel Z-Z60,70 Front panel 1 201248200028
11 Front net Z-Z50,60,70 Front net 1 201235390011
12 Clamp for front net Z-Z26,35,50,60,70 Clamp for front net 8 201135110801
13 Motor mounting bracket assembly Z-Z60 Motor mounting bracket assembly 1 201238190011
14 868518 Asynchronism motor Z-Z60 Asynchronism motor 1 202400410643 YDK53-6C
15 868519 Axial flow fan Z-Z60,70 Axial flow fan 1 201100300202
16 Left supporter Z-Z60 Left supporter 1 201245300063
18 Support board for motor holder Z-Z60,70 Support board for motor holder 1 201248200095
20 Top cover assembly Z-Z60,70 Top cover assembly 1 2012482G0013
21 868520 Compressor Z-Z60 Compressor 1 201400600870
22 liquid valve assembly Z-Z60 liquid valve assembly 1 201637990556
22.1 868521 Liquid valve Z-Z60 Liquid valve 1 201600740297
23 4-Ways valve assembly Z-Z60 4-Ways valve assembly 1 201637990559
23.1 868522 Gas pipe valve Z-Z60,70 Gas pipe valve 1 201600720398
23.2 868523 4-Ways valve Z-Z60,70 4-Ways valve 1 201600600119
24 Electrical box assembly Z-Z60 Electrical box assembly 1 203337990143
24.2.1 Clip, capacitor Start Z-Z60,70 Clip, capacitor - Start 1 201200100011 KFR-75W/K.3-3 60uF
24.2.2 Clip, capacitor Run Z-Z60,70 Clip, capacitor - Run 1 201200100027 KFR-61W/K.3-3 50 uF
24.3.1 868524 Capacitor, compressor Z-Z60,70 Capacitor, compressor - compressor start 1 202401090057 50UF/440V-450V(VDE)
24.3.2 868525 Capacitor, compressor Z-Z60,70 Capacitor, compressor -Soft start 1 202401090058 60uF/450V
24.4.1 Terminal 2 Z-Z60,70 Terminal - 2 2 202301450035 JXZ-PZ2P-B (middle)
24.4.2 Terminal 8 Z-Z60,70 Terminal -8 1 202301450072 JXZ-AD8Z-B (main)
24.6 Insulation plate Z-Z26,35,50,60,70 Insulation plate 1 201135000004
24.7 868502 Fan motor capacitor Z-Z50,60 Fan motor capacitor 1 202401100353
24.9 868526 Contactor Z-Z60,70 Contactor 1 202300870023
24.12 Installation box for E-parts Z-Z60,70 Installation box for E-parts 1 20123819G000
24.13 868527 soft-start controller Z-Z60,70 soft-start controller 1 202301820501
25 868528 Evaporator temp sensor Z-Z60,70 Evaporator temp sensor 1 202440500004 CGQ-GWJ-L850-SMP3B-P750
26 Handle Z-Z60,70 Handle 2 201145400003
45
No. Sage code Sage description Part Name Quantity BOM code Remark
1 868505 Front panel and Panel frame assy G-Z60,70 Front panel and Panel frame assy 1 201133090672
2 Air filter G Z60 70 Air filter 2 201130790047 CE KFR70G/I1Y 1 3
Exploded View Parts for DWMG-Z 70 - INDOOR
SAGE CODE : 857609
Power Supply: 220-240V, 50Hz, 1Ph
2 Air filter G-Z60,70 Air filter 2 201130790047 CE-KFR70G/I1Y.1-3
3 Air cleaner G-Z60,70 Air cleaner 1 201130790097
6 Window cover for repairing G-Z60,70 Window cover for repairing 1 201130790487
7 Screw cap G-Z60,70 Screw cap 3 201133090423
9 Air out frame assy G-Z60,70 Air out frame assy 1 201133090472
9.1 Vertical grille G-Z60,70 Vertical grille 15 201130790144 CE-KFR70G/I1Y.2-4
9.2 Louver holder G-Z60,70 Louver holder 3 201130790145 CE-KFR70G/I1Y.2-5
9.3 868506 Horizontal louver,up G-Z60,70 Horizontal louver,up 1 201133090762
9.4 868507 Horizontal louver,down G-Z60,70 Horizontal louver,down 1 201133090763
10 868508 Louver motor G-Z60,70 Louver motor 1 202400200004
11 Drain hose G-Z60,70 Drain hose 1 201101090005
15 Evaporator,assy G-Z60,70 Evaporator,assy 1 201533090067
16 Motor cover G-Z60,70 Motor cover 1 201130790483
17 868509 Motor G-Z60,70 Motor 1 202400400721
18 Bearing holder G-Z60,70 Bearing holder 1 202730790001
19 868510 Cross flow fan G-Z60,70 Cross flow fan 1 201100290010
20 Chassis G-Z60,70 Chassis 1 201133090473
21 Connecting pipe clamp G-Z60,70 Connecting pipe clamp 1 201233090031
23 Installation plate G-Z60,70 Installation plate 1 20123309G010
24 Electronic control box,indoor unit G-Z70 Electronic control box,indoor unit 1 203333090269
24.2 E-Parts box G-Z60,70 E-Parts box 1 201133090446
24.3 868530 Main control board G-Z70 Main control board 1 201333090352
24.4 868512 Indoor temp sensor G-Z60,70 Indoor temp sensor 1 202433190000
24.5 868513 Evaporator temp sensor G-Z26,60,70 Evaporator temp sensor 1 202301300080
24.6 Wire join 6T G-Z60,70 Wire join 6 Terminal 1 202301450125 J XZ-AD6Z-A
24.6 Wire join 3T G-Z60,70 Wire join 3 Terminal 1 202301450121 J XZ-AD3ZG1-A
24.6 Wire join 3TPower G-Z60,70 Wire join 3 Terminal-Power 1 202301450120 J XZ-AZ3HG1-B
24.7 868531 wires capacitor G-Z70 wires capacitor 1 202401100353
24.9 Power module assy G-Z60,70 Power module assy 1 201333090405
24.11 868514 Display board assy G-Z60,70 Display board assy 1 201330790156
25 868493 Remote Controller G-Z26,35,50,60,70 Remote Controller 1 203355091296
26 Holder,Remote Controller G-Z26,35,50,60,70 Holder,Remote Controller 1 201155091083
27 Seal G-Z26,35,50,60,70 Seal 1 202720090001
28 Connector for watering G-Z26,35,50,60,70 Connector for watering 1 201101020011
29.1 Copper nut Liquid G-Z26,60,70 Copper nut - Liquid 1 201600320001 TLM-B02
29.2 Copper nut Gas G-Z60,70 Copper nut - Gas 1 201600320003 TLM-D04
38 E Parts box's cover G Z60 70 E Parts box's cover 1 201130790478 38 E-Parts box's cover G-Z60,70 E-Parts box's cover 1 201130790478
41 Sensor fix clamp G-Z26,35,50,60,70 Sensor fix clamp 1 201102000305
46
No. Sage code Sage description Part Name Quantity BOM code Remark
DERBY AIR CONDITIONING DWM-Z 70
Exploded View Parts for DWMZ-Z 70 - OUTDOOR
SAGE CODE : 857610
Power Supply: 220-240V, 50Hz, 1Ph
1 Rear net Z-Z60,70 Rear net 1 2011482G0001
2 Condenser coil assembly Z-Z70 Condenser coil assembly 1 201538090023 AU-KFR90W/N1PW-310(C0).ZL.2
3 Valve plate Z-Z60,70 Valve plate 1 201245370923
4 Base pan assembly Z-Z60,70 Base pan assembly 1 2012483G0007
5 Big handle Z-Z60,70 Big handle 1 201145320903
6 Water collector Z-Z60,70 Water collector 1 201135490001
7 Rear right clapboard assembly Z-Z60,70 Rear right clapboard assembly 1 201238190015
8 Front right clapboard assembly Z-Z60,70 Front right clapboard assembly 1 201245320903
9 Partition plate assembly Z-Z60,70 Partition plate assembly 1 201248200030
10 Front panel Z-Z60,70 Front panel 1 201248200028
11 Front net Z-Z50,60,70 Front net 1 201235390011
12 Clamp for front net Z-Z26,35,50,60,70 Clamp for front net 8 201135110801
13 Motor mounting bracket assembly Z-Z70 Motor mounting bracket assembly 1 201238190000
14 868535 Asynchronism motor Z-Z70 Asynchronism motor 1 202400430315 YDK100-6
15 868519 Axial flow fan Z-Z60,70 Axial flow fan 1 201100300202
16 Left supporter Z-Z70 Left supporter 1 2012484G0001
18 Support board for motor holder Z-Z60,70 Support board for motor holder 1 201248200095
20 Top cover assembly Z-Z60,70 Top cover assembly 1 2012482G0013
21 868536 Compressor Z-Z70 Compressor 1 201400620500
22 liquid valve assembly Z-Z70 liquid valve assembly 1 201638090527
22.1 868537 Liquid valve Z-Z70 Liquid valve 1 201600700010
23 4-Ways valve assembly Z-Z70 4-Ways valve assembly 1 201638090598
23.1 868522 Gas pipe valve Z-Z60,70 Gas pipe valve 1 201600720398
23.2 868523 4-Ways valve Z-Z60,70 4-Ways valve 1 201600600119
24 Electrical box assembly Z-Z70 Electrical box assembly 1 203338090169
24.2.1 Clip, capacitor Start Z-Z60,70 Clip, capacitor Start 1 201200100011 KFR-75W/K.3-3 60uF
24.2.2 Clip, capacitor Run Z-Z60,70 Clip, capacitor Run 1 201200100027 KFR-61W/K.3-3 50uF
24.3.1 868524 Capacitor, compressor Start Z-Z60,70 Capacitor, compressor - Compressor Start 1 202401090057 50UF/440V-450V(VDE)
24.3.2 868525 Capacitor, compressor Soft start Z-Z60,70 Capacitor, compressor - soft start 1 202401090058 60uF/450V
24.4.1 Terminal -2 Z-Z60,70 Terminal - 2 2 202301450035 JXZ-PZ2P-B
24.4.2 Terminal -8 Z-Z60,70 Terminal - 8 1 202301450072 JXZ-AD8Z-B
24.6 Insulation plate Z-Z26,35,50,60,70 Insulation plate 1 201135000004
24.7 868538 Fan motor capacitor Z-Z70 Fan motor capacitor 1 202401100505
24.9 868526 Contactor Z-Z60,70 Contactor 1 202300870023
24.12 Installation box for E-parts Z-Z60,70 Installation box for E-parts 1 20123819G000
24.13 868527 soft-start controller Z-Z60,70 soft-start controller 1 202301820501
25 868528 Evaporator temp sensor Z-Z60,70 Evaporator temp sensor 1 202440500004 CGQ-GWJ-L850-SMP3B-P750
26 Handle Z-Z60,70 Handle 2 201145400003