SAIC-D-2007
WBS / BI / JO NUMBER
1-Dec-06
MECH-
CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) LAYOUT DRAWING NUMBER SCHEDULED INSPECTION DATE & TIME SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO INSPECTION LEVEL
EQPT CODE
SYSTEM ID.
PLANT NO.
ACTUAL INSPECTION DATE & TIME SAUDI ARAMCO ACTIVITY NUMBER CONTRACTOR INSPECTION LEVEL
ITEM No. A.
ACCEPTANCE CRITERIA
REFERENCE
PASS
FAIL
N/A
RE-INSP DATE
GENERAL REQUIREMENTS: See Note 1 & Attachment 1 (Use PIPs) Vessel location and foundation were verified to conform with the coordinates and elevation in the plan drawing. Alignment of flange face of nozzles shall be within 1/2 degree of the specified plane. (PIP-VEFV1100/1102, Page 1, Note 7) Bolt holes are within 1/8" of the specified location. (PIP-VEFV1100/1102, Page 1, Note 28) VERTICAL VESSELS Vertical centerlines and base line of vertical vessel are punched and circled with paint. (VEFV1100/1102Page 1, Note 25) Orientation line for vertical vessels is based on a directional centerline (e.g.;North, South, etc.) and as referenced on the construction drawings. (VEFV1100/1102, Page 2) Distance of bottom of base support to the base line of vertical vessel shall be within the tolerance of +0 , -1/32" per foot of vessel diameter to a maximum of 1/2". (PIP-VEFV1100/1102, Pg 1, Note 12) Supports are level or are with in the following tolerances: + 1/8" or + 0.02" per foot of vessel diameter, but not to exceed 3/8". (PIP-VEFV1100/1102 Page 1, Note 26) Supports located are within the following tolerances: +0", -1/32" per foot of vessel diameter with max of 1/2". (VEFV1100/1102 Page 1, Note 13) HORIZONTAL VESSELS Orientation line for horizontal vessels is based on the vertical centerline. (PIP-VEFV1100/1102, Page 2) Centerlines (orientation lines) are punch marked and circled with paint. (PIP-VEFV1100/1102, Page 1, Note 25) Supports of horizontal vessel are located within the tolerance of +0", + 1/8" from the horizontal centerlines. (PIP-VEFV1100/1102, Page 1, Note 22) Supports are level or are with in the following tolerances: + 1/8" or + 0.02" per foot of vessel diameter, but not to exceed 3/8". (PIP-VEFV1100/1102, Page 1, Note 26) SAES-D-001, Par. 3.2 SAES-D-001, Par. 3.2 SAES-D-001, Par. 3.2 SAES-D-001, Par. 3.2 SAES-D-001, Par. 3.2
A1
A2
A3
B.
B1
B2
B3
B4
B5
C.
C1
C2
C3
C4
Page 1 of 4
SAIC-D-2007
WBS / BI / JO NUMBER
1-Dec-06
MECH-
CONTRACTOR / SUBCONTRACTOR
ACCEPTANCE CRITERIA
REFERENCE
PASS
FAIL
N/A
RE-INSP DATE
NOTES: Use PIPs during Equipment Alignment & Elevation Checks in the field. See Attachment 1. Use PIP VEFV1100. ATTACHMENTS: ATTACHMENT 1 - VEFV1102 - Vessel Tolerances (Elevation) REFERENCE DOCUMENTS: 1- SAES-D-001 -- Design Criteria for Pressure Vessels, 31 December 2001 2- VEFV1100/1102 -- Process Industry Practices (Fabrication/Installation Details), 21 April 1999
Contractor / Third-Party
Construction Representative*
Work is Complete and Ready for Inspection: Name, Initials and Date: Name, Initials and Date:
Saudi Aramco
PMT Representative
T&I Witnessed QC Record Reviewed Work Verified
QC Inspector
Performed Inspection Name, Initials and Date: Work / Rework May Proceed
PID Representative
T&I Witnessed Name, Initials and Date: QC Record Reviewed Work Verified
QC Supervisor
Quality Record Approved: Name, Sign and Date: *Person Responsible for Completion of Quality Work / Test
Y = YES
N = NO F = FAILED
Page 2 of 4
SAIC-D-2007
1-Dec-06