SF6 GAS CIRCUIT BREAKER

40.5kV~550kV GCB

Xian Electric Import & Export Co.,Ltd.


A Member of China Xian Electric Group

China Xian Electric Group ( XD for short ):


XD is the largest base for manufacturing complete sets of ultra-high voltage AC transmission and transformation equipment in China. XD is the largest base for manufacturing complete sets of ultra-high voltage DC transmission and transformation equipment in China. XD is the largest base for researching and developing complete sets of ultra-high voltage AC & DC transmission and transformation equipment in China , and is appointed by the state as the national profession center responsible for the quality supervision, examination and test. XD is the largest base for exporting complete sets of ultra-high voltage AC & DC transmission and transformation equipment in China.

Main Products
40.5-550kV Live Tank Type Circuit Breaker 40.5-550kV Dead Tank Type Circuit Breaker 40.5kV Vacuum Circuit Breaker 1 13 21

40.5-550kV LIVE TANK TYPE CIRCUIT BREAKER

1. 363kV SF6 Iive tank circuit breakers 2. 550kV SF6 Iive tank circuit breaker 3. 252kV/300kV SF6 Iive tank circuit breaker 4. 252kV/300kV SF6 Iive tank circuit breakers 5. 126kV/145kV SF6 Iive tank circuit breaker 6. 126kV SF6 Iive tank circuit breakers 7. 40.5kV SF6 Iive tank circuit breaker 2

FEATURES 1 Superior interrupting capability


These breakers can cope with all known switching phenomena. The severe rate of rise of the recovery voltage by a short-line fault and the high recovery voltage peak by out-of-phase interruption are both cleaned by the efficiently designed interrupter. In magnetizing current switching, the overvoltage is less than twice the applied voltage. No restrike or reignition occurs in charging current switching.

2 Reliable insulating and current-carrying capability


Because of the isolation of the insulating medium (SF6 gas) from the atmosphere, the breakers have a reliable insulating capability. SF6 gas does not deteriorate with age and it protects the insulators in the gas space. It also protects the contacts from oxidization and other chemical reactions as SF6 gas is stable and inert when used with most materials.

3 Reduced maintenance work


The unit construction of the breakers minimizes inspection and maintenance work. Since the spring operating mechanism does not require compressed air, it seldom require inspection.

4 Reliable earthquake withstand capability


These live tank SF6 gas circuit breakers are substantially resistant to seismic shock since most parts of the interrupter unit are made simple and light in weight.

RATINGS
Main Technical Data of 40.5~550kV Live Tank Type CB (Based on IEC)

=N O

Rated voltage (kV)

40.5

72.5

126

145

252

300

363

550

Rated frequence (Hz)

50,60

Rated current (A)

1600/2000

2500

2000 / 2500 / 3150

4000

3150 / 4000

3150

3150 / 4000

Rated breaking current (kA)

25 / 31.5

25 / 31.5

31.5 / 40

31.5 / 40

40 / 50

40

40

50 / 63

Making current (kA)

63

80

80 / 100

80 / 100

100 / 125

100

100

125 / 160

Rated short-time withstand current 3s (kA) 25/31.5 (4s) 31.5 (4s) Rated peak withstand current (kA)

31.5 / 40 (4s) 31.5 / 40 (4s) 40 / 50 (4s)

40 (3s)

40 (3s)

50 / 63 (3s)

63

80

80 / 100

80 / 100

100 / 125

100

100

125 / 160

Creepage distance (cm/kV)

2.5

2.5

2.5 / 3.1

2.5 / 3.1

2.5 / 3.1

2.5 / 3.1

2.5 / 3.1

2.0 / 2.5

1 min. power frequence withstand voltage (kV)

To earth

95

160

230

275

460

380

510

740

Rated lightning impulse withstand voltage (kV) To earth 185 350 550 650 1050 1050 1175 1675

5 min, power frequence withstand voltage under zero-gauge pressure (kV)

To earth

2 x 40.5 / 3

2 x 72.5 / 3

1.5 x126 / 3

1.3x145 / 3

1.5 x 252 / 3

1.3 x 300 / 3

1.3 x 363/ 3 1.3 x 550 / 3

Close time (ms)

==

100

150

100

100

100

100

100=====

100

Open time (ms)

===

70

30

30=======

30

===

30

25

25

20

Breaking time (ms)

60

================

50======

50 ======

40

Rated reclose operating dudy

O-0.3s-CO-180s-CO = 40

Close-open time (ms)

60 0.50 (31.5kA) 0.4 (25kA)

40

50~70

40

===40

Rated pressure of SF6 gas (MPa)

0.45

0.50

0.60

Leakage of SF6 gas (%/year)

==================

1%=====================

1%

1%

Rated voltage (kV)

40.5

72.5

126

145

252

300

363

550

Number of breaks per pole Close resistance (/ phase) Equipped mechanism 1400

1 ___ Pneumatic or Spring or Hydrulic 4500

400 Pneumatic

20

Pneumatic or Spring

Weight of a CB (kg)

1000

1200 / 1800 1400 / 2000 3500/4500

7200

11400

Spring operating mechanism


No. Item Unit Ratings

Voltage of control & auxiliary circuit

DC110 / DC220

Current of open winding

5.8 / 2

Current of close winding

3.3 / 2

Voltage of energizing motor

DC220 (AC220)

Voltage of heater

AC220

Pneumatic operating mechanism


No. Item Unit Ratings

Rated operating air pressure

MPa

1.50

Locking operating air pressure of CB

MPa

1.20

0.03

Unlocking operating air pressure of CB

MPa

1.30

0.03

Air pressure of locking in auto reclosing operating duty

MPa

1.43

0.03

Air pressure of unlocking in auto reclosing operating duty

MPa

1.46

0.03

=P Q

CONSTRUCTION
Generally 252kV and below SF6 high voltage circuit breakers by XD are typed in 1-break (per pole), not being equipped with parallel capacitors; 363kV-550kV are typed in 2-break (per pole) but being equipped with parallel capacitors and close resistors. The driving unit for the close resistors is touched first and some oscillating energy on the circuit is absorbed by the close resistors so to control the close overvoltage.On opening, the contact with the resistors is separated prior to the main contact. 252kV and below SF6 high voltage CB are equipped with spring operating mechanism, and 252kV and above with the pneumatic operating mechanism. The pneumatic operating mechanism takes compressed air as its driving power to do open operation ( A CB is equipped with a complete set of air compressing system), and to do close operation depends on spring force. lt is also equipped with a mechanical anti-tripping device, electric anti-tripping device, phase protective unit, SF6 density control unit and air pressure control unit. The spring operating mechanism takes spring force as its driving power to do either open or close operation. Before operation, the close spring is energized by the close spring that is performing the close operation. lt is also equipped with a mechanical anti-tripping device, electric anti-tripping device and SF6 density control unit.

1 Interrupter

Fixed main contact

Fixed arcing contact

Moving main contact

Key
Live parts (moving parts) Live parts (fixed parts)
Piston Fixed finger Arc Nozzle Moving arcing contact Puffer cylinder

lnsulators

lnner construction of interrupter

2 Spring operating mechanism


The design of this mechanism ensures the high performance required by reliable operation. The lever engaged with the locking device, which is released when the trip coil is energized, is rotated counterclockwise by the trip spring (Fig.1). The cam and the ratchet wheel engaged with the locking device, which is released when the closing coil is energized, are rotated counterclockwise by the closing spring. The lever is rotated clockwise, compressing the trip spring by torque from the cam (Fig.2). As soon as the closing sequence is completed, the closing spring is charged by the ratchet linked to the motor (Fig.3).
Trip spring

Cam

Ratchet Closing spring Lever Ratchet wheel

Closing-holding latch Closing trigger Trip-holding latch Closing coil interrupter Trip trigger

open coil

Fig1. Closed position (closing spring charged)

Fig2. Open position (closing spring charged)

Fig3. Closed position (closing spring discharged)

=R S

3 Pneumatic operating mechanism


Stationary contact Moving contact

Pin Cam Lever Trigger Piston rod Piston Cylinder

Plunger Trip coil Latch Trigger Exhaust port Cylindrical valve Air reservoir Compressed air(15kg/cm2) Control valve Valve seat Closing spring Shock absorber Compressed air (15kg/cm2)

Fig1. Closed position

Fig2. Open stage Opening operation (by compressed air)


--Opening signal is introduced to trip coil --Lock system of linkage is released by plunger of trip coil Pin --Cylindrical valve is driven to open spring --Moving contact connected to piston is pulled down Roller Exhaust port port Air reservoir Compressed air Piston rod --Cylindrical valve is driven to ciose by linkage --Compressed air in cylinder is exhausted through exhaust

Stationary contact

Moving contact

Plunger Open coil Cam Anti-pumping lever Holding latch Cylinder Piston

Closing operation (by spring)


--Closing signal is introduced to closing coil --Lock system of linkage is released by plunger of closing coil --Holding latch becomes free and is released from pin A --Piston is pushed up by discharging of closing spring --Moving contact connected to piston is driven to close --Moving contact and piston are held by closing spring at

Closing spring Shock absorber

Fig3. Open position

closed position

DIMENSIONS AND FOUNDATION


72.5kV SF6 Live Tank Type CB
1 1100 1100

4 QRMS QOQP

5 PNOP

OOMP

2580 6 12 10 7 B 11 OMR 280 B

730

OMM

240

Key
1. Upper terminal 2. Lower terminal 3. Bushing of arc chamber PPM 523 280 13 792 1595 5. Frame 6. Supporter 7. Level of concrete 8. Anchor bolt 9. Nameplate 10. Earthing plate 11. Cable hose ( 114) 12. Control box 13. Cable entrance OQM 4. Supporting bushing B-B Foundition

OMM

=T U

126kV /145kV SF6 Live Tank Type CB


1700 1700

Upper terminal Bushing of arc chamber Lower terminal

Pressure gauge, Supporting bushing iN counter,indicator Nameplate

iO

OOMM

Control box 3780 Cable hose Earthing terminal A PMM

Frame

Supporter

Level of concrete 240

Anchor bolt 140 A-A Foundition 340 RM PMM OQM 250 250

Anchor bolt 1:20

QMM

QOM

QMM

280 Anchor bolt 8-M24


100

NMM

280 UQR 80 2000

Level of concrete

250 PNR

Type 126 kV 145 kV

L1 4806 4956

L2 3450 3500

QUM

OMM

R8

05

Cable entrance

NQOM

NQM

252kV/300kV SF6 Live Tank Type CB


3000~4000 3000~4000 A

1525 QRTU 6 NRM 150 NUM ORM Cable 760 760

NPUN

OOMM

100

1200 670 NMM

250

Entrance of cable 150

190

NMM

Cable plate

STM NOMM

NNOM

OMM

C C D-D 1: 15 100
TR

A 1: 3 4 - 18

250 Anchor bolt 8-M24

20

QM QM QM

SPM

SPM

150 Earthing terminal

TM

TNQV

=V NM

363kV SF6 Live Tank Type CB

Close resistor

Capacitor

Supporting bushing

1240 OOMM 4
PMM

2 3 D

5 D
800X720

820 C-C 1: 10

D-D 150 NMMM 250 UM 150 80 Entrance of cable pipe


QRM

1200
NRM

Cable
380

PMM

ORM

Air pipe 1

150

Cable

NRM

1: 20 b
SPM

RM

5 4 3 2 1

22X1.5 T2-Y Copper pipe A22: 3-way joint A22: 1-way joint A22: 1-way joint B22X2G 1/2: 1-way joint

20-24m Anchor bolt 1 2 Type 1 3 363 kV With or without close resistor With close resistor Without close resistor a 4800 4800 b 5000 5000 h 7000 6400 l 5242 5245

SPM

550kV SF6 Live Tank Type CB


a

Close resistor

Capacitor

Supporting bushing

1240 OOMM 3 4
PMM

2 D

5 D
800X720

820 C-C 1: 10
NRM

D-D 150 250 UM 150 80 Entrance of cable pipe


QRM

1200

NMMM

ORM

Cable
380 NRM

PMM

Air pipe 1 1: 20

150

Cable
RM

5 4 3 2 1

22X1.5 T2-Y Copper pipe A22: 3-way joint A22: 1-way joint A22: 1-way joint B22X2G 1/2: 1-way joint

20-24m 1 2 1 3 550 kV Type With or without close resistor With close resistor Without close resistor a 6400 6400 b 8000 8000

SPM

Anchor bolt h 8300 7700 l 6490 6490

SPM

=NN NO

40.5-550kV DEAD TANK TYPE CIRCUIT BREAKER

1. 550kV SF6 dead tank type circuit breakers 2. 550kV SF6 dead tank type circuit breakers 3. 363kV SF6 dead tank type circuit breakers 4. 252kV SF6 dead tank type circuit breakers 5. 126kV/145kV SF6 dead tank type circuit breakers 6. 40.5kV/72.5kV SF6 dead tank type circuit breakers 2

FEATURES
Besides those advantages the live tank type SF 6 circuit breaker possesses, the dead tank type SF6 circuit breaker has excellent anti-seismic and pollution-resisting capabilities. lt is also characterized by a compact construction and small occupation of space due to the current transformer that is equipped to the dead breaker. The dead tank type SF6 circuit breaker is suitably used to such places where earthquake often takes place and severe pollution exists, and also to higher elevation area.

RATINGS
Main Technical Data of 40.5~550kV Dead Tank Type CB (Based on IEC)

Rated voltage (kV)

40.5

72.5

126

145

252

363

550

Rated frequence (Hz) 1250 / 2000

50/60 1250 / 2000 / 3150 40 / 50 2000 / 2500 / 3150 50 2500 / 3150 /4000 50 / 63

Rated current (A) 40

1600 / 2000 / 3150

Rated breaking current (kA)

31.5

Making current (kA)

100

80

100 / 125

125

125 / 150

Rated short-time withstand current 3s (kA)

40

31.5

40 / 50

50

50 / 63

Rated peak withstand current (kA)

100

80

100 / 125

125

125 / 150

Creepage distance (cm/kV)

2.5 / 3.1

1.7 / 2.5

2.5 / 3.1

1.7 / 2.5 / 3.1

1.7 / 2.5

=NP NQ

Rated voltage (kV)

40.5

72.5

126

145

252

363

550

1 min. power frequence withstand voltage (kV)

To earth

95

160

230

275

460

510

740

Rated lightning impulse withstand voltage (kV)

To earth

185

350

550

650

1050

1175

1675

5 min, power frequence withstand voltage under zero-gauge pressure (kV)

To earth

40.5 / 3

1.5

72.5 / 3 1.3

126 / 3

1.3

145 / 3

1.3

252 / 3 1.3

363 / 3

1.3

550 / 3

Close time (ms)

=========

100===================

150

100

Open time (ms)

30

30===============

25

50 =======

20

Breaking time (ms)

60

60=====================

50

40

Rated reclose operating dudy

0.3s-CO-180s-CO

Close-open time (ms)

40

Rated pressure of SF6 gas (MPa)

0.5

0.6

0.5

Alarm/lock pressure of SF6 gas (MPa)

0.45 / 0.40

0.55 / 0.50

0.45 / 0.40

Leakage of SF6 gas (%/year)

===

0.5

Number of breaks per pole

1 __ __

Close resistance ( / phase)

400

20

Equipped mechanism

Pneumatic or Spring mechanism

Pneumatic mechanism

Weight of a CB (KB)

1500

1550

3400

17000

18000

24000

DIMENSIONS AND FOUNDATION


40.5kV/72.5kV SF6 Dead Tank Type CB
L3 L4 L6 L5 L6

iN

iO

1280

920 1200

Type 40.5 kV 72.5 kV

CT model Outside lnside Outside

L1 2690 2840 2690

L2 3234 3385 3490

L3 2028 2055 2080

L4 968 968 1060

L5 2087 2175 2340

L6 944 1032 1065

A-A 1400 1280 A NMQM VOM A PSR 950


SM OR

Cable ditch

Fixing of anchor bolt Supporter Mud

RMM

Concrete base 20 Shim 80 Anchor bolt (4-M20)

Earthing cable

160

160

Earthing cable

Cement cast on second time

=NR NS

126kV/145kV SF6 Dead Tank Type CB

3200 1460 1460

2030 1510

150X150

Cable ditch

Fixing of anchor bolt

Mud 500 NRMM NMMM Earthing cable 925 E Shim 1300 2000 150 Cement cast on second time Anchor bolt Concrete base

NQPM

PRVM

252kV SF6 Dead Tank Type CB

4000(5000)

4000(5000)

2860

RMMM

2 8 ORRM NOOM

3 1 4

6 915 1220 1520 3000 NMM 7


22 Alu. alloy plate

5 680 900

45 45 45

NQR

9 - 18

245

a==~=

Key
1. View window of open-close indicator, 3000~4000
PMM 70

3000~4000
100

Air reservoir

operation counter and pressure gauge 2. CT 3. Nameplate 4. SF6 gas entrance 5. Air reservoir

PMM

PMM

250 RMM t==~= 350 350 OTM

250

NOMM

Casting mouth of cement when CB located 220 220

PMM

6. Joint for connection with 3-phase air pipe 7. Cable entrance 8. Operating mechanism

OTM

PMM

OMMM NOOM

NPMM

80

680

Ditch of air pipe

Second time cast mouth

1500

PMM

QR

QR

=NT NU

363kV SF6 Dead Tank Type CB (single break)

4000(5000)

4000(5000)

(3530)

13 1
PSMM

2 ESSVOF

640

TTM (957)

UOM

5 6 860
Anchor bolt Mud Air pipe Cement cast on second time Air tank

NRMM

ENSOMF 9 8 (1434) (3350)

700

920

250

Earthing terminal OTM

PRM

450 Anchor bolt OSM

OQMM

NQPQ

350

700

A
O 251

NTQM

Air pipe RMM 950 1600

A RMM
PQT

Key
1. Wiring plate 2. Bushing 3. CT 4. Nameplate 5. Viewing window

RMM

373

Ditch of air pipe

RMM

NQPQ

Air tank

A-A 4000
251 251 Anchor bolt Cement cast on second time PRM 700 2 PMM Mud

4000
521

Air tank

6. Arc chamber 7. Air tank 8. Control cable NOMM 9. Operating housing 10. Air pipe
VMM

UOM

USS

10

550kV SF6 Dead Tank Type CB


8000 8000 D 6100(6189) 6 D 5 3756 4 TSMM=EUOMMF 7

70 8 PNQR OQMM NSMM

OQMM

1 3 2 1000 1120

13

10

450 PMM

9 11

980

3160 4725

200

12

A
Operating box 45 45
R=1 100 R=1 100 R=1 100

80 NMMM

320

QR QR NQR

215

Cable entrance 170X320

NMRM

200

Key
1. SF6 gas entrance 2. Earthing terminal 8000
450 OMM PTM 450

8000
Air tank GL PRM 450 CL

3. Air reservoir 4. Center of gravity 5. Terminal 6. Bushing 7. Bushing CT 8. Touch hole 9. Anchor bolt 10. Nameplate
215

A 450 Earthing terminal OMM E

E Cable ditch 500

OMMM

450

450

PNSM

QRMM

Cable entrance 170X320

VUM

320

NTM

SMM

B 1000

280

22 Air pipe

11. Operating box 12. Foundation 8 air pipes 13. window of indicator counter and pressure gauge

280

OMM

Anchor bolt M30X1000

2200

OUM NMM

22 Alu. alloy plate

VUM

X
Anchor bolt 125

=NV

OM

40.5kV VACUUM CIRCUIT BREAKER

The 40.5kV is an outdoor VCB designed for system voltages up to 40.5kV and for rated short-circuit currents up to 31.5kA. The design incorporates a compact vacuum interrupter based on the experience from previous interrupter design.

FEATURES
1 High fault current breaking abilities
A compact vacuum interrupter is used in the circuit breaker. lt is high reliable when breaking or making fault current and restrike free when interrupting capacitive currents due to optimized contact movement.

2 High dielectric strength


The compact vacuum interrupter is installed in a SF6 outdoor bushing at atmospheric SF6 pressure. The dielectric strength of the vavuum interrupter is little affected by circumstance.

3 Low maintenance
The circuit breaker is operated by a motor charged spring operating mechanism.

4 Short installation period


Each element is pre-tested and shipped to installation site in the form of a few pre-assembled units.

RATINGS
No. 1 2 3 4 5 6 7 8 9 10 11 Item Rated voltage Rated frequency Rated current Making current Rated breaking current Power frequency withstand voltage Ratedr lightning impulse withstand voltage Short-time withstand current Peak withstand current Rated pressure of gas (at 20 Mechanical duration ) Unit kV Hz A kA kA kV kV kA/s kA MPa times Ratings 40.5 50 2000 80 31.5 Dry: 95; Wet: 80 185 31.5/4 80 0.02 10000

DIMENSIONS
1820 750 750

OVTM

SUM 760 476

=ON

OO

SALES NETWORK OVER THE WORLD

The products are successful in operation in China, Malaysia, Pakistan, Thailand, Philippines, Burma, New Zealand and etc. SF6 Gas Circuit Breakers Supply Including Units Under Manufacturing ( as of Dec.2002 )
Number 1 2 Rated voltage (kV) 550 252 145/126 (Spring operating mechanism) 145/126 (Pneumatic operating mechanism) 72.5 550 363 252 145/126 72.5/40.5 Number of bays 50 1391 4771 2255 461 94 312 101 318 365

Live tank type CB

3 4 5 1 2

Dead tank type CB

3 4 5