Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
First published in April 2009 by Manufacturing and Engineering Educational Services NSW TAFE Commission PO Box 218 Bankstown NSW 2200 This work is copyright. Any inquiries about the use of this material should be directed to the publisher.
FEEDBACK
We value your opinion and welcome suggestions on how we could improve this resource manual.
CONTENTS
INTRODUCTION 1. CONTROL SYSTEM FUNDAMENTALS AND DIAGRAMS PRACTICAL EXERCISE 1 - CONTROL CIRCUIT DIAGRAMS PRACTICAL EXERCISE 2 - CONTROL CIRCUIT DIAGRAMS REVIEW QUESTIONS 1 3 24 27 30
2. TYPES OF CONTROL SYSTEMS GENERAL OVERVIEW AND FLUID FLOW CONTROL 35 PRACTICAL EXERCISE 1 CONTROL SYSTEMS PRACTICAL EXERCISE 2 FLUID FLOW CONTROL REVIEW QUESTIONS 3. ENERGY MANAGEMENT AND BUILDING MANAGEMENT PRINCIPLES 4. ELECTRIC CONTROL SYSTEMS PRACTICAL EXERCISE 1 ELECTRIC CONTROL SYSTEM PRACTICAL EXERCISE 3 ELECTRIC CONTROL SYSTEM FAULT FINDING REVIEW QUESTIONS 5. ELECTRONIC CONTROL SYSTEMS PRACTICAL EXERCISE 1 ELECTRONIC CONTROL SYSTEM PRACTICAL EXERCISE 2 ELECTRONIC CONTROL SYSTEM
COMMISSIONING
50 53 56 61 65 76 80 82 87 98 100 103 105 109 122 124 127 129 135 142 145 149 150
REVIEW QUESTIONS 6. PNEUMATIC CONTROL SYSTEMS PRACTICAL EXERCISE 1 - PNEUMATIC CONTROL SYSTEM PRACTICAL EXERCISE 2 - PNEUMATIC CONTROL COMMISSIONING PRACTICAL EXERCISE 3 - PNEUMATIC CONTROL FAULT FINDING REVIEW QUESTIONS 7. PROGRAMMABLE LOGIC CONTROLLERS AND DIRECT DIGITAL CONTROLS PRACTICAL EXERCISE REVIEW QUESTIONS SAMPLE TESTS SAMPLE THEORY TEST 1
PRACTICAL TEST 1 SAMPLE THEORY TEST 2 SAMPLE PRACTICAL TEST 2 ANSWERS REVIEW QUESTIONS SAMPLE THEORY TEST 1 PRACTICAL TEST 1 SAMPLE THEORY TEST 2 PRACTICAL TEST 2
Additional Reference
The following texts and videos may be of further assistance for this module. Coffin, M.J. Direct Digital Control for Building HVAC Systems ISBN 0 442 23797 9 Van Nostrand Reinhold, New York, USA. Electrical and Electronic Drawing Practice for Students - SAA/SNZ HB31996. ISBN 0 7337 0246 5 Standards Australia, Homebush, New South Wales. Engineering Manual of Automatic Control (SI Ed). Library of Congress Catalog Card Number: 94-073455 Honeywell, USA, 1995. General Information and General Index (AS 1102.101-1996) to Analogue Elements (AS 1102.113-1996) Standards Australia, Homebush, New South Wales. Heating Ventilation Air Conditioning Seminar Booklet produced by Honeywell Langley, B.C. Control Systems for Air Conditioning and Refrigeration Prentice-Hall ISBN 0 13 171679 4 01 New Jersey, USA
Suggested Videos
Air Conditioning 84-065 Regency College of TAFE, SA
Acknowledgments
TAFE NSW acknowledges and thanks all companies and individuals who generously supplied diagrams, pictures and information. The following companies provided information: Atlas Cop Co Belimo Australia Pty Ltd Celsius Magazine Daikin Australia Email Major Appliances Honeywell Limited Johnson Controls Kirby Refrigeration- Erie Controls Landis and Staefa Division of Siemens Building Technology SMC Pneumatics (Australia) Pty. Ltd Toshiba International Corporation Pty. Ltd
Introduction
This resource manual contains learning exercises, review questions and sample assessment instruments. It is designed to assist students achieve the outcomes and purpose described in the national module descriptor NR15 and is an example of the depth and breadth of learning expected. The topics listed in the content are arranged in the preferred learning sequence. It is recognised that this is not the only sequence in which the material could be learnt. Assessment arrangements and sample assessment instruments are based on the sequence of topics listed above. A teacher may decide that for a particular student or group of students it is more effective to present the topics in a different sequence. In this case the students must be informed in writing of the resulting changes in the assessment events before starting the module.
Learning plan
The following topic weighting will help you plan and allocate the effort needed to achieve the purpose and outcomes of the module. 1. 2. 3. 4. 5. 6. 7. Control System Fundamentals and Diagrams Energy Management Principles Electric Control Systems Electronic Control Systems Pneumatic Control Systems PLC and DDC Control Systems 2.5% 12.5% 12.5% 18.75% 18.75% 12.5%
Imagine a world where humans manually operated air conditioning systems. Whenever the temperature and / or humidity of a room moves outside preagreed parameters, someone would have to start either the refrigeration or heating equipment. Once the conditions move back into the agreed parameters, the equipment would then have to be manually turned off. This scenario is most impracticable and fortunately we know this is not necessary because of the use of automatic controls. This module is designed as an introduction to the various control systems used in the air conditioning industry. The systems that will be covered include electromechanical, pneumatic, electronic and microprocessor systems. If at the end of this module you feel you wish to learn more about control systems at a greater depth than that provided by this module, you should consider doing further modules in the controls area.
Exercise
Drawing - Control circuit diagrams from a circuit diagram Drawing - Control circuit diagrams
Practical exercise
A 600 word assignment on the principles behind Energy Management and Building Management Explain the operation of various electric controls. Electric control system commissioning Electric control system fault finding
Observe the operation of a DDC air conditioning control system and / or a PLC air conditioning control system.
Objectives
At the end of this topic you should be able to: list and explain the principles of air conditioning control define various terms used in air conditioning control describe the operation of various simple control diagrams list various applications employing air conditioning control explain the sequence of operation of a simple air conditioning circuit diagram draw a circuit diagram for a simple air conditioning system explain the sequence of operation of a simple air conditioning control system diagram draw a control system diagram for a simple air conditioning system.
Content
Terminology and Definitions Symbols Control System Fundamentals Principles Method of Control Closed Loop Open Loop Factors that Affect Loop Stability Automatic Control Elements Six Basic Functions of Automatic Control Symbols and Diagrams Diagrams - Air Conditioning Diagrams - Pneumatic and Logic Control Diagrams - Electrical Diagrams
- Block Diagrams - Circuit Diagrams (Schematic Diagram) - Wiring Diagrams Revision of Control Circuits Control Symbols Air Conditioning Circuit Diagrams
References
ARAC Volume 2, pages 29.3; Volume 1, page 12.35; pages 12.43 12.44 and Glossary of Terms Terms and definitions ARAC Volume 2, pages 29.1 29.3 Loops, control elements and functions of automatic control ARAC Volume 2, pages 28.16 28.18; pages 29.7 29.13; pages 29.38 39 Symbols and electrical diagrams NR08 Appliance Motors and Circuits and NR12 System Control module books Discusses circuit components
Controller - A device that sense change in the controlled variable (or receives input from a remote sensor) and derives the proper correction output. Corrective action - Control action that results in a change of the manipulated variable. Initiated when the controlled variable deviates from setpoint. Cycle - One complete execution of a repeatable process. In basic heating operation, a cycle comprises one on period and one off period in a twoposition control system. Cycling - ARAC Volume 2, page 29.3 Cycling rate - The number of cycles completed per time unit, typically cycles per hour for a heating or cooling system. The inverse of the length of the period of the cycle. Dead band - A range of the controlled variable in which no corrective action is taken by the controlled system and no energy is used. See also Zero Energy Band." Desired value / controlled value - ARAC Volume 2, page 29.4 Deviation - the difference between the set point and the value of the controlled variable an any moment. Also called Offset." Differential gap / differential - ARAC Volume 2, page 29.4 ARAC Glossary page 7 Digital - A series of on and off pulses arranged to convey information. Morse code is an early example. Processors (computers) operate using digital language. Digital control - A control loop in which a microprocessor-based controller directly controls equipment based on sensor inputs and setpoint parameters. The programmed control sequence determines the output to the parameter. Direct Acting (DA) - A positive operation of the actuator caused by a positive signal from a controller or visa versa. Direct Digital Control (DDC) - ARAC Volume 2, page 12.36 Also see Digital and Digital control. Droop - A sustained deviation between the control point and the setpoint in a two-position control system caused by a change in the heating or cooling load. Electric control - A control circuit that operates on line or low voltage and uses a mechanical means, such as temperature-sensitive bimetal or bellows,
NR15 Air Conditioning Controls Module Resource Manual April 2009
to perform control functions, such as actuating a switch or positioning a potentiometer. The controller signal usually operates or positions an electric actuator or may switch an electric load directly or through a relay. Electronic control - A control circuit that operates on low voltage and uses solid-state components to amplify input signals and perform control functions, such as operating a relay or providing an output signal to position an actuator. The controller usually furnishes fixed control routines based on the logic of the solid-state components. Final control element - A device such as a valve or damper that acts to change the value of the manipulated variable. Positioned by an actuator. Hardware - Physical components of a computer, (not including the software). Interface - A device that a computer uses to communicate with another computer. Input / Output (I/O) - Input is where information passes into a controller and output is where information leaves the controller. Lag - ARAC Volume 2, page 29.4, ARAC Glossary page 12 Load - ARAC Glossary page 12 Logic - The process of arriving at a decision based upon information that has been provided. Manipulated variable - The quantity or condition regulated by the automatic control system to cause the desired change in the controlled variable. Measured variable - A variable that is measured and may be controlled (e.g. discharge is measured and controlled, outdoor is only measured). Microprocessor - ARAC Glossary page 13 Microprocessor-based Control - ARAC Volume 2, page 12.35 Modulating - An action that adjusts by minute increments and decrements. Offset - ARAC Volume 2, page 29.4 On / Off control - A sustained deviation between the control point and setpoint of proportional control system under stable operating conditions. Pneumatic control - A control circuit that operates on air pressure and uses a mechanical means, such as a temperature-sensitive bimetal or bellows, to perform control functions, such as actuating a nozzle and flapper or a
NR15 Air Conditioning Controls Module Resource Manual April 2009
switching relay. The controller output usually operates or positions a pneumatic actuator, although relays and switches are often in the circuit. Program Logic Control (PLC) - This is a computer based device that replaces the hard wired control circuit and allows connections to be done by way of a program. Potentiometer / POT - ARAC Glossary page 15 Primary element - The proportion of the controller that senses the controlled medium. For example, a thermostat bi-metal is a primary element. Process - A general term that describes a change in a measurable variable (e.g. the mixing of return and outdoor air streams in a mixed-air control loop and heat transfer between cold water and hot air in a cooling coil) Usually considered separately from the sensing element, control element, and controller. Proportional band - In a proportional controller, the control point range through which the controlled variable must pass to move the final control element through its full operating range. Expressed in percent of primary sensor span. Commonly used equivalents are throttling range and modulating range." Proportional control - A control algorithm or method in which the final control element moves to a position proportional to the deviation of the value of the controlled variable from the setpoint. Proportional - Integral (PI) control - A control algorithm that combines the proportional (proportional response) and integral (reset response) control algorithms. Reset response tends to correct the offset resulting from proportional control. Also called proportional-plus-reset or two-mode control. Proportional-Integral-Derivative (PID) control - A control algorithm that enhances the PI control algorithm by adding a component that is proportional to the rate of change (derivative) of the deviation of the controlled variable. Compensates for system dynamics and allows faster control response. Also called three-mode or rate-reset control. Relay - ARAC Volume 2, page 29.4 & ARAC Glossary page 16 Reverse acting - To reverse the signal from a controller and used that signal to open instead of close an actuator or visa versa. Sensing device / element - ARAC Glossary page 17 Set point - ARAC Volume 2, page 29.3
NR15 Air Conditioning Controls Module Resource Manual April 2009
Signal - The message that is sent between components. Changes in voltages or air pressures are primarily used in air conditioning control systems Software - ARAC Volume 2, pages 12.43 - 44 Programs for computers. Throttling range - In a proportional controller, the control point range through which the controlled variable must pass to move the final control element through its full operating range. Expressed in values of the controlled variable (e.g. degrees C, percent relative humidity, kPa). Also called proportional band." In a proportional room thermostat, the temperature change required to drive the manipulated variable from full off to full on. Time constant - The time required for a dynamic component, such as a sensor, or a control system to reach 63.2 percent of the total response to an instantaneous (or step) change to its input. Typically used to judge the responsiveness of the component or system. Two-position control - See On / Off control. Variable - Something that can be changed or adapted (e.g. pressure is variable) Zero energy band - An energy conservation technique that allow temperatures to float between selected settings, thereby preventing the consumption of heating or cooling energy while the temperature is in this range. Zone / zoning - ARAC Glossary page 22
Symbol
Description
Symbol
Description
Double junction of conductors This shall be of used if required by layout considerations Double junction of conductors This shall be used if required by layout considerations
Direct Current
Alternating Current
Positive Polarity
i.
Negative Polarity
Contactor main contacts - load bearing. i. Main make contact ii. Main break contact
ii.
Battery of accumulator or primary cell. NOTE: The longer line represents the positive pole, the short line represents the negative pole.
i. ii.
i.
Connection of conductors
10
Symbol
Description
Conductor or group of conductors. (A line for a particular path may be emphasised by increasing its thickness.) Conductor crossing (no connection)
Symbol
Description
Circuit breaker
i. ii. i. ii.
i. Manually operated control. ii. Manually operated switch - Normally open (General symbol) i. Operated by push button ii. Normally closed push button switch non-latching. i. Emergency switch (mushroom-head safety feature) ii. Normally closed emergency stop button.
i. ii.
i.
i. ii. t
i. Resistor (General symbol) ii. Temperature dependent resistor with negative resistance temperature coefficient (thermistor) Heating element
ii.
Break contact, delay when the device containing the contact is being activated. Break contact, delayed when the device containing the contact is being de-activated. Make contact; delay when the device containing the contact is being activated.
Make contact; delay when the device containing the contact is being de-activated.
11
Symbol
Description
Fuse
Symbol
Description
Operated by electromechanical effect
Fuse switch
i. ii.
Information showing the form of energy stored may be added, e.g. t Temperature p Pressure r.h. Relative humidity Flow Fluid level Thermal Sail Capacitor (General symbol)
Solenoid valve
Single phase automatic transformer. (If used as an autotransformer, tapping % can be written on the diagram.)
M 3
M 3
i. ii.
1 2
i. Terminal strip
12
Symbol
Description
General symbol for a clock
Symbol A
Description
Meters A = Amp meter V = Volt meter
Watt-hour meter
Signal Lamp K1 4
Incandescent Lamp
(a) (b)
i
K1-1
ii.
K2-2
Contact Identification Identification numbers are always to be opposite the moving contact
13
Symbol
Description
Pressure Control (Breaks on rise in pressure.)
Symbol
Description
Multi-stage Thermostat Two Stage Cooling (Make on a rise in temperature.) Two Stage Heating (Makes on a fall in temperature) Pressure Differential Switch (Contacts make on the correct air pressure differential.)
HP
t Pressure Control (Makes on rise in pressure.)
LP
Manual Reset Pressure Control (Break on rise in pressure.) HP
t LP
Manual Reset Oil Pressure Failure Switch Note the doted lines around the control shows that all the components are in the same body. Domestic Defrost Timer - Time initiated, temperature terminated. (Make one contact, break the other.)
OP
Dual Pressure Control HP Note the doted lines around the controls to show that theyre in the same body. HP: Break in rise t
LP
OR HP
LP
Thermostat (Breaks on a rise in temperature.) t Domestic Defrost Timer Time initiated, temperature terminated. (Make one contact, break one contact Thermostat (Make on a rise in temperature.) t L R R S Single Phase Motor Compressor Starter
14
Control system fundamentals Principles Method of control (ARAC Volume 2, page 29.1)
Air conditioning systems are designed to perform a number of processes in order to maintain constant conditions within a controlled space. Most systems are able to cool and / or heat but there are other processes they can carry out, depending on the equipment supplied. ARAC Volume 2, pages 23.38 - 40 describes the following: Cooling Cooling and Heating Cooling and Dehumidification Heating Heating and Humidification Evaporative Cooling (Used in warmer and drier climates) No matter the process the air conditioning system is trying to control, they all operate by using one or a combination of the two control methods described below, those being Closed Loop and Open Loop Control. (Other control loops include cascade loops and interactive loops.)
Air Flow
15
16
placed in stagnant, non consistent areas, e.g. bends and outlets of ductwork.
2. A controller:
3. A controlled device: used to carry out the actual corrective action. The three elements can be seen in the controlled loop diagrams previous. The control device in this instance is an actuator on a water valve.
4. Corrective Action
NR15 Air Conditioning Controls Module Resource Manual April 2009
17
Filter
Fan
Humidifier
Air Cooler
Air Heater
Pneumatic and logic control diagrams (ARAC Volume 2, pages 29.3839) The following diagram shows a typical simple pneumatic control diagram used in the Air Conditioning Industry. Pneumatic control circuit diagrams will be discussed in a later section.
18
+
Return Air Supply Air Outside Air T
Thermostat
Contactor B
Contactor Coil B
19
2. Circuit Diagrams (Schematic Diagram) Circuit Diagrams are ideal for fault finding as it shows a circuit operation in a logical sequence. Energy flows is from top to bottom and / or left to right. Circuit diagrams can be either of a vertical or horizontal layout.
Contactor O/Load Resistors A
L1 L2 L3 N
Motor
Start
Stop A4
A4 T T1
B3
20
3. Wiring Diagrams Wiring diagrams are used to allow unskilled workers to complete wiring of equipment. Often it is drawn on a panel layout drawing and shows point to point connection of cables. A numbering system is often used on more complicated diagrams.
L1 L2 L3 N
1 2 3 1 12 Contactor A 10 N
4 5 6 14 Contactor B 7 8 9 N
1 12 Timer 14 N
10 4 5 6 Resistors 11
7 8 9
21
Components like thermostats, head pressure controls, low pressure controls, etc are found in the control side of the diagram. You should also be able to design basic electrical diagrams (with both power and control circuits) and in addition be able to read a basic wiring diagram. If you are not confident with working with control diagrams, ARAC 29.14 29.24 shows how control systems are build by using various components through to a completed wiring diagram. It is from the understanding of the basic control system that an understanding of more complicated Air Conditioning Control systems can be gained and hence the ability to trouble shoot these systems in event of a fault.
22
Kelvinator Room Air Conditioning Unit (Reproduced with the permission of Email Major Appliances)
23
Procedure
1. Briefly write the sequence of operation for the wiring diagram of a Kelvinator Heat Pump air conditioning unit (found below and in ARAC Volume 2, page 29.9).
2. Convert the diagram into a circuit diagram so that it can be used for fault finding. Notes for Diagrams Be sure to use the symbols supplied in this module. When you draw a line on the circuit diagram, cross out the original line on the wiring diagram as you go. This avoids repeating wires that you have already done on the circuit diagram or missing any wires. Draw sketches elsewhere so only your finished drawing appears in the spaces provided.
24
Active
Circuit diagram for the Kelvinator Heat Pump air conditioning unit Neutral
25
Check your work with your teacher to be sure that you have identified the correct sequence of operation and correctly converted the diagram. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
26
Procedure
1. Draw a control system diagram for a simple air conditioning system using the components listed below. Briefly explain the sequence of operation for the air conditioning system diagram
2.
Notes for Diagrams Be sure to use the symbols supplied in this module. Draw sketches elsewhere so only your finished drawing appears in the spaces provided.
Components
Three phase compressor fitted with sump heater Three phase evaporator fan motor Condensing unit containing three (3) single phase condenser fans. Three phase electric heater bank protected by an over temperature manual reset thermostat. One heat / one cool thermostat Safety controls for compressor Fuses and / or circuit breakers Control switches
27
L1 L2 L3
Neutral
28
Check your work with your teacher to be sure that you have identified the correct sequence of operation and correctly converted the diagram. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
29
Review questions
These questions will help you revise what you have learnt in this topic. 1. What are the three essential components of a control loop?
2. Describe the six major functions of these components. 3. What is the controlled variable in the control loop?
30
11. What is the difference between a closed loop control system and an open loop control system?
31
Review questions
13. What are the three types of diagrams discussed in section 1? 14. What is a typical application for each of the diagram types: Air Conditioning Diagrams
Block Diagrams
Circuit Diagram
Wiring Diagrams
32
Review questions 15. Write down any control system components that you would expect to find in a control diagram for a basic system to control conditioned air.
16. Identify the control system components that you would expect to find in a control diagram for a system to condition water.
17. Draw the symbol for the following components: A thermostat that makes on rise.
A sail switch
33
Notes
34
Objectives
At the end of this topic you should be able to: list and explain the principles of air conditioning control explain the operation of various fluid flow control devices and systems.
Content
Control Systems Control Signal Types Energy Transmission Types - Electric Control Systems - Electronic Control Systems - Microprocessor - Pneumatic The Three Elements of a Control System Sensing Elements - Pressure Sensing - Temperature Sensing - Humidity Sensing - Fluid Flow Sensors - Orifice Plate or Vortex Nozzles Control Action - On / Off or Two Position Controller - Anticipators - Multiposition or Multistage control - Step Control - Floating Control - Proportional Control (PI & PID) Operation Type Control Valves Liquid and Air Flow Control Other Forms of Drive
35
References
ARAC Volume 1, pages 12.5 12.7 Discusses On / Off control, humidity sensing ARAC Volume 2, pages 29.5 29.7 Discusses anticipators, floating control and proportional control ARAC Volume 1, pages 11.36 11.38; Volume 2, pages 29.23; 29.32 34 Discusses actuator / drive types Honeywells Heating, Ventilation Air Conditioning Training Manual Discusses principles of automatic control Automatic Control Principles Discusses principles of automatic control
36
Control systems
Automatic control systems are used to maintain a controlled variable to a desired condition. They are classified by the type of control signal it uses to perform its function, either analog or digital and the type of energy transmission. There are four energy transmission types commonly used in the air conditioning industry, they are electric, electronic, microprocessor and pneumatic control systems. Many control systems use a combination of the above categories.
37
Microprocessor
Microprocessor-based controllers use digital control for a wide variety of control sequences.
Pneumatic
Similar to electric but use compressed air as its energy source.
Sensing elements
As mentioned previously, electric and pneumatic controls are similar in operation and so use similar sensing equipment, called primary elements, to attain automatic control. Electronic sensing is done by using low mass primary elements that respond quickly to changes in the controlled condition. Sensors are used to sense: Pressure Temperature Humidity
NR15 Air Conditioning Controls Module Resource Manual April 2009
38
Fluid flow Other sensor types are available but will not be discussed in this module.
Pressure sensing
The following primary elements are used to sense pressure: Electromechanical (ARAC Volume, pages 12.5 6 & Automatic Control Principles page 7) Diaphragm Bellows Inverted bells immersed in oil
Electronic (Excerpt from Honeywell Engineering Manual of Automatic Control page 127) An electronic pressure sensors is usually a transmitter which converts pressure into a variable such as voltage, current or resistance that can be used by an electronic controller. Strain Gauge
Flexible base Pressure being exerted from system
As pressure is exerted onto the strain gauge the length of the fine wire / thin film metal stretches. The wires resistance changes according to the amount of stretching that it undergoes. Capacitance Types Pressure Sensor
Pressure being exerted from system Flexible Plate Fixed Plate
The capacitance type pressure sensor has two plates in its assembly, a fixed plate and a flexible plate. As the pressure on the flexible plate varies it moves closer to the fixed plate and changes the capacitance.
39
Force is exerted onto a strain gauge in two directions. As with the strain gauge mentioned above, the resistance varies depending on the pressure exerted. This type of sensor can measure small differential pressure changes even with high static pressure.
Strain Gauge
Electronic Thermocouples Resistance Temperature Detectors (RTD) Integrated Circuit Temperature Transducer (ICTT) ICTTs are one of the latest progresses in sensor technology being that it is a silicon chip soft soldered into a printed circuit board. They operate on the principle that with a change in temperature the output, either a voltage in millvolts or a current in milliamps, will vary accordingly. Thermistors Thermistors can have either a positive or negative temperature coefficient. Positive Temperature Co-efficient (PTC): with a rise in temperature there will be a rise in the resistance. Negative Temperature Co-efficient (NTC): with a rise in temperature there will be a reduction in the resistance.
40
Ohms
Ohms
Temperature
Temperature
Humidity sensing (ARAC Volume 1, pages 12.6 12.7 & Automatic Control
Principles, page 10 11) The following primary elements are used to sense humidity: Electromechanical Nylon Ribbon or hair, either human or horse Wood Any material that responds to humidity like leather, horn and silk.
Electronic Hygroscopic (Gold Foil Grid) The Capacitive Sensor (Excerpt from Honeywell Engineering Manual of Automatic Control page 126)
Moisture Sensitive Polymer Leads to controller or sensing circuit Gold foil or other type of electrode plates
The capacitive sensor is a capacitor that has lithium chloride as a dielectric. As the resistance of the lithium chloride varies with a change in humidity so does the capacitance between the plates. With a change in capacitance there will be either more or less current flow from the plates.
41
Sail switches are directional components that rely on airflow to make the switch. Air movement lifts the sail that in turn makes a microswitch. Sail switches are used for interlocking purposes; i.e. to hold off conditioning until the fan is running.
A heated resistance element on a microchip is used as the primary sensing element. By comparing the resistance of the heated element to the resistance of an unheated element, the air velocity can be indicated. Liquid flow sensor paddle switch
Paddle switches are used to detect water flow and are used for interlocking purposes, i.e. as an indication that water is flowing before starting a chiller.
42
NR15 Air Conditioning Controls Module Resource Manual April 2009
Water movement makes a paddle move in the direction of the water flow, see the diagram below. The paddle is connected to a microswitch that makes with movement. It should be noted that this sensor / switch is a directional component and must be installed accordingly.
On off signal to controller
Microswitch
Pivot
Liquid Flow
(Reproduced with permission of Kirby Refrigeration) No flow position Paddle fitted perpendicular to flow
Differential water pressure sensor These switches are designed both as a safety cut out and is used to detect water flow. A typical application would be to mount the switch across a water vessel (either a water cooled condenser or chilled water evaporator) to confirm there is water flow.
43
To Controller
Orifice Plate
Control action
Controllers are the link between a sensor and the equipment used to change the controlled variable. There are two basic control types: On / Off and Proportional though there are several variants of each. The following diagrams are used to represent the behavior of a controller to show the output versus the input relationship.
On
Off
Set point
Diagrams used to represent cycling in electronic controls The above diagrams represent compressors cycling on and off on cooling
44
Off
Undershoot
Step control
Step Control uses proportional input to obtain proportional output using equipment with On / Off control. This type of control is typically used on larger air conditioning systems. Step controllers can be mechanical in that they use cams to drive open and close microswitches or they can be electronic.
Differential Throttling Range
Off Off On
3
S T A G E S
On
On
Off
Off
On
2 1
On Off Off On
20
21
23
24
45
Output
Heating
Cooling
Full Off
46
The proportional band can be calculated by the formula: % Proportional Band = Throttling Range x 100 Span of Sensor Example: A sensor has a range of 0 to 30C, it would a range (called sensor span) of 30K. If the final control element has a throttling range of 3K with the set point at 22C, the proportional band would be: % Proportional Band = Throttling Range x 100 Span of Sensor = 3K x 100 30K = 20% Other types of proportional control used include Proportional Integral (PI) and Proportional Integral Derivative (PID). A brief description and a graphical comparison of each are given below. PI and PID controls will be discussed at greater depth in latter control modules.
Fig. 1 Proportional
47
Actuators/drives
Many of the actuators listed below will be discussed at greater depth in other sections of this workbook. An actuator is a device that converts electric or pneumatic energy into a rotary or linear action. Electronic systems do not have the inherent power to drive valves or dampers. Electronics are used for the logic part of the operation that in turn operates electric relays to do the physical work of actuating the valves or dampers. An actuator creates a change in the controlled variable by operating a variety of final control devices such as valves and dampers.
Operation type
Motorised Actuators including pneumatic actuators and motors: (ARAC Volume 2, page 29.23, ARAC Volume 2, pages 29.32 34 and Automatic Control Principles, page 28) Electronic Actuators
Method of controlling flow Sliding plug valve Rotary plug valve Butterfly valve
Three Way Mixing and Diverting Valves
(Reproduced with permission of Kirby Refrigeration)
Type of dampers Flap type Splitter damper Pinch damper Louver damper Parallel blade damper Opposed blade damper
Solenoid Coil Fitted to a Single Seated Valve
(Reproduced with permission of Kirby Refrigeration)
Electronic Triac - (ARAC Volume 1, page 11.38) Transistor (ARAC Volume 1, pages 11.36 - 37)
A fluid that is used in an actuator that when heated will expand moving a shaft that in turn can be used to drive open or closed dampers or valves. See electronic control for further details.
49
Procedure
1. Observe the operation of simple air conditioning control devices, one system using On / Off control, one using step control and one system using proportional control. (Do not observe Honeywell/ Johnson electric modulating motors at this stage, they will be investigated in electric control). 2. Briefly explain the operation of the simple air conditioning control devices shown.
Remember: Work safely at all times! Systems may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. You cannot see electricity so consider all systems to be live until proven otherwise. Make sure you are supervised when working on live circuits. If you are working with live circuits to diagnose electrical problems, used extreme caution so as to avoid damage to testing equipment, electrical shock or even electrocution.
50
51
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
52
Procedure
1. Observe the operation of a simple fluid flow control system, either a water distribution system / or an air distribution system. 2. Briefly explain the operation of the water distribution system and / or an air distribution system. 3. Draw a control system circuit diagram of the fluid flow control circuit.
Remember: Work safely at all times! Systems may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. You cannot see electricity so consider all systems to be live until proven otherwise. Make sure you are supervised when working on live circuits. If you are working with live circuits to diagnose electrical problems, used extreme caution so as to avoid damage to testing equipment, electrical shock or even electrocution. Cooling towers may be contaminated, use safety equipment.
53
54
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
55
Review questions
These questions will help you revise what you have learnt in this topic. 1. What are the four major types of control systems available in the air conditioning industry?
6. What is the primary function of a Fluid Flow Sensor within an air conditioning control system?
56
Review questions
7. Where would a sail switch be fitted into a control circuit to keep conditioning (heating and cooling) off until airflow was established?
11. What are the operating differences between on-off and floating control types?
12. What are the operating differences between floating and proportional control types?
57
Review questions
13. What is the term for the device, which incorporates an actuator that drives a shaft that has many cams, mounted on it to operate microswitches for a number of output devices?
15. What are the major design and operational difference between opposed blade dampers and parallel blade dampers?
16. What effect would a parallel blade air damper and an opposed blade damper have on the airflow at the half-open position?
58
Review questions
17. In the following sketch are the valves mixing or diverting types?
18. Sketch in the correct location of a mixing valve on the cooling coil below. Show all piping and indicate water flow directions.
59
Review questions
19. Sketch in the space below a face and bypass damper control arrangement and describe its operation.
Operation
60
Objectives
At the end of this topic you should be able to: Explain the principles of both energy and building management and the various systems used in air conditioning.
61
Other 14%
Cooking 4%
Lighting 26%
HVAC 39%
The graph shows that HVAC makes up the largest percentage of the consumption of energy, consumption that has to be paid for, consumption that can be reduced. Energy management has become a major concern for building owners in that large savings can be made once different energy saving methods have been installed. You are required to investigate the various methods that can be used to attain those energy savings, the assignment for this section can be found on following page.
62
Other information to be investigated is: Running Costs What are the potential savings (if any)? Capacity Control What type of capacity control is / can be used in Building Management and Energy Management?
Many of the topics listed above will discuss by your teacher throughout this module. Suggested area for your research: 1. Text Books 2. 3. ARAC Honeywell Engineering Manual of Automatic Control. Celsius Magazines AIRAH Journals
Industry Magazines
The Internet Hints on using the Internet. Use just the words you are looking for, i.e. night purge in the search box. The Internet will look for the words night and purge and will show you a list of matches to your inquiry. You then can go through the findings as you wish.
63
To narrow the findings, many of the search engines allows you to link the words and so receiving findings closer to your needs. Try Night and Purge, Night Purge etc. for example. Use questions to provide you with the answers you require, like: What is night purge? etc. Use a variety of search engines. The author of this module has found the search engine Infoseek to be a good for technical information. Other search engines include Excite, Yahoo, Alta Vista and Lycos, etc.
4. 5.
Manufacturers of BMS systems, like: Honeywell, Landis and Staefa, etc Ring building owners / building managers who are currently using Energy Management / Building Management systems and speak to them about their systems. Your college may supply you with a list of building owners / managers that you may be able to approach. It should be noted that questions will be asked on this topic in the theory tests.
64
Objectives
At the end of this topic you should be able to: list and explain the principles of electric control systems determine the settings for various control devices safely and correctly start up, adjust and commission a simple electric air conditioning control system identify electric system faults and their cause repair electric control system faults.
Content
What is Electric Control Advantages of Electric Control Disadvantages of Electric Control What is in an Electric Controller Electric Control Components Integral Sensor / Controllers Step Controllers Electric Controller Types Electric Actuators Modulating Motors Application of Electric Control Electric Control System Commissioning Equipment Required When Testing and / or Commissioning Electric Controls Controlled Variable Calibration Testing Two Stage Temperature Control Adjustments NR15 Air Conditioning Controls Module Resource Manual April 2009
Setpoint Adjustment
65
Differential Adjustment
- Cutout Adjustment Other Tests that Can be Done to Electric Control Systems Insulation Resistance Test Resistance Tests Line Current Tests Volt Meter Tests
References
Automatic Control Principles Discusses principles of automatic control
66
Electrical control systems What is electric control? (Automatic Control Principles, page 5)
Electric controls have been around from the advent of air conditioning. It is the most basic of control systems, using heavy robust components to provide On / Off control. Variants of proportional control are possible either by using modulating motors or step controllers (the use of On / Off control to achieve a stepped output similar to proportional). Typical voltages used with electric control range anywhere from 12 volts through to 415 volts. All connection between control components is hard wired.
67
Picture showing both the switching and sensing element all in the one Multistage Thermostat
(Reproduced with permission of of Johnson Controls)
MERCURY BULB
BI-METAL STRIP
68
Cams
90
Bi-directional synchronous motor Microswitches Common (1) Switch Position (2) Switch Position (3) A B
1 2 1 2
69
Forward
Reverse
Motors ranging from the synchronous motor shown in the step controller above to the reversible motors seen on pages 28 - 29 of Automatic Control Principles. Synchronous Permanently Split Capacitor Shaded Pole Spring Return
Light Duty Motor Actuator
(Reproduced with permission of Johnson Controls)
Modulating motor Described as electronic motors in Automatic Control Principles (pages 32-35).
70
3.
If in doubt of any adjustments call the manufacturer of the control and get them to send out the relevant information on their product. The information below shows typical adjustments that can be made on a variety of controls:
72
Setpoint adjustment
To adjust the setpoint turn the adjustment shaft in the desired direction required.
Differential adjustment
Rotating the adjusting cam counter clockwise as shown in the diagram will increase the differential between the stages.
Other controls have adjustments located on the front of the control like that of the Low Pressure control shown earlier in this section.
Other tests that can be done to electric control systems Insulation resistance test
NEVER TEST ELECTRONIC COMPONENTS WITH AN INSULATION TESTER AS ELECTRONICS WILL NOT TAKE HIGH VOLTAGES. Testing should be done between all live conductors and earth (without power on). According to the Electrical Wiring Rules AS 3000: You should always test the electrical component at approximately twice the rated voltage, ie. 240 component use the 500V setting of the meter.
73
An electrical component is bad between zero (0) and one (1) and good between one (1) megohm and infinity. Between one (1) and two (2) megohm you would be very wary of using it.
Resistance tests
Test circuit wiring, switches, safety controls, etc for continuity. Check coils on relays, motors and heater elements for correct resistance.
Voltmeter tests
Check for correct voltage across: Supply Motors Coils Heater etc.
The voltmeter can be a very useful tool to detect open circuit by simply turning the circuit on and checking where the supply stops.
74
3. 4.
Once the fault and its cause have been identified, the technician must carry out all necessary repairs to the equipment. With all repairs complete, the plant can be restarted and a final check done to ensure its correct operation.
When touching electric component, care should also be taken to avoid electric shock.
75
Procedure
You will observe the operation of various electric control systems including an example of on/off control, proportional controller (e.g. a Johnson or Honeywell modulating motor), etc. From your observations you are required to describe the operation of various electric controls that your teacher will identify. Remember: Work safely at all times! Systems may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. You cannot see electricity so consider all systems to be live until proven otherwise. Make sure you are supervised when working on live circuits. If you are working with live circuits to diagnose electrical problems, used extreme caution so as to avoid damage to testing equipment, electrical shock or even electrocution.
76
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
77
Procedure
From the commissioning sheet provided, you will: 1. Wire a basic electric air conditioning control system as per the wiring diagram provided (using the equipment available in your college.) Your teacher will provide you with any alterations that are necessary. 2. Test the integrated sensor / controller for accuracy and make any adjustments that are required. 3. Commission all actuators.
Remember: Work safely at all times! Systems may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. You cannot see electricity so consider all systems to be live until proven otherwise. Make sure you are supervised when working on live circuits. If you are working with live circuits to diagnose electrical problems, used extreme caution so as to avoid damage to testing equipment, electrical shock or even electrocution.
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
78
K2 3
t
Sail Switch Heater Safety
K3 5
t
One Heat / One Cool Thermostat
RH
Humidistat
79
Procedure
1. One or a number of faults will be placed on an electric fluid control system by your teacher and you will be required to identify the fault/s as you see it / them. 2. Your teacher may require you to repair the fault/s and then test the system for correct operation or you may simply be required to describe the repairs required in the space provided below.
Remember: Work safely at all times! Systems may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. You cannot see electricity so consider all systems to be live until proven otherwise. Make sure you are supervised when working on live circuits. If you are working with live circuits to diagnose electrical problems, used extreme caution so as to avoid damage to testing equipment, electrical shock or even electrocution.
Fault Identification
Type of Fault:
80
Repairs Required:
Type of Fault:
Repairs Required:
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
81
Review questions
These questions will help you revise what you have learnt in this topic. 1. What control action does the electric control system lend itself to best?
2. Is it possible to attain true proportional control from electric control? Explain your answer.
3. Name three advantages of electric control. 4. Name three disadvantages of electric control. 5. Step Controllers are used on large air conditioning applications. Describe how a Step Controller would operate in conjunction with an integrated temperature sensing / floating controller.
82
Review questions
6. Step controllers are fitted with microswitches. What are microswitches and what is their function?
8. Permanently split capacitor motors can be used as actuators. Describe how the motors direction can be changed.
10. Briefly describe the operation of the balancing relay in the modulating motor.
83
Review questions
12. How would an integrated humidity sensor / controller be tested for accuracy when it was being commissioning?
14. Describe how the insulation resistance tester is used (ie, the settings and expected outcomes)
15. What are the four things technicians must do every time they fault find on an air conditioning system?
16. When fault finding, why was it suggested that the senses be used?
17. Which senses were suggested and what faults could they be used to identify?
84
Review questions
18. In the following drawings of simple electric control circuits, identify the various components as indicated by the numbers.
5 3 4
Heater Stage 1
8 2 1
t t 7
Heater Stage 2
1. 2. 3. 4. 5. 6. 7. 8.
85
Notes
86
Objectives
At the end of this section you should be able to: list and explain the principles of electronic control systems determine the settings for various control devices safely and correctly start up, adjust and commission a simple electronic air conditioning control system identify electronic system faults and their cause repair electronic control system faults.
Content
What is Electronic Control Advantages of Electronic Control Disadvantages of Electronic Control What is in the Electronic Controller NR15 Air Conditioning Controls Module Resource Manual April 2009
The Bridge The Amplifier The Output Circuit Magnetic Actuators Motorised Actuators Thermal Actuators Electro-hydraulic Actuators
87
Electronic Control System Commissioning The Sensor The Controller Final Control Devices
References
Automatic Control Principles Discusses principles of automatic control
88
The Bridge
The bridge
The bridge incorporates the sensing part of the controller. It works on the principle of the Wheatstone Bridge described in the Automatic Control
NR15 Air Conditioning Controls Module Resource Manual April 2009
89
Principles (page 18 - 20) but with the addition of an electronic sensing element and a variable resistor for set point adjustments.
Resistor Resistor
The amplifier
As the signal from the bridge circuit of the controller does not have enough power to operate an actuator connected to the output, the signal must be amplified. The amplifier must increase the millivolt signal from the bridge to an output voltage of between 0 10 volts. The controller generally has two amplifiers fitted, one for direct acting signals and one for reverse acting signals.
90
With a drop in temperature below the set point temperature, the reverse acting output signal will increase proportionally to 10 volts and the direct acting output will be at zero. At set point both outputs will be at zero, this point is considered to be the null position. With an increase in temperature above the set point temperature, the direct acting output signal will increase proportionally to its maximum output and the reverse acting output will be at zero.
Other control types are available like high and low selectors, etc.
Electronic actuators (Control Systems for Air Conditioning and Refrigeration, pages 117 119) Electronic Actuators are available as proportional, two-position, and twoposition with spring return configurations. There are primarily four main types of electronic actuators, they are: Magnetic Motorised Thermal Electro Hydraulic
Magnetic actuators
There are two types of magnetic actuator: On / Off Variable Solenoid type actuator The core of the actuator changes its position against a counter spring with each change in current. This allows for small movements to be transferred to the valve being controlled.
92
Motorised actuators
The motorised actuator makes use of synchronous motors that convert rotary motion into linier motion.
Thermal Actuators
Thermal actuators are made up of a heating element and a solid expansion medium. The heater heats up and cools down according to the variation in the output voltage from the electronic controller. With an increase in temperature, the solid expansion medium will expand causing a force to be exerted creating a stroke movement. If the voltage is reduced from the controller, the heater cools, the expansion medium contracts again causing the opposite effect in stroke movement.
Expansion Medium ie Wax
Heater Seal
93
Electro-hydraulic actuators
Electro hydraulic actuators use an oil pump and a pump valve (similar to a solenoid) to create valve or damper movement. If the voltage from the output of the electronic controller increases the pump valve closes isolating the actuators bottom chamber from the top. The pump fills the bottom chamber, extending the actuator shaft. If the voltage from the controller decreases, the servo valve opens relieving pressure back into the top chamber. The actuator shaft retracts.
Oil Reservoir Pump Valve Hydraulic Fluid Flow Hydraulic Pump Pressure Chamber Diaphragm Piston
Electro-hydraulic Actuator
The sensor
Electronic sensors are used to measure a variety of mediums, for example, temperature, humidity, pressure, pressure difference, etc. Where there is a
94
NR15 Air Conditioning Controls Module Resource Manual April 2009
change in the medium condition, the sensor senses the change and reacts by varying its output to the controller. Sensor outputs vary between manufacturers, and the output types used are listed below: resistance (PTC or NTC), voltage (mV) amperage (mA). The manufacturer of the sensor will produce a table or a chart that compares the change in medium to the output for the sensor in question. If you find that the sensor being tested does not compare to the manufacturers specifications, either adjust the sensor (if possible) or replace it.
The controller
The controller takes the signal from the sensor and amplifies it into some form of energy that can be used to turn on and off components, drive actuators open and closed etc. Again as with sensors, each controller will vary in the type of adjustments available. Many of the domestic controllers only have simple adjustments available to both the service person as well as the customer. They tend to have a combination of the following alterations available: temperature fan speed zoning Your teacher will show you typical domestic electronic controls with simple adjustments. Other controllers, typically commercial and up are more complicated in that they have a wide variety of alterations available to the service person and minimal alterations available to the customer. The controls described can include the following alterations: Set point Differential Dead band Proportional band, etc
Your teacher will show a controller or controllers that contains some / all of the above adjustments. The adjustments are typically done using a pots or button adjustment.
95
Landis and Gyr (now Landis and Staefa Controls) Electronic Controller Access Tool
(Reproduced with permission of Landis and Staefa Controls)
96
97
Procedure
You will observe the operation of a complete electronic control system and from your observations briefly explain the operation of various electronic controls that your teacher will identify. Remember: Work safely at all times! Systems may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. You cannot see electricity so consider all systems to be live until proven otherwise. Make sure you are supervised when working on live circuits. If you are working with live circuits to diagnose electrical problems, used extreme caution so as to avoid damage to testing equipment, electrical shock or even electrocution.
98
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
99
Procedure
From the wiring diagram and commissioning sheet provided by your teacher, you will: 1. 2. Wire a basic electronic air conditioning control system such as Micro Air, Eberle, Carel, Innotceh etc. Identify the operating temperatures, setpoint, dead bands / zones, proportional bands and differentials that the electronic controller/s and actuators will operate at to satisfy the diagram requirements. Commission the electronic controllers within the settings provided. Commission all actuators attached to the electronic controllers.
3. 4.
Remember: Work safely at all times! Systems may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. You cannot see electricity so consider all systems to be live until proven otherwise. Make sure you are supervised when working on live circuits. If you are working with live circuits to diagnose electrical problems, used extreme caution so as to avoid damage to testing equipment, electrical shock or even electrocution.
100
Step 1 The operating temperatures, setpoint, dead bands / zones, proportional bands and differentials identified on the commissioning sheet.
Controller 1 (Type) _______________________________________ Setpoint Proportional Band Differential Dead Zone Dead Zone Forward / Reverse Acting Forward / Reverse Acting ____________________ ____________________ ____________________ ____________________ ____________________ ____________________ ____________________
Actuator Operating Range (in volts) Full open: Full closed: ______________ Volts ______________ Volts
Step 2 Commission the controllers and actuators according to the figures identified above. Do not forget to set the switches to ensure correct operation. Your teacher MUST check your wiring before power is supplied to the controllers!
101
Step 3 Confirm that the electronic controllers are operating as per the commissioning sheet. Is the controller operating as per the commissioning sheet? Yes / No Explain your answer
Is the actuator operating as per the commissioning sheet? Explain your answer
Yes / No
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
102
Procedure
1. One or a number of faults will be placed on the electronic system by your teacher and you will be required to identify the fault/s as you see it / them. Your teacher may require you to repair the fault/s and then test the system for correct operation or you may simply be required to describe the repairs required in the space provided below.
2.
Remember: Work safely at all times! Systems may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. You cannot see electricity so consider all systems to be live until proven otherwise. Make sure you are supervised when working on live circuits. If you are working with live circuits to diagnose electrical problems, used extreme caution so as to avoid damage to testing equipment, electrical shock or even electrocution.
103
Repairs Required:
Repairs Required:
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
104
Review questions
These questions will help you revise what you have learnt in this topic. 1. What is the major difference between the electronic control system and the electric control system?
2.
What are the two types of control action provided by electronic controllers?
3.
What are the three major components in a simple electronic control system?
4.
5.
105
Review questions
6.
7.
8.
9.
106
Review questions
11. What meter should never be used when servicing electronic control systems? Explain your answer.
12. Draw a graphical representation using the following system description on the graph provided below. System description The room temperature in the controlled space is to be maintained at 19C. It is not to deviate further away than + 1K or 0.5 K. There is to be no dead zone.
Full Open / On
13. Using the information provided in the description and the graph from question 10, complete the following table. Controller Type: Set Point Proportional Band 1 Dead Zone 1 Proportional Band 2 Dead Zone 2
107
Review questions
14. Using the information provided in the graph shown below, complete the following table.
Full Open / On
Controller Type: Set Point Differential 1 Dead Band 1 Differential 2 Dead Band 2
108
Objectives
At the end of this topic you should be able to: list and explain the principles of pneumatic control systems determine the settings for various control devices safely and correctly start up, adjust and commission a simple pneumatic air conditioning control system identify pneumatic control system faults and their cause repair pneumatic control system faults.
Content
What is Pneumatic Control Advantages of Pneumatic Control Disadvantages of Pneumatic Control What is in a Pneumatic System Air Compressors Operating Conditions of a Pneumatic Circuit
Keeping the Air Supply at the Correct Operating Pressure, Clean and Dry Pressure Reducing Device Main Line Filter Refrigerated Air Dryer Pneumatic Transmission
109
Humidity and Air Pressure Sensors Pneumatic Actuators or Motors Applications of Pneumatic Control Systems Pneumatic Control System Commissioning Specialised Service Tools Required for Pneumatic Controls Work Component Commissioning Air Regulator Commissioning Pneumatic Thermostat Commissioning Testing the Operating Range of a Water Valve Setting the Stroke of a Damper
References
ARAC Volume 2, pages 29.27 29.39 Discusses pneumatic control
110
Pneumatic controls (ARAC Volume 2, pages 29.27 29.39) What is pneumatic control?
Pneumatic control is the use of clean dry air as a power source in place of voltages and currents in the operation of control equipment within the air conditioning plant. In place of a mains power supply, an air compressor is used to supply the systems energy needs. Instead of copper conductors, soft drawn copper tubing with soldered fittings or nylon-reinforced plastic or polyethylene tubing is used to transport the air around the control system. Apart from these significant differences much of the controls equipment stays the same (other than the fact that they operate by air.) Sensors are still required to sense the conditions; controllers to operate according to the sensor signal and pneumatic controlled devices to operate to control the load. Electricity and / or electronics can be coupled into the pneumatic system. This is done so i. equipment like compressors, heaters, etc can be initiated and ii. to get the benefit of accuracy that electronics give. Control equipment like Pneumatic Electric (PE) relays (switching devices) and Electronic Pneumatic transducers (sensing devices) are used to link the different systems together.
111
Air Receiver
Air Compressor
(Reproduced with permission of Atlas Copco)
MA
The above diagram helps to identify the names and the extent of the various air supply regions of a pneumatic control system. The list below is a description of the different supplies and the operating pressures that they operate within. System Air (SA): is the air that is held in the stored in the receiver tank of the compressor and feeds to the pressure reducing
112
NR15 Air Conditioning Controls Module Resource Manual April 2009
device. ARAC suggests the operating pressure to be approximately 700 kPa. Main Air (MA): is the supply to the components like controllers and valves etc, after the system air has been reduced to between 100 and 120 kPa. is the air that leaves a controller and that is varied according to load. ARAC suggests that the operating pressure in the branch to be between 20 and 90 kPa. The Branch Line is sometimes called the Pilot line (P).
Branch (B):
Keeping the air supply at the correct operating pressure, clean and dry
As was mentioned in the introductory paragraph, the air supply must be kept both clean and dry to ensure the reliable operation of the pneumatic control system. Equipment throughout the control system has many small orifices and hence the potential for blockages due to impure air. There are two minimum requirements necessary for the supply air, to be kept clean and dry. The components use to meet these requirements are shown below.
AX Valve Water Separator Compressor
Condenser
113
It should be noted that oil discharged into the main supply line would eventually penetrate the whole system causing similar problems to those mentioned under dehydration.
Pneumatic transmission
The transmitter is a sensor that is used to measure temperature and relative humidity. It measures the controlled variable and converts it into a pressure signal of between 20 and 90 kPa. The sensitivity of a transmitter is equal to the change in output pressure divided by the change in the measured variable.
114
The pilot bleed system A combination of the bleed-type and non-bleed systems. High Capacity controller
Controllers may be either direct acting or reverse acting. (See the Glossary in this module for further details.)
Selector relays
Load Analyser
115
Proportional relays
Reverse-acting relays
Transducers
There are many more control types available and these can be found in the Honeywell Engineering Manual of Automatic Control. Other suppliers of pneumatic controls (like Johnson Controls) can be approached for information relating to their products.
116
A pneumatic actuator is a controlled device that is the part of the system that does the work, i.e. opens dampers, opens valves etc. When air from the controller enters the space above the piston (see the diagram below) it causes the piston to move against the spring. The force exerted and the amount of movement depends on two factors: 1. The strength of the spring 2. The amount of pressure above the spring. If greater forces are required than can be delivered by a piston type actuator, the diaphragm actuator is commonly used. (To calculate the force (Newton) being exerted, multiply the diaphragm area ( d2 ) by the pressure (Pascal). 4
117
Stab Gauge
Test Probe Assembly with hypodermic needle.
(Reproduced with permission of Johnson Controls)
A hand pump (also known as a squeeze bulb) is used to test actuator operation.
Knurled knob used to relieve pressure slowly when testing actuators
Hand pump similar to the blood pressure tester that your local doctor would use.
Squeeze Bulb
(Reproduced with permission of Johnson Controls)
118
Drain No.3
1. Check the supply pressure before adjusting the main pressure. 2. By turning the adjusting knob clockwise (No.1) there will be an increase in the main air pressure and by turning the knob counter clockwise the pressure will be reduced. A pressure gauge (No.2) is generally fitted to the regulator to show the operating pressure. 3. Test the setting by bleeding air from the drain (No.3) to make sure the regulator will maintain the correct pressure feed that has just been set.
1
Calibration Screw
119
For both the following steps, the stab gauge must be installed in the thermostat and air must be supplied to the system. Step 1 Adjusting the throttling range 1. Move the temperature adjusting dial (No. 1) until the stab gauge pressure reads zero. 2. Move the temperature so the pressure on the stab gauge moves in a positive direction noting how many Kelvin it takes for the pressure to raise from the minimum operating pressure to the maximum operating pressure, see commissioning diagram for throttling range. 3. If the pressure range did not occur over the throttling range, adjust the throttling range Honeywell, Sensitivity Johnson Controls (No.2) until it does. 4. Retest and recalibrate if necessary. The throttling range is now set. Step 2 Calibrating the set point 1. Measure the control point of the area as close as possible to the thermostat. Do this three times to be sure of an accurate reading. 2. Set the setpoint dial (N0.1) until the needle lines up with the temperature you had just taken. Be sure not to submit the thermostat to any outside temperature influence, i.e. your breath or heat from your hand etc as you do this. 3. Adjust the set point calibration screw (N0.3) until the pressure on the stab gauge reads the set point pressure, see the commissioning diagram for details. Again this must be done without disturbing the sensor by breathing on it or touching it, etc. 4. Return the setpoint dial to its correct setting, usually 22 C but check the diagram. 5. Allow time for the thermostat to settle and regain control. Take further temperature readings to ensure the correct operation of the system, whilst remembering that offset will increase with deviation of the control point from the set point. The thermostat is now calibrated to the requirements of the diagram.
120
2. Pump up the pressure on the valve to its minimum operating pressure while watching the valves spindle. The valve should not have moved. 3. Continue to pump while watching the valve as you do. If the valve is operating OK, it should be completely open at its rated maximum operating pressure. 4. Open the knurled knob on the pump to slowly release the pressure on the valve. Watch as the pressure on the valve is reduced back to its minimum. 5. The check is now complete, reconnect the valve to the system.
121
Procedure
You will observe the operation of a complete pneumatic control system and from your observations briefly explain the operation of various pneumatic controls that your teacher will identify. Remember: Work safely at all times! Air compressors may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. High air pressures can be present throughout pneumatic systems.
122
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
123
Procedure
From the commissioning sheet provided, you will: 1. Identify the operating temperatures, setpoint and pressures that the thermostat, chilled water valve and outside air damper will operate at to satisfy the diagram requirements. 2. Commission an air regulator to maintain a constant pressure of 120 kPa. 3. Commission a thermostat to operate within the settings provided. 4. Confirm that the chilled water valve will open and close at the desired operating pressures by testing with the hand pump. 5. Stroke an outside air damper to operated within the parameters set out below.
Remember: Work safely at all times! Air compressors may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. High air pressures can be present throughout pneumatic systems.
The operating temperatures, setpoint and pressures that a thermostat, water valve and outside air damper. Thermostat Setpoint Setpoint Pressure: Throttling Range: Operating Pressure Range: _________________________ C ________________________ kPa _________________________ K ________________________ kPa
124
Chilled Water Valve Operating pressures on diagram: On the valve made available to you: ________________________ kPa ________________________ kPa
Outside Air Damper Fully Opened Pressure: Fully Closed Pressure: ________________________ kPa ______________________ kPa
Confirm that the chilled water valve will open and close at the desired operating pressures Is the chilled water valve working within the range required by the: Diagram: Pressures recorded on the head of the actuator on the valve: Stroke an outside air damper Has the outside air damper been stroked as per the diagrams requirements? Yes / No If no, what is the problem and what can be done to rectify it? Yes / No Yes / No
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
125
Commissioning sheet for an outside air sequence with chilled water valve
D/A R/A MA SP 220C TR 20C
DM3
21-56 kPa DM1 O/A
DM2
SA
LEGEND
91 CHWV Open SP = TR = ASV = SA = MA = R/A = O/A = S/A = D/A = Setpoint Throttling Range Air Solenoid Valve System Air Main Air Return Air Outside Air Supply Air Discharge Air
kPa
56
Closed O/A
21
Open Setpoint 21 22 C 23
Further Notes
ASV1 is energised through the supply fan contactor. ASV2 is energised through an outside air thermostat which is set to make at 180C and break at 220C.
126
Procedure
1. One or a number of faults will be placed on the pneumatic system by your teacher and you will be required to identify the fault/s as you see it / them. 2. Your teacher may require you to repair the fault/s and then test the system for correct operation or you may simply be required to describe the repairs required in the space provided below.
Remember: Work safely at all times! Air compressors may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery. High air pressures can be present throughout pneumatic systems.
Fault Identification
Type of Fault: _________________________________________________ Possible Cause for Fault:
Repairs Required:
127
Repairs Required:
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
128
Review questions
These questions will help you revise what you have learnt in this topic. 1. What is pneumatic control?
2. What is the purpose of combining electronic / electric control with pneumatic control?
3. What is the purpose of fitting refrigeration units in the supply air of the air compressor?
4. What are the pressure ranges mentioned in the pneumatic section and what lines would you find them in? Range Lines Pressure Range Used In
129
Review questions
8. It is not effective to use a bleed thermostat on large capacity actuators. Why is this the case and what is done to overcome this problem?
9. What is the difference between direct acting and reverse acting sensors?
10. What are the following relays used for: Two Position Relay
Select relay
130
Review questions
13. A spring is also incorporated in the actuator. What is the purpose of the spring?
14. What problem/s can occur if the air compressor breaks down on a system without a fail safe operation? What can be done to overcome the problem / s? (See Applications for Pneumatic Control Systems)
15. List the steps to service a pneumatic system on a three monthly maintenance program.
16. What tools are required to commission pneumatic control equipment like thermostats, valves and dampers and describe what they are used to do.
131
Review questions
17. To increase the mains pressure at the regulator, the regulator would need to be turned Clockwise / Counter Clockwise 18. From the diagram below, identify the:
91
HWV kPa 56
CWV
21 20 21 22 C 23 24
Set Point: Hot Water Valve Full Open Position Pressure: Hot Water Valve Full Closed Position Pressure: Chilled Water Valve Full Open Position Pressure:
Chilled Water Valve Full Closed Position Pressure: __________ kPa Dead Band: between __________C
19. In the diagram in question 18, if the thermostat reaches 24C the pressure in the branch line from the thermostat would be 91 kPa. What is the problem with this scenario and what can be done to rectify the problem?
132
Review questions
20. Briefly describe in your own words how to calibrate the setpoint of a pneumatic thermostat.
21. Describe how to test the hot water actuator operation if the system had no air being supplied to it and what tool/s would be required?
133
Notes
134
Objectives
At the end of this topic you should be able to: list and explain the principles of PLC and DDC control systems.
Content
Microprocessors Programmable Logic Controllers (PLC) Advantages of PLC Disadvantages of PLC Application of PLC Systems What is Direct Digital Control Sensing Function Decision Function Memory Function Action Function
References
ARAC Volume 2, pages 29.25 29.27 Discusses programmable logic control
135
Microprocessors
The microprocessor is a computer-based system that can be used to control air conditioning systems. The main benefit of microprocessor control is that it can control more accurately than other forms of control systems. The two main types of microprocessor control are: Programmable Logic Controllers Direct Digital Controls
The following block diagram shows the basis of how a microprocessor systems work.
Microprocessor
The following diagram shows the control panel with the programming keys and the program display window. Large programs can go over a number of pages (screens) and can be scrolled through at any time.
NR15 Air Conditioning Controls Module Resource Manual April 2009
136
The following diagram shows how a typical cool only ladder diagram would appear as a PLC ladder diagram. Further note the key used to identify the inputs and the outputs.
Inputs On / Off Switch Sail Switch Thermostat Thermal Overload Outputs Evaporator Fan Compressor Condenser Fan X1 X2 X3 X4 Y1 Y2 Y3
On /off Switch
t
Sail Switch Thermostat O/Load
Compressor
X1
Y1
Y1
Y2
Y3
137
Advantages of PLC
Less hard wiring is required with PLC controls. Changes to the control circuit can be done with a program alteration where hard-wired systems (like electric and electronic systems) may need wiring alterations to effect the same outcome. Less output components are required like timers, relays, etc as they are incorporated within the control body
Disadvantages of PLC
Programming can be difficult to grasp as unlike typical ladder diagrams, the ladder diagrams used in programming do not allow for crossing over of lines. Other peculiarities exist between the normal ladder diagram and programming ladder diagram.
138
As mentioned, DDC are computer based (microprocessor) machines that can be used to maintain set conditions of an air conditioning application. To maintain those conditions, the DDC system must perform four functions, they are: Sense Function Decision Function Memory Function Action Function
Sensing function
As with the other control systems, the sensor senses the control variable and transfers the information to the microprocessor for interpretation and response through the input of the controller. The input can be either On / Off (binary) or analog. Sensing inputs can include temperature, humidity, pressure, etc. The typical signal input can include one or more of the following types: A variable resistance signal Variable milliamps signal i.e. 0-20 mA Variable DC voltage signal i.e. 0-12 V
139
Decision function
This is where the input information is processed. It compares the input to the information stored in the memory by making calculations on the deviation. Once the calculations are made a logical decision on the corrective action is taken.
Memory function
The memory of the processor is like our brain. It is where the DDC remembers what to do, how it does it, and even analyzes the result of every completed task. It does this with the use of a program. The program provides both the information and instructions for the DDC system. If programmed correctly the system will perform the correct sequence of operations to provide optimal conditions of the medium being controlled.
Action function
Once the decision has been made for some form of action, the microprocessor carries out the corrective action by using action units of the DDC. The action functions are called the outputs of the system. The two types of outputs include Binary (On / Off) and Analog (variable) The action unit can be used to turn on and off supply fans, compressors, etc, communicate information to humans and / or other computers (alarms, etc).
Advantages of DDC
DDC equipment tends to be smaller and sometimes simpler. DDC systems are very accurate and they do not loose their set point, i.e. they do not drift like other control systems. They are energy efficient under all load conditions; this makes for long term cost savings. DDC control is compatible with building management systems. Adjustments can be done through the program. The building manager / owner / control company can even make alterations remotely to where the air conditioning system is located, i.e. in another building, in another state, etc. Programs can incorporate adaptive control capability that allows the air conditioning system to adjust itself to changing conditions in the controlled environment. Programs can be password protected to protect against tampering. DDC can use pneumatic actuators.
140
Disadvantages of DDC
The initial cost of installing a DDC system. Equipment Computers, desktop and / or lap top computer. The cost of someone writing the system specific program, etc.
Programs can be password protected to protect against tampering but this may incur the added cost of employing a controls company to make a minor alteration.
141
Practical exercise
If there is no operational DDC or PLC system available for viewing in the section, it is recommended that an excursion to a DDC or PLC controlled building be arranged! If you are on an excursion, remember that you are a guest in someones establishment. Be courteous to the people showing you around and dont tamper with any equipment that you see.
Task
Observe the operation of a DDC air conditioning control system and / or a PLC air conditioning control system.
Procedure
Observe the operation of a DDC controlled building. Identify the inputs, microprocessor, and the outputs of the DDC system Draw and label one page of the program as seen on the monitor of the computer Describe the operation of the drawn screen.
Remember: Work safely at all times! Systems may start automatically so make sure you keep fingers, tools, hair, clothing etc away from rotating machinery.
Type of microprocessor used Manufacturer of the program: __________________________________ Is it Windows or DOS base: ___________________________________ What computer language was used to write the product:______________
142
If the building was another form of control system before being converted to computer based system: has it saved money due to energy conservation YES / NO Explain your answer
Draw and label one page of the program as seen on the monitor of the computer.
143
Check your work with your teacher to be sure that you have carried out the work required by this exercise. Note below anything you wish to further investigate. NB: If you have any questions dont hesitate to ASK! The teacher is there to help you.
144
Review questions
These questions will help you revise what you have learnt in this topic. 1. What is the major difference between an electronic system and a microprocessor based system?
2. What is the major difference between a programmable controller and a conventional computer?
3. Why would a building owner install DDC control in place of either an electric or electronic control system?
145
Review questions
9. Write down the typical input signal values for a DDC control
146
Review questions
10. Name two devices used to provide input into the input interface.
11. Name two devices used to receive control system output. 12. What is the name of the device located between the input and the output of a PLC control system?
13. Why is it easier to change the performance of the PLC controller than an electronic controller?
147
Notes
148
Sample tests
The following tests are included as an example of the expected coverage and depth. The assessment of this module is holistic in nature and to successfully pass the module, you must show evidence that you have achieved the module purpose, which incorporates the module outcomes. The Sample Tests provide for an overall assessment of the module, as follows: Test Theory test 1 Practical test 1 Theory test 2 Practical test 2 Topic Covered 1, 2, 3 and 4 2 and 4 1 to 7 2 to 6 Timing 18/36 18/36 36/36 36/36 Duration 60 minutes 30 minutes 60 minutes 60 minutes
149
Desired Value
Temperature Sensor
Perimeter Temperature
(A) a resistive loop circuit (B) a capacitive loop circuit (C) a closed loop circuit (D) a open loop circuit
2.
A high temperature alarm sensor is part of: (A) a resistive loop circuit (B) a capacitive loop circuit (C) a closed loop circuit (D) a open loop circuit
150
3.
(A) reverse acting two position controller schedule (B) direct acting two position controller schedule (C) reverse acting proportional controller schedule (D) direct acting proportional controller schedule
4.
22C (A) reverse acting two position control (B) direct acting two position control (C) reverse acting proportional control (D) direct acting proportional control
151
5.
Flow control sensors include: (A) air pressure switch, sail switch and paddle switch. (B) differential water pressure sensor, orifice plate and sail switch (C) air pressure switch, pressure differential switch and orifice plate (D) sail switch, paddle switch and orifice plate.
6.
The objective of Building Management is to: (A) centralise the monitoring, operation and management of a building. (B) decentralise the monitoring, operation and management of a building. (C) allow building owners to manage the air conditioning system. (D) allow the service technician to manage the air conditioning system.
7.
Economiser Cycle is: (A) the use of iced water that was produced during low tariff periods. (B) the use of smaller capacity compressors during low load conditions (C) the use of return air conditions to cool the building in preference to mechanical cooling (D) the use of outdoor conditions to cool a building in preference to mechanical cooling.
8.
Electric control is described as the most basic of control systems. Electric control primarily lends itself to which type of control? (A) On / Off Control (B) Proportional Control (C) Step Control (D) Analog Control
152
9.
The use of four senses were recommended when fault finding. The four senses are: (A) Sight, Smell. Taste and Touch (B) Taste, Touch, Sound and Sight (C) Sight, Smell, Sound and Touch (D) Smell, Taste, Touch and Sound
10. In an automatic electric control system a Permanently Split Capacitor Motors direction is changed using: (A) A thermostat with a double pole double throw switching arrangement (B) A thermostat with a single pole double throw switching arrangement (C) A Potentiometric controller (D) A spring return
153
2.
3.
4.
154
5.
6.
Briefly describe the difference between the output signal of a twoposition control and the output signal of floating control.
7.
8.
What control characteristics are indicated by the letters on the graph? Overshoot Undershoot Setpoint Differential
155
9.
10. Fluid control sensors are used to do two things, they are: 11. Explain what is meant by the term Energy Management.
156
14. Draw an integrated cool only sensor / controller labeling all parts and describe its operation.
15. With the aid of the wiring diagram for a package unit on the next page answer the following questions. (a) During what part of the operating cycle is the crankcase heater energised.
(c) What is the function of the normally closed contact 52C [at terminal point (7)]?
157
(f) What is the result if MF1 fails to energise due to a burnt out contactor coil? List all results of this failure.
158
159
Wiring Diagrams
In the space below draw a 240 volt circuit diagram in a ladder format for a simple air conditioning system containing the following components: Compressor Evaporator Fan Condenser Fan Electric Heater (including a heater safety thermostat) One Stage Heat / One Stage Cool Thermostat All Relevant Operating and Safety Controls No Lockout Relay Use pencil to sketch out your diagram before completing it in pen.
Active
Neutral
160
Cooling
Heating
161
Practical test 1
Time Allotted: 30 minutes Your teacher will set a series of fault finding and practical commissioning exercises on Electric and / or Fluid Flow control systems to reflect what you have learnt in class. The following examples of fault finding and commissioning exercises are typical of what your teacher could provide you. The following are examples of typical faults that could be fitted on electric and fluid flow control systems. Identify the fault and recommend the repairs that would be required to correct the fault.
162
Indoor Unit
24 V Relay
Defrost Timer Crankcase Heater Compressor Contactor Outdoor Unit Pressure Control
Repairs Required:
163
164
165
166
Sample theory test 2 5. The simplest pneumatic control is: (A) a non-bleed type controller (B) a bleed type controller (C) a pilot-bleed controller (D) a sensor controller 6. The control (branch line) pressure for pneumatic control system actuators is: (A) 20 Pa to 150 Pa (B) 20kPa to 150 kPa (C) 150 kPa to 400 kPa (D) 150 Pa to 400 Pa 7. The main (line) pressure used in pneumatic control systems is: (A) 20 Pa to 150 Pa (B) 20kPa to 400 kPa (C) 150 kPa to 400 kPa (D) 150 Pa to 400 Pa 8. The following diagram is an example of a:
(A) reverse acting bleed type controller (B) direct acting bleed type controller (C) reverse acting proportional controller (D) direct acting proportional controller
167
9.
DDC stands for: (A) Direct Digital Control (B) Direct Digital Controller (C) Direct Digit Control (D) Direct Digit Controller
10. DDC systems is made up of three main parts, they are: (A) the input, the controller and the output (B) the input, the switching mechanism and the output (C) the input, the microcomputer and the output (D) the input, the microprocessor and the output
168
2.
3.
4.
169
5.
What are three advantages and three disadvantages of electronic control? Advantages:
Disadvantages:
170
Sample theory test 2 7. Name the Actuator seen in the diagram below and describe its operation.
Hydraulic Fluid Hydraulic Pump
Pump Valve
Oil Reservoir
Pressure Chamber
Diaphragm Piston
Actuator Name:
Operation:
8.
Name the Actuator seen in the diagram below and describe its operation.
Expansion Medium ie Wax Heater
Seal
Actuator Name:
Operation:
171
9.
Deadband:
Differential:
Control Point:
Offset:
10. How would you test a resistive sensor if you suspected it to be inaccurate?
11. Identify two advantages and two disadvantages of pneumatic systems when compared to electrical systems. Advantages Disadvantages
NR15 Air Conditioning Controls Module Resource Manual April 2009
172
Sample theory test 2 12. From the following diagram below name the components indicated. A B
173
14. Name the two primary types of pneumatic actuators: 15. What is the purpose of a refrigerated air dryer?
16. Briefly explain the function of the following pneumatic control equipment: Two position relay
Selector switch
Electro-pneumatic transducer
17. What is the difference between a pneumatic direct and reverse acting temperature sensor / controller?
174
Sample theory test 2 18. The following diagram shows a basic pneumatic control system. Name and explain the function of the four components numbered. Explain the sequence of operation of this circuit.
3 2
______________________________________________________________ 4 _____________ ______________________________________________________________ ________________ 1
Sequence of Operation:
175
176
Sample theory test 2 21. Identify the type of control systems from the diagrams provided. 1. Type of System
2. Type of System
22. Identify the blocks marked A, B and C of the following Microprocessor diagram
B
Microprocessor
177
24. What are the four functions that a DDC must perform to maintain a set of conditions of an air conditioning application?
178
20
21
24
Identify the fault and recommend the repairs / alteration required. Fault: ______________________________________________________________
179
MA
180
Repairs Required:
Output
181
Actuator Position
Closed
21
24
Type of Controller: _________________________________________ Setpoint: Deadband 1: Proportional band: ____________________ ____________________ ____________________
182
CWV
21
Setpoint: CWV Full Open Position: Full Open Position: Full Closed Position: Full Closed Position:
____________________ C
HWV Full Open Position: Full Open Position: Full Closed Position: Full Closed Position: ____________________ kPa ____________________ C ____________________ kPa ____________________ C ____________________ K
Throttling Range:
183
Notes
184
Answers
Review questions
1. Control system fundamentals and diagrams
1. The three essential components of a control loop are: Sensing device Controller Control device 2. The six major functions of these components are: The sensor senses a change to the controlled variable. The controller amplifies the sensor signal. The amplified signal is transported to the control device. A corrective action takes place. The sensor senses the corrective action and signals the control device. The control device ends the corrective action. 3. The controlled variable in the control loop is the control medium, i.e. water, air or many other material whose condition is being controlled. The set point of a controller is the value at which the indicator is set to on the controls scale. The control point of a control loop is the value of the condition actually maintained in the space as recorded by the control. The differential gap is the range through which the space condition must travel from on to off. The offset of a control loop is the difference between the set point and the control point. The lag in a control loop is the delay in the effect on the controlled space if the corrective action. Cycling in a control loop is the consistent repetition of change in the control point.
4.
5.
6.
7.
8.
9.
10. An actuator is a motor, relay, solenoid etc., in which energy from the controller is converted into rotary, linear or switching action to bring about change in the controlled space or condition.
185
11. The difference between a closed loop control system and an open loop control system is that closed loop systems receive feed back and controls accordingly. The open loop system on the other hand operates regardless of the impact on the space, i.e., has no feedback. 12. The control point is the value of the conditions actually maintained in the space. 13. The three types of control diagrams are: Air conditioning diagrams Pneumatic and Logic Control diagrams Electrical diagrams 14. A typical application for each of the following diagrams would be: Air Conditioning Diagrams: used to show the transport of air throughout a ducted system. Pneumatic and Logic Control Diagrams: Used to show circuit operation of pneumatic and logic circuit. Block Diagrams: used to aid in the understanding of circuit operation Circuit Diagram: used for fault finding Wiring Diagrams: used to complete wiring equipment Control Circuit Diagrams: used to show circuit operation and can be seen in most air conditioning units circuit boards from the simple domestic through to industrial applications. 15. The control components that you would expect to find in a control diagram for a basic system to control conditioned air would be: Switches to turn on and off the system Thermostat to automatically turn on and off the compressor Contactors for starting and starting the compressor, fan motors, etc Protective controls like: Overloads to protect against excess current High pressure, low pressure or dual pressure controls to protect against high and low system pressures. Over temperature devices like thermistors to protect motors against excessive operating temperatures. 16. Other control system components that you would expect to find in a control diagram for a system to condition water would be: Safety thermostats: to protect chillers against icing up. Contactors for starting and stopping chilled water pumps. Water valves Flow switches to allow the system to know that the pump is circulating water.
186
17. The symbol for the following components are: A thermostat that makes on rise.
M or
A sail switch
187
2.
3.
4.
5.
6.
7.
Condition Switch
8.
A paddle switch is fitted into a chilled water circuit to stop the compressor/s starting and icing up the evaporator causing major damage. The controlled differential is the difference between the cut in and cut out temperatures or pressures.
9.
188
10. The throttling range of a proportional controller is the control point range through which the controlled variable must pass to move the final control element through its full operating range. 11. The operating differences between on-off and floating control types is that on-off has only two positions where floating control has a sensing element that is attached to a selector that is free to drift between contact points. When the selector makes, it drives an actuator motor in one direction until the sensed condition moves back into tolerable limits and then the contacts open. 12. The operating differences between floating and proportional control types is that proportional is always on and there is constant feedback between the controlled device and the sensing element. Floating is like an On-Off version of proportional control. 13. The term used for the device, which incorporates an actuator that drives a shaft that has many cams, mounted on it to operate micro-switches for a number of output devices is a step controller. 14. The purpose of a relay in a control system is to perform a function beyond the capacity of the original controller. 15. The major design and operational difference between opposed blade dampers and parallel blade dampers is that: Parallel blade dampers: all the blades rotate in the same direction Opposed blade dampers: alternate blades rotate in opposite directions. 16. The effect on the airflow of a parallel blade air damper and an opposed blade damper at the half-open position would be that: Parallel blade air damper: there would be approximately 80% of the supply air moving through the damper. Opposed blade damper: there would be approximately 40% of the supply air moving through the damper. 17. The valves shown in the sketch are mixing valves. Mixing valves have two lines in and one line out. See Automatic Control Principles (p.39) to see the difference between the two valve types.
189
18. The correct location for the mixing valve on the cooling coil is shown below with directional arrows to identifying water flow. -
19. The following sketch shows a face and bypass damper control arrangement.
Bypass Damper Air Flow Cooling Coil Face Damper
Damper Motor
Operation As the temperature of the space rises the modulating motor opens the face damper opens allowing air to pass across the cooling coil and then to the space. The bypass damper closes off at the same time as the face damper opens. As the temperature of the space drops the face damper closes back down again while the bypass damper opens allowing air to bypass the cooling coil.
190
2.
3.
More complex than pneumatic control Often needs more maintenance Elaborate protection required in hazardous locations Needs skilled service personnel Higher voltages so greater care must be taken Many control changes require wiring alterations to achieve the change Accuracy can be difficult to achieve Physical size of control components can be a problem Modulating actuators can be complex
191
5. If the temperature varies above or below the set point, the thermostat makes, driving the step controller in one direction or the other. The cams in the step controller are turned making microswitches in their travel. The microswitches are used to energise or de-energise heating and cooling components according to the load requirement. 6. A microswitch is a snap acting switch whose contacts are made or broken by the movement of a sensing element or cam mechanism. 7. The simplest type of control system actuation is On / Off. 8. The permanently split capacitor motors direction can be changed simply with the use of a single pole double pole switch.
Single Pole, Double Throw Switch
9. The function of limit switches on modulating motors is to stop the motor from continually driving in one or the other direction. 10. The balancing relay in the modulating motor works on the principle that if more current flows through one coil and less to the second coil, the magnetic fields created causes the relay to pivot.
Coil with the least current Coil with more current
11. An integrated sensor / controller has both the sensor and the contacts contained within the one body. 12. To test for an integrated humidity sensor / controllers accuracy you must: Take the humidity of the area being controlled. Set the controllers set point to the same humidity setting as the condition that was just taken. Make adjustment if necessary. Check the differential and adjust if necessary. 13. The insulation resistance tester is used to test for earth leakage.
192
14. To use the insulation resistance tester for earth leakage: Connect one of the meter leads to the electrics of the component being tested and the other lead to the metal frame. Set the meter to that which is recommended in the wiring rules, (approximately double the voltage rating of the component being tested. Take a reading. If the component reads from zero to 1 megohm the component is faulty. If the meter reads from 1 megohm to infinity the component is OK.
15. The four things technicians do every time they fault find are: Recognise that a fault or faults has occurred on the plant. Locate the fault(s) and the reason for the fault. Carry out all necessary repairs to the equipment. Restart the plant and do a final check
16. The use of the senses can be a quick way of identifying faults. Verification with the appropriate testing equipment should always be done to confirm the fault. 17. The senses suggested and the types of faults that can be identified are listed below: Sight: Smell: Hearing: Touch: Visually identifies breaks or damaged components. The scent of burnt components and wiring Listen for unusual noises like chattering, buzzing or groaning coming from components. Feel for excess temperature
18. The components indicated are: 1. 2. 3. 4. 5. 6. 7. 8. Sail switch Transformer Three phase switch Fuses Heater Contactor coil Two stage heating thermostat High-limit manual reset thermostat.
193
2.
3.
4.
5.
Listed below are typical advantages of electronic control systems: Simple , low voltage interconnections Smaller equipment size Sensing elements are faster to respond Can be mounted in any position Vibration and dirt resistant Remote set point capability Application flexibility Superior calibration Simple adjustment
6.
The three disadvantages of electronic control are: Some temperature sensing elements will continue with temperature change beyond their own control range. The initial purchase cost can be expensive. Actuators and controls tend to be complex.
194
7.
The three basic parts of a single element controller and the function for each are listed below: Bridge Amplifier Output Circuit The sensing circuit for the controller Increases the signal into a useable signal Connection point for actuators, contactors, relays, etc.
8.
The four major types of actuator used in the air conditioning industry is: Magnetic Motorised Thermal Electrohydraulic
9.
Operation of a Thermal Actuator: Thermal actuators are made up of a heating element and a solid expansion medium. The heater heats up and cools down according to the variation in the output voltage from the electronic controller. With an increase in temperature, the solid expansion medium will expand causing a force to be exerted creating a stroke movement. If the voltage is reduced from the controller, the heater cools, the expansion medium contracts again causing the opposite effect in stroke movement.
10. Operation of a Electrohydraulic Actuator Electro hydraulic actuators use an oil pump and a pump valve (similar to a solenoid) to create valve or damper movement. If the voltage from the output of the electronic controller increases the pump valve closes isolating the actuators bottom chamber from the top. The pump fills the bottom chamber, extending the actuator shaft. If the voltage from the controller decreases, the servo valve opens relieving pressure back into the top chamber. The actuator shaft retracts. 11. An insulation resistance tester should never be used on electronic controls because the excess voltage that it produces will damage the electronic equipment.
195
12. Your graphical answer to question 13 should look the same as the one shown below.
Full Open / On
13. The answers are both bolded and italic Controller Type: Set Point Proportional Band 1 Dead Zone 1 Proportional Band 2 Dead Zone 2 14. The answers are both bolded and italic Controller Type: Set Point Differential 1 Dead Band 1 Differential 2 Dead Band 2 On / Off Controller 22C 2.5 K - 0.5 K 1.5 K 0.5 K Proportional Controller 19C 0.5 K 0K 1K 0K
196
6. Pneumatic controls
1. Pneumatic control is the use of air as an energy source in place of electric or electronics. 2. The purpose of combining electronic / electric control with pneumatic control is to allow for: Electronic- for the greater accuracy of electronic control. Electric for the initiation of electric components.
3. Refrigeration units are fitted to the supply air of the air compressor to remove any moisture before it enters the rest of the system where it may cause problems. 4.
Lines Pressure Range Used In From the air compressor tank and the supply lines to the regulator From the regulator through the mains lines to controllers. This pressure can also be supplied to control devices. From controllers to control devices.
20 90 kPa
5. The type of primary element used in pneumatic thermostats is the bimetal strip. 6. Bleed thermostats operate by bleeding various amounts of branch line pressure to the atmosphere. The position of the flapper with respect to the nozzle will determine how quickly the air is bled off and vary the branch line accordingly. The position of the flapper is determined by a temperature sensitive bimetal element. The branch line is used to control an actuator or become the input signal to a controller. 7. The two styles of controller described in ARAC are: Proportional controllers and High capacity controllers. 8. A simple bleed thermostats capacity would be too small to operate large capacity actuators at a reasonable speed. High capacity controllers or pilot operated actuators are used to overcome this problem. 9. The difference between direct acting and reverse acting thermostat is: Direct Acting: Reverse Acting: With an increase in temperature there is an increase in the pressure output. With an increase in temperature there is a decrease in the pressure output.
197
10. A two position relay is used to open one branch and close another. A select relay is used to select a highest or lowest signal from a number of controllers and direct an actuator. A Reverse-Acting Relay is used to reverse the signal from a controller so that an actuator may open instead or close or vice versa. 11. The following materials are used to sense humidity: human hair, wood or nylon, or electric-pressure transducers may be used. 12. The method of operation of a pneumatic actuator is that as air is admitted into the actuator, it fills the space between the rubber sealing diaphragm on top of the piston. As the pressure rises, it overcomes the spring pressure (and the load) to force the piston and shaft down. 13. Springs are used in actuators to set the operating range that they will operate over. 14. The problem/s that can occur in the event of an air compressor breaks down on a system without a fail safe operation is that without pneumatic pressure full cooling would be applied. To overcome this problem a reversing relay and a normally closed valve with the same operating range would need to be fitted. 15. The steps described to service a pneumatic system on a three monthly maintenance program include: Cleaning of all components Checking all moving parts for operation (thermostats, actuators, etc). Check to ensure that the control sequences are effective as originally commissioned. Recalibrate where necessary. Check all airlines, actuators, diaphragms, etc, for air leaks. Other checks could include: check operation of automatic water bleeds, check strainers, filters, refrigeration equipment in supply air from air compressor, etc, clean / repair as necessary. 16. The tools that would be required to commission pneumatic control equipment include: Stab Gauge: used to identify system operating pressures. Hand pump: used to pressure test operating ranges of pneumatic of pneumatic actuators. Small Flat Blade Screwdriver: used to calibrate the pneumatic actuators.
NR15 Air Conditioning Controls Module Resource Manual April 2009
198
Large Flat Blade Screwdriver and or shifter: used to stroke dampers and valves. Sling Psychrometer or Digitemp thermometer: used to calibrate the thermostat. 17. To increase the mains pressure at the regulator, the regulator must be turned clockwise. 18. From the graph in question 4: Set Point: 22 C Hot Water Valve Full Open Position Pressure: 91 kPa Hot Water Valve Full Closed Position Pressure: 21 kPa Chilled Water Valve Full Open Position Pressure: 91 kPa Chilled Water Valve Full Closed Position Pressure: 21 kPa Dead Band: between 21.5 and 22.5 C 19. If the thermostat reaches 24C the pressure in the branch line from the thermostat would be 91 kPa. The problem with this scenario is that both the chilled water valve and the hot water valves would be open. To rectify this problem a reversing relay would have to be fitted to the hot water circuit. 20. To calibrate the setpoint of a pneumatic thermostat Measure the control point of the area as close as possible to the thermostat. Do this three times to be sure of an accurate reading. Set the setpoint dial until the needle lines up with the temperature scale. Be sure not to submit the thermostat to any outside temperature influence, i.e. your breath or heat from your hand etc as you do this. Adjust the set point calibration screw until the pressure on the stab gauge reads the set point pressure, in this instance 56kPa. Again this must be done without disturbing the sensor by breathing on it or touching it, etc. Return the setpoint dial to its correct setting in this case 22 C. Allow time for the thermostat to settle and regain control. Take further temperature readings to ensure the correct operation of the system, whilst remembering that offset will increase with deviation of the control point from the set point.
199
21. To test the hot water actuator operation if the system had no air being supplied to it you would have to use a hand pump. Disconnect the valve actuator from the system and connect the hand pump to it. Pump up the pressure on the valve to its minimum operating pressure while watching the valves spindle. The valve should not have moved. Continue to pump while watching the valve as you do. If the valve is operating OK, it should be completely open at its rated maximum operating pressure. Open the knurled knob on the pump to slowly release the pressure on the valve. Watch as the pressure on the valve is reduced back to its minimum. The check is now complete, reconnect the valve to the system.
7.
2.
3.
4. The four functions that a direct digital control performs are: Sensing Function Decision Function Memory Function Action Function
200
5. The Sensing Function is the sensing of control variable and the transferring of that information to the microprocessor for interpretation and response. The Decision Function is the processing of the input information The Memory Function is where the controller remembers what to do, how to do it, and the analysis of the result of every completed task. The Action Function is the corrective action of the DDC system, the output of the system. 6. The program is a set of instructions that tells the microprocessor what to do. 7. There are two functions of the terminal: to allow for programming and trouble shooting the circuit. 8. The function of the central processing unit is to establish the electronic circuitry needed to carry out the instructions and to perform those instructions. 9. The typical input signals for a DDC control could include: A variable resistance signal Variable milliamps signal ie. 0-20 mA Variable DC voltage signal ie. 0-12 V
10. Examples of devices used to provide input into the input interface are start / stop switches flow switches pressure switches (ie. HP / LP controls) time clocks thermostats, etc.
11. Examples of devices used to receive control system output are: motors (if small enough), lights, solenoid coils, contactor coils, etc. 12. The name of the device located between the input and the output of a PLC control system is called a microprocessor.
NR15 Air Conditioning Controls Module Resource Manual April 2009
201
13. To change the performance of the PLC controller it is simply a case of changing the program. With than an electronic controller, hard wiring may have to be changed to attain the same performance.
202
8. 9.
10. (B) A thermostat with a single pole double throw switching arrangement
Short answer
1. An Automatic Control System is a system that will automatically regulate a HVAC system output in response to varying indoor and outdoor conditions to maintain general comfort conditions. The factors that affect loop stability include: Speed of operation of the control equipment Speed of the controlled equipment and Thermal Inertia Air change rate Sensor Location The six functions which should be performed by an automatic control system is The sensor senses a change to the controlled variable The controller amplifies the sensor signal The amplified signal is transported to the control device A corrective action takes place The sensor senses the corrective action and signals the control device The control device ends the corrective action
2.
3.
203
4.
The difference between digital control and analog control is in the control signal it uses. Analog controller receives and acts upon data continuously. The digital controller samples digital data at set time intervals. The function of a sensor is to detect and measure a disturbance in the control variable. The difference between the output signal of a two-position controller and the output signal of a proportional controller is: The two-position controller signal is either On / Off or open / closed. The proportional controller signal is variable, it can range anywhere between open and closed or on and off. The type of control method represented in the graph is On / Off control. The control characteristics indicated by the letters on the graph are: Overshoot A Undershoot D Stepoint B Differential C The function of the actuator is to convert electric energy into a rotary action
5.
6.
7. 8.
9.
10. Fluid control sensors are used to show fluid flow or measure flow 11. Energy Management is the optimisation of the operation, temperature and process of an air conditioning system within a building. 12. Night Purge in relation to Energy Management is where outside night air is used to cool a building space when outside conditions are favourable. 13. Thermal storage is the process of making use of lower tariff periods to store energy, i.e. turning water into ice. The energy stored can then be reused at a more expensive tariff period, i.e. remelting the ice to chill water which is then fed to air handling units. This is to in place mechanical cooling.
204
14. The diagram of the integrated cool only sensor / controller could look like the following diagram, it is an example only:
Mechanical connection between sensing element and contacts Contacts Bellows
Operation:
As the temperature of the controlled variable warms, the bulb pressure increases forcing the contacts to close. Cooling would be initiated by the making of the contacts. With a decrease in the controlled variable temperature, the bulb pressure decreases opening the contacts. The cooling cycle is complete.
15. The answers that relate to the wiring diagram are as follows: The crankcase heater is energised during the off cycle. The supply of the control circuit is 24 volts. The function of the normally closed contact 52C at terminal point 7 is to open and de-energise the crankcase heater. The supply voltage to the control transformer in Australia is 240 volts at 50 hertz. Item 62C is a recycle guard timer and its function is stop the compressor short cycling. (Ensures the compressor will not stop and then try to restart too quickly.) The results of MF1 failing to energise due to a burnt out contactor coil is that the compressor, evaporator fan and condenser fans will not operate. The system will not therefore cool.
205
Wiring diagrams
The following diagram is only meant to show one possible answer to the wiring diagram exercise.
Active Neutral
M
Condenser Fan Motor
t
Thermostat
Heating Element
Operation Fan Only The fan will operate once the vent (fan) switch is turned on. Conditioning cannot come on until the vent switch is turned on even if the condition switch is turned on. Cooling The compressor will only start once the vent and condition switches are turned on, the thermostat is calling for cooling and all the safety controls are closed. As the condenser fan is in parallel with the compressor, it will start as well.
206
Heating As with cooling, heating will only come on once the vent and condition switches are turned on and there is a call for heating. The over temperature thermostat will trip in the event of excess heat (i.e. due to no fan).
207
Practical test 1
Electrical control fault finding
Fault: The neutral of the reversing valve solenoid coil is connected straight to the neutral (at the defrost timer) so it will never change over and deactivate the coil. Repairs Required: The neutral of the reversing valve solenoid coil must be reconnected at the same terminal as the outdoor fan motor on the defrost timer.
Repairs Required: The repairs could include, depending on the fault: Replacement of the switch. Refit the line/s back into the ductwork securing them so that they will not fall back out. Unblock the air line/s if possible, etc.
208
Electrical commissioning
Your answer to the electrical commissioning exercise could include the following: Set the compressor overload to 7 amps (FLA), NO HIGHER. Set the HP/LP control to the required pressures and test their operation. (See NR12 - System Control how to calculate cut out and cut in pressures). Set the thermostat to 22C and test for calibration, dead bands, differentials, etc. Carry out an amperage test (using a tong tester) on all motors to ensure that they are operating within amperage limits. (See diagram for FLA ratings). Check the system on both heating and cooling operation to make sure that the system operates correctly on both cycles. Test both the de-ice thermostat and the de-ice heating element for correct operation, (the operating conditions are not described on the diagram so you may have to call the manufacturer for details). Test the low ambient thermostat and low ambient heating element / circuit operation.
Further commissioning tests you may need to do: (see NE172 - Electrical Wiring and Equipment and Australian Standards 3000 - SAA Wiring Rules (current edition). Check to make sure that there is no excess uninsulated conductors hanging out of terminals, etc. Test to make sure all terminals are tight (no loose joints.) Ensure correct fixing of conductors. Test for earth leakage and resistance between conductors. (The electrician wiring the job should have carried out these tests before handing it over to you.)
209
(A) A proportional band setting that is too narrow. (B) (B) (C) A bleed type controller. 20kPa to 150 kPa. 150 kPa to 400 kPa.
(A) Reverse acting bleed type controller. (A) Direct Digital Control.
Short answer
1. The PTC (Positive Temperature Co-efficient of resistance) sensors resistance increases with a rise in temperature and visa versa. The Bridge of an electronic controller operates on the principle of a Wheatstone Bridge. It operates by using two sets of two resistors connected in parallel across a DC power source. In the event that the sensing element resistance changes due to temperature change, the bridge would no longer be in balance and a voltage difference will occur. The difference in voltage between the two paths can then be amplified. The Amplifier of an electronic controller is to increase the signal from the bridge circuit. The output circuit is where the actuators are connected on the controller to provide the correct sequence of operation.
2.
3.
4.
210
5.
Listed below are typical advantages and disadvantages of electronic control systems that you could have written: Advantages Simple , low voltage interconnections Smaller equipment size Sensing elements are faster to respond Can be mounted in any position Vibration and dirt resistant Remote set point capability Application flexibility Superior calibration Simple adjustment
Disadvantages 6. Some temperature sensing elements will continue with temperature change beyond their own control range. The initial purchase cost can be expensive. Actuators and controls tend to be complex.
A Two in One Controller is a controller that can control two types of variables, i.e. temperature and humidity. The type of actuator shown is an Electro-hydraulic Actuator. Its operation: Electro hydraulic actuators use an oil pump and a pump valve (similar to a solenoid) to create valve or damper movement. If the voltage from the output of the electronic controller increases the pump valve closes isolating the actuators bottom chamber from the top. The pump fills the bottom chamber, extending the actuator shaft. If the voltage from the controller decreases, the servo valve opens relieving pressure back into the top chamber. The actuator shaft retracts. The actuator shown in question 7 is a Thermal Actuator Its Operation Thermal actuators are made up of a heating element and a solid expansion medium. The heater heats up and cools down according to the variation in the output voltage from the electronic controller. With an increase in temperature, the solid expansion medium will expand causing a force to be exerted creating a stroke movement. If the voltage is reduced from the controller, the heater cools, the expansion medium contracts again causing the opposite effect in stroke movement.
7.
8.
211
9.
The Set Point: is the desired value that the controller is expected to maintain The Dead Band: is the range through which an input signal will be varied without initiating a response from the controller. The Differential: is the difference between on and off state. The Control Point is the actual value of the controlled variable that the controller maintains. The Offset is the sustained deviation between the control point and the setpoint of a control.
10. To test the resistive sensor, you would: Disconnect the sensor from the controller and measure the resistance. Measure the ambient air close to the sensor. Compare the temperature and the resistance of the sensor against the relevant resistance curve for its accuracy.
11. Advantages of a pneumatic systems when compared to electrical systems: Pneumatic systems can be safely used in hazardous environments. Pneumatic actuators can be built to operate from the smallest to the largest valves and dampers. The controller is naturally and inherently operates as proportional control but tow-position is easily provided. It is easy to include a great variety of control sequences.
Disadvantages of a pneumatic systems when compared to electrical systems: Expensive to purchase and more equipment to maintain (i.e. air compressors, driers, etc.) Many mechanics consider pneumatic controls difficult to work with.
12. The components identified in the pneumatic diagram are: (A) Intake filter (B) (C) (E) Air compressor Pressure switch Refrigerated air dryer
NR15 Air Conditioning Controls Module Resource Manual April 2009
(D) Motor
212
(F)
Pressure regulator
13. The bleed thermostat operates that with a change in temperature a bimetal strip will either open or close a tiny nozzle, so varying the air pressure in the valve or damper actuator. 14. The two primary types of pneumatic actuator include: Two position actuator Proportional actuator
15. The purpose of the refrigerated air dryer is to remove all moisture before it enters the system and causes blockages in the many small orifices throughout. 16. The function of each component listed is explained below: Two position relay: To open one branch line and close another Selector switch: To choose either the highest or lowest signal from a number of controllers and with this signal /s operate an actuator/s. Electro-pneumatic transducer: To change an electric signal into a pneumatic signal or vice versa. 17. The difference between a direct and a reverse acting sensor is that with an increase in temperature the direct acting sensor will deliver an increase in output where the reverse acting sensor would deliver a decrease in output. 18. The name and the function of the four components numbered are: 1. Reverse acting thermostat: to send a signal to the hot water valve actuator and also to the reversing relay. 2. Chilled Water Valve: meters the flow of chilled water into the chilled water coil 3. Hot Water Valve: meters the flow of hot water into the hot water coil. 4. Reversing relay: changes the signal from the thermostat to operate the chilled water valve.
213
The sequence of operation: With a decrease in temperature, the reverse acting thermostats branch press increases and modulates the hot water valve open (between 60 and 90 kPa). The chilled water stays closed because the branch pressure has been reversed by the reversing relay. As the temperature increases the branch pressure decreases modulating the hot water valve closes at 60 kPa. With a further increase in temperature the thermostat branch pressure continues to drop. The reversing relay will reverse this signal until the chilled water range is begins to operate. Between 50 and 60 kPa branch pressure (from the thermostat), both valves will be closed
19. The recommended period for maintenance of a pneumatic control system is three monthly. 20. The maintenance should include the following: Clean all components Check all moving parts for operation (thermostats, actuators, etc.) Check the sequence of operation as installed Recalibrate where necessary Check for air leaks on all lines.
21. The two systems shown are 1. 2. Programmable Logic Controller Direct Digital Control
22. A: Analog to Digital Converter B: Central Processor (CPU) C: Digital to Analog Converter 23. An application for a PLC would be in the fire alarm system of a building. 24. The four functions that of a DDC must perform to maintain a set of conditions are: Sense Function Decision Function Memory Function Action Function
214
25. Sense Function: As with the other control systems, the sensor senses the control variable and transfers the information to the microprocessor for interpretation and response through the input of the controller. Decision Function: This is where the input information is processed. It compares the input to the information stored in the memory by making calculations on the deviation. Once the calculations are made a logical decision on the corrective action is taken. Memory Function: The memory of the processor is like our brain. It is where the DDC remembers what to do, how it does it, and even analyzes the result of every completed task. It does this with the use of a program. Action Function: Once the decision has been made for some form of action, the microprocessor carries out the corrective action by using action units of the DDC. The action functions are called the outputs of the system. 26. An application of a DDC system might include larger applications like multistory buildings, hospitals, clubs, etc.
215
Practical test 2
Electronic control fault finding
Fault: The controller has been set up without a dead band between heating and cooling. The unit will constantly go from heating to cooling and back again without ever turning off. Repairs / Alterations Required: The dead band between heating and cooling must be reset to allow for an off cycle.
216
217