Sei sulla pagina 1di 4

CAPTIVE POWER PLANT PANIPAT NAPHTHA CRACKER PROJECT,

LARSEN & TOUBRO LTD.

INDIAN OIL CORPORATION LTD.

TITLE: TECHNICAL SPECIFICATION FOR HT CABLES [33kV (E) CABLES]

L&T SARGENT & LUNDY LTD. Doc. No. : 6556-EPCC4-52-SP-E-0016 Rev.: 1 LOI No.: IOCL/PUR/SU/E19/254 Dated 23.03.07

Item No.

Description Manufacturer Voltage Grade Cable sizes and no. of core Type designation Applicable standard Conductor a) Nominal area and construction b) Shape of conductor c) Number and dia of strands (Nom.) d) Material and grade e) Max. D.C. resistance at 20C (/km) Normal current rating of cable circuit under as installed conditions in air at ambient temperature of 45oC Estimated conductor temperature under as installed condition Conductor short circuit carrying capacity for one (1) sec cable loaded as item 7 before short circuit : a) Short circuit current b) Conductor temperature

Units 1 C x 240 1 C x 300


19 / 33

1 C x 400
19 / 33

1 2 3 4 5 6

Polycab Wires Pvt. Limited .Daman

kV

19 / 33

1 C x 240
2XWaY

1 C x 300
2XWaY

1 C x 400
2XWaY

I S 7098 ( PART - II ) / 85

mm2

240

300

400

Compact Circular
35 / 3.08 35 / 3.4 57 / 3.06

Annealed Bare Copper


0.0754 0.0601 0.0470

570

655

750

90

kA
0

34.3

42.9
250

57.1

10

Conductor screen:
Page 1 of 4

CAPTIVE POWER PLANT PANIPAT NAPHTHA CRACKER PROJECT,


LARSEN & TOUBRO LTD.

INDIAN OIL CORPORATION LTD.

TITLE: TECHNICAL SPECIFICATION FOR HT CABLES [33kV (E) CABLES]

L&T SARGENT & LUNDY LTD. Doc. No. : 6556-EPCC4-52-SP-E-0016 Rev.: 1 LOI No.: IOCL/PUR/SU/E19/254 Dated 23.03.07

a) Type of material b) Nominal Thickness c) Method of application 11 Insulation a) Material b) Nominal thickness c) Tolerance on insulation thickness d) Type of extrusion and curing process e)Estimated cable insulation temperature under as installed condition f) Identification of cores
g) Dia under inner sheath (approx.) mm mm

Semi conducting XLPE Compound 0.5 By Extrusion XLPE Compound

mm

8.8 The Smallest value of insulation thickness shall not fall below the Nom. Value by 0.1 + 0.1 ti , where ti is the Nom. Values given above. Triple Extrusion and Dry Curing.

The Respective ground or Air temperature at Site


NA NA NA

mm

43.0

45.0

48.0

12

13

Insulation Screen a) Material b) Nominal thickness c) Method of application Metallic screen a) Screen or metallic sheath short circuit carrying capacity for one (1) sec cable loaded as item 7 before short circuit. b) Recommended screen or sheath temperature c) Material and Type

Semi conducting XLPE Compound


mm

0.5 By Extrusion

kA

17.9

80 C

Annealed Plain Copper Wires PVC Type "ST2" as per IS 5831 / 84

14

Inner sheath : a) Material & Type b) Minimum thickness c) Tolerance on thickness

mm

0.5 0.5 0.5 NO Tolerance . The above Mentioned Minimum Shall be met.
Page 2 of 4

CAPTIVE POWER PLANT PANIPAT NAPHTHA CRACKER PROJECT,


LARSEN & TOUBRO LTD.

INDIAN OIL CORPORATION LTD.

TITLE: TECHNICAL SPECIFICATION FOR HT CABLES [33kV (E) CABLES]

L&T SARGENT & LUNDY LTD. Doc. No. : 6556-EPCC4-52-SP-E-0016 Rev.: 1 LOI No.: IOCL/PUR/SU/E19/254 Dated 23.03.07

d) Wrapped or Extruded e) Colour of sheath f) Filler material g) Dia below Armour (if applicable) Approx. mm 15 Armour (if applicable) a) Material b) Round wire / strip c) No. and Dimension of round wire / strip(approx.) d) Dimension ( mm ) e) Max.Resistance (DC) at 20c f) Diameter. below outer sheath ( Approx. ) mm 16 Outer Sheath : a) Material & Type b) Colour of outer sheath c) Minimum thickness of outer sheath d) Tolerance on thickness 17 Electrical parameters at maximum operating temperature : ( i ) Resistance ( ii )Reactance (iii) Capacitance 18 (iv) Impedance Guaranteed value of minimum oxygen index of outer sheath to ASTMD / km / km F/km / km
0.0975 0.1233 0.217 0.1572

Extruded Black Not Applicable 44.2 46.2 49.2

Hard Aluminium Wires Round wires 50 2.5 / km 0.130 49.2 52 2.5 0.125 51.2 55 2.5 0.118 54.2

PVC Type "ST2" ( FRLS ) to IS 5831 / 84

Black mm 1.88 2.04 2.04

NO Tolerance . The above Mentioned Minimum Shall be met.

0.0783 0.1216 0.234 0.1446

0.0622 0.1161 0.259 0.1317

29

Page 3 of 4

CAPTIVE POWER PLANT PANIPAT NAPHTHA CRACKER PROJECT,


LARSEN & TOUBRO LTD.

INDIAN OIL CORPORATION LTD.

TITLE: TECHNICAL SPECIFICATION FOR HT CABLES [33kV (E) CABLES]

L&T SARGENT & LUNDY LTD. Doc. No. : 6556-EPCC4-52-SP-E-0016 Rev.: 1 LOI No.: IOCL/PUR/SU/E19/254 Dated 23.03.07

2863. Maximum acid-gas generation by weight (%) of outer sheath to IEC 754-1. Minimum light transmission to ASTMD 2843. Approx. weight of finished cable (kg/km) O .D . ( Approx. ) mm Recommended minimum bending radius Maximum pulling force for each cable Type test reports enclosed Catalogue attached Type of Drum (Wooden / Steel) Standard length per drum (EIL's.) - Mts. 1000 3 %
Kg/km mm

19 20 21 22 23 24 25 26 27 28

20 40
5350 54 6175 56 20 x O D 12 15 20 7270 59

xD kN Yes / No Yes / No

Yes Yes Wooden 1000 3 % 1000 3 %

Page 4 of 4

Potrebbero piacerti anche