Characteristics

MVS08N3NF6L

EP MVS CB 800A 50kA 3P EF 240VAC ET6 fixed electrical circuit breaker

Main
Range of product Circuit breaker name Device short name Circuit breaker application Poles description Protected poles description Network type Breaking capacity code Suitability for isolation Utilisation category Trip unit name Trip unit technology Trip unit rating EasyPact MVS MVS08N MVS08N Standard 3P 3P 3d AC N - 50 kA Yes conforming to IEC 60947-2 ET6G Micro-processor based 800 A (-5...70 C)
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

Category B

Complementary
Network frequency Control type Mounting mode Mounting support Connection position Location of connection [In] rated current [Ui] rated insulation voltage [Uimp] rated impulse withstand voltage [Ue] rated operational voltage Circuit breaker CT rating Breaking capacity [Ics] rated service breaking capacity Mechanical durability Electrical durability 50/60 Hz Electrically operated Fixed Base plate Rail Horizontal Vertical Rear 800 A (40 C) 1000 V AC 50/60 Hz conforming to IEC 60947-2 12 kV conforming to IEC 60947-2 690 V AC 50/60 Hz conforming to IEC 60947-2 800 A 50 kA (Icu) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2 20000 cycles (with maintenance) conforming to IEC 60947-2 4000 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conforming to IEC 60947-2 6000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conforming to IEC 60947-2 115 mm (without spreader) Yes 105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 LSIG Earth fault Instantaneous short-circuit protection Overload protection (long time) Short time short-circuit protection

Connection pitch Contact position indicator [Icm] rated short-circuit making capacity [Icw] rated short-time withstand current

Trip unit protection functions Protection type

Aug 15, 2013

Fault indication

Overload Short-circuit Internal fault Earth fault Adjustable 9 settings 0.4...1 x In Adjustable 9 settings 0.5...24 s (6 x Ir) Adjustable 9 settings 1.5...10 x Ir Adjustable 5 settings 100...400 ms Adjustable 9 settings 2...15 x In Off Adjustable 9 settings Adjustable 5 settings 100...400 ms 0.2...1 x In With 400/2000 A 25 ms < 70 ms 352 mm 422 mm 297 mm 40 kg

Long time pick-up adjstment type Ir Long time pick-up adjustment range Long time delay adjustment type [Tr] long-time delay adjustment Short-time pick-up adjustment type Isd [Isd] short-time pick-up adjustment range Short-time delay adjustment type [Tsd] short-time delay adjustment range Instantaneous pick-up adjustment type Ii Instantaneous pick-up adjustment range Ground-fault pick-up adjustment type Ground-fault time delay adjustment type -tg [Tg] ground-fault time delay adjustment range [Ig] ground-fault pick-up adjustment range Zone selective interlocking ZSI Current sensor rating range Maximum breaking time Closing response time Height Width Depth Product weight

Environment
Standards Product certifications IEC 60947-2 CCC GOST IEC CCS IP40 4 conforming to IEC 60664-1 -5...70 C -25...85 C (with control unit) -40...85 C (without control unit)

IP degree of protection Pollution degree Ambient air temperature for operation Ambient air temperature for storage