Sei sulla pagina 1di 12

AJUSTES PROPUESTOS RELE DE PROTECCION PROYECTADO S.E.

COL

UBICACIN RELE DE PROTECCION Parmetros de Ajuste GLOBAL SETTINGS CT RATIO Line CT Primary Line CT Sec E/Gnd CT Primary E/Gnd CT Sec PROTECTION SETTINGS Phase O/C [50/51] I> ? I> Threshold

I> Delay Type tI> I> TMS I> Time Dial Reset Delay Type I> DMT tReset I> I>> ? I>> Threshold

I>> Delay Type tI>> I>> TMS I>> Time Dial Reset Delay Type I>> DMT tReset I>> I>>> ? I>>> Threshold tI>>> E/Gnd Fault [50N/51N] IN> ? IN> Threshold

IN> Delay Type tIN> IN> TMS IN> Time Dial Reset Delay Type IN> DMT tReset IN>

IN>> ? IN>> Threshold tIN>>

AJUSTES PROPUESTOS RELE DE PROTECCION PROYECTADO S.E. COLPEX

Descripcin

Phase CT input's primary current rating Phase CT input's secondary current rating Earth fault CT input's primary current rating Earth fault CT input's secondary current rating

N SETTINGS 0/51] Setting for Disable or enable of protection element Pick-up setting for first stage of the O/C element

Tripping characteristic for the first stage O/C element Time-delay for the DT setting if selected for first stage element Time multiplier setting to adjust the operating time of IEC/UK IDMT characteristic Time multiplier setting to adjust the operating time of IEEE/US IDMT characteristic Setting to determine the type of reset/release characteristic of the IEEE/US curves Setting that determines the reset/release time for definite time reset characteristic Setting for Disable or enable of protection element Pick-up setting for second stage of the O/C element

Tripping characteristic for the second stage O/C element Time-delay for the DT setting if selected for second stage element Time multiplier setting to adjust the operating time of IEC/UK IDMT characteristic Time multiplier setting to adjust the operating time of IEEE/US IDMT characteristic Setting to determine the type of reset/release characteristic of the IEEE/US curves Setting that determines the reset/release time for definite time reset characteristic Setting for Disable or enable of protection element Pick-up setting for this stage of the O/C element Time-delay for the DT setting if selected for this stage element Setting for Disable or enable of protection element Pick-up setting for first stage of the O/C element

50N/51N]

Tripping characteristic for the first stage O/C element Time-delay for the DT setting if selected for first stage element Time multiplier setting to adjust the operating time of IEC/UK IDMT characteristic Time multiplier setting to adjust the operating time of IEEE/US IDMT characteristic Setting to determine the type of reset/release characteristic of the IEEE/US curves Setting that determines the reset/release time for definite time reset characteristic

Setting for Disable or enable of protection element Pick-up setting for second stage of the O/C element Time-delay for the DT setting if selected for this stage element

UESTOS ECTADO S.E. COLPEX


Pag. 1 de 1 ACOMETIDA EN 10 KV S.E. COLPEX MICOM P115 Ajuste Secundario

Rango de ajuste

Unidad

5-30000 n/a 1-30000 n/a

n/a n/a n/a n/a

100 5 50 1

Disabled, Enable Trip, Enable Alarm 0.2 - 4.0 (0.01) DMT, IEC (SI, VI, EI), UK (LTI, STI, RC), RI, (IEEE MI, VI, EI, US (CO2, CO8) 0.02 - 200 (0.01) 0.02 - 1.6 (0.01) 0.02 - 200 (0.01) DMT or IDMT 0.0 - 200 (0.01) Disabled, Enable Trip, Enable Alarm 0.2 - 4.0 (0.01) DMT, IEC (SI, VI, EI), UK (LTI, STI, RC), RI, (IEEE MI, VI, EI, US (CO2, CO8) 0.02 - 200 (0.01) 0.02 - 1.6 (0.01) 0.02 - 200 (0.01) DMT or IDMT 0.0 - 200 (0.01) Disabled, Enable Trip, Enable Alarm 0.2 - 40.0 (0.1) 0.0 - 200 (0.01) Disabled, Enable Trip, Enable Alarm 0.05 - 1.0 (0.01) DMT, IEC (SI, VI, EI), UK (LTI, STI, RC), RI, (IEEE MI, VI, EI, US (CO2, CO8) 0.02 - 200 (0.01) 0.02 - 1.6 (0.01) 0.02 - 200 (0.01) DMT or IDMT 0.0 - 200 (0.01)

n/a x In

Enabled 1

n/a s n/a n/a n/a s n/a x In

DMT 0.1 --DMT 0 Disabled --

n/a s n/a n/a n/a s n/a x In s n/a x Ien

------Disabled --Enabled 0.05

n/a s n/a n/a n/a s

DMT 0.5 --DMT 0

Disabled, Enable Trip, Enable Alarm 0.05 - 10.0 (0.1) 0.0 - 200 (0.01)

n/a x In s

Disabled ---

AJUSTES PROPUESTOS RELE DE PROTECCION PROYECTADO S.E. COL

UBICACIN RELE DE PROTECCION Parmetros de Ajuste GLOBAL SETTINGS CT RATIO Line CT Primary Line CT Sec E/Gnd CT Primary E/Gnd CT Sec PROTECTION SETTINGS Phase O/C [50/51] I> ? I> Threshold I> Delay Type tI> I> TMS K Reset Delay Type I> DMT tReset I> I> >> >>> Interlock I>> ? I>> Threshold I>> Delay Type tI>> I>> TMS K Reset Delay Type I>> DMT tReset I>> I>>> ? I>>> Sample I>>> Threshold tI>>> E/Gnd Fault [50N/51N] Ie> ? Ie> Threshold Ie> Delay Type tIe> Ie> TMS K Reset Delay Type Ie>

DMT tReset Ie> Ie> >> >>> Interlock Ie>> ? Ie>> Threshold Ie>> Delay Type tIe>> Ie>> TMS K Reset Delay Type Ie>> DMT tReset Ie>> Ie>> ? I>>> Sample Ie>> Threshold tIe>> Ie>>>> ? Ie>>>> Threshold Ie>>>> Delay Type tIe>>>> Ie>>>> TMS K Reset Delay Type Ie>>>> DMT tReset Ie>>>> AUTOMAT. CTRL Blocking Inrush Blocking Inrush Inr. Harmonic 2 Ratio T Inrush reset Blocking Inrush Function

AJUSTES PROPUESTOS RELE DE PROTECCION PROYECTADO S.E. COLPEX

Descripcin

Phase CT input's primary current rating Phase CT input's secondary current rating Earth fault CT input's primary current rating Earth fault CT input's secondary current rating

N SETTINGS 0/51] Setting for Disable or enable of protection element Pick-up setting for first stage of the O/C element Tripping characteristic for the first stage O/C element Time-delay for the DT setting if selected for first stage element Time multiplier setting to adjust the operating time of IEC/IEEE IDMT characteristic Time multiplier setting to adjust the operating time of RI characteristic Setting to determine the type of reset/release characteristic of the IEEE/US curves Setting that determines the reset/release time for definite time reset characteristic Interlock of first threshold by the second and third thresholds Setting for Disable or enable of protection element Pick-up setting for second stage of the O/C element Tripping characteristic for the second stage O/C element Time-delay for the DT setting if selected for second stage element Time multiplier setting to adjust the operating time of IEC/IEEE IDMT characteristic Time multiplier setting to adjust the operating time of RI characteristic Setting to determine the type of reset/release characteristic of the IEEE/US curves Setting that determines the reset/release time for definite time reset characteristic Setting for Disable or enable of protection element Select the mode of operation of the third threshold Pick-up setting for this stage of the O/C element Time-delay for the DT setting if selected for this stage element Setting for Disable or enable of protection element Pick-up setting for first stage of the O/C element Tripping characteristic for the first stage O/C element Time-delay for the DT setting if selected for first stage element Time multiplier setting to adjust the operating time of IEC/IEEE IDMT characteristic Time multiplier setting to adjust the operating time of RI characteristic Time multiplier setting to adjust the operating time of RXIDG characteristic Setting to determine the type of reset/release characteristic of the IEEE/US curves

50N/51N]

Setting that determines the reset/release time for definite time reset characteristic Interlock of first threshold by the second and third thresholds Setting for Disable or enable of protection element Pick-up setting for second stage of the O/C element Tripping characteristic for the second stage O/C element Time-delay for the DT setting if selected for second stage element Time multiplier setting to adjust the operating time of IEC/IEEE IDMT characteristic Time multiplier setting to adjust the operating time of RI characteristic Time multiplier setting to adjust the operating time of RXIDG characteristic Setting to determine the type of reset/release characteristic of the IEEE/US curves Setting that determines the reset/release time for definite time reset characteristic Setting for Disable or enable of protection element Select the mode of operation of the third threshold Pick-up setting for third stage of the O/C element Time-delay for the DT setting if selected for this stage element Setting for Disable or enable of derived earth overcurrent threshold Pick-up setting for derived earth overcurrent threshold Tripping characteristic for the derived earth overcurrent threshold Time-delay for the DT setting if selected for derived earth overcurrent threshold Time multiplier setting to adjust the operating time of IEC/IEEE IDMT characteristic Time multiplier setting to adjust the operating time of RI characteristic Time multiplier setting to adjust the operating time of RXIDG characteristic Setting to determine the type of reset/release characteristic of the IEEE/US curves Setting that determines the reset/release time for definite time reset characteristic

TRL sh The crossing of the Harmonic H2 ratio threshold on any phase activates the Inrush Blocking Logic function instantaneously Set the value for the 2nd harmonic threshold ratio calculated as a percentage of the fundamental component Set the value for the Inrush tReset time Enables or disables Inrush blocking for the function

UESTOS ECTADO S.E. COLPEX


Pag. 1 de 1 ACOMETIDA EN 10 KV S.E. COLPEX MICOM P123 Ajuste Secundario

Rango de ajuste

Unidad

5-30000 n/a 1-30000 n/a

n/a n/a n/a n/a

100 5 100 1

Yes, No 0.1 - 25 (0.01) DMT, IEC (SI, VI, EI), RI, IEEE (MI, VI, EI), US (CO2, CO8) 0.04 - 150 (0.01) 0.025 - 1.5 (0.001) 0.1 - 10 (0.1) DMT or IDMT 0.0 - 600 (0.01) Yes, No Yes, No 0.1 - 40 (0.01) DMT, IEC (SI, VI, EI), RI, IEEE (MI, VI, EI), US (CO2, CO8) 0.04 - 150 (0.01) 0.025 - 1.5 (0.001) 0.1 - 10 (0.1) DMT or IDMT 0.0 - 600 (0.01) Yes, No Current sample base (Yes) or Discrete Fourier Transformation (No) 0.5 - 40.0 (0.01) 0.0 - 150 (0.01) Yes, No 0.01 - 8 (0.01) DMT, IEC (SI, VI, EI), RI, RXIDG (IEEE MI, VI, EI), US (CO2, CO8) 0.00 - 150 (0.01) 0.025 - 1.5 (0.001) 0.1 - 10 (0.1) 0.3 - 1 (0.1) DMT or IDMT

n/a x In n/a s n/a n/a n/a s s n/a x In n/a s n/a n/a n/a s n/a n/a x In s n/a x Ien n/a s n/a n/a n/a n/a

YES 1 DMT 0.1 --DMT 0 No No -------No ---Yes 0.05 DMT 0.5 ---DMT

0.0 - 600 (0.01) Yes, No Yes, No 0.01 - 8 (0.01) DMT, IEC (SI, VI, EI), RI, RXIDG (IEEE MI, VI, EI), US (CO2, CO8) 0.00 - 150 (0.01) 0.025 - 1.5 (0.001) 0.1 - 10 (0.1) 0.3 - 1 (0.1) DMT or IDMT 0.0 - 600 (0.01) Yes, No Current sample base (Yes) or Discrete Fourier Transformation (No) 0.01 - 8 (0.01) 0.0 - 150 (0.01) Yes, No 0.01 - 8 (0.01) DMT, IEC (SI, VI, EI), RI, RXIDG (IEEE MI, VI, EI), US (CO2, CO8) 0.00 - 150 (0.01) 0.025 - 1.5 (0.001) 0.1 - 10 (0.1) 0.3 - 1 (0.1) DMT or IDMT 0.0 - 600 (0.01)

s s n/a x Ien n/a s n/a n/a n/a n/a s n/a n/a x In s n/a x Ien n/a s n/a n/a n/a n/a s

0 No No --------No ---No ---------

Yes, No 10 - 35 (0.1) 0.00 - 2 (0.01) Yes, No

n/a % s n/a

Yes 15 0.1 Yes

Potrebbero piacerti anche