Resistance temperature sensors
Instructions for ISA Forms $20.13a and 20.13
Refer to Scientific Apparatus Manufacturers Association (SAMA) Tentative Standard on Resistance,
RC 5-10-1956.
1) Complete assembler includes head, element, and well; as shown in sketch.
5) Give size and pipe schedule of nipple. Check if union is required
7) The ice point resistance in ohms usually defines the resistance vs. temperature curve. Ifnot,
provide additional data as an attachment.
8) Give maximum range over which the elements will be used
9) Specify sealing of leads.
11) This thread is on the element termination, not the wel
12) Itisnecessary to specify the number of wires, depending on the compensation required. The
other items refer to the element termination.
14) A built-up well has a welded tip and connection
16) Internal thread of flange if well lange is threaded
Instructions for the tabulation:
17)
Process Connection is the connection on the element or welll which is connected to the pipe
orvessel. Well dimensions are illustrated in the sketch. Itisnot necessary to specify Element
Length if well dimensions are already given. Single or Dual elements are assumed to be
within the same sheath. Refer to Notes by number or letter and explain in the space at the
bottom of the form,
TSA-S20-1981%6