Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Version 4.4
Carrier Corporation 6304 Carrier Parkway P.O. Box 4808 Bldg TR-4, Room 400A E. Syracuse, NY 13057 Phone 800.253.1794 Fax 315.432.6844 e-mail: software.systems@carrier.utc.com ALL RIGHTS RESERVED. No part of this work covered by the copyright hereon may be reproduced or used in any form or by any means graphic, electronic, or mechanical, including photocopying, recording, taping, Web distribution or information storage and retrieval systemswithout the written permission of Carrier Corporation.
For permission to use material from this text, contact us by Tel (800) 253-1794 Fax (315)432.3871 e-Mail software.systems@carrier.utc.com
Table of Contents
EARNING CEU CREDITS FOR SUCCESSFUL COMPLETION OF THIS TRAINING ...........................................4 COURSE LEANING OUTCOMES .................................................................................................................4 WELCOME TO HAP 4.4 ............................................................................................................................5 WORKBOOK ORGANIZATION ...................................................................................................................5 PROJECT DATA MANAGEMENT ................................................................................................................5 PROJECT DEFINITION AND OUTLINE ........................................................................................................9 WORKSHOP # 1 - PROJECT CREATION AND WEATHER DATA .................................................................16 WORKSHOP # 2 EDITING SCHEDULES ..................................................................................................24 WORKSHOP # 3 WING D AIR SYSTEM INPUT 4PFCU..........................................................................32 WORKSHOP # 4 WING D AIR SYSTEM INPUTPACKAGED ROOFTOP UNIT ..........................................47 WORKSHOP # 5 MODELING CHILLERS, BOILERS, & TOWERS ..............................................................68 WORKSHOP # 6 FINALIZING CHILLER AND BOILER PLANTS ................................................................94 WORKSHOP # 7 DEFINING AND SIMULATING BUILDINGS .................................................................119 WINDOWS SOFTWARE BASICS .............................................................................................................164 USING HAP 4.4 FOR SYSTEM DESIGN LOADS ......................................................................................169 APPENDIX C .....................................................................................................................................176 THE SIZING DILEMMA..........................................................................................................................176 WHICH SIZING METHOD TO USE? .......................................................................................................177 PUTTING LOAD CALCULATION METHODS IN PERSPECTIVE..................................................................179 THE BENEFITS OF THE TRANSFER FUNCTION / HEAT EXTRACTION LOAD CALCULATION METHOD ..........................................................................................................................................182 DIAGNOSING THE THERMOS BOTTLE EFFECT...................................................................................183 USING OUTDOOR VENTILATION CONTROL OPTIONS ...........................................................................188 DEMAND CONTROLLED VENTILATION CONTROL ................................................................................189 UNDERSTANDING ZONE LOADS AND ZONE CONDITIONING .................................................................192 PITFALLS OF ECONOMIZER OPERATION ...............................................................................................195 DIFFERENCES BETWEEN PEAK COIL LOAD CFM, MAX BLOCK CFM, SUM OF PEAK ZONE CFM .......198 SELECTING EQUIPMENT WHEN COIL CFM (L/S) DIFFER .....................................................................201 HOW VENTILATION LOADS ARE CALCULATED IN HAP .......................................................................202 SYSTEM BASED DESIGN LOAD CALCULATIONS ...................................................................................204 APPENDIX D.....................................................................................................................................212 NOTES..................................................................................................................................................224
For Technical Support Please contact Software Systems Network at 1.800.253.1794 or e-mail: software.systems@carrier.utc.com For additional information and Program Downloads visit us at: www.commercial.carrier.com
This Symbol is used throughout this manual and represents required learning outcomes. Each student is expected to comprehend the subject content and successfully demonstrate competency in these areas.
his manual was created for the engineers and designers using the Carrier Hourly Analysis Program v4.4 for calculating commercial building cooling and heating loads and energy simulation. This manual is a companion to the hands-on training for the Hourly Analysis Program Basic Training course facilitated by Carrier Software Systems Network. This manual includes all class exercises and workflow tips. The goal of this manual is to make each student comfortable and familiar with the input routines and the calculated results of the HAP design loads and energy simulation.
Workbook Organization
The intent of the sections in this manual is to follow the logical process of the hands-on workshops and workflow. We cover the common process and special features of the Carrier HAP program. We arranged the topics of discussion in the same order as our hands-on training classes. The first two sections address the program installation, basic system requirements and general housekeeping. We also highlight and discuss the program interface and functionality. The remaining sections follow the logical path of the programs modules including detailed discussions and examples of the workflow process used to create a complete HAP data set. This includes detailed discussions of the input forms, editing, document outputs and more. This manual also includes three appendixes. Appendix A consists of detailed schematics of all air system types in the HAP program. Appendix B, includes a discussion on basic HAP and Windows program functions Appendix C includes detailed discussions of common questions about the HAP program. Appendix D includes several white papers discussing the advantages of the HAP program.
Edit descriptive data for the project, such as the project name, using the Properties option on the Project Menu Archive project data for safe keeping using the Archive option on the Project Menu Retrieve data that you earlier archived using the Retrieve option on the Project Menu Convert data from a previous version of HAP using one of the Convert HAP Data options on the Project Menu Import data from another project into the current project using the Import Data option on the Project Menu
How Project Data is Stored. When a new project is saved for the first time, you designate the folder that will hold the project files (either by accepting the default folder \E20-II\Projects\ProjectName or by specifying a folder yourself). This folder is the permanent storage location of project data. When you open the project to work with its data, temporary copies of the projects data files are made. As you enter data, make changes and perform calculations, all this data is stored in the temporary copy of the data files. Only when you use the Save option on the Project Menu, are the changes you have made copied to permanent storage. Therefore, if you ever need to undo changes you have made to a project, simply re-open the project without saving the changes you have made. When you re-open the project, the changes stored in the temporary copy of the data files are discarded, and data from your last project/save is restored. Recommended Project Management Practices. Project data represents an important investment of your time and effort. And, as the saying goes, time is money. Therefore, it is important to safeguard your investment in project data. We recommend adopting the following practices when working with projects: Create a separate project for each job you work on. It is usually more efficient to keep data for separate jobs in separate projects. It is also safer to store data in smaller, focused units. If you keep data for all jobs in a single project, and this project becomes damaged, your data loss will be greater than if you keep data for separate jobs in separate projects. Use a descriptive name for the project so you can quickly recognize what it contains, both now and when you need to refer to the project in the future. Because the selection list for projects is arranged alphabetically, it is useful to use a consistent naming convention. Many firms begin the project name with their internal project number followed by descriptive text (e.g., P2002-47 Lincoln School). Save early and often. While entering data, changing data and generating reports, save the project periodically. This practice is useful in the event that you make a mistake and need to undo changes. If the last time you saved the project was 15 minutes ago, undoing your mistake will only cause you to lose 15 minutes of work. On the other hand, if the last time you saved the data was 4 hours ago, undoing a mistake may cause you to lose 4 hours worth of work. Archive your data periodically for safekeeping. These days, data on hard disks is relatively safe. However, it is still possible for hard disk drives to become damaged, or for files on the hard disk to be damaged or erased. Therefore, it is a good practice to periodically archive your project data. Data can be archived to a separate location on
Copyright Carrier Corp. 2008
your hard disk, to a different hard disk drive or to removable media such as a compact disk, zip drive or floppy disks. For example, if you archive data for a large project at the end of each day and your hard disk drive fails, at most you will have lost one days worth of work. On the other hand, if data for the same large project was never archived and your hard disk drive fails, all the project data would be lost.
This topic describes enhancements in HAP v4.40. It is intended for readers who have upgraded from HAP v4.34 to v4.40. Most of the enhancements made in v4.40 relate to two major themes:
1. Theme 1 Using HAP for LEED Energy and Atmosphere Credit 1 Analysis.
HAP was modified to streamline steps in performing a LEED EA Credit 1 analysis making it faster and easier to perform. Specific modifications include:
LEED NC 2.2 EA Credit 1 Summary Report. This new report provides data found in sections 1.1, 1.3, 1.5, 1.8.1, 1.8.1b, 1.8.2 and 1.8.2b of the LEED NC 2.2 EA Credit 1 on-line submittal template and imitates the format of the submittal template. This report eliminates the tedious work of assembling submittal template report data from multiple HAP reports. Duplicate Building with Spaces and HVAC Eqpt option. This new option automatically duplicates a HAP building and all the systems, plants, spaces, chillers, cooling towers and boilers it contains in one-step. This option is useful when starting definition of the Baseline building based on a duplicate of data for the Proposed Building. More importantly, it facilitates placing Proposed and Baseline buildings in a single project so the Credit 1 Summary Report can be generated. Perform LEED (90.1 PRM) Rotations option. This new option automatically makes three copies of the "Baseline 0 Degree" building and all of its systems, plants, spaces, chillers, cooling towers and boilers. In the three copies, spaces are rotated 90 deg, 180 deg and 270 deg respectively. This provides a rapid way to generate the three rotations of the Baseline building. It also makes it efficient to place all Proposed and Baseline buildings in a single project so the Credit 1 Summary Report can be generated. Autosizing for DX and Plant Equipment. This feature allows you to specify that equipment gross capacity be automatically determined as peak load plus a specified percent oversizing factor. For example, peak cooling load + 15%. Input DX Equipment Performance as EER or COP. This feature allows you to specify DX equipment as EER for cooling or COP for heating. The software then automatically decompiles the EER or COP to determine compressor kW for use in the simulation. All Terminal Units Use Same Settings. When defining equipment performance for DX fan coils, WSHP, GWSHP or GSHP equipment, this new option allows you to specify one set of EER or COP performance values to apply to all zone terminal units in a system. This saves you from having to define compressor kW for each zone fan coil or heat pump separately. Baseline Fan kW Calculated per ASHRAE 90.1 Appendix G section G3.1.2.9. When defining air systems for a Baseline building, you have the option of defining supply fan performance be automatically calculated per the equation in section G3.1.2.9. This equation sets the total fan kW for the system. Fan Performance Defined as W/CFM. When specifying fan performance for fan powered mixing box terminals, performance can be input as W/CFM (W/L/s). The program will then automatically derive the fan watts from the design CFM for the box. 7
Copyright Carrier Corp. 2008
ASHRAE 90.1 Appendix G VAV Fan Part-Load Curve. VAV fan part-load performance can be modeled using the VAV fan curve found in Appendix G Table G3.1.3.15. Water Flow Rate Inputs as gpm/Ton or Delta-T. New options allow water flow rates to be defined in terms of gpm/Ton (L/s/kW) or delta-T in addition to gpm. Water Pump Performance as W/gpm or kW. New options allow water pump performance to be defined in terms of W/gpm (W/L/s) or kW in addition to the existing specification of pump head.
history, HAP has focused on system design and energy analysis tasks typically occurring in the detailed design phase of a project. These tasks involve detailed definition of the building envelope, layout and HVAC equipment, and require time-consuming data entry to create a suitably detailed building model. When performing energy analysis in the preliminary or schematic design phase of a project, the objective is to quickly and roughly compare a large set of design alternatives to identify the most promising designs. This work typically does not require as detailed a definition of the building and its HVAC equipment. To make HAP more efficient for performing these types of analyses, new Wizard features have been added to allow users to rapidly generate input data for an analysis. This work builds on the Building Wizard feature offered in HAP v4.3. Specific enhancements include:
New Wizards Menu. Provides options for running Building Wizard or Equipment Wizard alone, and for running an integrated session linking Building and Equipment Wizards together. Building Wizard Option. The Building Wizard option on the Wizards Menu can be used to rapidly generate space data for a building. The Building Wizard has been revised and upgraded for HAP v4.4. Equipment Wizard Option. The Equipment Wizard option on the Wizards Menu can be used to rapidly generate HVAC equipment for a building - specifically all of the air systems, plants, chillers, cooling towers and boilers, as applicable. Full Wizard Session Option. The "Full Wizard Session" option on the Wizards Menu allows you to run the Building Wizard and Equipment Wizard in tandem. In as single Wizard session you can generate space data and data for multiple equipment designs. This essentially creates 95% of the input data for an energy cost study in minutes rather than hours or days. Only weather and utility rate data must be added before running calculations.
10
11
12
13
14
Workshop # 1 Inputs
15
16
WEATHER DATA Review the already configured design weather data to insure that you are using default ASHRAE design weather data for St. Louis, MO. In the simulation input form under the simulation tab, configure energy simulation data for the same city. Select simulation weather by left clicking on the Change City button and navigating to the USA_MISSOURI_ST. LOUIS.TMY2.HW1 file. This action will link the TMY-2 simulation weather data to the project. The first day of the year selection, (use the default day Wednesday) determines where the weekends occur. The next step is to add the following dates to the Holidays List by double left clicking the date on the calendar: January 1 April 18 May 26 July 4 September 1 November 27, 28 December 25, 26,29,30,31
17
Weather reports are available by highlighting weather in the left tree then left clicking on Reports and choosing Print/View Input Data or
right click on < Weather Properties> and choose Print/View Input Data. Select the weather reports shown below. Design weather data is used for peak heating and cooling load calculations and equipment sizing purposes. HAP uses 8760 hourly Simulation weather data to simulate building energy consumption and calculate an annual operating cost.
18
Deg. Deg. ft F F F F F
BTU/(hr-ft-F) hours
19
Month January February March April May June July August September October November December
20
21
Friday, August 1
Hour Dry-Bulb ( F ) 76.3 75.0 72.9 72.0 70.2 68.7 66.0 65.5 66.9 70.0 73.0 75.9 77.0 80.1 80.1 81.0 82.0 82.0 81.0 80.1 78.1 75.9 73.9 72.0 Dry-Bulb ( F ) 71.1 70.0 70.0 68.0 68.0 66.9 66.9 68.0 70.0 72.0 78.1 79.0 82.0 84.0 86.0 87.1 87.1 86.0 87.1 84.9 82.9 81.0 80.1 78.1 Wet-Bulb ( F ) 66.4 65.6 64.4 63.8 62.6 61.7 60.4 60.4 60.5 61.6 63.2 63.1 62.4 64.5 63.5 63.8 63.8 64.7 64.8 64.1 63.4 62.7 62.0 61.3 Wet-Bulb ( F ) 61.0 61.1 60.0 61.0 59.9 60.0 60.6 61.0 61.6 64.1 65.5 64.1 66.1 67.4 69.0 70.0 70.0 69.7 70.0 69.8 69.3 69.3 69.0 69.0 Beam Solar on Horiz. ( BTU/(hr-ft) ) 0.0 0.0 0.0 0.0 0.0 0.0 0.5 23.9 83.7 111.6 166.2 207.4 189.7 195.1 153.4 161.0 126.3 102.2 44.0 5.6 0.0 0.0 0.0 0.0 Beam Solar on Horiz. ( BTU/(hr-ft) ) 0.0 0.0 0.0 0.0 0.0 0.0 1.0 25.2 28.8 33.6 19.9 203.7 257.3 175.6 127.7 136.7 134.9 74.1 52.8 13.3 0.0 0.0 0.0 0.0 Total Solar on Horiz. ( BTU/(hr-ft) ) 0.0 0.0 0.0 0.0 0.0 0.0 11.0 52.7 120.2 169.9 217.2 261.6 260.7 274.3 221.6 227.6 186.8 139.3 71.9 18.6 0.6 0.0 0.0 0.0 Total Solar on Horiz. ( BTU/(hr-ft) ) 0.0 0.0 0.0 0.0 0.0 0.0 9.6 50.2 84.0 114.4 97.2 268.0 282.3 253.3 234.2 212.1 180.2 121.0 74.7 22.5 1.0 0.0 0.0 0.0
0000 0100 0200 0300 0400 0500 0600 0700 0800 0900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
Saturday, August 2
Hour
0000 0100 0200 0300 0400 0500 0600 0700 0800 0900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
22
Workshop # 2 Inputs
23
24
PEOPLE - CLASSROOMS Profile #3 Energy Weekday Hours 00-07: 00% Hours 08-11: 100% Hour 12: 0% Hours 13-15: 100% Hour 16: 40% Hour 17: 10% Hours 18-23: 00% Profile #4 Energy Weekend Hours 00-23: 00% On the assignments tab, assign Profile #3 to day types Monday Thru Friday in all months except July. Assign Profile #2 to day types Monday through Friday for July only. Assign Profile #4 to day types Saturday, Sunday, and Holiday for all twelve (12) months.
25
PEOPLE CORRIDORS Profile #3 Energy Weekday Hours 00-06: 00% Hours 07-16: 50% Hours 17-23: 00% Profile #4 Energy Weekend Hours 00-23: 00% On the assignments tab, assign Profile #3 to day types Monday Thru Friday in all moths except July. Assign existing Profile #2 to day types Monday thru Friday for the month of July only. Assign Profile #4 to day types Saturday, Sunday, and Holiday for all twelve (12) months.
Profile #3 Energy Weekday Hours 00-05: Unoccupied Hours 06-17: Occupied Hours 18-23: Unoccupied Profile #4 Energy Weekends = Unoccupied 00-23 Apply Profile #2 to the month of July only
26
02 10
03 10
04 10
05 10
06 10
07 10
16 30
17 10
18 10
19 10
20 10
21 10
22 10
23 10
2:Summer Shutdown De Hour 00 01 02 Value 0 0 0 3:Energy Weekday Hour 00 01 Value 10 10 4:Energy Weekend Hour 00 01 Value 10 10
03 0
04 0
05 0
06 0
07 0
08 60
09 60
10 60
11 60
12 60
13 60
14 60
15 60
16 60
17 0
18 0
19 0
20 0
21 0
22 0
23 0
02 10
03 10
04 10
05 10
06 10
07 50
12 0
16 50
17 20
18 10
19 10
20 10
21 10
22 10
23 10
02 10
03 10
04 10
05 10
06 10
07 10
08 10
09 10
10 10
11 10
12 10
13 10
14 10
15 10
16 10
17 10
18 10
19 10
20 10
21 10
22 10
23 10
Assignments: Design Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday Jan 1 3 3 3 3 3 4 4 4 Feb 1 3 3 3 3 3 4 4 4 Mar 1 3 3 3 3 3 4 4 4 Apr 1 3 3 3 3 3 4 4 4 May 1 3 3 3 3 3 4 4 4 Jun 1 3 3 3 3 3 4 4 4 Jul 2 2 2 2 2 2 4 4 4 Aug 1 3 3 3 3 3 4 4 4 Sep 1 3 3 3 3 3 4 4 4 Oct 1 3 3 3 3 3 4 4 4 Nov 1 3 3 3 3 3 4 4 4 Dec 1 3 3 3 3 3 4 4 4
27
02 0
03 0
04 0
05 0
06 0
07 5
16 40
17 10
18 0
19 0
20 0
21 0
22 0
23 0
2:Summer Shutdown De Hour 00 01 02 Value 0 0 0 3:Energy Weekday Hour 00 01 Value 0 0 4:Energy Weekend Hour 00 01 Value 0 0
03 0
04 0
05 0
06 0
07 0
08 40
09 40
10 40
11 40
12 40
13 40
14 40
15 40
16 40
17 0
18 0
19 0
20 0
21 0
22 0
23 0
02 0
03 0
04 0
05 0
06 0
07 0
12 0
16 40
17 10
18 0
19 0
20 0
21 0
22 0
23 0
02 0
03 0
04 0
05 0
06 0
07 0
08 0
09 0
10 0
11 0
12 0
13 0
14 0
15 0
16 0
17 0
18 0
19 0
20 0
21 0
22 0
23 0
Assignments: Design Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday Jan 1 3 3 3 3 3 4 4 4 Feb 1 3 3 3 3 3 4 4 4 Mar 1 3 3 3 3 3 4 4 4 Apr 1 3 3 3 3 3 4 4 4 May 1 3 3 3 3 3 4 4 4 Jun 1 3 3 3 3 3 4 4 4 Jul 2 2 2 2 2 2 4 4 4 Aug 1 3 3 3 3 3 4 4 4 Sep 1 3 3 3 3 3 4 4 4 Oct 1 3 3 3 3 3 4 4 4 Nov 1 3 3 3 3 3 4 4 4 Dec 1 3 3 3 3 3 4 4 4
28
02 U
03 U
04 U
05 U
06 O
07 O
08 O
09 O
10 O
11 O
12 O
13 O
14 O
15 O
16 O
17 O
18 U
19 U
20 U
21 U
22 U
23 U
03 U
04 U
05 U
06 O
07 O
08 O
09 O
10 O
11 O
12 O
13 O
14 O
15 O
16 O
17 U
18 U
19 U
20 U
21 U
22 U
23 U
02 U
03 U
04 U
05 U
06 O
07 O
08 O
09 O
10 O
11 O
12 O
13 O
14 O
15 O
16 O
17 O
18 U
19 U
20 U
21 U
22 U
23 U
03 U
04 U
05 U
06 U
07 U
08 U
09 U
10 U
11 U
12 U
13 U
14 U
15 U
16 U
17 U
18 U
19 U
20 U
21 U
22 U
23 U
O = Occupied; U = Unoccupied Assignments: Design Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday Jan 1 3 3 3 3 3 4 4 4 Feb 1 3 3 3 3 3 4 4 4 Mar 1 3 3 3 3 3 4 4 4 Apr 1 3 3 3 3 3 4 4 4 May 1 3 3 3 3 3 4 4 4 Jun 1 3 3 3 3 3 4 4 4 Jul 2 2 2 2 2 2 4 4 4 Aug 1 3 3 3 3 3 4 4 4 Sep 1 3 3 3 3 3 4 4 4 Oct 1 3 3 3 3 3 4 4 4 Nov 1 3 3 3 3 3 4 4 4 Dec 1 3 3 3 3 3 4 4 4
29
30
Workshop # 3 Inputs
31
32
Ventilation Fan Data: Fan Type ................................................................................ Forward Curved Configuration ..................................................................................... Draw-thru Fan Performance ........................................................................................ 2.00 in wg Overall Efficiency ........................................................................................... 54 % % Airflow % kW % Airflow % kW 100 100 40 46 90 91 30 40 80 81 20 33 70 72 10 27 60 61 0 21 50 54
Duct System Data: Return Duct or Plenum Data: Return Air Via ............................................................................ Ducted Return 3. Zone Components: Space Assignments: Zone 1: Zone 1 D100-Computer Closet Zone 2: Zone 2 D101-Classroom Zone 3: Zone 3
x1 x1
33
D102-Classroom Zone 4: Zone 4 D103-Classroom Zone 5: Zone 5 D104-Classroom Zone 6: Zone 6 D105-South Vestibule Zone 7: Zone 7 D106-Classroom Zone 8: Zone 8 D107-Classroom Zone 9: Zone 9 D108-Music Auditorium Zone 10: Zone 10 D109-Music Practice Zone 11: Zone 11 D110-Music Files Zone 12: Zone 12 D111-Music Office Zone 13: Zone 13 D112-West Vestibule Zone 14: Zone 14 D113-Corridor Zone 15: Zone 15 D114-Corridor
x1 x1 x1 x1 x1 x1 x1 x1 x1 x1 x1 x1 x1
Thermostats and Zone Data: Zone .............................................................................................................. All Cooling T-stat: Occ. .................................................................................... 72.0 Cooling T-stat: Unocc. ................................................................................ 85.0 Heating T-stat: Occ. .................................................................................... 70.0 Heating T-stat: Unocc. ................................................................................ 60.0 T-stat Throttling Range ............................................................................... 3.00 Thermostat Schedule ................................ Occupied Schedule - Classroom Unoccupied Cooling is ....................................................................... Available
F F F F F
Common Terminal Unit Data: Cooling Coil: Design Supply Temperature ....................................................................... 58.0 F Coil Bypass Factor .................................................................................... 0.100 Cooling Source ........................................................................... Chilled Water Schedule .............................................................................. JFMAMJJASOND Heating Coil: Design Supply Temperature ..................................................................... 110.0 F Heating Source ................................................................................. Hot Water Schedule .............................................................................. JFMAMJJASOND Fan Control ........................................................................................... Fan On Terminal Units Data: Zone .............................................................................................................. All Terminal Type ..................................................................................... Fan Coil Minimum Airflow ........................................................................................ 15.00 CFM/person Fan Performance ........................................................................................ 0.75 in wg Fan Overall Efficiency .................................................................................... 50 %
4. Sizing Data (Computer-Generated): System Sizing Data: Hydronic Sizing Specifications: Chilled Water Delta-T .................................................................................. 10.0 F Hot Water Delta-T ....................................................................................... 20.0 F Safety Factors:
34
Cooling Sensible .............................................................................................. 0 % Cooling Latent .................................................................................................. 0 % Heating ............................................................................................................. 0 % Zone Sizing Data: Zone Airflow Sizing Method ................................. Sum of space airflow rates Space Airflow Sizing Method ............................. Individual peak space loads
After completing the inputs above, right click on C8-4PFCU D1- Wing D air system and Print/View Simulation Data
Shown below is the simulation report viewer prior to running a simulation. Notice the graph option is turned off and the category list in the bottom window is blank. Graphical reports are available however, after an initial simulation is run. For our C8-4PFCU D1- Wing D air system, preview these simulation tabular reports:
35
Air System Simulation Results (Table 1) : Precool Coil Load (kBTU) 0 0 458 1738 2574 8324 11223 9897 3058 441 126 0 Total 37839 Preheat Coil Load (kBTU) 36889 28705 18429 9312 4218 1183 364 296 2417 11035 15378 25207 153434 Terminal Cooling Coil Load (kBTU) 17258 20330 31617 45223 56228 77538 60683 79687 60507 42480 24526 15917 531994 Terminal Heating Coil Load Ventilation Fan (kBTU) (kWh) 11764 384 6400 1703 102 0 0 0 0 0 117 3991 14965 39042 349 367 367 367 367 352 367 367 402 314 314 4317
Month January February March April May June July August September October November December
Terminal Fan (kWh) 916 823 852 851 865 893 846 888 867 930 738 769 10237
Lighting (kWh) 10270 9316 9953 9845 9954 9843 6248 9950 9846 10585 8898 9005 113713
36
Air System Simulation Results (Table 2) : Electric Equipment Month (kWh) January 1535 February March April May June July August September October November December Total 1396 1466 1466 1466 1466 737 1466 1466 1605 1256 1256 16579
37
Daily Air System Simulation Results for August (Table 1) : Terminal Precool Coil Preheat Coil Cooling Coil Load Load Load Day (kBTU) (kBTU) (kBTU) 1 235 26 2823 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Total 0 0 508 237 95 96 166 0 0 368 276 174 261 122 0 0 848 826 744 268 117 0 0 594 905 1333 1232 491 0 0 9897 0 0 0 0 68 105 52 0 0 2 0 6 35 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 296 569 942 3810 2964 2689 2571 2628 447 641 3369 3479 2713 2804 3077 12 1051 4462 4136 4016 3615 2951 198 1053 4156 4085 4249 4311 3933 783 1147 79687
Lighting (kWh) 423 107 107 423 423 423 423 423 107 107 423 423 423 423 423 107 107 423 423 423 423 423 107 107 423 423 423 423 423 107 107 9950
38
Daily Air System Simulation Results for August (Table 2) : Electric Equipment Day (kWh) 1 70 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Total 0 0 70 70 70 70 70 0 0 70 70 70 70 70 0 0 70 70 70 70 70 0 0 70 70 70 70 70 0 0 1466
39
Table 1.1 Hourly Air System Simulation Results for Friday, August 1 Terminal Terminal Cooling Coil Heating Coil Precool Coil Preheat Coil Load Load Load Load Ventilation Fan Hour (MBH) (MBH) (kW) (MBH) (MBH) 0000 0.0 0.0 1.3 0.0 0.0 0100 0200 0300 0400 0500 0600 0700 0800 0900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 8.5 18.8 22.7 33.7 33.7 36.9 40.4 40.4 0.0 0.0 0.0 0.0 0.0 0.0 235.1 0.0 0.0 0.0 0.0 0.0 9.2 11.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 0.8 0.6 0.0 0.0 0.0 163.5 180.3 261.1 265.2 277.8 276.4 159.5 278.2 280.3 282.3 213.1 176.8 1.4 1.7 1.1 0.9 0.5 0.3 2823.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.0 0.0 0.0 0.0 0.0 0.0 17.5
Terminal Fan (kW) 0.0 0.0 0.0 0.0 0.0 0.0 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 0.0 0.0 0.0 0.0 0.0 0.0 40.4
Lighting (kW) 4.5 4.5 4.5 4.5 4.5 4.5 4.5 22.3 44.5 44.5 44.5 44.5 0.1 44.5 44.5 44.5 22.3 8.9 4.5 4.5 4.5 4.5 4.5 4.5 422.9
40
Table 1.2 Hourly Air System Simulation Results for Friday, August 1 Electric Equipment Hour (kW) 0000 0.0 0100 0200 0300 0400 0500 0600 0700 0800 0900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9.3 9.3 9.3 9.3 0.0 9.3 9.3 9.3 3.7 0.9 0.0 0.0 0.0 0.0 0.0 0.0 69.8
41
42
Now that we have run a simulation, graphics options are automatically turned on, and the graph category list will become visible. To demonstrate graphs for our workshop example, Print/View Simulation Data once again.
Air System Simulation Reports Viewer With Graph Options Ask for graphs for the fan coil (terminal) cooling and heating coil loads shown above.
43
44
45
46
Workshop # 4 Inputs
47
48
Another air system for Wing D could be multiple package rooftop units. These will be modeled as multiple single zone constant air volume air systems with built-in gas heat and DX cooling, one per zone. Due to the time constraints of this seminar, we will model only one packaged rooftop unit on a single zone, classroom D 101. Create a new air system called D28 RTU D2 Classroom D 101 Please complete the inputs for the Rooftop system for classroom D101. The following pages include copies of the required inputs to use.
49
x1
Thermostats and Zone Data: Zone .............................................................................................................. All Cooling T-stat: Occ. .................................................................................... 72.0 Cooling T-stat: Unocc. ................................................................................ 85.0 Heating T-stat: Occ. .................................................................................... 70.0 Heating T-stat: Unocc. ................................................................................ 60.0 T-stat Throttling Range ............................................................................... 3.00 Diversity Factor ............................................................................................ 100 Direct Exhaust Airflow ............................................................................... 400.0 Direct Exhaust Fan kW ................................................................................. 0.0 Thermostat Schedule ................................ Occupied Schedule - Classroom Unoccupied Cooling is ....................................................................... Available
F F F F F % CFM kW
Supply Terminals Data: Zone .............................................................................................................. All Terminal Type ...................................................................................... Diffuser Minimum Airflow .......................................................................................... 0.00 CFM/person
50
Zone Heating Units: Zone .............................................................................................................. All Zone Heating Unit Type ............................................................................ None Zone Unit Heat Source ..................................................... Electric Resistance Zone Heating Unit Schedule ................................................ JFMAMJJASOND 4. Sizing Data (Computer-Generated): System Sizing Data: Hydronic Sizing Specifications: Chilled Water Delta-T .................................................................................. 10.0 F Hot Water Delta-T ....................................................................................... 20.0 F Safety Factors: Cooling Sensible .............................................................................................. 0 % Cooling Latent .................................................................................................. 0 % Heating ............................................................................................................. 0 % Zone Sizing Data: Zone Airflow Sizing Method ................................. Sum of space airflow rates Space Airflow Sizing Method ............................. Individual peak space loads
These are program defaults and are not applicable to this air system type. No data entry is required in these fields
5. Equipment Data Central Cooling Unit - Air-Cooled DX Design OAT ................................................................................................ 94.5 Equipment Sizing ............................................................................ Auto-Sized Capacity Oversizing Factor ........................................................................... 0.0 ARI Performance Rating ........................................................................... 10.30 Conventional Cutoff OAT ............................................................................ 55.0 Low Temperature Operation ..................................................................... Used Low Temperature Cutoff OAT ....................................................................... 0.0
F % EER F F
Central Heating Unit - Combustion Equipment Sizing ............................................................................ Auto-Sized Capacity Oversizing Factor ........................................................................... 0.0 % Average Efficiency ...................................................................................... 82.0 % Misc. Electric 0.200 kW
51
Air System Properties- Equipment Tab The 5th tab in Air System Properties (shown below) is the Equipment tab. Because this workshop uses a packaged self-contained air system with DX cooling and builtin combustion heating, it does not utilize separate plants to produce hot and cold air. The heating and cooling plants are integral to the air system. For simulation calculations, equipment data is entered in the air system properties form under the equipment tab. In the Equipment tab click the Edit Equipment Data button for Central Cooling Unit.
1. Notice the Estimated Maximum Load is not yet displayed as shown here. 2.Select Auto-Sized Equipment Capacity and set over-sizing factor to 0%. 3. Select ARI Performance Rating from dropdown. 4. Select Low Temp Operation and set OAT cutoff to 0.0F.
52
Design Load Not Run Run the Design Load for D28 RTU D2 Classroom D 101and then re-check the equipment tab under Air System Properties. It will now display the Estimated Maximum Load for cooling and heating as shown below. Now we can input actual equipment data for energy simulation.
The rooftop unit equipment data used for simulations should reflect a gross cooling capacity of 51.0 MBH and a gross heating capacity of 36.2 MBH. Now we will show how to obtain actual rooftop unit data from Carrier in a direct transfer mode. E-Mail Project Archive To Your Carrier Representative At this point, the project can be archived and e-mailed to your Carrier representative in order to obtain actual equipment selection data. After a selection is made, the data can be returned to you to complete the HAP Equipment tab inputs for modeling energy simulations. We will demonstrate this in workshop # 4. Manufacturers product literature can also be used to obtain the equipment data required for HAP simulations. The Email address of your Carrier Sales Engineer can be entered under View and Preferences. This new HAP feature is done once and will apply to all subsequent projects. To obtain specific project data, the Design Engineer highlights Send Email to Sales Engineer under the Project pull down.
HAP V 4.4 Advanced Training Seminar
53
Send Email To Sales Engineer HAP will automatically archive the entire project in the users E20-II/archive folder and attach the Project.E3A file to an e-mail message.
54
HAP Automatically Attaches The Project Archive And Generates An Email At this point, the design Engineer sends the Email to the Carrier representative who performs an electronic selection based on the HAP requirements in the archive. For workshop # 4, the D28 RTU D2 - Classroom 101 rooftop unit has been selected from this Carrier software.
55
Capacity Requirements and Coil Conditions Are Used Based On The HAP Design Load Calculation
RTU Selected For Job Requirements For this example workshop, we will choose nominal 5-ton unit (006 size). This unit gives us a high efficiency and delivers a close sensible capacity to our HAP requirements. This unit is also equipped with a belt drive evaporator fan and enthalpy economizer.
56
Notice the actual bypass factor is greater (.163) than (.094) used in our initial load calculation.
Final Equipment Performance Summary For D28 RTU D2 For Classroom D 101
57
We can now extract the required data from this equipment selection to enter into the HAP equipment data tab, if desired: Gross Cooling Capacity = 60.79 MBH Gross Heating Capacity = 60.8 MBH Compressor Power Input = 3.99 kW OD Fan kW = (volts) (FLA) (1.73)/1000 = 230 x 1.5 x 1.73/1000 = 0.6 kW Enter Final Equipment Data In Equipment Tab Double click on the Air System Properties for the D28 RTU D2 Classroom D101 and go to the Equipment Tab. Enter the data calculated under Edit Equipment Data for the Central Cooling Unit and Central Heating Unit. Preview the following Design Load Reports.
58
Workshop # 4 Solutions
59
F F F F % F OK F
60
ZONE LOADS Window & Skylight Solar Loads Wall Transmission Roof Transmission Window Transmission Skylight Transmission Door Loads Floor Transmission Partitions Ceiling Overhead Lighting Task Lighting Electric Equipment People Infiltration Miscellaneous Safety Factor >> Total Zone Loads Zone Conditioning Plenum Wall Load Plenum Roof Load Plenum Lighting Load Return Fan Load Ventilation Load Supply Fan Load Space Fan Coil Fans Duct Heat Gain / Loss >> Total System Loads Central Cooling Coil Central Heating Coil >> Total Conditioning Key:
DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 94.5 F / 75.9 F HEATING OA DB / WB 2.0 F / 0.3 F Sensible Latent Sensible Latent Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) 96 ft 3903 96 ft 184 ft 323 184 ft 568 840 ft 3381 840 ft 3184 96 ft 1190 96 ft 4229 0 ft 0 0 ft 0 0 ft 0 0 ft 0 840 ft 0 840 ft 1101 0 ft 0 0 ft 0 0 ft 0 0 ft 0 2898 W 7853 0 0 840 W 2538 0 0 840 W 2578 0 0 25 4133 3000 0 0 0 0 0 0 0 0 0 0 0 0% / 0% 0 0 0% 0 0 25899 3000 9081 0 29015 3000 8886 0 0% 0 0 0 0% 0 0 0 0% 0 0 0 1370 CFM 0 1370 CFM 0 400 CFM 8382 9261 400 CFM 28576 0 1770 CFM 1312 1770 CFM -1312 0 0 0% 0 0% 0 38709 12261 36150 0 38709 12261 0 0 0 36150 38709 12261 36150 0 Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads
61
TABLE 1:
SYSTEM DATA
Dry-Bulb Temp (F) 94.5 79.1 58.5 58.5 59.2 59.2 74.6 74.6 74.6 Specific Humidity (lb/lb) 0.01534 0.01149 0.01000 0.01000 0.01000 0.01000 0.01036 0.01036 0.01036 Sensible Heat (BTU/hr) 8382 38709 0 1312 29015 0 Latent Heat (BTU/hr) 9261 12261 3000 -
Component Ventilation Air Vent - Return Mixing Central Cooling Coil Central Heating Coil Supply Fan Cold Supply Duct Zone Air Zone Direct Exhaust Return Plenum
Airflow (CFM) 400 1770 1770 1770 1770 1770 1770 400 1370
CO2 Level (ppm) 400 821 821 821 821 821 943 943 943
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.058 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4650.7 BTU/(hr-CFM) Site Altitude = 564.0 ft
TABLE 2:
ZONE DATA
Zone Sensible Load (BTU/hr) 25899 Zone T-stat Cond Mode (BTU/hr) Cooling 29015 Zone Temp (F) 74.6 Zone Airflow (CFM) 1770 CO2 Level (ppm) 943 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0
Component Ventilation Air Vent - Return Mixing Central Cooling Coil Central Heating Coil Supply Fan Cold Supply Duct Zone Air Zone Direct Exhaust Return Plenum
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.058 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4650.7 BTU/(hr-CFM) Site Altitude = 564.0 ft
TABLE 2:
ZONE DATA
Zone Sensible Load (BTU/hr) -9081 Zone T-stat Cond Mode (BTU/hr) Heating -8886 Zone Temp (F) 69.5 Zone Airflow (CFM) 1770 CO2 Level (ppm) 440 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0
62
Now ask for these simulation reports for D28 RTU D2 Classroom 101
63
Central Unit Central Heating Central Heating Central Heating Central Heating Clg Input Coil Load Eqpt Load Coil Input Misc. Electric (kWh) (kBTU) (kBTU) (kBTU) (kWh) 0 4123 4085 4982 23 0 55 159 257 604 592 675 342 53 19 0 2755 2354 860 139 4 0 0 0 2 179 989 3298 11946 2337 860 139 4 0 0 0 2 179 989 3271 11865 2850 1048 169 5 0 0 0 2 219 1206 3989 14470 13 5 1 0 0 0 0 0 1 5 18 66
Air System Simulation Results (Table 2) : Supply Fan (kWh) 105 94 97 97 99 103 97 102 99 106 84 88 Total 1171 Lighting (kWh) 862 782 835 826 835 826 525 835 826 889 747 756 9546 Electric Equipment (kWh) 139 126 132 132 132 132 67 132 132 145 113 113 1497
Month January February March April May June July August September October November December
64
2. Unmet Load Statistics - Central Heating Unit - Combustion Equipment Capacity Capacity Capacity is Insufficient Insufficient Sufficient by 0%-5% by 5%-10% Month (hrs) (hrs) (hrs) January 327 2 1 February March April May June July August September October November December Total 209 88 19 2 0 0 0 1 23 122 383 1174 0 0 0 0 0 0 0 0 0 0 2 4 0 0 0 0 0 0 0 0 0 0 1 2
Total Hours with Equipment Loads 334 211 88 19 2 0 0 0 1 23 122 390 1190
65
66
Workshop # 5 Inputs
67
68
RETREIVAL of Archive #2
1. While in the existing project, go to the menu bar; select Project \ Retrieve HAP v 4.4 Data. 2. Navigate to D:\E20-II\Archives 3. From the Archives Folder - retrieve the archive HAP 4.4 ADVANCED ARCHIVE 2 UNSOLVED.E3A. Allow this retrieved archive to overwrite the data you have created thus far in our workshops. After retrieval be sure to click Project, Save to update your project files. Upon completion of the retrieval process, all air systems for the remaining workshops are available.
CHILLER LIBRARY
In Workshop # 5 two chiller types will be added to the Chiller Library. These chillers will then be used to create two chilled water plants. The first chiller type will be an air-cooled packaged screw chiller. The second chiller type will be a water-cooled variable speed screw chiller.
The first design case for workshop # 5 uses the air-cooled packaged chiller and supplies chilled water to air systems A01- A10 (omitting A08 served by a packaged RTU) Chiller Library And Chilled Water Plants The chiller library is used to create a chilled water plant. The plant is used for energy simulations. The plant capacity may be handled by one chiller, but more often is divided between two or more chillers. Therefore, the plant capacity must be determined first before determining individual chiller sizes. This same concept applies to hot water and steam plants and their boilers, Plants features including piping and controls will be the focus of workshop #6.
To Place Chillers In The Library, We Need To Know Their Size First. HAP will consider all the air systems assigned to the plant to determine the peak coincident or "block" load. HAP takes into account diversity on several levels. Diversity is defined as the block load divided by the sum of the individual peak loads.
69
HAP considers diversity between the zones within an air system and also between systems when a plant serves multiple air systems (such as in workshop # 5). The plant design load calculation looks at the total plant load (sum of air system loads) for each hour and finds the largest load. Zone and system diversity is thus built in. Any multipliers assigned to identical systems served by the plant are used to determine the number of times coil loads for an air system are added to the plant profile. HAP will find the total building, project, or campus block load taking diversity into account for sizing central cooling and heating equipment such as chillers and boilers.
To perform load calculations for a chilled, hot water, or steam plant, double click on <new default plant> and pull down the generic model from the plant type pull down. For the first chilled water design case in workshop # 5. label the plant A- Base 2 A/C Plant. Under Plant Type, choose generic chilled water plant.
70
Next, in the Systems tab, add the A01- A10 air systems (omit A08). Say OK and right click on the plant to run the load. Ask for the Cooling Plant Sizing Summary.
71
Cooling Plant Sizing Summary The peak plant load using air-cooled chillers is 307.1 tons. This reflects diversity as discussed above. For this first design case will use two (2) air-cooled chillers equally sized even though a single air-cooled chiller is available in a capacity large enough to handle the total load. With the capacity requirements determined, the specific chillers can be selected for use in the final air-cooled chiller plant. This selection will be provided for use by the class in workshop # 5. AIR-COOLED CHILLER SELECTION REQUIREMENTS FOR WORKSHOP # 5 Qty: 2 Capacity: 153.5 tons each @ 95F ambient EWT: 44 F LWT: 54 F For this workshop, we will not run Carriers Chiller builder equipment selection software. However, the results of the selection are displayed on the following pages.
72
73
For workshop # 5 we will first add the air-cooled chillers to the library via IMPORT There are 3 methods of entering chiller data into HAP. 1. Import, 2. Template and 3. Chiller Type. We will use the first 2 methods in this workshop and discuss method 3. The Import Chiller button is used to import Carrier chiller data from an external (.CD2 or .CD4) file created by the Carrier Chiller Builder (selection) program. The Import function can be used if you want to model a specific Carrier chiller like the 30 XA 160 selected above. The chiller import file
HAP V 4.4 Advanced Training Seminar
74
(called an archive) can be obtained by running the Carrier selection program yourself or from your Carrier representative. It has a .CD2 or a .CD4 file extension.
HAP users may have HAP installed on the C or D drive of their computers. Chiller import files from the Carrier selection program should be placed in the \E20-II\Temp folder on the same drive on which HAP is installed. The 30 XA import file for workshop # 5 is in C:\E20-II\Temp folder or the desktop of the class computers
Double click on <New default Chiller> to bring up the chiller properties screen, then hit the Import Chiller button.
Navigate to C:\E20-II\Temp and open the file 30 XA 160 A-C Chillers.cd4. This imports the chiller into HAP.
75
Chiller Properties: General Tab The General tab on the Chiller form contains inputs which describe the general nature of the chiller being defined. In the General tab name the chiller 30XA 160 A - C Screw. Notice the chiller type has been identified by the archive as A/C Packaged Screw
76
The Design Inputs tab on the Chiller form contains items which describe the full load performance of the chiller. The content of this tab varies depending on the type of chiller being defined. The layout of the tab shown above is for an air-cooled screw chiller. Different sets of inputs are required for other types of chillers. For workshop # 5, define the minimum load as 15%. HAP will calculate a representative value for the chiller anyway. Notice all other inputs have been automatically completed by the import data contained in the archive.
The Performance Map tab on the Chiller form defines the off-design and part-load performance of the chiller. Performance Map tab data is not displayed when using a chiller import in HAP. The map data exists in the Carrier Electronic catalog program.
At this point we have completed the library entry for a packaged air-cooled screw using a Carrier electronic catalog program import file. The library chiller can now be used to create a chiller plant. We will discuss chiller plants in detail in Workshop # 6.
HAP V 4.4 Advanced Training Seminar
77
The next step for workshop # 5 will be to add a variable speed, water-cooled screw chiller to the library. As with the air-cooled design case, we will determine the plant load first, then select the chiller. This design case serves air systems C1-C8 (omit C7). These air systems comprise a mix of constant volume chilled and hot water rooftop units and 4-pipe fan coils.
Double click on <new default plant> and pull down the generic chilled water plant model from the Plant Type pull down. Label the plant C - Alt 2 - 23 XRV WC Rotary Screw.
In the Systems tab, add the C1-C8 Air systems (omit C7) as shown below. Say OK, right click on the plant to run the load. .
78
Ask for the Cooling Plant Sizing Summary in the Plant Design Reports screen.
79
The maximum plant load for the water-cooled design case using air systems C1-C8 is 264.7 tons. Note some of these air systems are 4 pipe fan coil units. For the air-cooled design case using air systems A01-A10, the plant load was 307.1 tons. Some of these air systems are VAV. Both plants serve identical 59,553 square ft. areas. What contributes to the load difference between the plants? The answer can be found by comparing the Air System Design Load Summaries for the two plant types. (Not done as part of this workshop).The air-cooled chiller plant requires more ventilation air than the water-cooled chiller plant. That is the primary reason for the tonnage increase. Sum of ventilation air amounts for A01-A10 = 37,198 cfm or .62 cfm/sq ft Sum of ventilation air amounts for C1-C8 = 27,762 cfm or .47 cfm/sq ft The ventilation sizing method selected was ASHRAE 62-2001 for all air systems in both plants. However, each VAV air system serves multiple zones so the ASHRAE 62-2001 multiple space equation is applied to the VAV systems. In order to satisfy the critical zones requirements and comply with ASHRAE 62-2001, the VAV air systems fan must over-ventilate the other zones. The result is more total ventilation and a greater total load.
Add a Chiller To The Library Via TEMPLATE The second method of adding a chiller to the library is the Chiller Template. Template can be used for both Carrier and non-Carrier chillers. This method uses full load and IPLV or NPLV data. With this data, the Chiller Template button is used to auto-generate a complete part-load performance map for a chiller. To use the Template feature, enter a name for the chiller and then press the Chiller Template button. The template function is currently offered for modeling these chillers: W/C Centrifugal W/C Rotary Screw W/C Packaged Screw W/C Packaged Reciprocating Enter a single 265 ton water-cooled rotary screw for workshop # 5. The chiller we will use is a new technology variable speed screw which falls under the rotary screw category. Rotary screw refers to a built to order type chiller versus packaged screw which tends to be off-the-shelf .
Double click on < New default Chiller> to bring up the Chiller Properties input screen.
80
Chiller Properties Select the Chiller Template button. Then, select W/C Rotary Screw from the drop down, and enter the following full load data which came from an actual selection from our Carrier engineering representative. Some of this data will be entered in
Chiller Design Inputs Chiller Name Variable Speed Screw Full Load LCHWT ................................ 44.0 F Full Load ECWT .................................. 85.0 F Full Load Capacity ................................ 265 Tons Full Load Power .0.599 kW/Ton Minimum ECWT ................................. 60.0 F Minimum Load ..................................... 15.0 % Cooler Flow Rate .............................. 635.0 gpm Cooler Pressure Drop ......................... 19.2 ft wg Condenser Flow Rate ....................... 795.0 gpm Condenser Pressure Drop ................... 16.0 ft wg 75%..................................................... .452 kW/ton 50%...................................................... .346 kW/ton 25%....................................................... .451 kW/ton
81
Enter the data from above into the chiller template form.
Tab1: General (Chiller Template) Check to see that all inputs from the General tab were transferred into Design Inputs. Enter the cooler and condenser pressure drops as shown below. These pressure drops apply to the chiller cooler and condenser vessels, not the entire water circuit resistance.
82
Tab 3: Performance Map The Performance Map tab shows points filled in by HAP for the 265-ton variable speed screw chiller. The chiller Performance contains chiller input power data for off-design and part-load conditions. In this table, each row contains performance data for a different entering condenser water temperature. Each column contains part load data at specific points. Together the rows and columns in this table define a "map" of performance data across the range of expected condenser water temperatures and part-load conditions. During energy simulations, HAP will use this data to perform 2-way interpolations to determine chiller input power at specific combinations of condenser temperature and part-load ratio. .
At this point we have added two chillers in the library. The first, a Carrier air-cooled packaged screw, was IMPORTED with an archive from the Carrier Chiller Builder selection program. The second, a water-cooled variable speed screw, was added via the TEMPLATE method.
Adding a Chiller to the Library via CHILLER TYPE Dropdown (not required for Workshop # 5). The Chiller Type dropdown permits chiller modeling when an archive is not available to import or when the full load and part load points required for the Template method are not known. The Chiller Type dropdown contains built-in chiller data for numerous chiller types as shown below. New choices are available not offered with Import or Template method such as absorption chillers and engine driven chillers. This method can also be used if the user knows the full load kW/ton along with all the part load points (more than just the PLV points required by Template method). In this case, sufficient part load points must be known to define the chiller performance map.
HAP V 4.4 Advanced Training Seminar
83
Following is an example of how to model a 265 ton air-cooled screw chiller knowing only the full load kW/ton. No IPLV or NPLV values or any other part load points are known.
84
The resulting HAP generated full and part load performance map is shown here. This map was generated based on the 95F ambient and full capacity 1.2 kW/ton value input on the previous tab.
85
COOLING TOWER LIBRARY The next step in creating our chilled water plant is to add a cooling tower for the water-cooled screw chiller. The cooling tower flow must match the condenser water flow of the connected chiller(s) exactly. Double click on <New default Cooling Tower> and enter the following data into the Cooling
There are several important terms related to cooling towers that we should understand. 1. Entering Wet Bulb temperature is an important parameter in tower selection. For most areas in North America, an entering wet bulb temperature of 78 F is common. 2. Approach is the difference between the water leaving the tower and the entering wet bulb temperature of the air. A 7F approach is common in HVAC systems with a 78 F entering wet bulb and 85 F water leaving the tower. (85 F - 78 F = 7 F) 3. Range is the difference in temperature of water entering the tower and water leaving the tower. An approximate 10 F range is most common in HVAC applications and reflects approximately 3 gpm/ton on the condenser loop. Check with your local cooling tower representative to confirm the design entering wet bulb and approach values for your area. The tower range must match the chiller condenser delta T.
86
BOILER LIBRARY
Similar to a chiller plant, the boiler plant may be comprised of one or more boilers from the library. The boiler(s) are placed in a plant which is linked to the air systems requiring the hot water, just as the chilled water plant was linked to air systems requiring chilled water. The boiler plant size reflects the largest peak heating load of all air systems connected to it. For workshop # 5, to create a library boiler, we must first size the boiler using a generic hot water plant like we did for the chiller plants. Double click on < New default Plant> and label our first boiler plant A Base Boiler Plant AC Chillers
Now assign the A air systems to the boiler plant as shown below:
87
88
Notice the A Base boiler plant has a required capacity of 3,223.6 MBH.
Now that we have run the load, we can add boilers to the library to meet the capacity requirements. The plant load was 3,223.6 MBH so we choose to use boilers of 3600 MBH output which provides some extra capacity. We will use an overall plant efficiency of 82% at all load points.
Whether the plant is comprised of a single boiler or multiple boilers, the overall efficiency value entered in HAP should reflect the entire plant at each load point.
89
At this point we have sized the hot water plant and created the library boiler for the A Base air- cooled chiller design case. Next, we will size the plant and create a library boiler for the C Alt-2 23 XRV Rotary Screw Chiller design case. Use air systems C1-C8 (omit C7) size the hot water plant and create the library boiler. Answers are shown on the next page.
90
91
The plant load was 2584.7 MBH so we choose to use boilers of 2800 MBH output which provides a little extra capacity. We will use an overall plant efficiency of 82% at all load points.
Chillers
Boilers
Tower
92
Workshop # 6 Inputs
93
Plants Created For Plant Load Sizing In Workshop # 5 A Plant is the equipment and controls used to provide cooling or heating to coils in one or more air systems. Examples include chiller plants, hot water boiler plants and steam boiler plants. This workshop consists of finalizing the two chiller plants and two boiler plants that were used in workshop # 5. The base design case chiller plant consists of two Carrier 30 XA A/C (air-cooled) packaged screw chillers. The air systems served by this plant include all A designated air systems. The configuration of the chiller plant is two chillers sequenced. The pumping and piping distribution system will be a Primary/Secondary, variable speed secondary system with a 12UT and 2% piping heat gain factor. The Alternate chiller plant serves the C designated 4PFCU air systems. This plant consists of one 265 ton Carrier 23XRV water-cooled, variable speed rotary screw chiller and a cooling tower. The pumping and piping distribution system will be a primary only variable speed system with a 12UT and 2% piping heat gain factor. For heating plants, the base case and alternate cases consist of a 3600 MBH and a 2800 MBH natural gas boiler respectively. All appropriate air systems are assigned to the plants. The distribution system is defined as, primary only constant speed pumping 40UT and 2% piping heat loss factor. The inputs for four (4) plants are on the following pages. There are two additional plants configured in the next archive we will retrieve into our project and no additional input is required on these imported plants. They will be used in the final workshop for energy comparisons. For workshop # 6, first step is to modify the generic plants from workshop # 5 by changing from Generic to Chiller or Hot Water Plant in the pull down. Then complete workshop # 6 inputs for the (4) plants on the following pages.
94
95
96
Chiller Plant Inputs A Base 30 XA Air-Cooled Chiller Plant With A01-A10 Air Systems
97
Chiller Plant Inputs 23XRV WC Rotary Screw with 4PFCU Air Systems
98
99
Boiler Plant Inputs, A Base Case 3600 MBH Boiler Input Data With A01-A10 Air Systems
100
Boiler Plant Inputs, C Alt- 2 2800 MBH Boiler Input Data With 4PFCU Air Systems
101
102
Workshop # 6 Solutions
103
Run all four Plant Simulation reports for the two chiller plants. For the two boiler plants omit the Daily and Hourly Simulation results.
On the pages that follow we will show the Plant Simulation Reports For the chiller plants first, followed by the boiler plants.
104
105
Daily Simulation Results For A - Base Air-Cooled Chiller Plant (Month Of August)
106
107
Hourly Simulation Results For A - Base Air-Cooled Chiller Plant (August 1st)
108
109
Unmet Load Report for A Base Case 30XA Air Cooled Chiller Plant
110
111
112
Workshop # 7 Inputs
113
The final Library items to define are the electric and fuel rate structures, required for simulating the building energy. This workshop consists of modeling one electric rate, one fuel rate and adding a time-of-day utility rate schedule.
Electric Rates
Highlight Electric Rates in the Library and Double click on <New default Electric Rate> then enter the following (reference input screens on following pages) Demand Units: Fixed customer charge: Minimum Charge: Tax rate: Seasonal Schedule: Time of day schedule: Demand Clause: Peak Months: Applies: KW $ 50.00 $ 0.00 7% Summer May through September Winter October through April Create a new schedule Utility time of day; refer to details on next page. Ratchet clause, 80% multiplier May to September October to April
114
115
116
Define the energy charges based on the step type, season, period, block size, block units and $/unit
117
Define any additional demand clauses for the complex rate structure
Highlight Fuel Rates in the Library and Double click on <New default Fuel Rate> and enter the following:
Select Simple rate type radio button for natural gas utility
118
I. Building Name: Cooling Plant: Heating Plant: Air Systems: Air System Types: Ventilation Control: Ventilation Sizing: II. Building Name: Cooling Plant: Heating Plant: Air Systems: Air System Types: Ventilation Control: Ventilation Sizing: III. Building Name: Cooling Plant: Heating Plant: Air Systems: Air System Types: Ventilation Control: Ventilation Sizing:
A-Base PFPMXB-Complex Rate (2) 30 XA 165 Air- Cooled Chillers 3600 MBH Capacity Gas Boiler(s) A01-A10 VAV PFPMXB , SZCV Constant ASHRAE 62-2001 B Alt-1 PFPMXB- Complex Rate (2) 30 XA 165 Air- Cooled Chillers 3600 MBH Capacity Gas Boiler(s) B01-B10 VAV PFPMXB , SZCV Demand Controlled Ventilation ASHRAE 62-2001 C Alt-2 4PFCU/VSS - Complex Rate (1) 23 XR variable Speed Screw Water-Cooled Chiller 2800 MBH Capacity Gas Boiler(s) C1-C8 4- Pipe Fan Coil Units, SZCV Constant (dedicated ventilation for 4PFCU) ASHRAE 62-2001
Copyright Carrier Corp. 2008
119
IV. Building Name: Cooling Plant: Heating Plant: Air Systems: Air System Types: Ventilation Control: Ventilation Sizing:
D Alt-3 SZCV/RTU- Complex Rate None (Integral to RTU- Air Cooled DX) None (Integral to RTU -Gas Combustion) D01-D36 SZCV RTU Constant ASHRAE 62-2001
Notice the B Alt-1 scenario utilizes demand controlled ventilation. Otherwise it is identical to the A-Base scenario. However, the use of DCV should result in overall energy savings due to the reduction in ventilation air at partial people occupancy. The C Alt-2 scenario uses a high efficiency screw chiller to supply chilled water to 4-pipe fan coil units and single zone air handlers. The fan coil systems utilize a common (dedicated) ventilation air system which results in a reduction in peak total ventilation airflow versus the A and B scenarios. The D-Alt 3 scenario utilizes multiple packaged single zone constant volume RTU units. The rooftop units use self-contained DX cooling with gas heating so are not connected to a chilled water or hot water plant. Double click on <New default Building> and select these plants for the first building. Call it A Base PFPMXB- Complex Rate
Check the box for the plants to include in this base case design scenario
Building Properties
120
Add air system A08 RTU C5 Mech/Storage to the building design scenario. This is a packaged unitary rooftop unit not assigned to a plant.
121
In each row for the check box enter the information for the additional building energy users not defined in the space input forms. Examples include: Domestic water heating, outdoor security lighting etc. Select the energy type, define the peak energy usage and then define a schedule.
Left click on the Edit button to assign a fractional schedule for each misc. energy item.
The following pages include screen captures of the schedules, profiles and assignments for the Misc. Energy items. DO NOT re-input this data, it already exist in the archive.
122
123
124
125
126
127
Meter Tab: For workshop # 7, link the A Base building to an electric and a gas meter.
Building Properties Meter Tab At this point, the first of four buildings is completed. It is necessary to perform the same steps outlined above for each of the remaining building design alternatives.
128
Complete the Misc. Energy and Meters tabs before going on to the C Alt -2 design case.
129
Alternate D-Alt 3 consists of SZCV/RTU Complex Rate and is the final building design case
130
Highlight and ADD all D designated RTU Packaged Rooftop air systems
Remember to complete all four tabs for all four building scenarios.
At this point we have created 4 buildings, each one a different design scenario. We will now run the building simulations and preview the results.
131
Highlight all four buildings and run simulation reports. Check the two comparative reports and preview the results.
132
Workshop #7 Solutions
133
Annual Cost Summary Table 1,2 C-Alternate 2 4PFCU/VSS is the lowest Annual Operating Cost scenario.
134
135
136
Annual Energy and Emissions Summary Table 4,5 Run the following simulation reports on the C-Alt 2 4PFCU/VSS Building. This scenario had the lowest annual operating cost.
137
138
139
140
141
142
143
144
145
146
147
148
149
150
Appendix A
151
152
153
154
155
156
157
158
159
160
161
162
163
Keyboard Input. Keys on your keyboard can also be used to navigate, choose options, select items, input data and press buttons in a Windows program: To move the cursor from one item to the next, press the [Tab] key. To move the cursor from one item to the previous item, press [Shift] and [Tab] together. To choose a menu option, first press [Alt] and the access key for the menu. For example, if the letter "P" in the name of the Project menu is underlined, "P" is the access key for this menu. Press [ALT][P] to display the Project menus options. To choose an option on a menu, press the access key for the desired item. To select an item on a list, use the up and down arrow keys to move the cursor through the list. When the desired item is highlighted, press the [ENTER] key.
164
To enter data, simply type the numeric or text information using the keyboard. When finished, DO NOT press [ENTER]. Instead use the TAB key or the mouse to move to another input item. [ENTER] very often will execute the default command button, which may cause you to exit to a different part of the program. To press a button (such as an OK button), use the [Tab] keys to navigate to the button and then press the [ENTER] key. Using Forms and Controls. In Windows programs, information is presented on one or more "forms. In HAP, the main program window is an example of one kind of form, which is used to perform basic tasks. HAP input forms are another example of a kind of form which is used to enter information. Individual items that appear on a form, or entire regions of a form are referred to as "controls. For example, on the HAP main program window, the left-hand panel in the center part of the window is a "tree view" control, which is used to switch between different categories of HAP data. A particular type of control always operates according to one consistent set of rules. Efficient use of Windows programs relies on quickly recognizing different kinds of controls and understanding how each kind of control is used. This sub-section summarizes the controls most frequently used in HAP. Pull-Down Menus. Pull-down menus typically appear toward the top of a form in the "menu-bar. To display the menus options, click on the menu name, or use press [ALT] and the menus access key. To select a menu option, click on the option name or use the arrow keys to move the highlight bar to the desired item and then press [ENTER]. An example showing HAPs Project menu appears below.
Toolbar Buttons. Toolbar buttons typically appear toward the top of a form and are used to perform common program operating tasks. Each toolbar button contains a picture that indicates its function. If you are uncertain of a buttons function, position the mouse cursor over the button. A "tool tip" - a short description of the buttons function - will appear. To press the button, use the mouse to click on the button. An example showing HAPs toolbar appears below.
Tree View. A tree view displays the relationships between data items in the form of a tree. For example, in Windows Explorer, the folder structure of your hard disk is shown in a tree view control. Branches of the tree represent folders on your hard drive and sub-folders beneath each of these folders. A tree view control is often accompanied by a list view control. In Windows Explorer, you use the tree view to locate a specific folder, and the accompanying list view displays the files in that folder.
165
In the HAP main program window, a tree view is used simply to show the categories of program data. You can perform the following tasks with this HAP tree view: Click on the category name to display its data in the list view. For example, clicking on the Space category name displays a list of spaces in your project in the list view. Right-click on the category name to display the pop-up menu for the category. Options on this menu perform work on all data in a specific category. For example, if you choose the Print Input Data option on the Space category pop-up menu, data for all spaces in your project will be printed.
List View. As its name implies, a list view contains a list of items that can be selected and used for various tasks. The list view can be displayed in four different formats: list, details, large icons and small icons. These formats show the contents of the list as line items or icons arranged in column or row format. The example below shows a list view from HAP containing spaces. This example uses the details format.
Standard procedures are used to select items in a list view: To select a single item, click on the item. It will be highlighted to indicate it is selected. To select multiple, consecutive items, click on the first item in the series. Hold the [Shift] key down and click on the last item in the series. All the items in the series you selected will be highlighted. To select multiple, non-consecutive items, hold the [Ctrl] key down and click on each item you wish to select. Each selected item will be highlighted. Other tasks that can be performed with list view items are: In some programs double-clicking on an item in the list view performs a special function. In HAP, double clicking on an item allows you to edit its data. In addition, right clicking on an item often displays its pop-up menu. In HAP, this feature is offered for all categories of program data.
166
Text Boxes. A text box is used to enter numeric or text data. Its appearance is shown below. When you move to the text box by clicking on it or using the [Tab] key, the existing value in the text box will be highlighted indicating you are in replace mode. If you begin typing, the existing value will be replaced with the new information you enter. To modify individual characters or numerals in the text box, click on the text box a second time or press the right or left arrow key. A blinking cursor will appear. In edit mode, you can move the cursor to a desired position in the box and insert or delete individual characters or numerals. When finished entering data, DO NOT press the [ENTER] key. In Windows software the [ENTER] key has no effect on a text box. Instead, it will often execute the default command button. Rather than [ENTER] moving you to the next input item, it will send you elsewhere in the program. Instead, use your mouse or the [Tab] key to move to the next input item.
Spin Buttons. As shown below, spin buttons sometimes accompanies text boxes. Spin buttons provide an alternate way to change data in a text box. If you click on the up button, the value in the text box will increase by a predetermined amount. If you click on the down button, the value will decrease. In the example below, the spin one uses buttons to increment or decrement the window quantity each time a spin button is pressed.
Drop-Down Lists. Drop-down lists are used to choose from a list of items. The example shown below is a drop-down list used to choose the overhead lighting fixture type in HAP. To display the list, click on the down arrow at the right-hand end of the control. Once the list appears, click on the desired item or use the arrow keys to move the highlight bar to the desired item and then press [ENTER].
Combo Boxes. A combo box is a modified version of a drop-down list. In addition to choosing from a list of items, a combo box allows you to enter your own item. The example shown below is a combo box for the city name from the Weather form in HAP. With this combo box, you can select from a list of pre-defined cities, or you can type in a city name of your own.
List Boxes. A list box contains a list of items from which you can select one or more items. Standard procedures are used to select items (see List View below). Sometimes you must scroll the list to see all of its items. The example below shows a list box used to select spaces included in a zone in HAP.
167
Check Boxes. A check box is typically used to indicate on/off or yes/no selections. In the example below, the box will be checked if you want the program to model glass as shaded all day, and will be unchecked if the glass is to be modeled as un-shaded. Clicking on the box changes a check box.
Radio Buttons. Radio buttons are used for selecting one item from a group of mutually exclusive choices. In the example below, only one of the four floor types can be selected at one time. To select an item using radio buttons, click on the button opposite the desired name or on the name itself. A black dot will be placed next to the item you choose, and the dot for the prior selection will be removed automatically.
Command Buttons. Command buttons are used to perform various tasks in a Windows programs. The example below shows the three command buttons that appear on all HAP input forms. Pressing the OK button, for example, saves the current data and returns to the HAP main program window. To press a command button, use your mouse to click the button, or use the [Tab] key to navigate to the button and then press [ENTER]. In some situations, a command button is highlighted in some manner to show it is the default for a form. In the example below, the OK button has a darkened outline indicating it is the default. Pressing [ENTER] from anywhere on the form has the same effect as pressing the default button.
168
169
Click on the "System" item in the tree view in the main program window. System information will appear in the list view. Double-click on the "<new default system>" item in the list view. The System input form will appear. Enter data for your first system. While entering the system, you will need to create a fan/thermostat schedule. You can do this by choosing the "create new schedule" item in the fan/thermostat schedule drop-down list. This will create a schedule and automatically assign it to your system. An alternate approach is to create this schedule before entering air system data. Press the OK button on the System input form to save your data and return to the main program window. To enter another system, in the list view right-click on the name of the system you just created. The system pop-up menu appears. Choose the Duplicate option on the pop-up menu. A copy of the original system will be created and its input form will appear. This is a quick way of generating new systems based on defaults from the previous system, if successive systems are similar. If they are not, use the "new default system" option to create each new system. Enter data for this new system. Press the OK button on the System input form to save your data and return to the main program window. Repeat the previous four steps to enter data for as many systems as you need. 5. Generate System Design Reports Click on the "System" item in the tree view in the main program window. System information will appear in the list view. Select the systems for which you want reports. Choose the "Print/View Design Data" option on the Reports menu. On the System Design Reports form, choose the desired reports. To view the reports before printing, press the Preview button. To print the reports directly, press the Print button. Before generating reports, HAP will check to see if system design calculations have been performed. If not, HAP automatically runs these calculations before generating the reports. 6. Enter Plant Data (if necessary) Click on the "Plant" item in the tree view in the main program window. Plant information will appear in the list view. Double-click on the "<new default plant>" item in the list view. The Plant input form will appear. Enter data for your first plant. For plant design load purposes users will only need to select from the first three plant types (Generic Chilled Water, Generic Hot Water, Generic Steam). HAP users have additional options for specific types of chilled water, hot water and steam plants, but these require extra data not relevant to the design load calculation. Therefore, it is best to use the Generic plant types for design loads. Later Generic plants can be converted into specific plant types without loss of data. Press the OK button on the Plant input form to save your data and return to the main program window. To enter another plant, in the list view right-click on the name of the plant you just created. The plant pop-up menu appears. Choose the Duplicate option on the pop-up menu. A copy of the original plant will be created and its input form will appear. This is a quick way of generating new plants based on defaults from the previous plant, if successive plants are similar. If they are not similar, use the "new default plant" option to create each new plant. Enter data for this new plant.
HAP V 4.4 Advanced Training Seminar
170
Press the OK button on the Plant input form to save your data and return to the main program window. Repeat the previous four steps to enter data for as many plants as you need. 7. Generate Plant Design Reports (if necessary) Click on the "Plant" item in the tree view in the main program window. Plant information will appear in the list view. Select the plants for which you want reports. Choose the "Print/View Design Data" option on the Reports menu in the menu bar. On the Plant Design Reports form, choose the desired reports. To view the reports before printing, press the Preview button. To print the reports directly, press the Print button. Before generating reports, HAP will check to see if plant design calculations have been performed. If not, HAP automatically runs these calculations before generating the reports.
171
All analysis work performed in HAP requires following the same general five-step procedure: 1. Define the Problem. First, define the scope and objectives of the Building Analysis. For example, what type of building is involved? What type of systems and equipment are required? Which alternate designs or energy conservation measures to compare in the analysis? 2. Gather Data. Gather information about the building including its environment, HVAC and non-HVAC equipment and cost for energy before simulating the building. This step involves extracting data from building plans, evaluating building usage, studying HVAC system needs and acquiring utility rate schedules. Specific types of information needed include: Building site climatic data Building construction material data: Walls and Roofs Windows, Doors and Exterior shading devices Floors Interior partitions Building size and layout data including wall, roof, window, door and floor areas, exposure orientations and external shading features
HAP V 4.4 Advanced Training Seminar
172
Internal load characteristics determined by levels and schedules for occupancy, lighting systems, office equipment, appliances and machinery within the building. Data for HVAC equipment, controls and components Data for chilled water, hot water and/or steam plants as applicable Data for non-HVAC energy-consuming equipment Utility rate information for electric service, and fuel sources
3. Enter Data Into HAP. Next, enter data into HAP for the analysis. When using HAP, your base of operation is the main program window. From the main program window, first create a new project or open an existing project. Then define the following types of data needed for the building analysis: Enter Weather Data. Weather data defines the temperature, humidity and solar radiation conditions the building encounters during the course of a year. These conditions influence loads and system operation throughout the year. Select Design Weather Select Simulation Weather Define Holiday calendar. Enter Space Data. Describe all elements affecting heat flow in space. Space information is stored in the project database and linked to zones in an air system. Enter Air System Data. An Air System is the equipment, controls used to provide cooling, and heating to a region of a building. Enter Plant Data. A Plant is the equipment and controls used to provide cooling via chilled water or heating via hot water or steam to coils in one or more air systems. Enter Utility Rate Data. Utility rate data defines the pricing rules for electrical energy use and fuel use. Enter Building Data. A Building is simply the container for all energy-consuming equipment included in a single energy analysis case. Create one Building for each design alternative in the study. 4. Use HAP to Generate Simulation Reports. Using the Reports Menu, select and generate simulation reports. 5. Evaluate Results. Finally, use data from the simulation reports you generated to draw conclusions about the most favorable design alternates. Copies of the typical HAP Simulation Reports are included on the Hand-out CD.
173
174
175
Zone airflow computed using peak zone load. Space airflow computed using zone CFM/sq.ft. or L/s/sqm.
With this method, the zone airflow is computed using the maximum zone sensible cooling load. The zone airflow is divided among spaces in the zone on the basis of zone CFM/sq.ft (L/s/sqm). Therefore, space airflow is not related to space loads unless all spaces in the zone have a consistent load density in BTU/hr/sq.ft (W/sqm). Sizing Method #2:
Zone airflow computed using peak zone load. Space airflow computed using coincident space loads.
With this method the zone airflow is calculated from the maximum zone sensible cooling load. The zone airflow is divided among spaces in the zone on the basis of the ratio of coincident space sensible cooling loads to peak zone sensible load. By coincident, we mean the space load computed for the month and hour when the zone sensible load peaks. Sizing Method #3:
Zone airflow computed using peak zone load. Space airflow computed using peak space load.
With this method, the zone airflow is computed using the maximum zone sensible load. Required space airflow rates are computed using the maximum sensible load for each individual space. Note that if spaces experience peak loads at the same time the zone peak occurs, the sum of space airflow rates will equal the zone airflow rate. Otherwise, the sum of space airflows will exceed the zone airflow rate. Sizing Method #4:
Zone airflow computed using sum of space airflows. Space airflow computed using peak space load.
With this method, required space airflow rates are computed using the maximum sensible load for each individual space. The zone airflow rate is calculated as the sum of space airflows for all spaces in the zone.
176
177
Using method 4 for constant volume systems is good practice since these types of systems normally should not be sized with diversified or block load air quantities. Let us discuss one of the most common systems, the packaged rooftop unit. In HAP language, this is a single zone constant air volume system. If the designer takes the time to describe the various areas served as spaces, some valuable information can be gained. An example is the amount of air needed in different places so diffusers and the duct system can be designed with some knowledge of the actual requirements. Again, if some of the spaces were peaking at different times of the year than others this would indicate the need for better zoning (another unit if you can afford it). At least you will know that the job probably will not work very well at this stage. This method also sizes the rooftop unit CFM (L/s) undiversified. This is good since it seems you need to get all the air you can on these types of jobs. We hope that this article has helped you think about the choices of space descriptions, zoning and sizing methods you must make. Make your choices with a purpose in mind. I am sure many of you may have differing thoughts and we would like to hear them. Even with faster computers and more complex software, system design still has a lot of art and designer experience involved. Remember this old saying: If a job is to work correctly, it must be designed right one time. The problem is when!
178
ASHRAE Transfer Functions ASHRAE RTS ASHRAE CLTD/CLF Carrier E20 Method Instantaneous Q=U A TD
179
The Heat Balance Method, the most rigorous method of calculating building loads, provides one solution to this problem. Heat balance is actually the foundation of all the other methods of calculating building loads. The heat balance method evaluates each conductive, convective, radiative and heat storage process that occurs in the building using the fundamental laws of heat transfer and thermodynamics. Using the heat balance method to determine building heat transfer requires an equation written for each surface and mass element considering each process involved. By solving all heat balances equations simultaneously, the total rate of heat transferred to room air can be determined and the dynamic ebb and flow of heat in the room can be successfully evaluated. The Heat Balance method can be highly accurate but it is also complex and requires powerful computer hardware, detailed inputs and long calculation time. An alternate solution is the Transfer Function Method which is endorsed by ASHRAE as the preferred method of calculating loads, and which is used in the HAP, System Design Load, Block Load and Block Load Lite programs produced by Carrier. The Transfer Function Method uses some mathematical tricks to simplify the heat balance solution process, thereby yielding calculation times that are faster than those of the Heat Balance Method without sacrificing too much of its accuracy. The Transfer Function procedure calculates how heat gains from sources such as warm ambient air, solar radiation, lights, people, etc. are converted to cooling loads via conduction, convection, radiation and heat storage processes. The procedures therefore account for the dynamic heat transfer found in a real world building. Further, calculations account for specific design, construction, environmental and building usage conditions and are therefore customized to each building application. Thus, for the current state of technology of computerized engineering tools, Transfer Functions provide a good compromise between complexity and accuracy.
180
When using programs that employ the Transfer Function Method, remember that nearly all loads involve dynamic heat flow. Heat gain received from a source such as lighting is not immediately converted to a cooling load. Rather, the portion of the heat gain that is thermal radiation is transferred to massive building elements such as floors and walls, and may be stored for a period of time before being released to air in the building. Once heat is transferred to the air, it is a load that must be removed by the air conditioning apparatus. Figure 2 shows a sample relationship between lighting heat gain and load. When the lights are first turned on, a significant portion of the lighting heat gain is absorbed and held by the building mass. Over time, this stored heat is discharged to air in the building, but additional radiant heat is received. When the lights are turned off, the stored heat continues to be discharged. Thus, loads continue even after the heat gains cease. All heat sources that involve a radiant component exhibit similar behavior. These include loads for walls, roofs, windows, partitions, people, lights and electrical equipment. Transfer Function calculations account for these dynamic processes. Remembering this is often very helpful when analyzing load calculation outputs. The Radiant Time Series method was introduced in ASHRAE 2001 Handbook of Fundamentals. It is a dynamic way of calculating loads, but is not as complex to calculate and is easier to understand than the TFM. It is a good method to obtain sizing data for a typical building. However, it is not a good method to simulate system operation.
181
The Benefits of the Transfer Function / Heat Extraction Load Calculation Method
The previous article (Putting Load Calculation Methods in Perspective) describes the transfer function and heat extraction procedures used to calculate loads in HAP. While the benefits of this calculation method for energy analysis are evident, customers often question whether such advanced calculation methods are worth using for system design applications, or whether simpler methods would be sufficient. Carrier feels that advanced methods such as transfer functions/heat extraction should be used because the method provides several important benefits to users. These include: 1. Accuracy. Advanced methods such as Transfer Functions account for the dynamic heat flow processes which occur in buildings and which significantly influence design loads and system behavior. Simpler methods either ignore these dynamics, or analyze them in much less detail than Transfer Functions. Advanced methods therefore can provide results that are more accurate. 2. Pull down Loads. One of the most important aspects of dynamic heat flow is the pull down load. Pulls down loads have a significant influence on system sizing results and therefore need to be considered. Advanced methods such as Transfer Functions/Heat Extraction are the only way to adequately account for pull down loads. Simpler methods can only make gross estimates of the effect of pull down loads. 3. Flexibility. Advanced methods such as Transfer Functions/Heat Extraction customize calculations to the application. Since loads are dynamic, loads in one hour are influenced by conditions in both the current hour and previous hours. The nature of 24-hour profiles of solar radiation, ambient temperature and internal heat gain need to be considered to accurately predict loads in any one hour. Transfer functions use the solar, temperature and internal gain profiles defined by the user for each specific application. Therefore, loads are customized to each application. Simpler table-based methods make assumptions, such as a standard operating profile or the use of July 40 deg N latitude for solar radiation. In some cases, correction factors are used to try to adjust for actual conditions. These adjustments are often not adequate and produce less accurate results than methods that customize calculations to each application.
182
While the heating energy use has been reduced substantially (93%), the cooling cost has increased by 6%. Investigation of energy consumption results for the building, plant and air system showed the root of the problem lay in the air system. Air system simulation results show that the annual heating coil load dropped from 62,972 (66,439 MJ) to 12,172 kBTU/yr (12842 MJ), but the annual cooling coil load increased from 776,844 (819,614 MJ) to 809,200 kBTU/yr (853,751 MJ). An examination of how cooling coil loads are distributed during the year begins to provide clues to why this happens.
183
Figure 1 is a plot of monthly total cooling coil loads for the original U= 0.104 and renovated U= 0.042 scenarios. This figure shows that the renovated case has lower cooling coil loads in the summer months, but higher cooling coil loads in the spring, fall and winter months. Increases in cooling loads during these off-peak seasons are larger than reductions in cooling loads during the summer months, so the annual effect is a net increase in cooling coil load.
184
Examination of hourly system performance provides further clues to what is happening. Figure 2 shows hourly cooling coil load profiles for July 19, a moderately sunny summer day in which the ambient temperature ranges between 69 F (20.5 C) and 82 F (27.8 C.) Cooling loads for this day are uniformly higher for the U=0.104 case than for the U=0.042 case.
185
Finally, Figure 3 shows hourly system performance for March 19, a moderately sunny day with ambient temperatures ranging between 35 F (1.7 C) and 50 F (10 C.) On this day the relationship between cooling coil loads is reversed. Coil loads for the original U= 0.104 case are uniformly less than those for the renovated U= 0.042 case.
186
With this system performance data as evidence, we can begin to deduce what causes the overall cooling cost to increase:
Because this is a single story building with a large roof area, the roof is a dominant pathway for envelope heat flow. Adding insulation to the roof serves to reduce heat flow through the roof. When the direction of heat flow is from outside to inside, such as on a warm, sunny summer day, the added insulation reduces the heat flow and therefore reduces the cooling coil load, as shown in Figures 1 and 2. When the direction of heat flow is from inside to outside, such as on a cold winter day, the added insulation reduces heat loss. Normally we only think of this in terms of reducing system heating coil loads, which it does. However, in a building with large internal heat gains, envelope heat loss allows internal heat to escape from the building. Added insulation prevents the escape of this internal heat. Therefore, heat that would normally have escaped naturally from the building must be removed by mechanical cooling. Evidence of this is shown in Figures 1 and 3.
Increasing envelope insulation has this effect in many types of buildings. But generally, the summer cooling savings far outweighs increases in off-peak cooling loads due to their small size and infrequent occurrence. It is in buildings with large internal heat gains and frequent cooling loads in off-peak months that this thermos bottle effect becomes prominent and cause an overall increase in cooling cost.
187
This article briefly describes these options and their intended applications. Each control option will be discussed separately below. Constant Airflow Control maintains outdoor ventilation at the design airflow rate for all occupied period hours and for unoccupied period hours when the ventilation dampers are open. For constant volume systems, constant ventilation airflow can be maintained without special controls and is the most common control option used for CAV systems. For VAV systems, it is assumed special damper controls or booster fans are used to maintain a constant ventilation rate as the supply fan airflow varies. Note that this control also allows the user to specify whether ventilation dampers are open or closed during unoccupied periods. Thus, this control provides simple scheduling capabilities for eliminating ventilation airflow for unoccupied times. Proportional to Supply Air Control represents the use of uncontrolled or partially controlled ventilation airflow for VAV systems. With this option, ventilation airflow varies naturally as the supply airflow changes. Uncontrolled outdoor airflow tends to vary as a constant percentage of supply air. Thus, if the supply fan has throttled to 60% of its design value, ventilation air is 60% of its design value also. As with Constant Airflow control, the user has the opportunity to schedule the ventilation dampers open or closed during unoccupied period hours as necessary. CO2 Sensor Control provides a simple model for outdoor ventilation air control based on a CO2 sensor. Actual controls vary ventilation air to maintain indoor air quality based on measured C02 levels in the building. To model this control on a simple basis, the program assumes CO2 levels are directly related to the number of occupants in a zone. The program therefore varies ventilation airflow using a constant CFM/person value and the number of occupants in the building for the current hour. Scheduled Control is used when special controls are used to vary the outdoor ventilation airflow according to a predetermined time-clock schedule. For example, based on the time clock schedule, ventilation dampers might modulate to provide 1000 CFM (472 L/s) of ventilation air from 6am to 9am, 1500 CFM (708 L/s) from 9am to 12 noon, and 1250 CFM (590 L/s) from 12 noon to 5pm. When this control option is used, the user specifies how ventilation air varies by choosing one of the schedules stored in the program schedule database. This schedule selection is made on the same input screen where you choose the method of ventilation control in HAP 4.0 for Windows. It is important to note that the Scheduled Control option should not be used simply as a means of eliminating ventilation air during unoccupied times. This can be done much more easily using the Constant Airflow and Proportional To Supply Air control options. Many users often overlook this and mistakenly use the Scheduled Control option when Constant Airflow or Proportional to Supply Air would be a more appropriate selection.
188
Qtot = Total heat gain per occupant, BTU/hr/person or W/person. This is the sum of sensible and latent heat gains defined by the occupant activity level, or directly specified by the user. K = Curve fit coefficient. 0.00883 CFM/Met in English or 0.25 L/s/Met in Metric. Figure C-2 "Metabolic Data" from ANSI/ASHRAE Standard 62-2001, Ventilation for Acceptable Indoor Air
HAP V 4.4 Advanced Training Seminar
189
Quality, plots the relationship between metabolic level and CO2 generation. The relationship can be represented as the following equations: CO2 generation in CFM = 0.00883 x MetsCO2 generation in L/s = 0.25 x Mets M = Heat flux for one metabolic unit or "Met", 18.4 BTU/hr/sqft or 5.39 W/sqm, where the sqft or sqm area refers to body surface area At. At = Body surface area for one "typical" occupant, sqft or sqm. For this analysis, HAP assumes the average adult male has a body surface area of 19.4 sqft (1.8 sqm) and the average adult female has a body surface area approximately 85% of that for the male (16.5 sqft or 1.53 sqm). HAP considers the typical space occupant to be an average of male and female body areas: 18.0 sqft or 1.67 sqm. The equations above are the combination of two separate equations. Stating the equations separately helps to understand the formulation better. First, the heat flux per person in Mets is calculated as: M = (Qtot BTU/hr/person) [1 Met / (18.4 BTU/hr-sqft)] [1 / (At sqft)] Example: One occupant with activity level of "office work" has a sensible heat gain of 245 BTU/hr/person and a latent heat gain of 205 BTU/hr/person. Therefore, the total heat gain is 450 BTU/hr/person and the metabolic rate per person is: M = (450 BTU/hr/person) (1/18.4 BTU/hr/person) (1/18.0 sqft) = 1.36 Met/person Second, the correlation between metabolic rate and CO2 generation, obtained via a curve fit of ASHRAE Standard 62 data is: CO2 generation in CFM = 0.0088 x M CO2 generation in L/s = 0.25 x M B. CO2 Mass Balance for Zones Once the CO2 generation rate for zone occupants is known, a CO2 mass balance can be performed for each zone in the system to estimate the CO2 level measured by a CO2 sensor in the zone. This mass balance assumes a steady state level of CO2 will be reached each hour. The mass balance is as follows: 0 = CO2 in supply air entering zone - CO2 in direct exhaust air leaving zone. - CO2 in return air leaving zone via the return plenum or return duct. + CO2 in infiltration air entering the zone. - CO2 in exfiltration air leaving the zone. + CO2 generated by occupants in the zone. To solve this equation for the zone CO2 level, the CO2 level in supply air is assumed. Later this assumption will be checked and if necessary, the calculation will be repeated with an adjusted assumption. Knowing the supply CO2 level, all the airflows and the CO2 generation by occupants, the equation can be solved for the zone CO2 level. C. Determining Outdoor Damper Position and Outdoor Airflow To determine outdoor damper position the DCV controller will first scan CO2 measurements by all zone CO2 sensors and identify the highest CO2 level. It then uses this CO2 reading to determine the indoor-outdoor CO2 differential: CO2 Differential = (Highest Zone CO2 Level) (Outdoor Air CO2 Level)
HAP V 4.4 Advanced Training Seminar
190
This CO2 differential is used with the DCV control profile to determine the required outdoor ventilation airflow. The figure below shows a sample control profile. In this example the outdoor CO2 level is 400 ppm. The minimum CO2 differential is 100 ppm, which equates to a CO2 level of 500 ppm and corresponds to a base ventilation rate of 810 CFM. The maximum CO2 differential is 700 ppm, which equates to a CO2 level of 1100 ppm and corresponds to a design ventilation rate of 2700 CFM. The DCV controller sets the outdoor damper position as follows: If the CO2 differential determined by the DCV controller is less than the minimum setting of 100 ppm (which equals a CO2 level of 500 ppm), the outdoor dampers will be set to provide the base ventilation rate of 810 CFM. If the CO2 differential is greater than the maximum setting of 700 ppm (which equals a CO2 level of 1100 ppm), the outdoor dampers will be set to provide the design ventilation airflow of 2700 CFM. If the CO2 differential is between the minimum and maximum settings, then the outdoor dampers will be set to provide the airflow corresponding to the control profile. Thus, outdoor airflow is a linear function of CO2 differential in this range and ranges between the minimum (810 CFM) and maximum (2700 CFM) values.
D. Calculation of System CO2 Levels Next, the program uses the zone CO2 data from part C and the outdoor ventilation airflow data from part D to calculate CO2 levels in the remainder of the system. This requires starting at the return grilles of all zones and working along the airflow path to determine CO2 levels at all state points in the return portion of the system, and then into the supply portion of the system. For example, return air from the zones mixes in the return plenum or duct to yield a mixed CO2 concentration in return air. Return air mixes with outdoor air, to provide a mixed CO2 concentration in supply air, which is delivered to the zones. E. Evaluation of Results and Iteration Finally, the supply air CO2 level produced by part D is compared with the initial assumption for supply air CO2 level that was made at the start of the CO2 balance calculation in part B. If the two values differ by more than 10 ppm, the calculation in parts B, C and D is repeated using the new supply air CO2 value. In this way the program iterates to converge on a solution in which the outdoor air flow, system CO2 levels and zone CO2 levels are all balanced and consistent for the hour.
191
A calculation tool which will account for all of the processes involved with building heat flow, A tool that is fast, A tool that is easy to use, and A tool that provides accurate, reliable results.
Understanding the Processes at Work. Providing accurate, reliable results requires accounting for all of the complicated heat flow processes occurring in the building. For the explanations of the Transfer Function and Heat Extraction Method later in this article to make sense, we first need to provide a quick refresher on the heat flow processes that occur in a building. First of all, our ultimate interest is in cooling or heating loads. A load is the rate of heat transfer to or from the air in the building. Heat transferred to air in a room changes the room air temperature. These changes are sensed by a thermostat, which sends a signal to the HVAC equipment to provide cooling or heating. Secondly, we are all familiar with the different sources of heat gain or loss, which influence cooling or heating demands in the building. These include solar radiation, temperature gradients across walls, heat gain from lighting, people, etc. Therefore, we know where the heat originates (the sources) and we know where it ultimately ends up (in the air in the building). The challenging part of this engineering problem is analyzing how heat travels from its source to its destination. As an example, let us consider the wall component of a cooling load. First, the outside surface of the wall is warmed by solar radiation and ambient air. This initiates heat flow across successive layers in the wall assembly. Heat does not flow instantaneously from outside to inside surfaces of the wall. Instead, it takes time. In addition, the amount of time depends on the intensity of heat flow at the outer surface plus the thickness, density, specific heat and thermal conductivity properties of material layers in the wall assembly. Ultimately, heat reaches the inside surface of the wall where it raises the wall surface temperature. At this point two things happen. First, a portion of the heat is convected to air in the room, raising the air temperature. Thus, this heat has become a cooling load. Second, a substantial portion of the heat at the wall surface is transferred as thermal radiation to other wall, ceiling and floor surfaces in the room. This raises the temperature of the other surfaces and triggers convection to room air, heat storage within the material and further radiative exchanges within the room. Eventually most or all of the original heat flow becomes a cooling load, but the complete conversion of the heat to cooling load takes time. The same sort of thermal processes occur for heat flow through roofs, windows, doors and partitions. Heat from other sources such as solar, lighting, electrical equipment and occupants is introduced directly into the room, and once in the room it undergoes the same sort of room heat
HAP V 4.4 Advanced Training Seminar
192
transfer processes described for walls. This is because all these heat gains are comprised of separate convective and radiative components. The convective components immediately become cooling loads. The radiative components are transferred directly to surfaces in the room and then undergo further radiant, convective and heat storage processes. In addition, an important factor governing heat flow to the air in the room is the temperature of the room air. The temperature difference between wall, ceiling and floor surfaces and the room air govern convection. Thus, for a cooling scenario, convective heat flow from warm room surfaces decreases as the room air temperature rises. As room air temperature falls, convective heat flow from warm room surfaces increases. Recognizing this is important for two reasons. First, all thermostats have a certain operating range within which they attempt to maintain room air temperature. Thus, room air temperature varies within this operating range and this influences convective heat flow. More importantly, nighttime setup control or equipment shutdown can cause room temperature to vary by 10 F (-12.2 C) or more during a 24-hour operating cycle. A large increase in room temperature greatly reduces convective heat flow. Heat is essentially trapped in the massive elements in the room, and the surface temperatures of these elements rise. In the morning when cooling equipment is turned on and room air temperatures are quickly reduced, there is a rush of convective heat flow due to the large temperature difference between room air and the surfaces in the room. This is what is known as a pull down load. Therefore, in summary:
There are many factors involved in building heat flow. This heat flow occurs over time rather than instantaneously. Room air temperature governs heat flow from surfaces in the room to the air in the room. The nature of the thermostat control in a room influences the rooms cooling loads by affecting convective heat flow.
Calculating Building Heat Flow. Now, in order to calculate realistic, accurate building loads, we need to account for all of the complicated processes we have just discussed. This is quite a challenge. One way to do this is with the Heat Balance Method which is essentially the mother of all load calculation methods. With this method, each of the heat flow processes is represented by a mathematical equation drawn from the laws of conduction, convection and radiation and from the first law of thermodynamics. The result is a large number of equations, and an equally large number of unknown quantities. Typically, no one equation can be solved directly. Instead, the whole set of equations must be solved simultaneously or by iteration. The results of this calculation are the temperatures and heat flows at each surface in the room, and ultimately the temperature and heat flow to room air, which tells us the cooling load. Currently, we cannot satisfy our original objectives of fast and easy with the Heat Balance Method because computer software using this method requires too much calculation time and too much input data. However, the day is fast approaching when this method will become feasible for everyday use on desktop computers. Until then, we need an alternate solution to our engineering challenge. That solution is the Transfer Function Method, first developed by researchers in the late 1960s. The Transfer Function Method uses several mathematical tricks to make solving heat balance equations much faster. While this method is faster, it continues to account for the complex processes involved in building heat flow and thus provides realistic, accurate results. Here is how it works. Within the method, there are three kinds of transfer function equations used to analyze different aspects of the building heat flow problem:
Conduction Transfer Function Equations are used to analyze the conductive heat flow through walls and roofs. Room Transfer Function Equations are used to analyze the radiative, convective and heat storage processes for all load components once heat reaches the interior of the room. Space Temperature Transfer Function Equations (aka Heat Extraction Equations) are used to analyze the effect of changing room temperatures on convective heat flow from
193
surfaces in the room to the room air. Included in this calculation is the behavior of the room thermostat in controlling room temperature levels and communicating demands to the cooling or heating apparatus. These three kinds of transfer function equations are used in sequence to determine how heat from various heat sources is converted into cooling loads in the building. However, there is one complicating factor that is crucial to this whole discussion. It has been said that there is no such thing as a free lunch, and that is certainly true in this case. As we noted earlier, the Transfer Function Method uses mathematical tricks to simplify and speed up the calculation process. The cost of increased speed is that the calculation has to be performed in two distinct stages. There are simply too many factors involved to be able to solve the entire problem in one pass when using the transfer function tricks. In the first stage of this calculation process, we use the Conduction and Room Transfer Function Equations to calculate room loads as if the room is held at precisely one temperature 24 hours a day. For a design cooling calculation, the cooling thermostat set point is used as the fixed room temperature for this calculation. Once room loads based on this simplifying assumption have been determined, the second calculation stage corrects these loads to account for the true behavior of the building (rising and falling room temperatures) using the Space Air Transfer Function Equations. In HAP, results of these two calculation stages appear throughout the system design reports. On the Air System Design Load Summary, all the results in the top portion of the report down to and including the Total Zone Load are from the first stage of the calculation, which assumed constant room temperature. The terms zone load and space load are used throughout the reports to refer to results from this first stage of calculations. The term Zone Conditioning is used to refer to the results of the second stage of calculations. The Total Zone Loads are corrected to produce Zone Conditioning by accounting for room temperature and thermostat effects. As such, Zone Conditioning represents the true amount of cooling or heating a room needs and is the basis for simulating operation of system components such as coils and fans. Results from the system simulation appear in the lower part of the Air System Design Load Summary. Differences between Zone Loads and Zone Conditioning are therefore due to the room temperature effects on heat transfer such as pull down loads and temperature variations within the thermostat throttling range. Conclusion. The Transfer Function Method allows us to consider as many of the complex aspects of building heat flow as possible to provide accurate results, and at the same time provide a calculation tool that is fast and easy to use. The price for these benefits is that the calculation must be performed in two distinct stages. The first stage yields what HAP calls zone loads and space loads which are calculated assuming a constant room temperature. The second stage yields what HAP calls zone conditioning which is derived by correcting the original zone loads to account for room air temperature effects. Zone conditioning represents the true demand for cooling or heating in a zone. Understanding this twostage process and the results it yields is important for successfully applying program results.
194
Air System Design Load Summary for July 0900. Hourly Zone Design Day Loads for July
Figure 1 shows that the system with the economizer experiences an odd increase in cooling loads for 0700, 0800 and 0900. For the remainder of the day, coil loads for the systems with and without economizer have identical values. To determine the cause of this behavior, let us focus on system behavior for 0900. The Air System Design Load Summary for the system with economizer shows that the ventilation and supply airflow rates are equal for this hour. Therefore, the outdoor air economizer is operating and is fully open. The Hourly Zone Design Day Loads output shows that the zone air is at 77.7 F and 44% RH for 0900. Using plenum load data from the Air System Design Load Summary the return air condition (after the plenum) can be computed. The return air condition is 80.2 F (26.8 C) dry-bulb, 63.7 F (17.6 C) wet-bulb. This equates to a specific humidity of 0.0091 lb/lb (kg/kg). The outdoor air condition for this hour is 79.8 F (26.6 C) dry-bulb, 70.0 F (21.1 C) wet-bulb for a specific humidity of 0.0138 lb/lb (kg/kg). An integrated dry-bulb economizer activates whenever the return air dry-bulb is equal to or warmer than the outdoor air dry-bulb. Therefore, for July 0900 the economizer control should be activated. The economizer damper will modulate to the fully open position since it cannot eliminate mechanical cooling completely for this operating condition. While this will reduce the sensible cooling coil load by using outdoor air that is slightly cooler than return air, it introduces a large volume of outdoor air with high moisture content. As a result, the latent component of the cooling coil load soars. The increase in the latent load outweighs the reduction in the sensible coil load, and the ultimate result is a large increase in the total coil load.
195
196
This case illustrates the fact that at marginal conditions in which the outdoor air dry-bulb is only slightly cooler than the return air temperature, and outdoor air is relatively humid, integrated drybulb economizer control can increase rather than decrease system cooling coil loads. This case also illustrates one of the benefits of the system-based design approach used by HAP and the System Design Load Program. By considering specific components and controls in the design calculation, potential problems can be identified while the system is being designed Correcting the Problem. There are several solutions to this problem:
Use temperature cutoff limits on economizer operation. For example, if a cutoff of 75 F (23.9 C) is used, the economizer will not operate when the outdoor temperature is warmer than 75 F (29.3 C), even if the return air temperature exceeds the outdoor temperature. This cutoff helps to prevent economizer operation for marginal situations that lead to the problems discussed above. However, choosing a cutoff temperature, which will guarantee that all such problem conditions are avoided, is difficult and is highly application-dependent. Use an integrated enthalpy economizer control. With this control, return air enthalpy is compared with outdoor air enthalpy to determine when to activate the economizer. Because enthalpy accounts for the sensible and latent heat of air, the marginal conditions that lead to operating problems will be avoided. Use non-integrated control. This dry-bulb economizer control is only activated when the outdoor air is equal to or cooler than the supply air temperature. Since this control will not activate the economizer until all mechanical cooling can be eliminated, marginal situations involving partial free cooling are avoided. However, this solution sacrifices the large number of operating hours at warmer outdoor air temperatures for which an integrated economizer can reduce mechanical cooling demands.
Other Problem Situations. A similar sort of problem can occur for integrated enthalpy economizer controls used in hot, dry climates for marginal conditions. This type of control activates when the return air enthalpy is equal to or greater than the outdoor air enthalpy. In a hot, dry climate, it is possible for outdoor air enthalpy to be less than return air enthalpy; while at the same time the outdoor air dry-bulb is warmer than the return air dry-bulb. The enthalpy economizer will activate for such a condition, and will open fully. Outdoor air will eliminate the latent component of the cooling coil load, but can cause the sensible component to increase significantly. The symptom of this problem in design load calculations is similar to that for integrated dry-bulb controls - a peak load at an unusual time of day. The problem can be diagnosed using the same procedures discussed for the dry-bulb economizer. And the solutions are similar: impose cutoff points for operation, or switch to a different type of control better suited for the climate.
197
Differences Between Peak Coil Load CFM, Max Block CFM, Sum of Peak Zone CFM
In the cooling coil section of the HAP Air System Sizing Summary printout, three coil airflow rates are listed: (1) the coil airflow for the time when the maximum coil load occurs, and (2) the maximum block airflow rate and (3) sum of the peak zone CFM (L/s). When analyzing VAV systems, these three airflow rates can often differ. This article explains why. An accompanying article provides recommendations for selecting equipment in these situations. In most cases, the coil airflow rates differ in VAV applications for one of the following two reasons:
The peak cooling coil load and peak zone sensible load occur at different times, resulting in different coil airflow rates at these times. Due to the ASHRAE sizing methodology used by HAP, the two airflow rates are computed using slightly different considerations. This can introduce small differences between the two airflow values even if the coil load and zone sensible load peak at the same time.
Each reason will be explained separately below. Differences Due to Timing of Peak Loads. The maximum airflow rate required for the supply fan and therefore for the central cooling coil depends on the cooling requirements in zones served by the air system. The individual component loads in the zones such as wall, roof, window, solar, lighting, people and equipment loads influence zone cooling requirements. These loads vary due to changes in outdoor air temperature, solar radiation and internal heat gains throughout the day. While the maximum cooling coil load is influenced by these same zone cooling requirements, it is also influenced by extra heat gains introduced by outdoor ventilation air, fan heat, return plenum heat, and the latent components of the coil load. Because extra factors influence the coil load, it is possible for the maximum coil load to occur at a different time than the peak zone sensible load occurs. In a VAV system, the coil airflow varies as zone cooling requirements vary. Therefore, if the peak cooling coil load and peak zone sensible load occur at different times, the coil airflow rates for the two times will differ. The following simple example illustrates how this situation can occur. Example #1. Consider a 1-zone VAV system that serves an east-facing zone. Figure 1 shows 24hour profiles for the total cooling coil load and the zone sensible load for this system. The zone has a large area of east-facing glass. Consequently, solar heat is the dominant load component and causes the peak zone sensible load to occur at 9 am. The total cooling coil load in this example is strongly influenced by ventilation loads, which peak during the mid-afternoon hours. Since the outdoor air temperature is relatively cool at 9 am versus mid-afternoon, the peak coil load occurs at 2 pm rather than 9 am. When the peak zone sensible load occurs at 9 am, the zone requires 5154 CFM of supply air. When the cooling coil load peaks at 2 pm, the zone sensible load has dropped to approximately 80% of its peak value and the zone requires only 4100 CFM of supply air. For such a situation, HAP will report the following data on the Air System Sizing Summary output Peak coil load occurs at: ............. Jul 1400 Coil CFM (L/s) at Jul 1400: ......... 4100 CFM (1935 L/s) Maximum block CFM (L/s): ......... 5154 CFM (2432 L/s) Sum of peak zone CFM (L/s)5369 CFM (2534 L/s) The Sum of the peak zone CFM (L/s) is useful for judging diversity in VAV systems and for sizing components for special periods when all VAV box dampers are full open at the same time. Differences Due to Methodology. The ASHRAE design procedure, which utilizes the transfer function method and heat extraction techniques, requires a two-stage calculation:
HAP V 4.4 Advanced Training Seminar
198
1. First, zone sensible loads are computed assuming the zone is held exactly at the cooling thermostat set point 24 hours per day. Results from this analysis are used to determine peak zone airflow rates and the peak central coil airflow rate. 2. Second, the program simulates system operation. When doing so, it takes the zone loads calculated in the first stage and corrects them for the actual system operating conditions. These corrections account for the use of different thermostat setpoints during occupied and unoccupied periods or the shutdown of cooling during the unoccupied times, and for the existence of a throttling range for the thermostat. Considering these real-life system operating factors changes the thermal dynamics of the system, causing zone temperatures to vary within the thermostat throttling range and introducing pulldown load components at certain times of day. The "Max block CFM (L/s)" is calculated in stage 1 and is therefore based on the idealized zone loads computed in this stage. The coil airflow at the peak coil load time is obtained from stage 2, and is therefore based on the corrected zone loads computed considering the actual system operating conditions. Because the two airflows are computed using slightly different considerations, differences between the two airflows often occur for VAV systems. The following example illustrates these method-based effects.
199
Example #2. Consider a VAV system that serves four zones. Hourly profiles of the total coil load and the zone sensible block load are shown in Figure 2. Here "block load" refers to the sum of the sensible loads for all four zones. The maximum zone sensible block load occurs at 5 pm in July. Based on this block load, the required coil airflow rate is 13269 CFM. The maximum cooling coil load also occurs at 5 pm in July. For this hour the coil airflow rate is 12355 CFM. Therefore, on the Air System Sizing Summary, HAP will report: Peak coil load occurs at .............. Jul 1700 Coil CFM (L/s) at Jul 1700 .......... 12355 CFM Max block CFM (L/s) ................... 13269 CFM In this example, the 900 CFM (425 L/s) difference between airflows is due to the different considerations used to calculate the required fan airflow in stage 1 of the analysis, and the coil airflow during the system simulation in stage 2 of the analysis. Further investigation of the results showed that the zone air temperatures are close to 76 F (24.4 C), which is the upper limit of the thermostat throttling range for this example. For the initial zone loads calculated in stage 1 of the analysis, a thermostat setpoint of 75 F (23.9 C) was used. The difference in zone air temperatures used in the two calculations (75 F [23.9 C] versus 76 F [24.4 C]) and its effect on zone thermal dynamics ultimately results in lower coil airflow. The important thing to recognize is that each airflow is computed for different purposes and therefore uses different considerations. The maximum coil airflow is derived as part of the zone and fan airflow sizing calculation, which considers idealized conditions. The coil airflow at the time of the peak coil load is derived as part of the cooling coil analysis. This analysis considers all of the operating factors of the system, most notably the interaction between the zone thermostats and the VAV box dampers, and between zone air temperature and room loads.
200
Further Information. Differences between maximum coil airflow rate and coil airflow rate for the peak coil load time can also occur for Multizone, Bypass Multizone and Dual Duct CAV systems, and for single-zone constant volume systems using fan cycling.
Table 1
201
Equations and considerations involved in the calculation of these values are explained below. With this information, you should be able to duplicate computer calculations by hand. Ventilation CFM (L/s). The cooling ventilation airflow rate is for the month and hour for the cooling data on this printout. A separate airflow is listed for the design heating condition. In certain types of systems, the cooling and heating values will differ. For example, in a VAV air system using proportional control for ventilation air, the outdoor ventilation airflow varies as a constant percentage of supply fan airflow. Because the supply fan airflow rates for design cooling and heating conditions differ, ventilation airflow rates will differ. It is important to use the appropriate ventilation CFM (L/s) when calculating ventilation loads by hand. Cooling Sensible and Latent Loads. A ventilation load is the net heat gain or loss for the system due to outdoor ventilation air entering the system and exhaust air leaving the system. For conditions at sea level in which no direct exhaust is used, the common ventilation equations are: Qvs = 1.08 Voa (Toa - Tex) Qvl = 4746.6 Voa (oa - ex) In SI Metric units, these equations are: Qvs = 1.207 Voa (Toa - Tex) Qvl = 2946.7 Voa (oa - ex) where: Qvs 1.08 = = Sensible ventilation load, BTU/hr or W. Product of air density, specific heat of air and a units conversion factor in English Units. For sea level conditions. (0.075 lb/cuft)(0.24 BTU/lb-F)(60 min/hr) Product of air density, specific heat of air and a units conversion factor in SI Metric units. For sea level conditions. (1.201 kg/m3)(1004.8 J/kg-K)(m3/1000 L) Outdoor ventilation airflow rate, CFM or L/s. Outdoor air temperature, F or C. Exhaust air temperature, F or C. Latent ventilation load, BTU/hr or W. Product of air density, heat of vaporization for water and a units conversion factor. For sea level conditions. (0.075 lb/cuft)(1054.8 BTU/lbm)(60 min/hr) Product of air density, heat of vaporization for water and a units conversion factor in SI Metric units. For sea level conditions. (1.201 kg/m3)(2453.5 x 103 J/kg)(m3/1000 L)
oa
ex
=
=
202
When solving these equations, be aware of the following: The air density value used by the program is adjusted for site elevation. Thus, for sites not located at sea level, factors other than 1.08, 1.207, 4746.6 and 2946.7 are used. Equations used to adjust air density for elevation are discussed in the program help system and the Design Load User's Manual for HAP. The value of Tex is sometimes difficult to determine. First, the zone air temperature is often not equal to the cooling setpoint. Instead, it varies within the thermostat throttling range. Both the System Psychrometrics and Hourly Zone Design Day Cooling Loads reports list zone temperatures. For multiple zone systems, the mixed temperature for air exiting the zones must be considered. The System Psychrometrics report lists this value for air mixed from all the zones. In addition, after leaving the zone, air temperature can be affected by plenum heat gains and losses, return fan heat gain, duct leakage and heat transfer in ventilation reclaim devices. The effect of these heat gains or losses is shown on the System Psychrometrics report, culminating in the calculation of the exhaust air temperature Tex. If direct exhaust air is used, air will be exhausted from the system at two or more different temperatures (e.g. air directly exhausted from the zone and air exhausted after picking up plenum and other heat gains). Equations used in this situation are discussed in program help system and in the Design Load User's Manual for HAP.
Design Heating Sensible Load. The basic equations used for the heating analysis are the same as for the cooling sensible analysis, but with one exception. The convention that a positive heating load represents a heat loss requires that the position of the temperature and humidity values in the equation be switched: English Units: Qvs = 1.08 Voa (Tex - Toa) Qvl = 4746.6 Voa (ex - oa) SI Metric Units: Qvs = 1.207 Voa (Tex - Toa) Qvl = 2946.7 Voa (ex - oa) When solving these equations, be aware of the same considerations mentioned for cooling:
Air density adjustment for altitude. Problems with determining Tex. Complications introduced by direct exhaust air.
As with cooling, the System Psychrometrics report lists the key temperature and humidity components used in these calculations.
203
Sizing Overview. In HAP, sizing calculations are performed for all system types using the following three-step procedure: Size Zone Airflows. Zones are dealt with separately to determine peak sensible loads and required airflow rates. Size Supply Fan Airflow. Zone airflow requirements are then combined to determine the maximum supply fan airflow requirement. Size Coils. Given user specifications of air system characteristics plus the calculated zone and fan sizing data, the program simulates operation of the system for design cooling conditions each month. A simulation is also performed for the design heating condition. Coil loads resulting from these simulations are inspected to identify the maximum load for each coil in the system. These are reported on program outputs. the paragraphs below, each of these steps will be discussed in detail.
In
204
Step 1: Zone Airflow Sizing. The goal of this step is to identify the maximum sensible load and maximum airflow rate for each zone in the system. To do this the program deals with each zone separately. Using space and zone input data and ASHRAE transfer function procedures; the program calculates heat gains for all heat sources in a zone and converts the heat gains to "cooling loads". Per ASHRAE procedures, these cooling loads are based on the assumption that cooling equipment operates 24 hours per day and that the zone is maintained exactly at the cooling thermostat setpoint. Thus, these cooling loads are idealized unless the system will actually operate this way. This simplifying assumption will be compensated for later during the coil simulations using the heat extraction procedure. After calculating loads for all design cooling months specified, the program searches the data to identify the maximum zone sensible cooling load. For a given supply air temperature, the program calculates the required airflow rate to satisfy this load. Results of the zone airflow sizing analysis appear on the Zone Sizing Summary report. Zone sensible loads from this analysis also appear on the Air System Design Load Summary, Zone Design Load Summary and Hourly Zone Design Day Loads reports. On these reports, the cooling loads are interchangeably referred to as "zone load" and "zone sensible. Step 2: Fan Airflow Sizing. The goal of this sizing step is to determine the maximum airflow requirement for the central supply fan. This is the first calculation in which system-based sizing is involved. For a CAV system, the program adds peak CFMs (L/s) for all zones to determine the required supply fan airflow. For VAV systems, the program identifies the peak coincident CFM (L/s). This is done by first using zone sensible load data from the previous step to determine require airflow rates for each hour of the day. Hourly airflow requirements for each zone are then added together to build a fan airflow profile. Finally, the program searches this profile to find the maximum airflow rate.
205
Figure 1 illustrates this calculation for a VAV system. Zone airflow rates are shown in this figure for an east-facing zone and a west-facing zone. For each hour, the sum of east and west zone airflow rates is the required fan airflow rate. In Figure 1, the east zone peaks at 0900 with a 6252 CFM (2950 L/s) requirement, the west zone peaks at 1700 with a 6989 CFM (3298 L/s) requirement, and the supply fan peaks at 1600 with a 10213 CFM (4820 L/s) requirement. Note that this VAV fan airflow is 23% less than the 13241 CFM (6248 L/s) that would be required for a CAV system. Because a VAV system can take advantage of load diversity, its design airflow can often be less than the sum of peak zone CFMs (L/s). When a VAV air system is specified in HAP, the system-based sizing procedure automatically considers this. Step 3: Coil Sizing Calculations. The goal of the final sizing step is to determine maximum loads for all coils in the air system. Performing detailed simulations of air system operation for each design cooling month and the design heating condition does this. Air system input data, the airflow rates and zone sensible load profiles calculated in steps 1 and 2, and ASHRAE heat extraction procedures are used to perform these simulations. Simulations are specific to the type of system being dealt with and consider all system components and controls specified. The zone sensible load profiles calculated in step 1 are the basis for system simulations. As noted earlier, these load profiles were calculated assuming 24-hour equipment operation and a constant zone temperature equal to the occupied cooling thermostat setpoint. Consequently, these load profiles must be adjusted using the ASHRAE heat extraction equations if cooling equipment is operated for less than 24 hours, if an unoccupied period set-up temperature is used, if cooling equipment is shut down during the unoccupied period and if a thermostat throttling range other than 0 F (-17.8 C) is used. The heat extraction calculations yield the amount of heat the air conditioning system must remove each hour to maintain the zone in the thermostat throttling range. Once zone heat extraction rates have been computed, this data serves as the basis for calculations of airflow rates, temperatures and humidity at all points in the air system. Finally, these results allow loads for coils in the system to be determined. For example, the cooling coil inlet and outlet dry-bulb temperatures and the coil airflow rate are used to calculate the sensible coil load. Figure 2 provides sample results from a design simulation for a single-zone CAV air system. The figure provides a useful comparison between zone sensible loads, heat extraction rates (called "zone conditioning") and sensible and total cooling coil loads. The "zone sensible" load profile represents sensible cooling loads assuming 24-hour equipment operation and a constant 75 F (23.9 C) zone air temperature. The "zone conditioning" profile represents heat extracted from the zone during the 6am-7pm operating period (from 8pm to 5am the cooling system is off). During this operating cycle, the zone air temperature varies within in the 75 F (23.9 C) - 78 F (25.5 C) throttling range during the 6am-7pm operating period, and floats at higher temperatures during the nighttime shutdown period. Heat extraction method estimates of zone air temperature are shown in Figure 3. As a result of this behavior, extra load is imposed on the air conditioning equipment to pull down the zone air temperature and to remove heat that has accumulated in the building mass during the nighttime period. This pulldown load is the principal reason for differences between the zone sensible and zone conditioning profiles in Figure 2. Note that these differences are most significant at the start of the operating period, but also continue throughout the 13-hour operating period. The coil sensible profile in Figure 2 represents the sensible heat that must be removed at the central cooling coil. In addition to providing enough sensible cooling to meet zone-conditioning demands, the coil must also provide cooling to offset fan heat gain, sensible ventilation load and the portion of plenum heat gains that returns to the coil. These factors cause the coil sensible profile in Figure 2 to exceed than the zone conditioning profile for all hours. Finally, the total coil load profile in Figure 2 represents total heat removal at the cooling coil. The difference between the total and sensible coil profiles is the latent cooling provided by the coil.
206
Results from the coil sizing analysis are reported on the Air System Sizing Summary. Zone conditioning and coil load data are also provided on the Air System Design Load Summary and Hourly Air System Design Day Loads reports. Zone temperatures and zone conditioning are listed on Hourly Zone Design Day Loads reports. Implication: Performance-Based Coil Estimate. While it is useful to understand the sizing procedures used in HAP, it is even more important to recognize the implications of the procedures. The most significant of these is that the system simulation technique used yields a "performance-based" estimate of peak coil loads. By this, we mean that the calculation considers all system controls and operating variables. Perhaps most important among these is the variation of zone temperature. As noted earlier, zone temperature will vary during the unoccupied set-up or shutdown period, and within the thermostat throttling range during the occupied period. In Figure 3, for example, zone temperatures lie toward the upper end of the 3 F (-16.1) thermostat throttling range during the 13-hour occupied operating period. This is not necessarily always the case. If unoccupied cooling at a set-up temperature was provided, or 24-hour cooling was provided, the pulldown load component would be less severe or eliminated altogether and zone temperatures would tend to lie closer to the bottom of the throttling range. These temperature variations may or may not be desired by the designer. On one hand, some designers wish to consider actual operating characteristics in the calculation, including zone temperature variations, and are therefore comfortable with a performance-based calculation. Others may want to use idealized conditions with the zone temperature fixed exactly at a single setpoint temperature.
207
208
While the performance-based nature of the coil simulations cannot be eliminated completely, using a throttling range of 0.1 F (-17.7 C) can minimize it. Note that a finite throttling range is required by the heat extraction method. Without it, the analysis cannot be performed and pulldown loads cannot be computed; 0.1 F (-17.7 C) is the minimum allowed by the program. Using this throttling range will have an effect both on the zone conditioning and cooling coil loads calculated, as well as the estimates of zone temperatures. Results from the single-zone CAV example for both 3 F (-16.1 C) and 0.1 F (-17.7 C) throttling ranges are shown in Figures 4 and 5. Use of the 0.1 F (-17.7 C) throttling range results in a peak cooling coil load that is 4% larger than the 3 F (-16.1 C) throttling range case. It also results in estimated zone temperatures closer to the 75 F (23.9 C) cooling setpoint as shown in Figure 5. Thus, system based design using the heat extraction method offers powerful, sophisticated capabilities to user. But to successfully use the heat extraction method, a designer must understand the procedure and its implications.
209
210
211
Appendix D
The Benefits of System-Based Design
212
Introduction
In 1993 Carrier incorporated system-based design features in its Hourly Analysis Program (HAP) software. At the time, system-based design was a new concept that allowed the computer to do a more complete and accurate job of sizing equipment than the traditional load estimating approach. Ten years later, this approach still yields significant benefits to HVAC system designers because of the productivity advantage it offers. And even today it still serves to differentiate HAP from other load estimating and system design software on the market. This paper explains system-based design and its benefits. First the paper discusses how traditional system design methods work and the shortcomings of the traditional approach. Next, the concept of system-based design is explained, and the benefits it offers are explored.
Computes zone sensible cooling loads for all zones for a series of design cooling months. Identifies the maximum zone sensible load for each zone in order to calculate required zone airflow rates and the required supply fan airflow rate. Calculates central cooling coil loads for the months being considered in order to identify the maximum cooling coil load. If the system also provides heating, calculations are performed to determine the maximum heating coil load.
This procedure yields data useful for sizing terminal diffusers, the supply fan, the central cooling coil, and the central heating coil.
213
diversified peak airflow to zones, rather than the sum of zone airflows. The terminal reheat coils are sized using a procedure that is different from sizing a central heating coil. A VAV Fan Powered Mixing Box system serving multiple zones requires that supply diffusers, mixing box terminals, the supply fan and the central cooling coil be sized. Unlike other systems, the terminal equipment for this system includes both a fan and a reheat coil, both of which must be sized. Sizing procedures differ slightly depending on whether a series mixing box or parallel mixing box terminal is used. A 2-Fan Dual Duct VAV system serving multiple zones requires that supply diffusers, mixing box terminals, the cold deck supply fan, the hot deck supply fan, the cold deck cooling coil and the hot deck heating coil all be sized. This system contains a unique configuration of components not found in other systems. Procedures tailored to this type of system must be used to properly size the equipment.
The second problem with the traditional approach involves accuracy. If the traditional approach is used to size a system such as series Fan-Powered Mixing Box or 2-Fan Dual Duct, additional hand calculations will be required to size components not addressed by the calculation. These additional hand calculations make the design more difficult, more time consuming and prone to error. In more complex situations, sizing is often approximated to save time. Thus, the traditional approach plus hand calculations is often less accurate than a computerized approach that considers system type and does a complete job.
Input weather data. Input building construction, internal heat gain and layout information. Define the HVAC system. In addition to thermostat setpoints and sizing criteria, the engineer specifies exactly what type of HVAC system is involved and its attributes. For example, it could be VAV Reheat, VAV with baseboard heat, Series Fan Powered Mixing Box, Dual Duct VAV, etc...
Next, the system-based design computer program calculates loads and sizes system components:
214
1. Zone Load Calculation. The program first calculates hourly zone sensible cooling loads for all zones for the design cooling months being considered. 2. Zone Airflow Sizing. The program then identifies maximum zone sensible loads in order to determine required zone supply airflow rates and required central fan airflow rates. For some systems, such as fan powered mixing box systems, special aspects of system operation may influence the required airflow rates. 3. System Simulation. Once system airflows have been determined, the program simulates the hour-by-hour operation of the HVAC system and all its components to determine loads for all coils in the system. This mathematical simulation considers the interplay of component operation for the specific system being studied. Simulations are performed for the range of design cooling months specified by the designer and for the heating design condition. 4. Coil Sizing. Finally, the program searches results of system simulation to determine maximum required size for each component coil in the system. Benefits of System-Based Design The major benefit of the system-based design approach, of course, is that it gives the engineer exactly what is needed to design a system. Specific sizing data is provided instead of raw material for further hand calculations. The result is increased productivity for the designer because the computer is being put to work more effectively. The computer does a complete job of system sizing, not a partial job. A related benefit is that the system-based approach does a more accurate and therefore reliable job of generating sizing data. This is because sizing calculations consider the specific operating nature of the system, not the features of a simple, generic system. Further, the approach can evaluate more operating conditions than can be checked by hand, so that the approach is more thorough and comprehensive. Finally, because detailed, dynamic system simulations are part of this approach, the method can potentially be used to investigate the effect on sizing of such devices and controls as: Outdoor air ventilation energy recovery devices. Outdoor air economizers. Active dehumidification and humidification controls. Night-time free cooling controls.
Previously, such controls have only been evaluated in energy analysis simulations to determine effects on operating costs. But each can also have an effect on sizing which in turn can have a significant effect the first cost of the system.
CONCLUSION
Even though the concept is no longer brand new, system-based design still represents a promising advance in the field of HVAC system design. It offers improvements in productivity and accuracy, and opens new avenues of investigation to the designer in the pursuit of the optimal design. Look for it when choosing your HVAC design tools.
215
216
Introduction
As energy costs rise, building owners are becoming increasingly interested in operating costs and energy efficiency. As a result, building energy analysis (BEA) is becoming an important tool in the HVAC design field. Currently many BEA tools are available to engineers. Most are in the form of computer programs and employ a variety of methods with different benefits. Among these, BEA tools such as Carrier's HAP program that use the 8760 hour-by-hour method can offer the greatest benefits because they yield highly accurate, sophisticated system comparisons. This article will discuss the benefits of 8760 hour building energy analysis by first explaining the basics of building energy analysis and the requirements for high quality BEA system comparisons. Then, major BEA methods will be evaluated with special emphasis on the benefits of 8760 hour-byhour versus reduced hour-by-hour methods.
influencing building loads and equipment performance as possible. The ultimate result of the analysis is a predicted operating cost. An accurate cost prediction relies on energy use data, which in turn relies on equipment simulations, which must be based on building load predictions, all of which must be accurate. Concisely stated, high quality results can be obtained when the analysis considers: 1. The Range and Timing of Weather Conditions. Varying levels of temperature, humidity and solar radiation during the year influence building loads and equipment performance. In each geographical location conditions range from hot to cold, wet to dry and sunny to cloudy in different ways. Considering the actual ranges of these conditions and when they occur on a daily, monthly and yearly basis is crucial to producing accurate energy use results. 2. The Hourly and Daily Variation in Internal Loads. Patterns of building use involving occupancy, lighting and equipment operation can change significantly from one day to the next. Considering these use patterns in their correct day-to-day sequence is important in generating accurate load data. 3. The Dynamic Nature of Building Heat Transfer. The process of converting heat gains and losses to cooling and heating loads is a transient rather than a steadystate process. Heat gains occurring during one hour often affect loads over a number of succeeding hours. Consequently, it is important to consider accurate sequences of heat gains occurring during the day. In addition, because weather conditions and building use profiles vary from day to day, sequences of heat gains can affect loads from one day to the next. 4. The Response and Performance of HVAC Equipment. How controls, systems and equipment respond to demands for cooling and heating in a building, and the factors that affect part-
217
load performance of the equipment must be considered to yield accurate equipment energy use data. 5. The Details Of How Utilities Charge For Energy Use. Often prices for energy vary by season and time of day. Further, charges are often made for peak energy usage. As a result, the analysis must not only be able to produce accurate estimates of how much energy is used, but must also accurately determine when during the day energy is used. Evaluation of BEA Methods A wide variety of building energy analysis methods are currently available to HVAC engineers and range from simple to sophisticated. The simplest methods involve the largest number of simplifying assumptions and therefore tend to be the least accurate. The most sophisticated methods involve the fewest assumptions and thus can provide the most accurate results. Generally, BEA methods are divided into three categories: a) Single Measure Methods (example: Equivalent Full Load Hours) b) Simplified Multiple Measure Methods (example: Bin Method) c) Detailed Multiple Measure Method (example: Hour by Hour) While methods in the first two categories serve a useful role in providing quick, preliminary energy estimates, the simplifications they involve impair their accuracy. Each will be briefly discussed below. The main focus of the following discussions, however, will be the different hour by hour methods contained in the third category.
efficiency and equivalent full load hours to obtain annual energy use. In both cases, this level of simplicity is achieved by using such sweeping assumptions that the accuracy and reliability of these methods are very limited.
Simplified Multiple Measure Methods These methods involve calculations of energy use at several different conditions. With the Bin Method, for example, energy use is computed at a series of outdoor air dry-bulb conditions. Results are then weighted according to the number of hours each dry-bulb condition is expected to occur to determine annual energy use. For example, the temperature 47 F would be used to represent the range of conditions between 45 F and 50 F, referred to as a "bin". Building loads and equipment energy use would first be calculated for the 47 F bin. Next, energy results would be multiplied the number of hours per year temperatures are expected to occur between 45 F and 50 F to determine annual energy use for that bin. Similar calculations would then be repeated for all other temperature bins for the local climate and would be summed to determine overall annual energy use. While the Bin Method provides a vast improvement in sophistication over single measure methods, it has a fatal flaw. This flaw is that it must decouple weather conditions, loads and system operation from time. For example, hours in the 47 F bin, when the outdoor dry-bulb is between 45 F and 50 F, occur at a variety of times of day and night, days of the week and months of the year. Because a single calculation is performed to represent energy use for all these different times it is difficult or even impossible to accurately: a) Link solar radiation and humidity conditions to the bin. b) Consider hourly and daily variations in internal loads. c) Consider the transient hour to hour and day to day thermal performance of the building.
Copyright Carrier Corp. 2008
Single Measure Methods These methods involve one calculation of annual or seasonal energy use. The DegreeDay Method, for example, computes energy use by combining one degree-day weather value with a load value and an efficiency value to obtain seasonal or annual energy use. Similarly, the Equivalent Full Load Hour Method combines full load capacity, full load
HAP V 4.4 Advanced Training Seminar
218
d) Predict time-of-day energy use and peak demands. Inevitably averaging assumptions must be made to shoehorn all these considerations into the framework of the bin analysis. And these assumptions impair accuracy. While the Bin Method is useful for simple, preliminary estimates of energy use and operating cost, it cannot provide the level of accuracy and sophistication offered by the detailed multiple measure methods.
weather profile is still used for all three typical day simulations each month. b) Some methods also analyze equipment operation for a hot and cold day each month in an attempt to improve estimates of peak electrical demand. c) Some methods simulate building operation for one 7-day week each month to try to account for day-to-day building dynamics. However, a one average weather profile is still used for all 7 days of the simulation. The fundamental principle of this method is that building and equipment performance on hotter and colder than normal days each month averages out so that monthly energy use can be accurately predicted by simulating a small group of days using average weather conditions. The method offers the benefits of reduced calculation time and more moderate demands on computer memory and hard disk storage space.
219
detailed data about the quantity and timing of energy use. Both are requirements for accurate operating cost estimates.
days. Because only average winter weather is considered, most or all of the heating duty for the year may be missed by an averageday simulation approach. Finally, "linear" behavior is a requirement for averaging to be accurate. For example, if cooling loads are 20% larger when the temperature is 15 F warmer than average, and 20% smaller when the temperature is 15 F cooler than average, cooling loads are linearly proportional to outdoor temperature. Averaging of the warm day and cool day loads will result in loads similar to those produced by simulating only the average weather day. However, loads depend on more than just outdoor temperature. Solar radiation, internal loads and hour-to-hour and day-to-day dynamic behavior also affect loads and often result in non-linear behavior. Another example involves cooling equipment. If equipment input kW decreases 8% for every 10% drop in part-load ratio, input kW and load are linearly proportional. If this relationship holds true, simulation of equipment performance for one average day per month has the best chance of accurately approximating equipment performance on the collection of hot, average and cool days during the month. Unfortunately, the performance of equipment is often non-linear due to part-load, entering condenser temperature and other performance factors. Consequently, the accuracy of the average day approach can be degraded when equipment behavior is non-linear. The 8760-hour method avoids these problems by simulating building and equipment operation for the entire month. Actual weather data used by the simulation consists of a collection of days, all with different combinations of temperature, humidity and sunshine. Figures 1 and 2 provide an example of this kind of data for the month of September in Chicago. Figure 1 demonstrates the way drybulb temperatures can vary during a month. The dotted lines in this figure are the upper and lower limits of the average temperature profile for the month that would be used by
220
the reduced hour-by-hour method. Comparison of the average and actual data shows a significant number of hours outside the range of conditions considered by the average day simulation approach.
Further, because a full month of days are simulated, the appropriate factors influencing equipment performance are considered. There is no reliance on the assumption of "continuous" or "linear" behavior, and the estimates of monthly energy use can be highly accurate. 2. Higher Quality System Comparisons. The issues discussed under item (1) affect not only the accuracy of monthly energy estimates, but also the quality of system comparisons. This is because many of the system design alternatives commonly considered exhibit behavior that is both discontinuous and non-linear.
"Discontinuous" refers to inconsistent operation. That is, operation that starts and stops rather than continuing for all operating conditions during a month. "Non-linear" refers to the fact that there is often not a simple proportional relationship between load or outdoor temperature and equipment performance, as discussed in item (1). A comparison of air handling systems with and without a non-integrated outdoor air economizer provides a good illustration of this problem. With this type of economizer control, economizer dampers open when outdoor air temperature drops below the supply air temperature. The system can then immediately use outdoor air for free cooling; mechanical cooling can be turned off. For this example, assume the supply air temperature is 57 F and that we are simulating system operation for the weather data shown in Figure 1. The dotted lines in this figure indicate the upper and lower limits of an average temperature profile for the month. Because this average profile ranges between 58 F and 75 F, a simulation using the reduced hour-by-hour approach would never find a condition when the economizer dampers opened during September; free cooling would never be available. However, with the 8760 hour method, the use of actual temperature profiles for the month result in 119 hours during 13 days when temperatures drop below 57 F. If cooling loads exist during these times, the economizer would operate to provide free
Likewise, Figure 2 demonstrates the variation of solar radiation profiles during the month. The dotted line indicates the maximum solar flux in the average day profile used by the reduced hour-by-hour method. Once again, there are many conditions with greater sunshine and less sunshine than considered by the average day approach. More importantly, comparison of the peaks and valleys in Figures 1 and 2 shows that hot days are not always sunny, and cool days are not always cloudy. The diverse collection of hot, cold, sunny, cloudy and in between conditions shown in these figures illustrates the complex nature of actual weather data and provides evidence that building loads will not be a simple linear function of outdoor air temperature. By considering a diverse collection of weather conditions each month, the 8760 hour method produces a diverse, realistic set of cooling and heating loads for the month.
HAP V 4.4 Advanced Training Seminar
221
cooling. Therefore, because an economizer exhibits discontinuous operation, turning on and off at specific conditions, the reduced hour-by-hour approach may not be able to successfully account for its operation. In our example the reduced hour-by-hour method would underestimate the benefit of the economizer. Similar situations can exist for other system components and controls that involve discontinuous, on/off behavior. Examples include ventilation heat reclaim, supply air reset, humidity control, cooling tower fan cycling, and loading and unloading of chiller networks as well as many others. 3. More Accurate Load Histories. The fact that the 8760 hour method simulates building thermal performance day to day for the entire year means it can correctly account for day to day dynamic load behavior. This results in more accurate load profiles, which ultimately lead to more accurate energy use predictions. For example, on a Monday morning in the summer, pulldown loads tend to be larger than on other days of the week due to the heat accumulated by the building mass during the weekend. In addition to resulting in larger cooling loads, these conditions can sometimes set the monthly electric demand. In reduced hour-by-hour methods that do not simulate a full week of operation, each day is simulated separately from all other days. Consequently, day to day building dynamics cannot be considered, and the building load histories are more simplistic. In those reduced hour-by-hour methods that do simulate a 7-day sequence each month, results tend to be unrealistic since the same average weather profile is used for all 7 days. 4. Higher Quality Time Of Use Energy Data. Because of the diverse weather conditions and operating conditions, and because of the dynamic nature of building heat transfer, 8760 hour methods can produce energy use data that not only accurately defines how
HAP V 4.4 Advanced Training Seminar
much energy is used, but when during the day and week the energy is used. When energy prices vary with time of day, accuracy of the timing of energy use is critical for producing accurate operating cost data. 5. More Accurate Estimates of Peak Demand. Finally, by considering the full range of weather and operating conditions experienced by a building during a month, the 8760 hour method is able to produce more accurate estimates of peak energy demand. When utility rates include a demand charge component, a significant part of the energy cost can be due to the peak energy use rather than the quantity of energy used. Many reduced hour-by-hour methods must determine demands from average day simulations which tend to underestimate demand values. Those methods that add consideration of hot and cold day weather profiles can provide an improvement in demand estimates. However, it is important to recognize that demand will be dependant on more than just the outdoor air temperature. Solar radiation, internal loads, building use profiles and day to day building dynamics also play an important role. The 8760-hour method is the only method that can simultaneously consider all these factors. Thus, while the Reduced Hour-By-Hour Method considers many of the factors required for high-quality energy estimates, certain aspects of the method are flawed and can limit the accuracy of the method. Because the 8760 hour method uses a more detailed, comprehensive approach to building simulation, it can consistently overcome these problems to provide accurate, reliable energy estimates.
Conclusion
This article has discussed the important benefits of the 8760 hour-by-hour building energy analysis method. This method is certainly not new. Computer programs using this method have been available for nearly three decades. However, because many of these programs were developed on mainframe computers as research tools, the
222
programs, and by association, the 8760 hour method itself acquired a reputation of being complicated, difficult and impractical to use. It is important to note that these are problems with the implementation of the 8760 hour method, not with the method itself. If the 8760 hour method is implemented in a well-designed, welldocumented microcomputer program, the 8760 hour method can be as easy to learn and use as reduced hour-by-hour methods. In developing Carrier's Hourly Analysis Program we have put two decades worth of experience in the HVAC software field to work to produce an 8760 hour energy analysis tool that is both powerful and easy to use. The resulting program maximizes the benefits of the 8760 hour method while minimizing or even eliminating costs traditionally associated with use of this method.
223
Notes
224
HAP V 4.4 Advanced Training Seminar
225
Carrier Corporation P.O. Box 4808, Bldg. TR-4, Room 400A Syracuse, NY 13221 Phone: 800.253.1794 Fax: 315.432.6844 eMail: software.systems@carrier.utc.com
226