Prime Electric Ltd.

Transformer Engineering Division Purchase Specification: PS 2016 Title: 24 kV Post insulators

Page 1 of 2

No. 1

Issue Date 01062010

Revision No. Date -

Issued by KVP

1. Scope
This specification covers the standard specifications of 24kV Post Insulators used in transformers for support of Neutral grounding bar for star connected solidly earthed neutral system (38 kV AC class).

2. Application
a) A post insulator consists of one Post insulator unit or an assembly of such units and is intended to give rigid support to a live part which is to be insulated from earth or from another live part. b) The most important function is to support and isolate from tank the Neutral grounding bar, which runs from neutral bushing down to earth level for connection to the site earthing system. c) These are also used to form neutral of three single phase transformers.

3. General Requirements
a) The Specifications of 24 kV Post Insulator shall confirm to IS: 2544 and dimensions are to IS: 5350 (Part III). b) The porcelain shall be sound free from defects, thoroughly vitrified and smoothly gazed. c) Unless otherwise specified, the glaze shall be brown in colour. d) The finished galvanized surfaces of all ferrous metal parts shall be smooth. e) The post insulator unit shall be assembled in a suitable jig to ensure the correct positioning of the top and bottom metal fittings relative to one another.

4. Standard Insulators
4.1 Overall Dimensions Overall Dimensions of 24 kV Post Insulator are as given below: 24 kV Post Insulator

Prime Electric Ltd. Transformer Engineering Division Purchase Specification: PS 2016 Title: 24 kV Post insulators

Page 2 of 2

No. 1

Issue Date 01062010

Revision No. Date -

Issued by KVP

4.2 Specifications Description


Highest system voltage Creepage Distance, min Creepage Distance Protected

Standard specification
24 kV 430 mm 240 mm

Prime Electric Ltd. Transformer Engineering Division Purchase Specification: PS 2016 Title: 24 kV Post insulators

Page 3 of 2

No. 1

Issue Date 01062010

Revision No. Date -

Issued by KVP

Visible Discharge voltage Impulse withstand voltage Dry Power frequency withstand voltage Wet Power frequency withstand voltage Cantilever Strength upright Under hung Tensile Strength Compression strength Torsional strength Total weight (approximately) Standard Drawing

18 kV 125 kV 55 kV 55 kV 920 kgf (9000 N) 700 kgf (6800 N) 3060 kgf (30000 N) 4100 kgf (40000 N) 70 kgfm (680 Nm) 8 kg 4 SD 04 0011

(Note: Unless otherwise specified by the customer, 24 kV Post Insulator shall be used for all ratings of the Transformers.)

5. Test Requirements
Test requirements of Post Insulators shall confirm to section 9 of IS: 2544.

6. References
a) IS:2544 1973, Specification for Porcelain Post Insulators for systems with nominal voltages greater than 1000 V b) IS: 5350 (Part-III), Dimensions of Indoor and outdoor Porcelain Insulators and Post Insulator units for systems with nominal voltages greater than 1000 V