LA501-2T

LAW-CHAIN

2-stage Compressor Chiller Controller

Log Set LA501-2T


LAW - CHAIN

Panel

Specifications Temperature range : -50~+80.0 Input voltage12V/AC/DC/50~60HZ Display : 7 segment LED Working temperature : -15~+70 Mounting : snap-in Accuracy : 1 3 Fit-in size : 70*28*64mm Resolution : 0.1C Maximum output : 10A/250V (Resistance load)
Parameter setting: No. Symbol Description Parameter Compressor stop temperature 1. Temperature setting tS1 Temperature difference to restart compressor Differential temperature 2. td1 Compressor start-up delay time 3. Compressor start-up delay Sd Differential temperature between two compressors Temperature difference 4. tt 5. Start-up time difference Start-up time difference between two compressors when power on SS Compressor stops when water temperature in chiller outlet is 6. Antifreeze temperature tS2 lower than this setting. (available only when UF is set to y) Temperature difference for compressor to restart. Compressor will Antifreeze temperature 7. restart after the temperature is higher than ts2+td2 td2 difference (available only when rS is set to At) 8. tn Range -50~+80.0 +0.1~+15.0 0~15 min +0.1~+15.0 0~180 sec -50~+80.0 +0.1~+15.0 bd: when temperature is reached bt: by running time -10~+10.0 1~250 hours Default +12.0 +2.0 2 min +1.0 30 sec +2.0 +3.0

Rotation mode

The condition to change compressors start-up order

bt 0.0 100 hours

Sensor calibration adjustment 9. Temperature calibration tA Compressor rotation time 10. Rotation time ti Note: 1. Parameter tS2 and td2 are available only when parameter UF is set to y. 2. Parameter tn is available only when parameter dt is set to y. 3. Parameter ti is available only when parameter tn is set to bt.

Protective parameter setting: No.


1 2 3 4 5 6 7

Symbol
LO tH tL HC UF rS dt

Parameter Parameters protection The highest temperature The lowest temperature Cool/Heat mode Antifreeze mode Reset mode Compressor rotation

Description
Whether parameter protection is needed The highest temperature limit of ts1 The lowest temperature limit of ts1 Cool control or heat control Whether the function of antifreeze is adopted To reset the controller automatically or manually after compressor stop caused by a low temperature is detected to use rotation function

Range

Default

y:lock / n:unlock y tS1 ~ +80.0C +50.0C -50C ~ tS1 -50C Ht: heat control mode CL CL: cool control mode y: yes, n: no Y At: Auto, nL: manual y/n nL y

Notes: 1. Rotation time is counted by compressors running hours. When a compressors total running time reaches the rotation time setting, the controller will change compressors start-up order. 2. Presskey to show temperature of S2 when UF is set to y. 3. rS is available only when UF is set to y. 4. When rS is set to nL , pressLogkey to reset and back to normal operation. Error codes: Error code Chilling water Sensor Defrost Sensor E1H E1L E2H E2L UF Description Sensor shorted or the temperature is higher than +80.0C Sensor opened or the temperature is lower than -50C. Sensor shorted or the temperature is higher than +80.0C Sensor opened or the temperature is lower than -50C The temperature of water outlet is lower than ts2 setting.

Antifreeze

1050008 REV:2 C,S:C9B7H 070910

LA501-2T
LAW-CHAIN

2-stage Compressor Chiller Controller

Parameter setting operation: 1. PressSETagain to enter parameter mode and show the first parametertH.PressSETto show the value and then using and to adjust parameter value. After the value is set, pressSETto enter the next parameter. By repeating the operations as above till the last parameter, pressSETagain then the setting is saved. At this time, the display flashes god and shows the current temperature. 2. During parameter setting, the display will show god and returns to the normal display page without pressingSET,or in 30sec. 3. SET keyWhen entering parameter setting, use this key to choose parameters quickly. 4. When sensor short or broke circuits, the display will show error code until the breakdown is eliminated. Protective parameter setting operation: 1. PressSETkey, the display begins flashing pattern 888. While flashing, press andkeys simultaneously to enter protective parameters settingsLO. PressSETand then using andto chooseyorn.(y Locked , n Unlocked) 2. PressSETagain to enter parameter mode and show the first parametertH.PressSETto show the value and then using andto adjust parameter value. After the value is set, pressSETto enter the next parameter. By repeating the operations as above till the last parameter, pressSETagain then the setting is saved. At this time, the display flashes god and shows the current temperature. 3. During parameter setting, the display will show god and returns to the normal display page without pressingSET,or in 30sec. 4. During compressor stop for antifreeze, if rs is set to At (Auto reset), and system temperature reaches the setting temperature (td2), the system will reset automatically. If rs is set to nL (manual reset), compressor will stop because of the lower temperature which is detected, and it needs to press Log key to reset (tSt). 5. LogkeyExit parameter settings immediately and back to normal operation. Other operation: Compressor total running timepress both and keys simultaneously. The display will show symbol tot and numbers to indicate the total running time. For example, if display shows tot, 001, 234, it means the total running time is 1234 hours. Function keys LED Indicators
Increase/Decrease Set Exit To increase or decrease value Request for setting the parameter Exit parameter settings immediately Green Lamp flashes, compressor stands by Lamp on, compressor is running

Sensor specifications:
1.5M 4.5cm 6

C o r r e c t c o n n e c tio n m e th o d

S i g n a l w i r e w it h w h i te P V C j a c k e t

E x t e n d e d w ir e S h ie l d in g

I s o la t io n w i r e ( G r o u n d w ir e ) w it h b la c k o r r e d P V C ja c k e t

S ig n a l w ir e C o n n e c ts to t h e te r m in a l o n th e G ro u n d c o n t r o ll e r w ire

1.Isolation wire NTC sensor with BLACK PVC/1.5M/4.5cm 6 copper head 2.Isolation wire NTC sensor with RED PVC/1.5M/4.5cm 6 copper head

If you want to lengthen the NTC sensor probe, for isolating the noise, the extension wire must be shielded, and use the shielded wire as the ground wire. (as shown above).

Wiring diagram

Black Sensor (Chilling water sensor)s shield needs to connect to PIN 3 (for grounding purpose).

1050008 REV:2 C,S:C9B7H 070910