Sei sulla pagina 1di 4

TECHNICAL CORRECTION

February 2001

Process Industry Practices Piping

PIP PN01PV0C01 Piping Material Specification 1PV0C01 Poly (Vinyl Chloride) (PVC), 0.000" C.A. Process

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice.

This Practice is subject to revision at any time by the responsible Function Team and will be reviewed every 5 years. This Practice will be revised, reaffirmed, or withdrawn. Information on whether this Practice has been revised may be found at http://www.pip.org.

2001 Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3208 Red River Street, Suite 300, Austin, Texas 78705. PIP member companies and subscribers may copy this Practice for their internal use.

PRINTING HISTORY April 1999 June 1999 Issued Revision February 2001 Technical Correction

Not printed with State funds

TECHNICAL CORRECTION
February 2001
SERVICE: RATING CLASS: TEMPERATURE LIMIT: NOMINAL CORROSION ALLOWANCE: Process (Note 101) See Rating Table (Note 09) 0F to 140F (Note 09, 100) None

PIP PN01PV0C01 Piping Material Specification Line Class 1PV0C01


MATERIAL: DESIGN CODE: STRESS RELIEF: EXAMINATION: Poly (Vinyl Chloride) (PVC) ASME B31.3c-1998 None Required Per ASME B31.3

PRESSURE - TEMPERATURE RATINGS (For Non-Shock Service) TEMP F 0 to 100 110 120 130 TEMP C -18 to 38 43 49 54 For NPS 1/2 through NPS 8 psig kPag ITEM PIPE 150 1030 125 860 NOTES 09, 104, 105, 106, 107, 113, 114 09, 106, 109, 113 1/2 8 1/2 8 1/2 8 1/2 8 1/2 8 1/2 8 1/2 8 1/2 8 1/2 8 1/2 4 1/2 8 1/2 6 18 14 18 38 1/2 8 18 80 80 80 80 80 80 80 80 80 80 80 150 psi 150 psi 150 psi 150 psi 150 psi 150 psi 150 psi 100 690 NPS 75 520 SCH/RAT

140 60 50 340 ENDS DESCRIPTION

1/2 8 FITTINGS 90 ELL 45 ELL Tee Tee (RED) Cross 45 Lateral Reducer Coupling (CONC) Reducer Bushing (CONC) Coupling Union Cap VALVES Ball Ball Diaphragm Diaphragm Wafer Butterfly Ball Check Swing Check FLANGES Socket Weld Socket Weld Van Stone Blind Flange GASKETS BOLTING Machine Bolts MISCELLANEOUS Primer Solvent 111, 112

80 SW SW SW SW SW SW SW SW SW SW SW SW FLG SW FLG SW FLG

Type I, Gr 1, PVC 1120, ASTM D1784, ASTM D1785 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 Type I, Gr 1, PVC, ASTM D1784, ASTM D2467 True union PVC body and ball True union PVC body and ball True union PVC body and EPDM diaphragm PVC body and EPDM diaphragm PVC body and disc w/ lever operator True union PVC body and ball PVC body and disc BA00PV300 BA00PV500 DP00PV300 DP00PV500 BF00PV700 CL00PV300 CS00PV500

110

09, 106, 108, 120

64 62 09, 106, 108, 109, 113, 120 116

1/2 8 1/2 8 1/2 8 18

150 psi 150 psi 150 psi

FF FF FF

PVC type 1120, ASTM D1784, ASTM D1785 PVC type 1120, ASTM D1784, ASTM D1785 PVC type 1120, ASTM D1784, ASTM D1785 1/8" thick full face neoprene, 50 durometer nominal hardness ASTM A307, Gr B bolts w/ ASTM A563 Gr A heavy hex nuts and 2 ASTM F436 washers ASTM F656 ASTM D2564

09

Process Industry Practices

Page 1 of 2

PIP PN01PV0C01 Piping Material Specification Line Class 1PV0C01

TECHNICAL CORRECTION
February 2001

90 BRANCH CONNECTION Legend and Chart


8 6 BRANCH SIZE 4 3 2 1-1/2 1 3/4 1/2 T E B B C C C D D 8 T E A B C C C C 6 T E A B B B C 4 T E A A A B 3 T E E A A 2 T E A A 1-1/2 T E A 1 T E 3/4 T 1/2

HEADER SIZE

A B C D E T

Tee w/ Single Reducer Bushing (Utilize standard fittings as required.) Reducing Tee w/ One Reducer Bushing (Utilize standard fittings as required.) Reducing Tee w/ Two Reducer Bushings Reducing Tee w/ Three Reducer Bushings Reducing Tee Tee

NOTES: 09 62 64 100 101 104 105 106 107 108 109 110 111 112 113 114 116 120

Pressure and temperature rating may be limited by certain components permitted by this specification. Refer to manufacturers recommended pressure-temperature restrictions. Install in horizontal position with cover up or in vertical position with upward flow. Install in horizontal position or in vertical position with upward flow. Maximum allowable service temperature for PVC type 1120 pipe is 140F (60C) for water service. Rating may be lower for other services. Check manufacturers specifications for other specific services. Paragraph A323.4 of ASME B31.3 Code prohibits the use of this material in flammable fluid service above ground as well as compressed air or other compressed gas service. Pipe to be sized to keep maximum fluid velocity at 5 ft/sec (1.5 m/sec) or less. Consult with manufacturers specifications for support and mounting requirements for the intended service. See ASTM D2855. Fabrication with PVC and CPVC plastic pipe and components shall follow manufacturers instructions and ASME B31.3, Paragraph A328. Plastic pipe to be Type I, Gr 1 PVC 1120 and comply with ASTM D1784 for material and ASTM D1785 for dimensions. Flanged ends shall be full face that meet dimensions per ASME B16.1 Class 125. Fitting material to be Type I, Gr 1 PVC 1120 and comply with ASTM D1784 for material and ASTM D2467 for dimensions. Branch on lateral to be full sized. Washers shall be used on the back side of flanges. Torque to manufacturers requirements. Re-torque per manufacturers requirements. Heating of surfaces of plastic pipe is not permitted. Bending of plastic pipe is not permitted. To be used only for final fit up against fixed flanged equipment. Flanged connections to be used only where required.

REFERENCES: Process Industry Practices (PIP) PNF0200 - Vents, Drains, and instrument Connection Details PIP PNSMV045 - Plastic and Plastic-Lined Check Valve Descriptions PIP PNSMV046 - Plastic and Plastic-Lined Ball Valve Descriptions PIP PNSMV047 - Plastic and Plastic-Lined Butterfly Valve Descriptions PIP PNSMV048 - Plastic and Plastic-Lined Plug Valve Descriptions PIP PNSMV049 - Plastic and Plastic-Lined Other Valve Descriptions

Page 2 of 2

Process Industry Practices

Potrebbero piacerti anche