Switched mode power supplies CP-E Range

P su owe pp r lie s

DC OK output The CP-E range 24 V devices > 18 W offer a semiconductor output for function monitoring and remote diagnosis.

Wide range input Optimized for world-wide applications: The CP-E power supplies can be supplied with 85-265 V AC or 90-375 V DC.

Output voltages 5 V, 12 V, 24 V, 48 V DC Adjustable output voltages Output currents 0.625 A / 0.75 A / 1.25 A / 2.5 A / 3 A Power range 15 W, 18 W, 30 W, 60 W Wide range input 100-240 V AC (90-265 V AC / 120-370 V DC, 85-265 V AC / 90-375 V DC) High efficiency of up to 89 % Low power dissipation and low heating Free convection cooling (no forced cooling with ventilators) Ambient temperature range during operation -10...+70 C Open-circuit, overload and short-circuit stable Integrated input fuse U/I characteristic curve for devices > 18 W (fold-forward behavior at overload no switch-off) Redundancy unit CP-RUD offering true redundancy LED(s) for status indication Signalling output (transistor) for output voltage OK on 24 V devices > 18 W Approvals / Marks (depending on device, partly pending):

11

Adjustable output voltage The CP-E range types feature a continuously adjustable output voltage. Thus, they can be optimally adapted to the application, e.g. compensating the voltage drop caused by a long line length.

A, H, B, D, E / a, b

Redundancy unit CP-RUD 1SVR 423 418 R9000 For decoupling of parallellized power supply units. Thus, true redundancy can be achieved.

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com

r we ies o P pl p su

Switched mode power supplies CP-E

Type

Rated input voltage

Rated output voltage / current

Order code

Pack. unit pieces

Weight 1 piece kg / lb

CP-E 5/3.0 CP-E 12/2.5 CP-E 5/3.0 CP-E 24/0.75 CP-E 24/1.25 CP-E 24/2.5 CP-E 48/0.62 CP-E 48/1.25 CP-E 12/2.5

100-240 V AC 100-240 V AC 100-240 V AC 100-240 V AC 100-240 V AC 100-240 V AC 100-240 V AC

5 V DC / 3.0 A 12 V DC / 2.5 A 24 V DC / 0.75 A 24 V DC / 1.25 A 24 V DC / 2.5 A 48 V DC / 0.625 A 48 V DC / 1.25 A

1SVR 427 033 R3000 1SVR 427 032 R1000 1SVR 427 030 R0000 1SVR 427 031 R0000 1SVR 427 032 R0000 1SVR 427 030 R2000 1SVR 427 031 R2000

1 1 1 1 1 1 1

0.15 / 0.33 0.29 / 0.64 0.15 / 0.33 0.29 / 0.64 0.36 / 0.79 0.29 / 0.64 0.36 / 0.79

11

Redundancy module The CP-RUD monitors two CP-E range power supplies with an output current of up to 5 A each. If one power supply fails, CP-RUD automatically switches to the alternate supply without interruption of the load current. Max. voltage 40 V.
Pack. unit pieces Weight 1 piece kg / lb

Type

Description

Order code

CP-RUD CP-E 24/2.5

Redundancy module

1SVR 423 418 R9000

0.15 / 0.33

CP-E 48/0.62

CP-RUD

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com

Technical data CP-E Range


Data at Ta = 25 C, UIN = 230 V AC and rated values, if nothing else indicated
Type Input circuit Rated input voltage UIN Input voltage range Frequency range AC Typical input current / power consumption at 110 V AC at 230 V AC Inrush current Power failure buffering Internal input fuse Indication of operational states Output voltage OK: green LED LOW: red LED 310 mA / 19.65 W 183.2 mA / 19.85 W 18 A (max. 3 ms) min. 75 ms 580 mA / 35.18 W 328 mA / 36.6 W 40 A (max. 3 ms) min. 30 ms 90-265 V AC / 120-370 V DC 85-264 V AC / 90-375 V DC CP-E 5/3.0 CP-E 12/2.5 L, N 100-240 V AC 90-265 V AC / 120-370 V DC 336 mA / 22.6 W 197.4 mA/ 23.0 W 18 A (max. 3 ms) min. 75 ms CP-E 24/0.75

P su owe pp r lie s

CP-E 24/1.25

85-264 V AC / 90-375 V DC 568 mA / 36.38 W 326.6 mA / 37.05 W 40 A (max. 3ms) min. 30 ms

47-63 Hz

2 A slow-acting / 250 V AC

V: output voltage OK V: output voltage too low


5 V DC 4.7-6 V DC 15 W L+,L12 V DC 1 % 12-15 V DC 30 W 2.5 A 2.5 %/K max. 2 % max. 1 % max. 0.5 % max. 0.5 % < 2 ms max. 1 s max. 150 ms 50 mV yes, to enable redundancy yes, to increase voltage approx. 9 V DC approx. 18 V DC no Hiccup-mode Hiccup-mode thermal protection with switch-off and restart not possible U/I curve continuation with current limitation current limitation Hiccup-mode Hiccup-mode thermal protection with switch-off and restart not possible U/I curve continuation with current limitation current limitation approx. 35 V DC max. 2 % max. 1 % 21.6-28.8 V DC 18 W 0.75 A 3 %/K 24-28 V DC 30 W 1.25 A 2.5 %/K yes max. 0.5 % max. 0.5 % 24 V DC

V: output voltage too low

Output circuit Rated output voltage Tolerance of the output voltage Adjustment range of the output voltage Rated output power Rated output current Ir Derating of the output current Signalling output for output voltage OK Deviation with load change Ta m 60 C 60 C < Ta m 70 C DC OK statical dynamic 10-90 % change of input voltage within the input voltage range Control time Starting time after applying the supply voltage Response time Residual ripple and switching peaks Parallel connection Series connection Resistance to reverse feed Power factor correction (PFC) Output circuit - No-load, overload and short-circuit behavior Output curve Short-circuit protection Short-circuit behavior Overload protection at Ir at rated load BW = 20 MHz

11

3.0 A 3 %/K

continuous short circuit stability

No-load protection Starting of capacitive loads

continuous no-load stability unlimited unlimited

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com

r we ies o P pl p su

Technical data CP-E Range

Data at Ta = 25 C, UIN = 230 V AC and rated values, if nothing else indicated


Type General data Efficiency Duty time Dimensions (W x H x D) 23.9 x 88.5 x 115 mm [0.94 x 3.48 x 4.53 in] 0.15 kg (0.33 lb) typ. 75 % typ. 84 % 100 % 43.5 x 88.5 x 115 mm [1.71 x 3.48 x 4.53 in] 0.29 kg (0.64 lb) plastic DIN rail (EN 60715), snap-on mounting without any tool horizontal horizontal / vertical enclosure / terminals 25 mm / 25 mm (0.98 in / 0.98 in) IP20 / IP20 I fine-strand with wire end ferrule fine-strand without wire end ferrule rigid Stripping length 6 mm (0.24 in) 0.5-0.6 Nm operation full load storage Damp heat (cyclic) (IEC/EN 60068-2-30) Vibration (sinusoidal) (IEC/EN 60068-2-6) Shock (half-sine) (IEC/EN 60068-2-27) Isolation data Rated insulation voltage Ui Pollution category Standards Product standard Low Voltage Directive EMC Directive RoHS Directive Electrical safety Protective low voltage Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission electromagnetic field (HF radiation resistance) HF line emission IEC/CISPR 22, EN 55022 IEC/CISPR 22, EN 55022 IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 IEC/EN 61000-6-2 Level 4 (8 kV / 15 kV) Level 3 (10 V/m) Level 4 (4 kV) Level 4 (2 kV / 4 kV) Level 3 (10 V) IEC/EN 61000-6-3 Class B Class B EN 61204 2006/95/EC 2004/108/EC 2002/95/EC EN 50178, EN 60950-1, UL 60950-1, UL 508 SELV (EN 60950) input circuit / output circuit 3 kV AC 2 -10+70 C -10+60 C -25+85 C 4 x 24 cycle, 40 C, 95 % RH 10 m/s2, 10...500 Hz 40 m/s2, 22 ms, all directions Tightening torque Environmental data Ambient temperature range 0.2-2 mm2 (24-14 AWG) 23.9 x 88.5 x 115 mm [0.94 x 3.48 x 4.53 in] 0.15 kg (0.33 lb) 43.5 x 88.5 x 115 mm [1.71 x 3.48 x 4.53 in] 0.29 kg (0.64 lb) typ. 77 % typ. 86 % CP-E 5/3.0 CP-E 12/2.5 CP-E 24/0.75 CP-E 24/1.25

Weight Material of enclosure Mounting Mounting position Minimum distance to other units Degree of protection Protection class Electrical connection - Input circuit / Output circuit Wire size

11

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com

Technical data CP-E Range


Data at Ta = 25 C, UIN = 230 V AC and rated values, if nothing else indicated
Type Input circuit Rated input voltage UIN Input voltage range Frequency range AC Typical input current / power consumption at 110 V AC at 230 V AC Inrush current Power failure buffering Internal input fuse Indication of operational states Output voltage OK: green LED LOW: LED rot Output circuit Rated output voltage Tolerance of the output voltage Adjustment range of the output voltage Rated output power Rated output current Ir Derating of the output current Signalling output for output voltage OK Deviation with load change Ta m 60 C 60 C < Ta m 70 C DC OK statical dynamic 10-90 % change of input voltage within the input voltage range Control time Starting time after applying the supply voltage Response time Residual ripple and switching peaks Parallel connection Series connection Resistance to reverse feed Power factor correction (PFC) Output circuit - No-load, overload and short-circuit behaviour Output curve Short-circuit protection Short-circuit behaviour Overload protection No-load protection Starting of capacitive loads U/I curve continuous short circuit proof continuation with current limitation current limitation continuous no-load stability unlimited at Ir at rated load BW = 20 MHz max. 1 % max. 0.5 % < 2 ms max. 1 s max. 150 ms 50 mV yes, to enable redundancy yes, to increase voltage approx. 35 V DC no yes max. 0.5 % 24-28 V DC 60 W 2.5 A 30 W 0.625 A 2.5 %/K 24 V DC 1080 mA / 69.4 W 570 mA / 69.0 W 60 A (max. 3 ms) CP-E 24/2.5 CP-E 48/0.62 L, N 100-240 V AC 85-264 V AC / 90-375 V DC 47-63 Hz 566 mA / 35.34 W 320 mA / 36 W 40 A (max. 3 ms) min. 30 ms 2 A slow-acting / 250 V AC

P su owe pp r lie s

CP-E 48/1.25

1080 mA / 69.2 W 573 mA / 68.8 W 60 A (max. 3 ms)

V: output voltage OK
L+,L48 V DC 1 % 48-55 V DC 60 W 1.25 A 48 V DC

11

max. 1 %

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com

r we ies o P pl p su

Technical data CP-E Range

Data at Ta = 25 C, UIN = 230 V AC and rated values, if nothing else indicated


Type General data Efficiency Duty time Dimensions (W x H x D) Weight Material of enclosure Mounting Mounting position Minimum distance to other units Degree of protection Protection class Electrical connection - Input circuit / Output circuit Wire size fine-strand with wire end ferrule fine-strand without wire end ferrule rigid Stripping length Tightening torque Environmental data 6 mm (0.24 in) 0.5-0.6 Nm operation full load storage Damp heat (cyclic) (IEC/EN 60068-2-30) Vibration (sinusoidal) (IEC/EN 60068-2-6) Shock (half-sine) (IEC/EN 60068-2-27) Isolation data Rated insulation voltage Ui Pollution category Standards Product standard Low Voltage Directive EMC Directive RoHS Directive Electrical safety Protective low voltage Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission electromagnetic field (HF radiation resistance) HF line emission IEC/CISPR 22, EN 55022 IEC/CISPR 22, EN 55022 IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 IEC/EN 61000-6-2 Level 4 (8 kV / 15 kV) Level 3 (10 V/m) Level 4 (4 kV) Level 4 (2 kV / 4 kV) Level 3 (10 V) IEC/EN 61000-6-3 Class B Class B EN 61204 2006/95/EC 2004/108/EC 2002/95/EC EN 50178, EN 60950-1, UL 60950-1, UL 508 SELV (EN 60950) input circuit / output circuit 3 kV AC 2 -10+70 C -10+60 C -25+85 C 4 x 24 cycle, 40 C, 95 % RH 10 m/s2, 10...500 Hz 40 m/s2, 22 ms, all directions 0.2-2 mm2 (24-14 AWG) horizontal / vertical enclosure / terminals 0.36 kg (0.79 lb) typ. 89 % typ. 86 % 100 % 43.5 x 88.5 x 115 mm (1.71 x 3.48 x 4.53 in) 0.29 kg (0.64 lb) plastic DIN rail (EN 60715), snap-on mounting without any tool horizontal 25 mm / 25 mm (0.98 in / 0.98 in) IP20 / IP20 I 0.36 kg (0.79 lb) typ. 89 % CP-E 24/2.5 CP-E 48/0.62 CP-E 48/1.25

11

Ambient temperature range

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com

Technical data CP-E Range


Data at Ta = 25 C, if nothing else indicated
Type Input circuit - Supply circuit Rated input voltage UIN Input voltage range Rated input current IIN per channel Maximum input current per channel Transient overvoltage protection Output circuit Rated output voltage UOUT Voltage drop Rated output current IOUT Peak output current Resistance to reverse feed General data Dimensions (W x H x D) Weight Minimum distance to other units Degree of protection Material of enclosure Protection class Mounting Mounting position Electrical connection - Input circuit / Output circuit Wire size fine-strand with wire end ferrule fine-strand without wire end ferrule rigid Stripping length Tightening torque Environmental data Ambient temperature range operation full load storage Damp heat (IEC/EN 60068-2-3) Climatic category (IEC/EN 60721) Vibration (IEC/EN 60068-2-6) Shock (IEC/EN 60068-2-27) Isolation data Insulation voltage Pollution degree (EN 50178) Standards Product standard Low Voltage Directive EMC Directive Electrical safety Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 IEC/CISPR 22 / EN 55022 IEC/CISPR 22 / EN 55022 IEC/EN 61000-6-2 Level 3 (air discharge w8 kV, contact discharge w6 kV) Level 3 (10 V/m) Level 3 (w2 kV) Level 1 (w0.5 kV) Level 3 (10 V) IEC/EN 61000-6-3 Class B Class B 2006/95/EC 2004/108/EC EN 50178 between input / output / enclosure 2 -20...+60 C -20...+60 C -40...+85 C 93 % at 40 C, no condensation 2 x 0.75-2.5 mm2 (2 x 18-14 AWG) 2 x 0.5-4 mm2 (2 x 20-12 AWG) 7 mm (0.28 in) 0.6-0.8 Nm horizontal / vertical enclosure / terminals enclosure shell / cover 22.5 mm x 78 mm x 102 mm (0.89 x 3.07 x 4.02 in) 0.135 kg (0.30 lb) 10 mm / 10 mm (0.39 in / 0.39 in) IP20 / IP20 plastic / plastic DIN rail horizontal CP-RUD A: U1+/-U ; B: U2+/-U 24 V DC 5-35 V DC 0.5-2.5 A 10 A for 300 s no L+, L+, L+, L-, L- , L24 V DC typ. 0.6 V, max. 0.7 V 0.5-5 A 20 A for 150 s < 35 V

P su owe pp r lie s

11

electromagnetic field (HF radiation resistance)


HF line emission

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com

r we ies o P pl p su

Technical diagrams, circuit diagrams CP-E Range

Technical diagrams
Output curve at Ta = 25 C
Uout [V] 15 13 11 9 7 5 3 1 Uout [V] Uout [V]

CP-E 12/2.5

2.8

2.9

3.0

3.1

3.2

3.3

3.4

3.5

3.6 3.7 Iout [A]

CP-E 24/1.25

1.25 1.35 1.45 1.55 1.65 1.75 1.85 1.95 2.05 2.15 Iout [A]

CP-E 24/2.5

2.75 2.85 2.95 3.05 3.15 3.25 3.35 3.45 3.55 3.65 Iout [A]

Uout [V] 70 60 50

Uout [V] 70 60 50 40 30 20 10

11

40 30 20 10
0.665 0.705 0.745 0.785 0.825 0.865 0.905 0.945 0.985 1.025

CP-E 48/0.62

Iout [A]

CP-E 48/1.25

1.33 1.41 1.49 1.57 1.65 1.73 1.81 1.89 1.97 2.05 Iout [A]

Temperature curve at rated output voltage


Pout [%] 100 90 80 70 60 50 40 30 20 10 -10 0 10 20 30 40 50 60 70 Ta [C]

CP-E

Wiring instructions
RL > 700 q DC OK DC OK

Relay

5 V Signal
2.2 kq 0.5 W 5.1 V 0.3 W

L-

L-

CP-E 24/1.25, CP-E 24/2.5

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com

Approximate dimensions CP-E Range


CP-E 5/3.0, CP-E 24/0.75 CP-E 12/2.5, CP-E 24/1.25, CP-E 24/2.5, CP-E 48/0.62, CP-E 48/1.25
115 [4.53]

P su owe pp r lie s

23,9 [0.94]

43,5 [1.71]

115 [4.53]

88,5 [3.49]

CP-RUD
109,5 102 [4.31] 22,5 [.886]

[4.02]

88,5 [3.48]

11
78 [3.07] 100 [3.94]

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com