ARGUS 7
Description
Argus 7 is a combined check and system synchronising relay which can automatically select check or system synchronise from measurements of the relative phase angles between line and bus voltages. The relay will prevent closure of the circuit breaker if either the phase angle, slip frequency or the voltage magnitude of the incoming and running voltages fall outside prescribed limits. If the parameters are within the limits the relay will issue an output which can be used to close the circuit breaker directly or in conjunction with an autoreclose scheme. Both the check and system synchronise functions have independent settings and blocking features. The relay includes split system detection with a variable time delay, which can be used for blocking purposes within delayed autoreclose schemes. Synchronising bypass logic is provided to connect a dead line or bus to a live line or bus. For manual synchronising the relay includes a circuit breaker close guard feature which is used to prevent the control switch being held closed during a synchronising operation. This feature is implemented using internal logic and removes the need for an external relay.
Features
Protection
Check synchronising (25) and system synchronising Under voltage blocking (27) Differential blocking
Control
The basic Argus 7 relay contains 4 programmable digital (status) inputs with programmable pick-up and drop-off timers The Argus 7 relay contains 7 programmable output relays out of which 1 have CO contact 1 have NC contact and 5 have NO contacts Configurable dead bus and/or dead line charge Adjustable slip frequency, phase angle and time delay Integrated manual close guard feature Independent Check synchronising and system synchronising settings
Applications
Check synchronising (25) and system synchronising
Monitoring
Split system detection Storage of 500 time-tagged event records Storage of 5 wave form records Metering Primary RMS voltage for both line & bus Secondary RMS voltage for both line & bus Frequency of both line & bus Phase difference between line & bus Frequency slip between line & bus Phase - In/out limits Slip - In/out limits Line and bus health status (ie live and dead) Voltage blocking element status
Wiring Diagram
User Interface Backlit liquid crystal alpha-numeric display with 16-characters, 2 lines LEDs for check/system sync system split and protection healthy Push buttons for programming and resetting Communication Fibre optic communication port at rear Data communication using IEC 60870-5-103 protocol
Notes
1. VT Connections are shown for phase-neutral, phase-phase is also possible. 2. VT & Earth connections are typical only.
Technical Information
VT Input Rating
63.5/110V AC, 50/60Hz
volt DC working a 48 volt digital (status) input is supplied for use with external dropper resistors: 110/125V Resistor 2K7 5% 2.5W 270/250V Resistor 8K2 5% 6.0W
Settings
VT ratio Check sync Phase angle Slip timer Slip frequency Dead voltage Live voltage Line undervoltage Bus undervoltage Differential Voltage Sync bypass System split Split timer Manual close guard function System sync Phase angle Slip timer Slip frequency Close pulse 1:1 to 9999:1 AUTO, MANUAL 5 to 90 1 OFF, 0.1 to 100.0 sec 0.1 sec OFF, 0 to 2.000Hz 0.005Hz 5 to 127V 0.5V 10 to 132V 0.5V OFF, 22 to 132V 0.5V OFF, 22 to 132V 0.5V OFF, 0.5 to 44V 0.5V OFF, DL&LB, LL&DB, DL&DB, DL or DB, DL&/or DB OFF, 90 to 175 1 OFF, 0.1 to 100.0 sec 0.1 sec OFF/ON LOCKOUT, AUTO, MANUAL 5 to 90 1 OFF, 0.1 to 100.0 sec 0.1 sec OFF, 0 to 2.000Hz 0.005Hz 0.1 to 2 sec 0.1 sec
Burdens
AC DC < 0.2VA 3W Quiescent (Typical) 10W maximum
Indications
LEDs for check/system sync, system split and protection healthy indications LCD - alphanumeric display for settings, instruments and fault data
Environmental
Temperature IEC 68-2-1/2 Operating range -10C to +55C Storage range -25C to +70C Humidity IEC 68-2-3 Vibration IEC 255-21-1 class I Shock and bump IEC 255-21-2 class I Seismic IEC 255-21-3 class I Insulation IEC 255-5 2 KVrms for 1 min all terminals to earth. 2 KVrms for 1 min between independent circuits. 1 KVrms for 1 minute across NO contacts. Transient overvoltage IEC 255-4 class III 5KV 1.2/50s between all terminals and earth without damage or flashover. High frequency disturbance IEC 255-22-1 class III 2.5KV common mode < 3% deviation 1.0KV series mode < 3% deviation Electrostatic discharge IEC 255-22-2 class III 8KV direct without maloperation or damage Radio frequency disturbance IEC 255-22-3 20MHz to 1GHz at 10V/m < 5% deviation Fast transient IEC 255-22-4 class IV 4KV 5/50ns < 3% deviation
DC Auxiliary supply
Nominal 24, 30, 48V 110, 220V Operating range 18-60V 88-280V
Output relays
The Argus 7 relay contains 7 programmable output relays out of which 1 have CO contact 1 have NC contact and 5 have no contacts
Contact ratings
Carry continuously Make and carry Resistive break 5A AC or DC 30A AC or DC for 0.2sec 75W DC, 1250VA AC
Mechanical Classification
Durability 106 operations
DC digital(status) input
The Argus 7 relay contains 4 programmable digital (status) inputs which have programmable pick-up and drop-off timers. Nominal Operating Range 30 V DC 18 - 37.5V DC 48 V DC 37.5 - 60V DC 110/125 V DC 87.5 - 137.5 V DC 220/250 V DC 175 - 280 V DC For relays to ESI48-4 standard and 110/125 or 220/250
Cutout Details
Case Argus 7 - E4
Weight 3.15 kg
Ordering Information
Auxiliary and digital (status) input voltage
Qualification
ISO 9001 - 2000
The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment, which may differ slightly from that described and illustrated in this publication. HOSUR WORKS
#98, Sipcot Industrial Complex, Hosur 635 126, India. Tel: +91 4344 401600/01/02 Fax: +91 4344 276397
#17/3 Arakere, Bannerghatta Road, Bangalore-560 076, India. Tel: +91 80 26581023 / 3268 Fax: +91 80 26580642 Email: blrworks@easunreyrolle.net Ashirwad, #25, 29th Main, 4th B Cross, BTM Layout 2nd Stage, Bangalore-560 076, India. Tel: +91 80 26685496/51311405 Fax: +91 80 26685446 Email: smabp@easunreyrolle.net
AUTOMATION DIVISION EXPORTS DIVISION
SWITCHGEAR WORKS
Ernavur, Chennai-600 057, India. Tel: +91 44 25733715/358 Fax: +91 44 25733468 Email: switchgear@easunreyrolle.net
#17/3 Arakere, Bannerghatta Road, Bangalore-560 076, India. Tel: +91 80 26581023 / 3268 Fax: +91 80 26580642 Email: exports@easunreyrolle.net
Sales Offices
Mumbai
Delhi
Kolkata
Corporate Office Easun Reyrolle Limited. 98 Sipcot Industrial Complex Hosur 635 126 India. Tel: +91 4344 401600/01/02 Fax: +91 4344 276397 www.easunreyrolle.com
FACT/ARGUS 7/12-05/REV 0
BANGALORE WORKS