TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
The 3508-30C TELETRANSTM is a compact, HIGH PERFORMANCE SMART transmitter that performs measurement, processing and communication functions. Widely used in the oil, gas and water industry and provides a standard 4-20 mA dc current output (proportional to the primary variable). The TELETRANSTM distinguishes itself from all other transmitters by offering TWO MAJOR, UNPRECEDENTED FEATURES:
MULTIVARIABLE MEASUREMENT - DP, P & T in digital mode WIDE SELECTION OF DIGITAL COMMUNICATION MEDIA INCLUDING RS232, RS485 OR AN INTEGRAL MODEM, which is a unique feature among current Smart transmitter offerings in the market
Serial communications are achieved in any of three ways: a. By using a compact interface unit to access the superimposed Frequency Shift Keying (FSK) signal over the same 2-wire 4-20 mA loop. The interface unit provides asynchronous RS232 communications (1200 baud) with up to five transmitters and the PC or other intelligent devices. (In the case of Bristol s 33XX digital products, an interface board can replace the interface unit and also communicate with up to five transmitters). Direct RS232/485 digital communications (up to 9600 baud) between the master device (BBI 33XX s) and the transmitter via separate terminations on the transmitter, which are independent of the 4-20 mA loop wiring connections. Remote communications using the integral Private Line / Switched Network modem at 1200 baud.
differential pressure or flow), with superimposed digital output signal +0.1 % accuracy MULTI-VARIABLE CAPABILITY in digital mode, i.e., pressure, differential pressure and process temperature readings available as floating point values REMOTE COMMUNICATION CAPABILITY - via an integral Private Line / Switched Network modem at 1200 baud UP TO 9600 baud for local hard wired RS232/485 digital communications RTD input for process temperature measurements Wide rangeability Stainless Steel and Hastelloy C diaphragms Exotic flange materials including Hastelloy C, Monel and Stainless Steel Electronics contained within explosion proof housing SMARTKIT software for calibration/configuration via a PC Process wetted parts meet N.A.C.E. specification MR017591
b.
c.
The transmitter can be calibrated from a PC, or a host computer in a DCS or SCADA system (BBI s Network 3000) The 3508-30C is an adjustable range transmitter that is calibrated at the factory to a specific measurement range. The input ranges are 100, 150 and 300 inches of water and 25 PSID. The transmitter has a span adjustment capability of 20:1, in addition to zero elevation and suppression.
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
IMPROVEMENTS
Reduced susceptibility to pulsation Improved reliability due to Surface Mount Technology (SMT) Increased recommended RTD lead length (100 ft.) Improved noise reduction Greater communication signal integrity at lower voltages Lower voltage requirements when operating in digital mode allowing interface with 12V nominal systems when used with Bristol Babcock Low Power TIB assembly
form a pressure sensitive Wheatstone Bridge. The two outer process diaphragms (Hi and Lo sides) are hydraulically connected to the DP sensor using a suitable fill fluid. The static pressure strain gauge is contained in the Hi side of the DP fluid system to sense upstream process measurements. Both bridges are powered by a precision current source, and both develop millivolt signals that correspond to the inputs (DP and P) at the outer process diaphragms. Both analog outputs are converted to equivalent digital data via a multiplexer (MUX), a differential amplifier and a voltage count converter. The data is then read by the microprocessor (MP), which performs data acquisition, data processing and decision functions of the transmitter. The MP then converts the digital DP value back to an analog signal via a digital to analog converter (DAC), hence providing the standard 4 - 20 mA dc output signal. When the RS232, RS485, or modem options are present, the default serial communications path is set for the particular option selected. If local FSK communications are detected (using the 1200 baud transmitter interface unit), the MUX switches over to accommodate it on the serial port, and remains local for a time out period. Switching between local FSK and optional communications is automatic - one second after the last communications via FSK, the 3508 will begin listening to the option selected. All the circuitry for options (RS232, RS485 and modem) resides on an interface board sandwiched between the digital board and the customer termination plate. The transmitter can function with a 9-14/22-28 V supply source, based on options selected. The electronics also include a power fail detector that prevents the transmitter from operating when the applied power is below specifications.
OPTIONS
Choice of 9-14/22-28 V supply with RS232/485/modem communication options Metameter Pulse Duration Output (PDO) Integral digital LCD meter, in linear or engineering units
BENEFITS
MAJOR installation and product cost savings, in terms of the transmitter s MULTIVARIABLE CAPABILITY, i.e. this transmitter eliminates the need for separate pressure, differential pressure and temperature transmitters to be installed for a given application, by virtue of its multivariable output (P, DP, T) in digital mode TWO-YEAR WARRANTY, covering Service and Repair Easily configured through a Personal Computer, or from a Hostcomputer in a Distributed Control System (DCS) or SCADA System. Automatic temperature and static pressure compensation, resulting in consistent accuracy over the specified ambient temperature and operating pressure ranges LOW POWER requirements when operating in digital mode Lower wiring cost and ease of installation when utilizing remote capability Digital communications link between 3508-30C TELETRANSTM and Bristol s 33XX products
THEORY OF OPERATION
The differential pressure and static pressure measurements are performed by a dual strain gauge circuit. Both sensors consist of an internal silicon diaphragm into which piezoresistive strain gauge resistors are diffused, then interconnected to
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
the operator - to - transmitter interface. This software (available on a 3-1/2" disk) allows the operator to calibrate the transmitter, select a forward or reverse acting output, change ranges, select damping coefficients, select a linear or square root output, configure the RS232/485 and modem options, and read or write data. All digital signals such as pressure, differential pressure, RTD temperature, bridge sensor temperature, error flags, etc., are communicated via the SMARTKIT program. SMARTKIT can be run on an IBM compatible PC. Transmitter Interface Unit (TIU): A special Bristol Babcock Interface unit provides an RS232 interface for FSK communication. The interface unit provides a nine pin female D connector that accepts the RS232 interface from the PC, and receives power from drivers in the PC. Serial communications are at 1200 baud in the Bristol Standard Asynchronous/Synchronous Protocol (BSAP). Transmitter Interface Board (TIB): For communications with a DPC 3330/3335/RTU 3310, an interface board can be used as an alternative to the interface unit. The interface board is housed piggy back on the communications board of a DPC 3330 or RTU 3310, or in the option slot of a DPC 3335, and can accommodate up to 5 transmitters in a multi-drop loop arrangement using FSK communications. Polling speed is one transmitter per second. The interface board arrangement does not require any separate power source, as it draws power from the master device. The interface board allows the transmitter to function as a local node, network node (end device), or as a slave to a master device (BBI s Distributed Process Controller 3330/3335/RTU 3310). Reference Specification Summary D461SS-6 Note: For sole transmitter applications, the output current can be fixed at 3.8 mA (via SMARTKIT) when only FSK or PDO are required. For multi-transmitter applications, this mode is a requirement. Bristol Babcock Transmitter Interface (BBTI): Allows up to eight transmitters to be connected to a 33XX controller (RTU 3310, DPC 3330 and DPC 3335) process I/O card. The BBTI physically occupies one of the 33XX controller I/O slots and connects to a DIN rail mountable field termination module via a ribbon cable. Communication occurs at 1200 bps for each transmitter. Simultaneous, independent communication to up to eight transmitters is supported allowing floating point data for all transmitters to be refreshed in less than one second. A BBTI ACCOL software module is provided in the 33XX firmware. Reference Specification Summary D456SS-6 Low Power Transmitter Interface Board (LPTIB): Provides terminations for two 3508 transmitters with communications at 1200 bps. Fast polling for two transmitters can occur at a 3
one-second interval. The LPTIB will bracket-mount in a TeleFlow Plus or TeleRTU Plus enclosure. The Stand-alone LPTIB uses a cable harness assembly to interface with the serial port on an I/O expansion board. Reference product information package PIP-TIBS3530. Expansion Transmitter Interface Board (ExpTIB): Equivalent to the LPTIB. The ExpTIB mounts directly to the TeleFlow Plus or TeleRTU Plus CPU board. Reference product information package PIP-ETIBS. RS232 Interface: Provides point-to-point communications (using BSAP) from the transmitter to the master device (BBI 33XX). Baud rates are selectable using SMARTKIT - 1200, 2400, 4800, and 9600 baud are offered. Distance for hardwired slaves from the master should not exceed 50 feet. The RS232 output can also be connected to other devices such as a radio. RS485 Interface: Provides 4-wire, multi-drop communications between the master and slaves within the network - up to 32 transmitters can be accommodated off a communications port at the master (BBI s 33XX). Again, the same options for baud rates (up to 9600 baud) are offered, as is with the RS232 interface. Wiring length should not exceed 1000 feet. Modem: Provides asynchronous, 2 or 4-wire private line, 2wire switched network communications. Configurations possible are: Point-to-point (one-to-one) and multi-drop (up to 5 transmitters for 2-wire, 20 for 4-wire). 4-wire networks are always preferable, as they provide better noise immunity than 2-wire networks. Baud rate is set at 1200 for all these options.
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
Physical: RTD input requires DIN 43760 Platinum Resistance Bulb Provides 1/2" NPT port for direct sensor mounting or conduit connection. Recommended maximum lead length is 100 feet. Isolation limited to that provided by bulb. Input Temperature Range: -58 to 842 F (-50 to 450C)
Maximum Pulse Period: 120 seconds. Standard PDO ranges are listed below. The standard ranges are selectable in SMARTKIT. Current Loop: Open collector, opto-isolated output. Maximum open loop supply voltage is 200 V; maximum closed loop current is 100 mA.
Function: Provides temperature compensation for measurement circuit. Operating Range: -40 to 185 F (-40 to 85 C)
Analog Output
*User may also enter custom periods (120 sec. max.) **Incremental Resolution Error must be added to resolution due to turndown described above
Linear Mode: 4-20 mA for 0-100% of calibrated span Current Limited: 22 mA max. 3.8 mA min. Square Root Mode: Output clamped at 4 mA for zero and negative pressures. For pressures between 0 and .8%, output is linear. For pressures between 0.8% and 1% of URL, value is linear if entered from below, square root if entered from above. From 1% to 100%, output is square root. Above 100% output is linear. Reversible Output Action: For forward action, current increases with increase of pressure. For reverse action, current decreases with an increase of pressure. Fixed Current Output Mode: The 4-20 mA output may be fixed at 3.8 mA when only the FSK or PDO communications are required. The output current may be externally controlled via serial communications to provide a remote AO. Turndown Ratio: from 1:1 to 20:1 Resolution: .03% for turndowns between 1:1 and 7:1, .03% x (ratio/7) for turndowns greater than 7:1
Serial Communications
Method: Serial communications FSK signal using Bell 202, compatible frequencies (1200 and 2200 Hz) - with a maximum 1 Vp-p amplitude Transmission Speed: 1200 baud PC Interface: Requires Interface Unit for RS232 interface Operator Interface: SMARTKIT program provides access to 3508
Signal Access & Format: FP Values are returned in a list of IEEE floating point short reals (i.e. 32-bit FP values with 14-bit resolution). The list can be read by DPC 3330/3335/RTU 3310 masters. Signal Conditioning: Floating point values are linear, forward acting, and affected by input and output filtering. Displayed Parameters: DP, SP, estimated sensor temperature, RTD Temperature, and Flag-Indicating Internal Errors. Floating point values are available in user selected engineering units.
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
Method: Requires PC running SMARTKIT program. Operating Modes: Forward or Reverse Linear or square root Output current enable/disable / External AO RTD enable/disable PDO enable/disable (RTD and PDO are mutually exclusive) 4-20 mA Current Output: The 4 and 20 mA points may be recalibrated to correct for long-term drift. Span Calibration (4-20 mA): Current output span is adjustable from URL to URL/20. Zero Calibration (4-20 mA): Can be set to any value between the larger of -URL or full vacuum and .95 (URL). Floating Point (FP) Output: FP outputs may each have their zero point and span adjusted slightly for long-term drift correction. Damping: Output damping time constant is adjustable from 0-36 seconds, independent of calibration. These smoothing techniques are applicable to current output and PDO; floating point DP may optionally be damped. (Note: At 9600 baud only for the RS232 / 485 option, damping of the 4-20 mA output is disabled).
Load, R
Non PDO or Meter Option PDO or Meter Option Meter & PDO Option
Maximum loop capacitance is 0.1 uF. Loop capacitance is limited by drive capability of the TIU, loop resistance, and supply voltage.
Signal/Power Loop
Loop Supply Voltage: Reverse polarity protected 24 Vdc nominal 42 Vdc max. to 12.5 Vdc min. at transmitter 16 Vdc minimum at transmitter when PDO option is included Add 3 Vdc to minimum if optional digital meter is included Loop Impedance: Transmitter requires 12.5 V minimum to operate. Maximum loop resistance can be calculated by the following formula: Rmax= (Supply Voltage - Et) .020 Where: RMax = maximum resistance Et = Minimum transmitter voltage: 12.5 V for no options, 16 V for PDO only, 15.5 V for digital meter only,
Supply Voltage: 12 Vdc nominal 9 Vdc min to 14 Vdc max. at transmitter reverse polarity protected Supply Limitations: 12 V models only available when an RS232, RS485 or built-in modem option board is installed. PDO or digital meter options not offered for 12 V models Auxiliary Power Output: 12 V models provide boosted 20 Vdc output to power transmitter s signal/power loop
Supply Sensitivity: Less than 0.005% FS per volt Load Sensitivity: Less than 0.005% FS per 50 ohm change Surge Protection: Per IEEE Standard 472-1974 Bipolar, differential surge: 1000 watts for 1 ms A purchased auxiliary surge protector may provide additional surge protection
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
PERFORMANCE SPECIFICATIONS
Accuracy
Measurement Influence
DP & SP, Linear Mode: +0.1% of calibrated span or .02% of URL, which ever is greater DP Square Root Mode: For 1-3% input (10-17% flow): +0.60% calibrated span or +.16% URL, which ever is greater For 3-6% input (17-25% flow): + 0.30% calibrated span or +.08% URL, which ever is greater For 6-100% input (25-100% flow): +0.10% calibrated span or +.03% URL, which ever is greater Below 1% input (0-10% Flow): Linear signal clamped at 4 mA. Between 8% and 1%, may be linear or square root Static Pressure Effect on DP: Zero Error: + .1%/1000 PSI Span Error: + .1%/1000 PSI Overpressure Effect: +0.2% URL/2000 psi (linear with pressure) Reverse Overpressure Effect: +0.2% URL/2000 psi (linear with pressure) RTD Temperature: +0.7 C Estimated Sensor Temperature: +3 C
Differential and Static Pressure Temperature Effect: +0.25% of URL for any temperature between -40 C to +85 C (Note: This value represents maximum deviation that occurs from Temp changes. The T change will depend on the T @ calibration. The T effect will gradually occur with reference from the T @ calibration) RTD Temperature Effect: + [.01 (22 C-Ambient)] C Estimated Sensor Temperature: Not applicable Mounting Position Effect: +2 in H2O maximum which can be calibrated out Power Supply Effect: +0.005% of URL for all variables Ripple and Noise: Per ISA 50.1, Section 4.6 Reproducibility: +0.1% in 1-hour period (Including hysteresis and repeatability) Thermal Hysteresis (0 - 100" and 0 - 150" H2O ranges only): thermal hysteresis will be. 1% or less in temperature range of -24 to 50 C for any temperature excusion in a 24 hour time period
Resolution
Current Output: .03% of URL for turndown <7:1 .03% x (Turndown/7); for turndown >7:1 PDO Output: Add IRE value given in PDO table to current output resolution Floating Point Pressures: .007% of URL RTD Temperature: .05 C Estimated Sensor Temperature: 0.1 C
Wet end (w/DC 200 fill): -40 to 185 F (-40 to 85 C)* Electronics: Operating: -40 to 185 F (-40 to 85 C) With Digital Display: -22 to 176 F (-30 to 80 C) Storage: -40 to 212 F (-40 to 100 C)*
*Low end limited to .5 F (-17.5 C) with Fluorolube fill (Special order only)
Humidity Limits
Differential and Static Pressure: +0.1% URL/year typical RTD Temperature: +0.25C/month Estimated Sensor Temperature: +1 C/year
15-95% RH (non condensing) over electronics operating temperature range with cover in place Local indicator (digital): 15% to 95% RH at 60 C max. 15% to 50% RH at 80 C max.
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
EMI Effect
Conditions: Current output (only) twisted-pair wires; RTD or PDO covers installed and wiring run in grounded conduit (does not include units with local indicators) DP and SP: +0.25% of URL @ 10 V/M, 20-500 MHz (SAMA PMC-33-1C) RTD Temperature: +1% of URL @ 10 V/M, 20-500 MHz (SAMA PMC- 33-1C) Estimated Sensor Temperature: +1% of URL @ 10 V/M, 20-500 MHz (SAMA PMC-33-1C)
delay of approximately 50 microseconds following transmission before the RS485 transmitter disconnects from the line. Line termination: Line termination and voltage bias level is handled externally by either the master or with add on external devices. Line fault: RS485 sets limits for line contention and line short at a maximum of 250 mA. The DC/DC supply will restrict this to an even lower value.
Baud Rates: 1200, 2400, 4800 and 9600 - selectable within SMARTKIT Supply Voltage: Two Options 9 to 14 volts: Nominal 24 volt requirement to power the basic transmitter will be met by the DC/DC converter which will boost the supply to 18 to 28 volts. The converter will also produce the additional floating supplies necessary for isolation. 22 to 28 volts: The on board DC/DC converter will develop the additional floating supplies necessary for isolation. Note: The transmitter must be externally powered for the RS232 / 485 options
Vibration Effect
Less than +0.1% of URL for 10 to 500 Hz at 1 G on any axis per SAMA PMC-31-1
Transient Protection: Nominal protection against transients on digital I/O via transorbs
Modem
Specific to RS232: Consists of four signals which are galvanically isolated from the chassis, power and the 4-20 mA loop via the internal type DC/DC power supply and opto-isolation. 1) RXD - Receive data, into the 3508 2) TXD - Transmit data, from the 3508 3) RTS - Request to send, from the 3508 4) CTS - Clear to send, to the 3508 5) XCOM - Communications common The 3508 provides a minimum delay of 10 ms between assertion of RTS and beginning of data transmission when CTS is tied to RTS. An external device (e.g. radio) may extend this time by delaying assertion of CTS after RTS assertion if needed, to a maximum of three seconds. Specific to RS485: Utilizes 4-wires, and consists of two signals, which are galvanically isolated from the chassis, power and the 4-20 mA loop via the internal type DC/DC power supply and opto-isolation. 1) RXD - Receive data, into the 3508 (2 lines) 2) TXD - Transmit data, from the 3508 (2 lines) 3) XCOM - Communications common RS485 is a balanced system with two connections for each signal. RTS and CTS are internally connected, providing a 10 ms delay between activation of the RS485 transmitter and beginning of transmission. There is a 7
Operational Characteristics: - Modulation/Demodulation: Frequency Shift Keying (FSK) - Data Rate: 1200 baud - Frequencies: Per Bell 202 and 212 specifications - Output: Private Line: 0 dBm Switched Network: -9 dBm - RTS/CTS Delays Private Line 0 to 2.5 sec. in 10 ms increments leading 0 to 250 ms in 1 ms increments trailing Switched Network - 200 or 600 ms increments, leading and trailing - Constant Carrier: Enable/Disable constant carrier when in Private line mode - RTS Antistreaming: Programmable true for 30 seconds or no time limit (Private line only). This limits the maximum amount of time a modem may put carrier on the line, and is intended as a fail-safe check. - Send Long Space (PSTN): Send 4 second space when RTS goes false or not - Receiver Operating Range: 0 to -43 dBm for carrier detect ON Carrier Detect OFF guaranteed at -48 dBm Receive data clamped to MARK when CD is OFF Carrier Detect Hysteresis 2 dBm
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
- Receiver Squelch: 9 ms for 1200 baud half duplex - Long Space Disconnect: Selectable disconnect / don t disconnect on reception of 1.6 second space - Calling Party Disconnect: Selectable disconnect / don t disconnect on 7 ms loop current interruption - Carrier Disconnect: Selectable disconnect / don t disconnect on selectable 1 to 255 second loss of carrier in 1 second increments - PSTN Time Limit: Selectable time limit from 1 to 255 minutes in 1 minute increments or no time limit (on Switched Network only) - P/L Time Limit: Selectable time limit from 1 to 255 minutes or no time limit - Auto Answer: Enable or disable - Isolation: 500 V modem to phone lines
Environmental Specifications: - Temperature: -20 to +70 C (-4 to 158 F) 212 operating -40 to +70 C (-40 to 158 F) 202 operating -40 to +100 C (-40 to 212 F) storage - Humidity: 15 to 95% Relative Humidity (non condensing) over the operating temperature range - Vibration: 1G for 15 - 150 HZ, 0.5 G for 150 - 2000 Hz - RFI Susceptibility: 10 V/m from 20 - 500 MHz
PHYSICAL SPECIFICATIONS
All options are configurable via SMARTKIT
Diagnostic Features: Analog and Digital loopback per CCITT V.54 Power Requirements: 9 - 40 Vdc Modem DC/DC power converter generates the following outputs: 1) 20 Vdc non-isolated at 20 mA nominal, 25 mA maximum to provide the necessary loop current to run the transmitter. This output follows the input power supply when 22 to 28 Vdc is present. 2) 5 Vdc at 30 mA nominal, 40 mA maximum to run the modem and associated circuitry
Diaphragm Material 316 Stainless Steel Hastelloy C Flange Material 316 Stainless Steel Hastelloy C Monel Flange Bolt Material 316 Stainless Steel Filling Media DC 200 Silicone Fluorolube fill can be obtained via special order only. Contact Watertown. Process Connections 1/4" NPT on Flanges 1/2" NPT with connection blocks Electrical Connections 1/2" NPT conduit connection Housing Material and rating Low Copper Aluminum with Epoxy Paint NEMA 4X Local Indication 3 1/2 Digit LCD Meter: Linear (0 to 100%), or in engineering units Size of digits = 0.3" Size of window = 1.13" (L) x 0.39" (W) Green backlight Zero: can be adjusted approximately 20% of span Polarity: Automatic (-) displayed
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
RTD Sensor (Optional) 2/3 wire, 100 ohm PT DIN 43760 Lead length is 100 feet maximum (recommended) Dimensions: Please refer to diagrams Weight Standard: 8 lbs. With Meter: 8 1/2 lbs. Interface Unit 9 pin D female connection (PC compatible) at one end Pair of wires with clip leads at other end which connects on to 4-20 mA loop 4.5" x 2.4" x 1.3" Cast Aluminum case coated with epoxy paint
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
CERTIFICATION UL/CUL Class I, Div. 1 Groups C&D FLANGE ORIENTATION Standard 90 degrees down 180 degrees to rear MOUNTING BRACKET None Flange Mounted L Bracket (Not available for selection N-1) Heavy Duty Bracket and Support (Available with selection N-0) Neck Mounted Bracket
0 1 2
0 1 2 3
DIAPHRAGM & CONNECTION MATERIAL 316 Stainless Steel 1 Hastelloy C 2 FILLING MEDIA DC 200 Silicone Fluid Fluorolube - Contact Watertown FLANGE MATERIAL 316 Stainless Steel Hastelloy C Monel 316 Stainless Steel FUNCTION MODULE Current / RTD Current / PDO Q 1
HOUSING ROTATION Standard, Facing Front 0 Rotated 180 degrees 1 (Not available with selection P-2) Warning Plate English Russian
1 2 3 5
1 2
1 2
COMMUNICATION OPTION None 12V, RS 232 Communications 12V, RS 485 Communications 24V, RS 232 Communications 24V, RS 485 Communications Modem
0 1 2 3 4 5
Transient Protector SMARTKIT Software Transmitter Interface Unit (TIU) Modem Cable - 6 feet Modem Cable - 15 feet 925 pin adapter (for PC)
MANIFOLD ADAPTER (Must match Flange Material) None Stainless Steel Hastelloy C Monel
0 1 2 3
0 1
Transmitter Interface Board (TIB): For DPC 3335 392059-07-0 For DPC 3330/RTU 3310 392523-01-9 Low Power TIB: Stand-alone (LPTIB) 392950-01-4 Expansion (ExpTIB) 392951-01-0 Bristol Babcock Transmitter Interface (BBTI): BBTI board 392535-01-7 Termination board 392536-01-3 Single 10cable 395334-01-2 Single 20cable 395334-02-0 Daisy chain cable 10 395335-01-9 Daisy chain cable 20 395335-02-7
10
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
OVERALL DIMENSIONS
Transmitter with L-type bracket
11
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
OVERALL DIMENSIONS
Transmitter with heavy duty bracket
12
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
4-1/8
2-13/16
OVERALL DIMENSIONS
Transmitter with Neck Type Mounting Bracket
13
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
14
TELETRANSTM 3508-30C
SMART DIFFERENTIAL PRESSURE TRANSMITTER
SPECIFICATION SUMMARY
B225SS-71e
15