Sei sulla pagina 1di 2

Technical Data MiCOM P441/P442 & P444

P44x/EN TD/E33 Page 17/30

6.
6.1 6.1.1

PROTECTION SETTING RANGES


Distance Protection Line Settings Setting Length of line (Ln) Positive sequence angle (-1) Range 0.3 - 1000 km 0.2 - 625 miles 90 - 90 Step size 0.010 km 0.005 miles 0.1

In = 1 A
Setting Positive sequence impedance (Z1) 6.1.2 Zones settings Setting Range 0.001 - 500 : Step size 0.001 :

In = 5 A
Range 0.002 199,8 : Step size 0.002 :

In = 1 A
Range Step size

In = 5 A
Range 0.0002 100 : 0 - 80 : Step size 0.0002 :

Impedance reaches 0.001 - 500 : 0.001 : (Zone 1, Zone 2, Zone 3, Zone P, Zone 4) Resistive reaches for phase earth faults (Zone 1, Zone 2, Zones 3 & 4, Zone P) Resistive reaches for phase earth faults (Zone 1, Zone 2, Zones 3 & 4, Zone P) 0 - 400 : 0.01 :

0.002 :

0 - 400 :

0.01 :

0 - 80 :

0.002 :

Setting Residual compensation angles (Zone 1, Zone 2, Zones 3 & 4, Zone P) Residual compensation factors (Zone 1, Zone 2, Zones 3 & 4, Zone P) Timer for zone 1/1X Timers for zone 2, Zone 3, Zone P, Zone 4

Range 180-180

Step size 0.1

0-7

0.001

0 - 10s 0 - 10s

0.002s 0.01s

P44x/EN TD/E33 Page 18/30 6.1.3 Power-swing settings

Technical Data MiCOM P441/P442 & P444

In = 1 A
Setting Powerswing detection boundaries: Delta R Delta X Range 0 - 400 : 0 - 400 : Step size 0.01 : 0.01 :

In = 5 A
Range 0 - 80 : 0 - 80 : Step size 0.002 : 0.002 :

Setting Imax line IN threshold I2 threshold Trip mode Unblocking time delay Power-swing detection boundary Block zones

Range

Step size 0.01 In 1%Imax 1%Imax 0.1s 0.01 :

In - 20 In
10 - 100 % Imax 10 - 100 % Imax Single/Three pole 0 - 30s 0 - 25 :

Bit 0: Z1&Z1X-Block, Bit 1: Z2 block Bit 2: Z3 block, Bit 3: Zp block, Bit 4:Z4block

6.2

Distance protection schemes Basic scheme functions: Instantaneous zone 1 tripping Time delayed tripping for all zones Directional earth fault protection Zero sequence Power protection (since B1.0) Switch on to fault logic Trip on reclose logic Loss of load logic Conversion to three pole tripping Channel-aided distance schemes: Permissive Overreach Protection Overreaching Zone 1 (POP Z1) Permissive Overreach Protection Overreaching Zone 2 (POP Z2) with with

Permissive Underreach Protection, Accelerating Zone 2 (PUP Z2) Permissive Underreach Protection Tripping via Forward Start (PUP Fwd) Blocking Overreach Protection with Overreaching Zone 1 (BOP Z1) Blocking Overreach Protection with Overreaching Zone 2 (BOP Z2) Permissive Scheme Unblocking Logic Permissive Overreach Schemes Weak Infeed Features Permissive Overreach Schemes Current Reversal Guard Blocking Scheme Current Reversal Guard

Potrebbero piacerti anche