Test And Drain Valve

A61

FEMALE x FEMALE Standard equipment: Female NPT inlet and outlet, forged brass body, brass finish ball with teflon seats.
FM approved at 300 psi * UL listed

CERTIFICATIONS

b a c

LISTED 36Y7

a/b (Orifice - K factor) 1(3/8-2.8)*


C H
PORT

c (plug) 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4

PORT 1-1/16 1-1/16 1-1/16 1-1/16 1-1/16 1-1/16 1-1/16 1-1/16 1-1/16 1-1/16

A 5-1/32 5-1/32 5-1/32 5-1/32 5-1/32 5-1/32 5-1/32 5-1/32 5-1/32 5-1/32

B 2-43/64 2-43/64 2-43/64 2-43/64 2-43/64 2-43/64 2-43/64 2-43/64 2-43/64 2-43/64

C 5-11/32 5-11/32 5-11/32 5-11/32 5-11/32 5-11/32 5-11/32 5-11/32 5-11/32 5-11/32

D 4-27/64 4-27/64 4-27/64 4-27/64 4-27/64 4-27/64 4-27/64 4-27/64 4-27/64 4-27/64

H 1-57/64 1-57/64 1-57/64 1-57/64 1-57/64 1-57/64 1-57/64 1-57/64 1-57/64 1-57/64

1(7/16- 4.2)* 1 (1/2-5.6) * 1(17/32- 8) * 1-1/4 (3/8-2.8)* 1-1/4 (7/16-4.2)*

B D

1-1/4 (1/2-5.6) * 1-1/4(17/32- 8) *

SPECIFY THREAD

1-1/4 (5/8-11.2)* 1-1/4 (3/4-14)*

A61
b

GROOVE X GROOVE Standard equipment: GROOVE inlet and outlet, forged brass body, brass finish ball with teflon seats.
FM approved at 300 psi

CERTIFICATIONS

a c

a/b (Orifice - K factor) c (plug) 1-1/4 (3/8 - 2.8)


C B D H
PORT

PORT 1-1/16 1-1/16 1-1/16 1-1/16 1-1/16 1-1/16

A 6-13/32 6-13/32 6-13/32 6-13/32 6-13/32 6-13/32

B 2-43/64 2-43/64 2-43/64 2-43/64 2-43/64 2-43/64

C 5-11/32 5-11/32 5-11/32 5-11/32 5-11/32 5-11/32

1/4 1/4 1/4 1/4 1/4 1/4

4-27/64 1-1/4groove 4-27/64 1-1/4groove 4-27/64 1-1/4groove 4-27/64 1-1/4groove 4-27/64 1-1/4groove 4-27/64 1-1/4groove

1-1/4 (7/16 - 4.2) 1-1/4 (1/2 - 5.6) 1-1/4 (17/32 - 8) 1-1/4 (5/8 - 11.2)

1-1/4 (3/4 - 14)

SPECIFY THREAD

42

(Technical communication n A039)

A61 Test and Drain valve


Standard equipment Female NPT inlet and outlet, forged brass body, chrome plated ball with teflon seats.

Products Test and drain valve Female x Female 1" (orifice 1/2") 1 1/4"(orifice 1/2") 1" (orifice 17/32") 1 1/4" (orifice 17/32")

Thread

A61Y005 A61Y006 A61Y015 A61Y016

1" NPT (orifice 1/2") 1 1/4" NPT (orifice 1/2") 1" NPT (orifice 17/32") 1 1/4" (orifice 17/32")

Dimensions
PORT 1" (orifice 1/2) 1" (orifice 17/32") 1 1/4" (orifice 1/2") 1 1/4" (orifice 17/32") A B 2 45/64" 2 45/64" 2 45/64" 2 45/64" C 5 11/32" 5 11/32" 5 11/32" 511/32"

1 7/64" 5 1/32" 1 7/64" 5 1/32" 1 7/64" 5 1/32" 1 7/64" 5 1/32"

Inspection and test of the wet pipe sprinkler system System Test Connections The initial test required on a wet pipe automatic sprinkler system is the hydrostatic test at not less that 200 psi for two hours, or 50 psi in excess of the static pressure, when the maximum static pressure exceeds 150 psi. During the hydrostatic test there should be no visible leakage from the sprinkler system piping. The underground mains leading to the sprinkler system should always be thoroughly flushed before the mains are connected to the system. A weekly inspection of all water control valves and alarm control valves is recommended to be certain they remain open. (Giacomini A200 valves have green indicator to see their open or closed position from 50 ft distance) Wet Systems A test connection not less than 1 in. (25 mm) in diameter, terminating a smooth bore corrosion resistant orifice, given a flow equivalent to one sprinkler of a type having the smallest orifice installed on the particular system, shall be provided to test each waterflow alarm device for each system. The test connection valve shall be readily accessible. The discharge shall be to the outside, to a drain connection capable of accepting full flow under system pressure or to another location where water damage will not result.

Drainage All sprinkler pipes and fittings shall be so installed that the system may be drained Giacomini Test and Drain valve merges in one valve the above two functions of testing and draining the system. Connections to the branch line (a and b) 1" and 1 1/4" Orifice 1/2" or 5/8" size

The valves will be available for two orifices: inch and 5/8" Special patented construction allows the ball to be supported at the flow inlet side by a special plastic housing. By rotation of the lever handle the valve can be set at: OFF position Test position Drain position

Stem seals: two "O" rings with stem inserted from inside of the valve. In multistory buildings where waterflow alarm devices are provided at each floor or where more than one alarm device is provided in one sprinkler system, a test type pipe shall be provided for

The intent of this section is to require inspector's test connection located in a manner which will provide for the testing of all water flow alarm devices. Pressure

It permits both an electrically operated alarm and a water motor alarm supplied from an alarm valve to be tested through a single test pipe.

VEHZ.EX4430 - Drain Fittings, Special Type

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpag...

VEHZ.EX4430 Drain Fittings, Special Type


Page Bottom

Drain Fittings, Special Type


See General Information for Drain Fittings, Special Type GIACOMINI SPA VIA PER ALZO 39 28017 S MAURIZIO D'OPAGLIO, NOVARA ITALY Model A61 Test and Drain fitting, 1 in. and 1-1/4 in. NPT size simulating a 2.8, 4.2, 5.6, 8.0, 11.2 and 14.0 K-factor, for installation in threaded steel pipe where pressures do not exceed 300 psig. Model A61 Test and Drain fitting, 2 in. NPT size simulating a 4.2, 5.6, 8.0, 11.2, 14.0, 16.8, 22.4 and 25.2 K-factors, for installation in threaded or grooved steel pipe where pressures do not exceed 300 psig. This fitting is intended for installation on sprinkler systems in accordance with the Standard for Installation of Sprinkler Systems, NFPA 13. Last Updated on 2009-09-28 Questions? Print this page Notice of Disclaimer Page Top Copyright 2010 Underwriters Laboratories Inc. The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright 2010 Underwriters Laboratories Inc." EX4430

1 de 1

19/07/2010 02:37 p.m.

Sprinkler System Alarm Testers


Each separate sprinkler system must be equipped with a separate waterflow alarm. In a high rise building, the system for each floor must be separately alarmed. Where pressure reducing valves are used, a dual alarm and drain piping arrangement is required. The alarm testers listed below combine test and drain valves, a waterflow sight glass, and a calibrated flow orifice in a single assembly to simplify the piping required for such arrangements.

Model A61
Model Designation A61 A61 Size, inches NPS 1 1 14 Nominal K-factor(s) 2.8, 4.2, 5.6, 8.0 2.8, 4.2, 5.6, 8.0, 11.2, 14.0 4.2, 5.6, 8.0, 11.2, 14.0, 16.8, 22.4, and 25.2 Rated working pressure, psi (kPa) 300 (2070) 300 (2070) Remarks a a, b

A61

300 (2070)

a, b

Remarks: a. Devices supplied with female NPT threaded end connections. b. Devices supplied with grooved end connections.

Company Name: Giacomini SpA Company Address: Strada Per Alzo 39, 28017 S Maurizio d'Opaglio, Italy Company Website: http://www.giacomini.com Listing Country: Italy Certification Type: FM Approved

2007-2010 FM Approvals. All rights reserved.