Current and voltage transformers for Low Voltage

Edition 05.07

Operation manual

1. Mounting site
Instrument transformers of ALCE shall be mounted in accordance with following conditions; a) Ambient temperature: -20C~40C (Avarage temp.: lower than 35C) b) Altitude: lower than 1000 meters. c) At the places not exposed to sea - breeze, rain, snow and sunlight and kept under 90% humidity. d) At places where the exceeded vapor, oil-vapor, explosive flammable gas shall not occur. e) At places not subject to exceeded dust & foreing particles. f) At places where exceeded oscillation and impact shall not occur. d) The connection shall be correctly done as per the terminals marks and connection diagram on the name plate. e) The earthing terminal on primary side of grounding type of instrument transformers shall be absolutely grounded. f) The earthing terminal on secondary side and the mounted base (flame) on the body shall be absolutely grounded. g) Bolts & Nuts for the connection of cables, busbars and lead wires shall be firmly fastened.

3.Maintenance and inspection


a) Please check instrument transformers once a month and pay your attention for noise, over - heat, corrosion and exceeded polluting. It is recommended to put the thermo-labels on surface of transformers and terminals portion. b) The operation shall be stopped at least once a year and the dust & foreing particles shall be wiped off with dry cloth. At that time, please check the appearance, the iron-core and looseness of bolts & nuts.

2. How to mount
a) Cable and busbar shall not be directly loaded onto CT&PT. b) Enough distance shall be taken that primary lead wires and busbars do not approach the surface of transformers except the connection terminals. Besides, please draw your attention for corona and partial discharge not to occur. c) Secondary lead wires shall be correctly connected to the terminals and shall not be approached to the surface of transformers.

ALCE 2005 - 07

- 01 -

Current transformers for low voltage


General information

Properties Location Standard, insulation level Frequency Insulation : indoor : IEC - 60044-1, DIN VDE 0414 edition 01/1994, Um: 0,72 kV : 50 - 60 Hz : thermoplastic casing, insulation class E

Rated continious thermal current : 1,2 In Secondary rated current Security factor : 5A or 1A : for class 0.5, at primary current <1500 A, FS5 ; at primary current < 4000 A, FS10 : for class 1.0, at primary current <2000 A, FS5 ; at primary current <4000 A, FS10 Rated short time thermal current : Ith =60 x In Rated dynamic current : Idyn = 2,5 x Ith

Standards

Terminal designation Primary Secondary S1 - S2 S1 - S2 k-l S1 - S2 S1 - S2 x1 - x2 Measuring 0,2 - 0,5 - 1 - 3 - 5 0,2 - 0,5 - 1 - 3 - 5 0,2 - 0,5 - 1 - 3 - 5

Class Protection 5P - 10P 5P - 10P 5P - 10P 5P - 10P - X P - PL C-T

TS 620 IEC 60044-1 VDE 414 BS 3938 AS 1675 ANSI 57.13

P1 - P2 P1 - P2 K-L P1 - P2 P1 - P2 X1 - X2

0,2 - 0,5 - 1 - 3 - 5 0,5M - 1M - 2M - 5M 0.3B - 0.6B - 1.2B

- secondary terminals M5 bolts. - upon request secondary reconnection - upon request different security factors.

Accessories
Connecting accessory Foot attachment

- 02 -

ALCE 2005 - 07

Current transformers for low voltage


General information

-all types are sealed or pivoted from inside, not openable

Types and descriptions Types ASS, ASK ASB ADS 20, A 20, ADS 30, ADB 30 ADS 40, ADB 40, A 50, A 61, ADS 62, ADB 80, ADB 81, A 101, ADB 111, ADB 120 ARS-1, ARS-2 ARK-1, ARK-2 ARD-2, ARD-3 A125 TA-2, TA-3, TA-4, TA-5, TA6 TDR Descriptions Wound current transformers (primary cable) Wound current transformers (primary busbar 25x3 mm x mm) Plug-in current transformers. For bars or round conductor.

Primary cable protection current transformer for relays. Bar-type. Protection current transformer for relays. Bar or cable type. Protection current transformer for relays. Bar-type cast resin. Summation current transformers with up to 6 separate independent primary input circuits. Current transformer for differential protection.

Types according to bar dimensions Bar widths Types ADS 20, A 20 ADS 30, ADB 30 ADS 40, ADB 40 A50 A61 ADS 62 ADB 80 ADB 81 A101 20 mm 30 mm 40 mm 50 mm 60 mm 80 mm 100 mm 120 120 mm mm 150 mm 200 mm

ADS 100, ADB 111 ADB120 ADB120 A 125 (*)

(*)

(*)

(*) Upon request

ALCE 2005 - 07

- 03 -

Current transformers for low voltage ASS, ADS20, ADS30, ADS40, ADS62, ADS100
Tables and dimensions

ASS
Cable mm Window
mm x mm

ASS

15 21 x 5,5 20 x 5 ADS20

23 31 x10,5 30 x 10 ADS30

28 41 x 15 40 x 10 ADS40

30 61 x 31

52 101 x 53

Bar
mm x mm

2(60 x 10) 3(100 x 10) ADS62 ADS100

Types Primary current A

0,5 1 2,5 5 10 15 20 25 30 40 50 60 75 80 100 125 150 200 250 300 400 500 600 750 800 1000 1200 1250 1500 1600 1800 2000 2500 3000 3200 2,5 2,5 5 5 5 5

1,0 2,5 2,5 5 5 5 5

0,5

1,0

For secondary 5A or 1A Rated power VA Class 0,5 1,0 0,5 1,0 0,5

ADS 20
1,0 0,5 1,0

ADS 30
() () () () () () 2,5 3,75 5 () () () () () () 2,5 2,5 5 5 5 () () 2,5 3,75 5 5 5 2,5 2,5 5 5 5 5 10 10 10 10 10 10 10 10 10 10 10 10 15 15 30 30 30 30 30 10 10 15 15 15 15 15 30 30 30 30 30 15 15 15 30 30 30 30 30 30 30 15 15 15 30 30 30 30 30 30 30

ADS 40

ADS 62

ADS 100

() Penetration winding current transformers

All types are protected against contact.

- 04 -

ALCE 2005 - 07

Current transformers low voltage ASK, ASB, A20, ADB30, ADB40, A50, A61
Tables and dimensions

Cable mm Window
mm x mm

ASK

ASB

16 21 x 11 20 x 10 A20

26 31 x 11 30 x 10 ADB30

30 41 x 11 40 x 10 ADB40

40 51 x 11 50 x 10 A50

62 x 12 60 x 10 A61

ASK

Bar
mm x mm

Types Primary current A 1 2,5 5 10 15 20 25 30 40 50 60 75 80 100 125 150 200 250 300 400 500 600 750 800 1000 1200 1250

For secondary 5A or 1A Rated power VA Class 0,5 1,0 0,5 1,0

ASB
0,5 1,0 0,5 1,0 0,5 1,0

0,5 10 10 15 15 15

1,0 10 10 15 15 15

0,5

1,0

15 15 15 15 15 15 15 15 15 15 15 15 15

15 15 15 15 15 15 15 15 15 15 15 15 15 5 5 10 15 15 15 15 5 10 15 15 15 15 15 (*) (*) 10 10 15 15 5 10 10 15 15 15 (*) 10 10 15 15 15 15 15 10 10 10 15 15 15 15 15 5 10 10 15 15 15 15 15 15 15 10 10 15 15 15 15 15 15 15 15 10 10 15 15 15 15 15 15 10 15 15 15 15 15 15 15

A20

ADB30

ADB40

A50

A61

All types are protected against contact (except type A20) ALCE 2005 - 07

- 05 -

Current transformers for low voltage ADB80, ADB81, A101, ADB111, ADB120
Tables and dimensions

ADB80
Cable mm Window
mm x mm

61 82 x 32 2(80 x 10) ADB80

30 81 x 31 2(80 x 10) ADB81

30 102 x 32

56 102 x 58

70 121 x 72

Bar
mm x mm

2(100 x 10) 3(100 x 10) 4(120 x 10) A101 ADB111 ADB120

Types Primary current A 400 500 600 750 800 1000 1200 1500 1600 1800 2000 2500 3000 4000 5000

For secondary 5A or 1A * Rated power VA Class 1,0 0,5 1,0 0,5 10 15 15 30 30 30 30 30 30 30 30 30 30 10 15 15 15 30 30 30 30 30 30 30 30 15 15 30 30 30 30 30 30 30 30 30 30 15 15 30 30 30 30 30 30 30 30 15 30 30 30 30 30 30 30 45 45 15 30 30 30 30 30 30 30 30 15 30 45 30 30 30 30 30 45 45

ADB81
1,0 0,5 1,0

0,5 10 10 15 15 15 30 30 30 30 30 30 30 30

1,0 10 15 15 30 30 30 30 30 30 30 30 30 30

0,5 10 10 10 15 15 15 30 30 30 30 30 30 30

A101

ADB111

ADB120

All types are protected against contact


* For primary currents >4000 A , only 5A secondary current is possible.

- 06 -

ALCE 2005 - 07

Current transformers for low voltage ARS-1, ARS-2, ARK-1, ARK-2, ARD-2, ARD-3
Tables and dimensions

ARS-1
Cable mm Window
mm x mm

ARS - 1

ARS - 2

ARK - 1

ARK - 2

30 82 - 32

30 102 - 32

Bar
mm x mm

2(80 x 10) 2(100 x 10) ARD - 2 ARD - 3

Types

For secondary 5A or 1A Primary current A 5 10 15 20 25 30 40 50 60 75 80 100 125 150 200 250 300 400 500 600 750 800 1000 1200 1250 1500 1600 1800 2000 2500 3000 4000 Rated power VA Class
5P5 5P10 5P5 5P10 5P5 5P10 5P5 5P10 5P5 5P10 5P5 5P10 10P5 10P10 10P5 10P10 10P5 10P10 10P5 10P10 10P5 10P10 10P5 10P10

ARS-2

15 15 15 15

5 5 5 5

30 30 30 30

15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 5 5 5 5 5 5 5 5 5 5 5 5 5 5 30 30 30 30 30 30 30 30 30 30 30 30 30 30 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 30 30 30 30 30 30 30 5 5 5 5 15 15 15 15 30 30 30 30 30 30 30 30 30 30 30 30 30 30 45 45 45 15 15 15 15 15 15 15 15 30 30 30 30 30 30

ARK-1

ARK-2

ARD-2

ARD-3

All types are protected against contact Primary bars (for type ARK) Primary current A 25 - 200 250 - 400 ALCE 2005 - 07 Bar width mm 5 10

- 07 -

Summation current transformers for low voltage TA-2, TA-3, TA-4, TA-5, TA-6
Tables and dimensions

Type 1
Primary A TA-2
5+5 / 5

Rated power VA Class 0,5 Class 1 Type 2 Type1 Type 1 Type 2 5 10 5 10 30 30 15 30 15 30 15 30 10 15 5 10 30 30 15 30 15 30 15 30

TA-3
5+5+5 / 5

TA-4
5+5+5+5 / 5

TA-5
5+5+5+5+5 / 5

TA-6
5+5+5+5+5+5 / 5

Type 2

Important : Summation current transformers are


designed according to the ratios of the main current transformers for summation.

Example :
Main current transformers : Summation current tranformers : Result : 300A , 100A , 100A 5 1 5 5+1+5 A 5

300 + 100 + 100 : 100 Ratio 5

Connection diagram of summation current transformer ( Type TA-3 )


One phase (R) of the three- phase A, B, C groups is shown in the picture

R S T K A k L * l
* *

K B k

L * l

* *

K C k

L * l

* *

R S T
Burden for measuring

AK AL BK BL k R

CK CL l S T * Main current transformers

Summation current transformers

Burden of summation current transformer

- 08 -

ALCE 2005 - 07

Current transformer for low voltage A125


Table and dimensions

Indoor current transformer Type A125 cast resin, for busbar fastening

A125
Window
mm x mm

126 x 72 4(120 x 10) A125 For secondary 5A or 1A Rated power VA Class 0,5 1,0 30 45 30 45 60 45 60 100

Bar
mm x mm

Tip Primary current A 5000 6000 7500 8000

ALCE 2005 - 07

- 09 -

Voltage transformers for measuring and protection VM, 2VM


Table and dimensions

- Insulation level 0,72 kV and 1,2 kV - Windings are cast resin.

Type 1 2

L1 40 50

L2 90 100

Weight (kg) 6.6 8.3

VM
Secondary voltage = Earth-fault winding = 100 V 110 V , 3 3 100 V 110 V , 3 3

2VM

For secondary voltage 100 V or 110 V Secondary thermal burden current; Isth

Rated voltage factor = 1.9 (30 sec.) Secondary thermal burden current; Isth

Primary voltage 100 : 3 110 : 3 200 : 3 220 : 3 380 : 3 400 : 3 500 : 3 1.2 kV, Isth=2A* 500 : 3 600 : 3 750 : 3 1000 : 3 15 30 45 60 VA

Class 0.5

Class 1

Class 3

Primary voltage 0.72 kV, Isth=2A VA

Class 0.5

Class 1

Class 3

0.72 kV, Isth=3A* 15 30 45 60 1 2 1 1 2 2 1 1 1 1

100 V 110 V 200 V 220 V 380 V 400 V 500 V 1.2 kV, Isth=1A

30 45 60

2 -

1 1 1

1 1 1

Rated output and sizes as above.

Rated output and sizes as above.

1 -

1 1 2 2

1 1 1 2

500 V 600 V 750 V 1000 V

15 30 45 60

1 2 -

1 1 2 2

1 1 1 1

* Isth = 1A with earth-fault winding

- 10 -

ALCE 2005 - 07