Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Point Description
Plumbing & Fire Protection Water Meters Incoming Water Flow [Water Meter] Total per Unit Total for all Units Total Water Meters Points Sump Pumps-SP1 TO SP2 [1-Duty & 1-Lag] - 2 Lift Sta. 1 2 3 4 5 4 Pump on/off Status Pump Trip Status Pressure in the Common Discharge Header Pump Auto / Manual Status Sump High & Low Level Total per Unit Total for all Units Total Sump Pumps Points Electric Water Heaters [EWH] 1 1 EWH On/Off Status TOTAL Total Electric Water Heaters -Points Total Electric Water Heaters -Points 0 0 1 2 1 1 1 1
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software OPC Network Client DI AO DO Thermostat Integration
Remarks
Flow Meter 0 0 1 0 0 0 0
2 1 1 2 6 24 26 0 0 0 0
From Pump Control Panel From Pump Control Panel Liquid Pressure Sensor From Pump Control Panel From Tank Float Switch
1 1 1 1 0 0 0 0
1 of 21
Project : ITCC -COMMERCIAL STORES Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Plumbing and Fire Protection Equipments Water Meters Incoming Water Flow [Water Meter] Total per Unit Total for all Units Total Water Meters Points Sump Pumps-SP1 TO SP5 [1-Duty & 1-Lag] -5 Lift Sta. 1 2 3 4 5 Pump on/off Status Pump Trip Status 10 Pressure in the Common Discharge Header Pump Auto / Manual Status Sump High & Low Level Total per Unit Total for all Units Total Sump Pumps Points Air Purification Unit (Aerator) - 1 no. each Grey Water Treatment Plant 1 1 Aerator On/Off /Fault Status TOTAL Total Aeratot Unit Points Total Aerator Unit Points 0 0 1 5 1 1 1 1
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
Remarks
1 1
Flow Meter 0 0 1 0 0 0 0
2 1 1 2 6 60 65 0 0 0 0
From Pump Control Panel From Pump Control Panel Liquid Pressure Sensor From Pump Control Panel From Tank Float Switch
3 3 3 3 0 0 0 0
Sand Filters & Activated Carbon Filters for Grey Water Treatment Plant [1 nos. Sand Filters x 1 nos.plant + 1 nos. Activated C.Filters x 1 plant] High D P of Sand Filters 1 TOTAL 1 2 0 0 2 0 0 0 0
Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points Total Sand Filter and Carbon Filters for Grey Water Treatment Plant -Points Electric Water Heaters [EWH] 1 10 EWH On/Off Status TOTAL Total Electric Water Heaters -Points Total Electric Water Heaters -Points
1 0 0 1 10 10 0 0 0 0
2 of 21
Project : ITCC -COMMERCIAL CENTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Plumbing and Fire Protection Equipments Water Meters Incoming Water Flow [Water Meter] Total per Unit Total for all Units Total Water Meters Points Grey Water Tanks 1 2 3 4 5 6 1 Tank Low Level Tank High Level Potable Make-up Incoming Water Flow Influent Dirt Interceptor SHOCKED Alarm Tank water volume reading Tank Level (%) Monitor Total per Unit Total for all Units Total Grey Water Tanks Points Sump Pumps-SP1 TO SP-5 [1-Duty & 1-Lag] - 5 Lift Sta. 1 2 3 4 5 Pump on/off Status Pump Trip Status 10 Pressure in the Common Discharge Header Pump Auto / Manual Status Sump High & Low Level Total per Unit Total for all Units Total Sump Pumps Points 1 5 1 1 1 3 3 1 1 1 1
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
Remarks
1 1
Flow Meter 0 0 1 0 0 0 0
1 1 1
From Tank Float Switch From Tank Float Switch Solenoid valve Float Switch Relay Output From BMS (4-20)mA from the Level Indicator
3 3 6
0 0
0 0
2 1 1 2 6 60 65 0 0 0 0
From Pump Control Panel From Pump Control Panel Liquid Pressure Sensor From Pump Control Panel From Tank Float Switch
Odor Control Unit, Chlorination Unit & Coloring Dye Unit of Grey Water Treatment Plant (1 unit each plant x 1no. plant) 1 2 3 4 5 6 7 3 Dosing Pump On/Off Status Chemical flow status Dosing Pump Trip Alarm Dosing Pump Auto / Manual Status Dosing Pump Start/stop command Chemical Tank Level Chemical Tank Low Level Alarm TOTAL Total Odor Control, Chlorination, Coloring Dye Units Points 0 0 1 1 6 18 0 0 1 3 1 1 1 1 1 From Grey Water Treatment Plant Panel Flow switch From Grey Water Treatment Plant Panel From Grey Water Treatment Plant Panel Relay Output From BMS From Grey Water Treatment Plant Panel From Grey Water Treatment Plant Panel
3 of 21
Project : ITCC -COMMERCIAL CENTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Total Odor, Chlorination, Coloring Dye Units Points Air Purification Unit (Aerator) - 1no. each Grey Water Treatment Plant 1 1 Aerator On/Off /Fault Status TOTAL Total Aerator Unit Points Total Aerator Unit Points Non-Potable water pumps [2-Duty&1-Standby]- 1set 1 2 3 4 5 6 7 8 3 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Discharge header pressure Pump motor temperature high TOTAL Total Non-Potable Water Pumps Points Total Non-Potable Water Pumps Points Filter Pumps for Grey Water Treatment Plant, [2-pumps x 1-set] 1 2 3 4 5 6 7 2 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Pump motor temperature high TOTAL Total Filter Pumps for Potable Water -Points Total Filter Pumps for Potable Water -Points 1 1 2 1 1 2 6 0 0
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
21
Remarks
3 3 3 3 0 0 0 0
1 1 1 1 1 1
VFC From Pump Control Panel Flow switch VFC From Pump Control Panel VFC From Pump Control Panel Relay Output From BMS Liquid pressure switch Liquid pressure sensor From Pump Control Panel
5 15 24
0 0
1 3
1 1 1 1 1 1 5 10 14 0 0 1 2
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch From Pump Control Panel
Sand Filters & Activated Carbon Filters for Grey Water Treatment Plant [1 nos. Sand Filters x 1 nos.plant + 1 nos. Activated C.Filters x 1 plant] High D P of Sand Filters 1 TOTAL 1 2 0 0 0 0 0 0
Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points
4 of 21
Project : ITCC -COMMERCIAL CENTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
2
Remarks
Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points Electric Water Heaters [EWH] 1 16 EWH On/Off Status TOTAL Total Electric Water Heaters -Points Total Electric Water Heaters -Points 0 0 1 1 16
5 of 21
Project : ITCC - SPORTS CLUB Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Plumbing and Fire Protection Equipments Water Meters Incoming Water Flow [Water Meter] Total per Unit Total for all Units Total Water Meters Points Flow Meter for Swimming Pool Water Flow Total per Unit Total for all Units Total FlowMeters Points Swimming Pool Surge Tank 1 2 3 4 1 Tank Low Level Alarm Tank High Level Alarm Potable Make-up Incoming Water Flow Tank Level (%) Monitor Total per Unit Total for all Units Total Swimming Pool Surge Tank Points Grey Water Tanks 1 2 3 4 5 6 1 Tank Low Level Tank High Level Potable Make-up Incoming Water Flow Influent Dirt Interceptor SHOCKED Alarm Tank water volume reading Tank Level (%) Monitor Total per Unit Total for all Units Total Grey Water Tank Points 1 1 3 3 1 1 1 2 2 1 1 2 1 1 1
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
Remarks
Flow Meter 0 0 1 0 0 0 0
Flow Meter 0 0 2 0 0 0 0
1 1
From Tank Float Switch From Tank Float Switch Solenoid valve (4-20)mA from the Level Indicator
2 2 4
0 0
0 0
1 1 1
From Tank Float Switch From Tank Float Switch Solenoid valve Float Switch Relay Output From BMS (4-20)mA from the Level Indicator
3 3 6
0 0
0 0
6 of 21
Project : ITCC - SPORTS CLUB Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.
1 2 3 4 5 4 Pump on/off Status Pump Trip Status Pressure in the Common Discharge Header Pump Auto / Manual Status Sump High & Low Level Total per Unit Total for all Units Total Sump Pumps Points Chrlorine Injection Unit & Acid Injection Unit for Swimming Pool 1 2 3 4 5 6 7 2 Dosing Pump On/Off Status Chemical flow status Dosing Pump Trip Alarm Dosing Pump Auto / Manual Status Dosing Pump Start/stop command Chemical Tank Level Chemical Tank Low Level Alarm TOTAL Total Chlorine Unit & Acid Unit Points Total Chlorine & Acid Unit Points 0 0 1 2 1
Point Description
Sump Pumps-SP1 TO SP-2 [1-Duty & 1-Lag] - 2Lift Sta.
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
2 1 1 2 6 24 26 0 0 0 0
Remarks
From Pump Control Panel From Pump Control Panel Liquid Pressure Sensor From Pump Control Panel From Tank Float Switch
1 1 1 1 1 1 1 6 12 14 0 0 1 2
From Swimming Pool Control Panel Flow switch From Swimming Pool Control Panel From Swimming Pool Control Panel Relay Output From BMS From Swimming Pool Control Panel From Swimming Pool Control Panel
Odor Control Unit, Chlorination Unit & Coloring Dye Unit of Grey Water Treatment Plant (1 unit each plant x 1no. plant) 1 2 3 4 5 6 7 3 Dosing Pump On/Off Status Chemical flow status Dosing Pump Trip Alarm Dosing Pump Auto / Manual Status Dosing Pump Start/stop command Chemical Tank Level Chemical Tank Low Level Alarm TOTAL Total Odor Control, Chlorination, Coloring Dye Units Points Total Odor, Chlorination, Coloring Dye Units Points 0 0 1 1 6 18 21 0 0 1 3 1 1 1 1 1 From Grey Water Treatment Plant Panel Flow switch From Grey Water Treatment Plant Panel From Grey Water Treatment Plant Panel Relay Output From BMS From Grey Water Treatment Plant Panel From Grey Water Treatment Plant Panel
7 of 21
Project : ITCC - SPORTS CLUB Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.
1
Point Description
Air Purification Unit (Aerator) - 1no. each Grey Water Treatment Plant Aerator On/Off /Fault Status TOTAL Total Aerator Unit Points Total Aerator Unit Points Non-Potable water pumps [2-Duty&1-Standby]- 1set
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
3
Remarks
From Grey Water Treatment Plant Panel
0 0
3 3 3
0 0
0 0
1 2 3 4 5 6 7 8 3
Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Discharge header pressure Pump motor temperature high TOTAL Total Non-Potable Water Pumps Points Total Non-Potable Water Pumps Points Filter Pumps for Grey Water Treatment Plant, [2-pumps x 1-set] 1 1 2 6
1 1 1 1 1 1
VFC From Pump Control Panel Flow switch VFC From Pump Control Panel VFC From Pump Control Panel Relay Output From BMS Liquid pressure switch Liquid pressure sensor From Pump Control Panel
5 15 24
0 0
1 3
1 2 3 4 5 6 7 2
Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Pump motor temperature high TOTAL Total Filter Pumps for Grey Water Treatment Plant -Points Total Filter Pumps for Grey Water Treatment Plant -Points 1 1 2
1 1 1 1 1 1 5 10 14 0 0 1 2
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch From Pump Control Panel
Sand Filters & Activated Carbon Filters for Grey Water Treatment Plant [1 nos. Sand Filters x 1 nos.plant + 1 nos. Activated C.Filters x 1 plant] High D P of Sand Filters 1
8 of 21
Project : ITCC - SPORTS CLUB Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.
2 TOTAL Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points Swimming Pool Filter High D P of Sand Filters TOTAL Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points Swimming Pool Circulating Pumps [2-Duty&1-Standby]- 1set 1 2 3 4 5 6 7 8 3 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Discharge header pressure Pump motor temperature high TOTAL Total Swimming Pool Circulating Pumps Points Total Swimming Pool Circulating Pumps Points Hot Water Circulating Pumps [1-Duty & 1-Standby] 1 2 3 4 5 2 Pump On/Off Status Pump Trip Alarm Pump Start/stop command Discharge header pressure Pump motor temperature high TOTAL Total Hot Water Circulating Pumps Points Total Hot Water Circulating Pumps Points 1 1 2 4 1 1 2 6
Point Description
AI
1 2
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
0 0 2 0 0 0 0
Remarks
Treatment Plant Panel
1 1 2 0 0 2 0 0 0 0
1 1 1 1 1 1
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch Liquid pressure sensor From Pump Control Panel
5 15 24
0 0
1 3
1 1 1
From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure sensor From Pump Control Panel
2 4 10
0 0
1 2
9 of 21
Project : ITCC - SPORTS CLUB Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Water Quality Monitor Unit for swimming pool 1 1 PH of swimming pool water TOTAL Total Water Quality Monitor Points Total Water Quality Monitor Points UV Reactor for Swimming Pool 1 2 1 UV Reactor ON/Off /Fault Status UV Lamps run hours TOTAL Total Aerator Unit Points Total Aerator Unit Points Electric Water Heaters [EWH] for Swimming Pool 1 1 EWH On/Off Status TOTAL Total Electric Water Heaters -Points Total Electric Water Heaters -Points Electric Water Heaters [EWH] for Building 1 11 EWH On/Off Status TOTAL Total Electric Water Heaters -Points Total Electric Water Heaters -Points 0 0 0 0 0 0 0 0
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
Remarks
1 1 1 1 0 0 0 0
3 3 3 4 0 0 1 1 1
1 1 1 1 0 0 0 0
1 1 11 11 0 0 0 0
10 of 21
Project : ITCC -SCHOOL Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Plumbing and Fire Protection Equipments Water Meters Incoming Water Flow [Water Meter] Total per Unit Total for all Units Total Water Meters Points Sump Pumps [1-Duty & 1-Standby] - 1 no. Lift Sta. 1 2 3 4 5 2 Pump on/off Status Pump Trip Status Pressure in the Common Discharge Header Pump Auto / Manual Status Sump High & Low Level Total per Unit Total for all Units Total Sump Pumps Points 1 1 1 1 1 1
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
Remarks
Flow Meter 0 0 1 0 0 0 0
2 1 1 2 6 12 13 0 0 0 0
From Pump Control Panel From Pump Control Panel Liquid Pressure Sensor From Pump Control Panel From Tank Float Switch
Electric Water Heaters [EWH] 1 3 EWH On/Off Status TOTAL Total Electric Water Heaters -Points Total Electric Water Heaters -Points 0 0 1 1 3 3 0 0 0 0 From Building Local Control Panel
11 of 21
Project : ITCC -APPARTMENT Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Plumbing and Fire Protection Equipments Water Meters Incoming Water Flow [Water Meter] Total per Unit Total for all Units Total Water Meters Points Sump Pumps [1-Duty & 1-Standby] - 1 no. Lift Sta. 1 2 3 4 5 2 Pump on/off Status Pump Trip Status Pressure in the Common Discharge Header Pump Auto / Manual Status Sump High & Low Level Total per Unit Total for all Units Total Sump Pumps Points 1 1 1 1 1 1
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software Network OPC Client DI AO DO Thermostat Integration
Remarks
Flow Meter 0 0 1 0 0 0 0
2 1 1 2 6 12 13 0 0 0 0
From Pump Control Panel From Pump Control Panel Liquid Pressure Sensor From Pump Control Panel From Tank Float Switch
Electric Water Heaters [EWH] 1 3 EWH On/Off Status TOTAL Total Electric Water Heaters -Points Total Electric Water Heaters -Points 0 0 1 1 3 3 0 0 0 0 From Building Local Control Panel
12 of 21
Project : ITCC CLUSTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Plumbing & Fire Protection Combined Potable Water & Fire Water Tanks 1 2 3 4 5 6 7 2 Tank Low Level Tank High Level Motorized valve feedback Main water Tank Incoming Water Flow [Water Meter] Motorized valve control Tank water volume reading Tank Level (%) Monitor Total per Unit Total for all Units Total Combined Potable water and Fire Water Tanks Points Grey Water Tanks 1 2 3 4 5 6 4 Tank Low Level Tank High Level Potable Make-up Incoming Water Flow Influent Dirt Interceptor SHOCKED Alarm Tank water volume reading Tank Level (%) Monitor Total per Unit Total for all Units Total Grey Water Tanks Points Underground Fountain Water Tank No. 1 for Fountains Nos. 1 & 2 1 2 3 4 5 6 7 8 1 Tank Quick Fill Level Tank Running Level Tank Safe Off Level Motorized valve feedback Main water Tank Incoming Water Flow [Water Meter] Motorized valve control Tank water volume reading Tank Level (%) Monitor Total per Unit Total for all Units Total Underground Fountain Water Tanks No. 1 Points 1 1 3 3 1 1 1 3 12 1 1 1 3 6 1
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software OPC Network Client DI AO DO Thermostat Integration
Remarks
1 1 1 1
From Tank Float Switch From Tank Float Switch From the valve Flow Meter Relay Output From BMS Relay Output From BMS (4-20)mA from the Level Indicator
3 6 14
0 0
1 2
1 1 1
From Tank Float Switch From Tank Float Switch Solenoid valve Float Switch Relay Output From BMS (4-20)mA from the Level Indicator
3 12 24
0 0
0 0
1 1 1 1 1
From Tank Float Switch From Tank Float Switch From Tank Float Switch From the valve Flow Meter Relay Output From BMS Relay Output From BMS (4-20)mA from the Level Indicator
4 4 8
0 0
1 1
13 of 21
Project : ITCC CLUSTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Sump Pumps-SP1 [1-Duty & 1-Standby] - 4 Lift Sta. 1 2 3 4 5 8 Pump on/off Status Pump Trip Status Pressure in the Common Discharge Header Pump Auto / Manual Status Sump High & Low Level Total per Unit Total for all Units Total Sump Pumps Points Sump Pumps-SP2 [1-Duty & 1-Standby] - 14 Lift Sta. 1 2 3 4 5 Pump on/off Status Pump Trip Status 28 Pressure in the Common Discharge Header Pump Auto / Manual Status Sump High & Low Level Total per Unit Total for all Units Total Sump Pumps Points 1 14 1 1 4 1
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software OPC Network Client DI AO DO Thermostat Integration
Remarks
2 1 1 2 6 48 52 0 0 0 0
From Pump Control Panel From Pump Control Panel Liquid Pressure Sensor From Pump Control Panel From Tank Float Switch
2 1 1 2 6 168 182 0 0 0 0
From Pump Control Panel From Pump Control Panel Liquid Pressure Sensor From Pump Control Panel From Tank Float Switch
14 of 21
Project : ITCC CLUSTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.
1 2 3 4 5 6 7 8 9 10 5 Pump On/Off Status Fuel flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Discharge header pressure Pump motor temperature high Bulk Storage Tank Fuel Level Bulk Storage Tank Low Level Alarm Total per Unit Total for all Units 2 10 1 1
Point Description
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software OPC Network Client DI AO DO Thermostat Integration
1 1 1 1 1 1
Remarks
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch Liquid pressure sensor From Pump Control Panel
Diesel Fuel Transfer Pumps + Bulk Storage Tank [1-Submersible Pump Duty & 1-Manual Pump Standby] -5 sets
1 1 7 35 50 0 0 1 5
Odor Control Unit, Chlorination Unit & Coloring Dye Unit of Grey Water Treatment Plant (1 unit each plant x 4 nos. plants) 1 2 3 4 5 6 7 Dosing Pump On/Off Status Chemical flow status Dosing Pump Trip Alarm 12 Dosing Pump Auto / Manual Status Dosing Pump Start/stop command Chemical Tank Level Chemical Tank Low Level Alarm TOTAL Total Odor Control, Chlorination, Coloring Dye Units Points Total Odor, Chlorination, Coloring Dye Units Points Air Purification Unit (Aerator) - 2 no. each Grey Water Treatment Plant 1 8 Aerator On/Off /Fault Status TOTAL Total Aerator Unit Points Total Aerator Unit Points 0 0 3 3 24 24 0 0 0 0 From Grey Water Treatment Plant Panel 0 0 1 1 6 72 84 0 0 1 12 1 1 1 1 1 From Grey Water Treatment Plant Panel Flow switch From Grey Water Treatment Plant Panel From Grey Water Treatment Plant Panel Relay Output From BMS From Grey Water Treatment Plant Panel From Grey Water Treatment Plant Panel
Chlorination Unit, PH Control Unit & Sanitizer Unit of Fountains [1 unit each for 2 fountain system] 1 Dosing Pump On/Off Status 1 From Fountain Control Panel
15 of 21
Project : ITCC CLUSTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.
2 3 4 5 6 7 6 Chemical flow status Dosing Pump Trip Alarm Dosing Pump Auto / Manual Status Dosing Pump Start/stop command Chemical Tank Level Chemical Tank Low Level Alarm TOTAL Total Odor Control Unit Points Total Odor Control Unit Points Potable water pumps-DP-1 [2-Duty&1-Standby]- 4 sets 1 2 3 4 5 6 7 8 Pump On/Off Status Water flow status Pump Trip Alarm 12 Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Discharge header pressure Pump motor temperature high TOTAL Total Potable Water Pumps Points Total Potable Water Pumps Points Non-Potable water pumps-DP-1 [2-Duty&1-Standby]- 4 sets 1 2 3 4 5 6 7 8 Pump On/Off Status Water flow status Pump Trip Alarm 12 Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Discharge header pressure Pump motor temperature high TOTAL Total Non-Potable Water Pumps Points Total Non-Potable Water Pumps Points 1 1 2 8 1 1 2 8 0 0
Point Description
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software OPC Network Client DI AO DO Thermostat Integration
1 1 1 1 1 1 6 36 42 0 0 1 6 Flow switch
Remarks
From Fountain Control Panel From Fountain Control Panel Relay Output From BMS From Fountain Control Panel From Fountain Control Panel
1 1 1 1 1 1
VFC From Pump Control Panel Flow switch VFC From Pump Control Panel VFC From Pump Control Panel Relay Output From BMS Liquid pressure switch Liquid pressure sensor From Pump Control Panel
5 60 80
0 0
1 12
1 1 1 1 1 1
VFC From Pump Control Panel Flow switch VFC From Pump Control Panel VFC From Pump Control Panel Relay Output From BMS Liquid pressure switch Liquid pressure sensor From Pump Control Panel
5 60 80
0 0
1 12
16 of 21
Project : ITCC CLUSTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.
1 2 3 4 5 6 7 8 2 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Discharge header pressure Pump motor temperature high TOTAL Total Fountain No. 1- Water Pumps Points Total Fountain No. 1- Water Pumps Points Fountain No. 3 - Pumps [F3A & F3C] 1 2 3 4 5 6 7 8 2 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Discharge header pressure Pump motor temperature high TOTAL 1 1 2 1 1 2 4
Point Description
Fountain No. 1 - Pumps [F1A & F1B]
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software OPC Network Client DI AO DO Thermostat Integration
1 1 1 1 1 1
Remarks
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch Liquid pressure sensor From Pump Control Panel
5 10 16 1 1 1 1
0 0
1 2
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel 1 Relay Output From BMS Liquid pressure switch Liquid pressure sensor From Pump Control Panel
17 of 21
Project : ITCC CLUSTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Total Fountain No. 3- Water Pumps Points Total Fountain No. 3- Water Pumps Points Filter Pumps for Potable Water Filter, [2-pumps x 4 nos. Filters] 1 2 3 4 5 6 7 8 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Pump motor temperature high TOTAL Total Filter Pumps for Potable WaterFilters -Points Total Filter Pumps for Potable Water Filters -Points Filter Pumps for Grey Water Treatment Plant, [2-pumps x 4sets] 1 2 3 4 5 6 7 8 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Pump motor temperature high TOTAL Total Filter Pumps for Grey Water Treatment Plant -Points Total Filter Pumps for Grey Water Treatment Plant -Points Filter Pumps for Fountains No. 1 & 2 ,[1-Duty & 1-Standby] 1 2 3 4 5 6 7 2 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Pump motor temperature high TOTAL 1 1 1 1 4 1 4 32
AI
4
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software OPC Network Client DI AO DO Thermostat Integration
10 16 0 2
Remarks
1 1 1 1 1 1 5 40 80 0 0 1 8
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch From Pump Control Panel
1 1 1 1 1 1 5 40 52 0 0 1 8
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch From Pump Control Panel
1 1 1 1 1 1 5 0 1
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch From Pump Control Panel
18 of 21
Project : ITCC CLUSTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Total Filter Pumps for Fountains Nos. 1 & 2 -Points Total Filter Pumps for Fountains Nos. 1 & 2 -Points Filter Pumps for Fountains No.3 ,[1-Duty & 1-Standby] 1 2 3 4 5 6 7 2 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Discharge header pressure switch Pump motor temperature high TOTAL Total Filter Pumps for Fountain No. 3 -Points Total Filter Pumps for Fountain No. 3 -Points Sand Filters for Potable Water Supply (1-no. x 4 Booster set) High D P of Sand Filters TOTAL Total Sand Filter for Potable Water Supply -Points Total Sand Filter for Potable Water Supply -Points 1 1 2
AI
2
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software OPC Network Client DI AO DO Thermostat Integration
10 14 0 2
Remarks
1 1 1 1 1 1 5 10 14 0 0 1 2
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS Liquid pressure switch From Pump Control Panel
1 1 4 0 0 4 0 0 0 0
16
Sand Filters & Activated Carbon Filters for Grey Water Treatment Plant [2 nos. Sand Filters x 4 nos.plants + 2 nos. Activated C.Filters x 4 plants] High D P of Sand Filters 1 TOTAL 1 16 0 0 16 0 0 0 0
Total Sand Filter& Carbon Filters for Grey Water Treatment Plant -Points Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points
Sand Filters for Fountain No. 1 & 2 High D P of Sand Filters TOTAL Total Sand Filter for Fountains 1 & 2 -Points Total Sand Filter for Fountains 1 & 2 -Points
1 1 3 0 0 3 0 0 0 0
19 of 21
Project : ITCC CLUSTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty. Point Description
Sand Filters for Fountain No. 3 High D P of Sand Filters TOTAL Total Sand Filter for Fountain No. 3 -Points Total Sand Filter for Fountain No. 3-Points Fountain Basins for Fountains Nos. 1, 2 & 3 1 2 12 Fountain Basin Level (%) Monitor Fountain Basin Low Level TOTAL Total Fountain Basin for Fountains Nos. 1,2 &3- Points Total Fountain Basins for Fountains Nos. 1,2&3 - Points Electric Water Heaters [EWH] 1 58 EWH On/Off Status TOTAL Total Electric Water Heaters -Points Total Electric Water Heaters -Points Diesel Driven Fire pumps 1 2 3 4 5 6 7 8 9 1 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Low diesel tank level Low charge batteries Low pressure discharge switch Low pressure switch TOTAL Total Diesel Driven Fire Pumps Points Total Diesel Driven Fire Pumps Points 0 0 0 1 12 1
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software OPC Network Client DI AO DO Thermostat Integration
Remarks
1 1 1 0 0 1 0 0 0 0
1 1 58 58 0 0 0 0
1 1 1 1 1 1 1 1 1 8 8 9 0 1 1
From Diesel Pump Control Panel Flow switch From Diesel Pump Control Panel From Diesel Pump Control Panel Relay Output From BMS Level switch From Diesel Pump Control Panel Liquid pressure switch Liquid pressure switch
20 of 21
Project : ITCC CLUSTER Subject : BMS Input / Output List - Plumbing & Fire Protection Item Qty.
1 2 3 4 5 6 7 8 2 Pump On/Off Status Water flow status Pump Trip Alarm Pump Auto / Manual Status Pump Start/stop command Pump motor temperature high Low pressure discharge switch Low pressure switch TOTAL Total Eelctric Driven Fire Pumps Points Total Electric Driven Fire Pumps Points 1 2 1
Point Description
Electric Fire pumps (Electric Driven Fire Pump & Jockey Pump)
AI
Note: Fire Protection Control with Fire Alarm Panel BACnet Required Points Software OPC Network Client DI AO DO Thermostat Integration
1 1 1 1 1 1 1 6 12 16 0 1 2
Remarks
From Pump Control Panel Flow switch From Pump Control Panel From Pump Control Panel Relay Output From BMS From Pump Control Panel Liquid pressure switch Liquid pressure switch
21 of 21