SECTION 15860 VENTILATION AND EXHAUST SYSTEM 00000000PART 1 - GENERAL 1.1 SECTION INCLUDES A. 1.

2 The Work shall consist of furnishing and installation of ventilation and exhaust system as shown on the drawings and specified herein.

REFERENCES A. AFBMA The Anti-Friction Bearing Manufacturers Association AFMBA 9 AFMBA 11 B. Load Ratings and Fatigue Life for Ball Bearings. Load Ratings and Fatigue Life for Roller Bearings.

AMCA - Air Movement and Control Association, Inc. AMCA 210 AMCA 300 AMCA 301 AMCA 500 Laboratory Methods of Testing Fans for Rating. Reverberant Room Method for Sound Testing of Fans. Fan Sound Ratings from Laboratory Test Data. Test Methods for Louvers, Dampers and Shutters.

C.

ASTM - American Society for Testing and Materials ASTM A 36 ASTM C 150 Specifications for Structural Steel. Specifications for Portland Cement.

D.

IEEE - Institute of Electrical and Electronic Engineers IEEE 122 Poly-phase Induction Motors and Generators.

E.

NEMA - National Electrical Manufacturers Association MG 1 Motors and Generators.

F.

NFPA - National Fire Protection Association NFPA 90A NFPA 101 Installation of Air Conditioning and Ventilating Systems. Life Safety Code.

G.

UL - Underwriters Laboratories, Inc. UL 33 UL 555 Heat Response Links For Fire Protection Services. Fire Dampers.
15860-1 Ventilation & Exhaust System

ITCC in Riyadh Residential Complex J10-13300

UL 555 UL 353 H.

Ceiling Dampers. Limit Controls

UBC Uniform Building Code. Section 905 Section 906 Smoke Control. Smoke and Heat Venting.

1.3

SUBMITTALS A. Product Data: Submit manufacturer's technical data for air distribution equipment, including capacity ratings, fan performance curves with operating point clearly indicated, gages and finishes of materials, dimensions, weights, furnished accessories, and installation and instructions. Shop Drawings: Submit manufacturer's assembly type shop drawings indicating dimensions, required clearances, installation details and field connection details. Wiring Diagrams: Submit the manufacturer's electrical requirements for power supply wiring to the units. Operation and Maintenance Data: Submit maintenance and lubrication instructions, motor and drive replacement instructions, and spare parts list for each unit. Spare Parts List: Submit the manufacturer's spare parts list for ventilation equipment for a period of 2 years for the Engineer's review and approval.

B. C. D.

E. 1.4

TRANSPORTATION, HANDLING AND STORAGE A. Deliver materials to the site in manufacturer's original factory wrappings and containers, clearly labeled for identification of manufacturer, brand name and contents. Store materials off ground in original undamaged packages and containers, inside well-ventilated area protected from weather, moisture, soiling, extreme temperatures, and humidity. Follow manufacturer's recommendations regarding the transportation, handling and storage of materials.

1.5

QUALITY ASSURANCE A. B. Motors and electrical accessories shall comply with the applicable NEMA Standards. Electrical components and installation shall comply with NFPA 70 - National Electrical Code.

1.6

WARRANTY A. Submit a written guarantee signed by manufacturer and installer agreeing to replace systems or equipment which fail in material or workmanship within a period of 1 year from the date of substantial handing over.

ITCC in Riyadh Residential Complex J10-13300

15860-2

Ventilation & Exhaust System

00PART 2 - PRODUCTS 2.1 GENERAL: A. The design, manufacture and installation of the ventilating fans shall meet the requirements of AMCA 300, ASHRAE 51/210 or EUROVENT and shall be listed and labeled by UL. Fans shall be licensed to bear AMCA Seal for sound and air performance. Fans shall be provided with speed controller (where required) to perform the duty as mentioned on schedules. The fans shall be selected such that the sound levels within the area will not exceed the specified levels. Each fan shall be equipped with disconnect switch, backdraft damper (except for kitchen exhaust fans) and bird screen. Fans shall be of sizes, types and capacities as shown on the drawings. Roof-Mounted Centrifugal Exhaust Fans: 1. Spun aluminum exhaust fans shall be belt drive/direct drive type as shown on drawings. The fan wheel shall be centrifugal backward inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy duty gauge aluminum with a rigid internal support structure and a birdscreen. Motors shall be heavy duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Drive frame assembly shall be constructed of heavy duty gauge steel. Motors and drives shall be mounted on vibration isolators, out of the airstream. Fresh air for motor cooling shall be drawn into the motor compartment through a large space between the fan shroud and the motor cover. Motors and drives shall be readily accessible for maintenance. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum cataloged operating speed. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. A disconnect switch shall be factory installed and wired from the fan motor to a junction box installed within the motor compartment. A conduit chase shall be provided through the base to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Certified Ratings Seal for sound and air performance. Each fan shall bear a permanently affixed manufacturers engraved metal nameplate containing the model number and individual serial number for future identification. Ratings, type and size of fans shall be as indicated on Drawings. Exhaust fans shall be Model GB, G or GB-HP as manufactured by GREENHECK or approved equal.

B.

2.

3.

4.

5.

C.

Roof-Mounted Up-Blast Exhaust Fans (Kitchen Exhaust Fan): 1. Spun aluminum exhaust fans shall be centrifugal direct/belt driven type.
15860-3 Ventilation & Exhaust System

ITCC in Riyadh Residential Complex J10-13300

The fan wheel shall be centrifugal backward inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy gauge aluminum with a rigid internal support structure. A leakproof fan housing shall be constructed with a one piece windband with an integral rolled bead for added strength and shall be joined to the curbcap with a continuously welded seam. 2. Motors shall be heavy duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Drive frame assembly shall be constructed of heavy gauge steel. Motors and drives shall be mounted on vibration isolators, out of the airstream. Fresh air for motor cooling shall be drawn into the motor compartment through a tube free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum cataloged operating speed. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. A disconnect switch shall be factory installed and wired from the fan motor to a junction box installed within the motor compartment. A conduit chase shall be provided through the base to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Certified Ratings Seal for sound and air performance. Each fan shall bear a permanently affixed manufacturers engraved metal nameplate containing the model number and individual serial number for future identification. Rating, type and size of exhaust fans shall be as indicated on Drawings. Exhaust fans shall be Model CUBE, CUBE-HP, or CUBE-XP as manufactured by GREENHECK or approved equal.

3.

4.

5.

D.

IN-LINE CABINET FANS (BELT DRIVEN - DUCT MOUNTED TYPE) 1. Duct mounted supply, exhaust or return fans shall be of the centrifugal belt driven in-line type. The fan housing shall be of the square design constructed of heavy galvanized steel and shall include square duct mounting collars. Fan construction shall include two removable access panels located perpendicular to the motor mounting panel. The access panels must of sufficient size to permit easy access to all interior components. The fan wheel shall be centrifugal backward inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. Motors shall be heavy duty ball bearing type, carefully matched to the fan load and furnished at the specified voltage, phase and enclosure. Motors and drives shall be mounted out of the airstream. Motors shall be readily accessible for maintenance.

2.

ITCC in Riyadh Residential Complex J10-13300

15860-4

Ventilation & Exhaust System

3.

Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum (L50) life in excess of 200,000 hours at maximum cataloged operating speed. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. A NEMA 1 disconnect switch shall be provided as standard, except with explosion resistant motors, where disconnects are optional. Factory wiring shall be provided from motor to the handy box. All fans shall bear the AMCA Certified Ratings Seal for both sound and air performance. Each fan shall bear a permanently affixed manufacturer's nameplate containing the model number and individual serial number for future identification. Fans shall be of type and capacity as shown on the drawings.

4.

5.

E.

IN-LINE CABINET FANS (DIRECT DRIVEN - DUCT MOUNTED TYPE): 1. Duct mounted supply, exhaust or return fans shall be of the centrifugal direct driven in-line type. The fan housing shall be of the square design constructed of heavy galvanized steel and shall include square duct mounting collars. Fan construction shall include two removable access panels located perpendicular to the motor mounting panel. The access panels must of sufficient size to permit easy access to all interior components. The fan wheel shall be centrifugal backward inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. Motors shall be permanently lubricated and carefully matched to the fan loads. Direct drive motors shall be mounted in the airstream. Motors shall be readily accessible for maintenance. A NEMA 1 disconnect switch shall be provided as standard, except with explosion resistant motors, where disconnects are optional. Factory wiring shall be provided from motor to the handy box. All fans shall bear the AMCA Certified Ratings Seal for both sound and air performance. Each fan shall bear a permanently affixed manufacturer's nameplate containing the model number and individual serial number for future identification. Fans shall be of type and capacity as shown on the drawings.

2.

3.

4.

F.

IN-LINE CABINET FANS (SP - CEILING MOUNTED TYPE): 1. Ceiling mounted exhaust fans shall be of the centrifugal direct drive type. The fan housing shall be constructed of galvanized steel and shall include prepunched mounting brackets. The housing interior shall be lined with 1/2" acoustical insulation (where applicable). The outlet duct collar shall include aluminum backdraft damper and shall be adaptable for horizontal or vertical discharge (where applicable). The grille shall be constructed of non-yellowing high impact polymer or polystyrene or aluminum as applicable. Access for wiring shall be external. The motor disconnect shall be internal and of plug in
15860-5 Ventilation & Exhaust System

ITCC in Riyadh Residential Complex J10-13300

type. The motor shall be mounted on vibration isolators. 2. The fan wheel shall be forward curve centrifugal type constructed of high strength polymer, dynamically balanced for vibration isolation. All fans shall bear the AMCA Certified Ratings Seal for both sound and air performance and shall be UL Listed and C.S.A. approved. Each fan shall bear a permanently affixed manufacturer's nameplate containing the model number and individual serial number for future identification, type, size and capacity as shown on the drawings.

G.

Make-Up Air Fans (Supply Fans): 1. Roof-mounted, filtered makeup air units shall have belt driven double width/double inlet, forward curved centrifugal type supply fans. The entire fan and motor assembly shall be mounted on a formed, reinforced support structure with vibration isolators to prevent noise transmission. Motors shall be permanently lubricated, heavy duty, ball bearing type, carefully matched to the fan load and furnished at the specified voltage, phase and enclosure. The fan shaft shall be ground and polished steel mounted in heavy duty, sealed ball bearings. Bearings shall be selected for a minimum (L50) life in excess of 200,000 hours at maximum cataloged operating speeds. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to the wheel and motor shafts. Motor sheaves shall be adjustable for final system balancing. Drives shall be sized for a minimum of 150% of driven horsepower. Fan wheels shall be of the forward curved type, constructed of heavy gauge steel and statically and dynamically balanced to ensure smooth, vibration free operation. Housing construction shall be of heavy gauge galvanized steel with removable panels. Filters shall be one inch aluminum mesh and sized to provide for optimum removal of contaminated outside air without exceeding the manufacturers recommendations for maximum velocity. The prewired control center shall include, but not be limited to, an integral master disconnect switch with fuse blocks for main power connection, magnetic motor starters with thermal overloads and manuals reset, fused 115 volt control transformer, and distribution terminal control strip for control wiring connection. All electrical components shall be U.L. Labeled where applicable and wired in compliance with the National Electrical Code (NFPA #70). Wiring shall be complete requiring only one point field connection for power service and one point field connection for control voltage. Fans shall be as manufactured by GREENHECK (Model KSU) or as approved equal; type, size and capacities as shown on drawings.

H.

Propeller Sidewall Exhauster (Belt Drive): 1. Belt driven, axial type sidewall fans shall be provided as specified herein. Propellers shall be constructed with fabricated steel blades and hubs. Propellers shall be securely attached to fan shafts. All propellers shall be statically and dynamically balanced. Motors shall be permanently lubricated, heavy duty type, carefully matched to the fan load and furnished at the specified voltage, phase, and enclosure. Ground and polished steel fan shafts shall be mounted in permanently
15860-6 Ventilation & Exhaust System

2.

ITCC in Riyadh Residential Complex J10-13300

lubricated, sealed ball bearing pillow blocks. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum cataloged operating speeds. Drives shall be sized for a minimum of 150 percent of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to wheel and motor shafts. Motor sheaves shall be adjustable for system balancing. 3. Drive frame and panel assemblies shall be galvanized steel or painted steel. Drive frames shall be formed channels and fan panels shall have prepunched mounting holes, formed flanges, and a deep formed inlet venturi. Drive frames and panels shall be bolted construction or welded construction. The axial exhaust fans shall bear the AMCA Certified Ratings Seals for both sound and air performance. Fans shall be Model SB (fabricated blades and hubs) and SBC (cast blades and hubs) as manufactured by GREENHECK or approved equal, type and capacity as indicated on drawings.

I.

Roof Mounted Centrifugal Upblast Exhaust Fan for Smoke Control System 1. Spun aluminum exhaust fans shall be centrifugal belt driven type. The fan wheel shall be centrifugal backward inclined, constructed of steel and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy gauge aluminum with a rolled bead and a rigid internal support structure. A leak-proof fan housing shall be constructed with a one piece windband with an integral rolled bead for added strength and shall be joined to the curb cap with a continuously welded seam. Motors shall be heavy duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Drive frame assembly shall be constructed of heavy gauge steel. Motors and drives shall be mounted on safety flange vibration isolators, out of the airstream. Fresh air for positive motor cooling shall be drawn into the motor compartment through a ten square inch tube free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum cataloged operating speed. Dual drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. A NEMA-3R disconnect switch shall be factory installed and wired from the fan motor to a junction box installed outside the motor compartment. All fans shall bear the AMCA Certified Ratings Seal for sound and air performance. Each fan shall bear a permanently affixed manufacturers engraved metal nameplate containing the model number and individual serial number for future identification. Fans shall be listed by Underwriters Laboratory for UL/cUL 705 for electrical components and UL Listed for Emergency Smoke Control Systems (500 degrees F for 4 hours and 1,000 degrees F for 15 minutes). Fans shall be of type, size and capacity as shown on drawings.
15860-7 Ventilation & Exhaust System

2.

3.

4.

5.

ITCC in Riyadh Residential Complex J10-13300

Fans shall be Model S-CUBE as manufactured by GREENHECK or approved equal. J. Utility Centrifugal Fans (SFB Type): 1. Supply, exhaust and return air fans shall be of the belt driven utility fan type in AMCA Arrangement 10 with a single width, single inlet housing in CW or CCW rotation as specified. The housing shall be constructed of heavy gauge steel with lock formed seams permitting no air leakage. The housing shall be field rotatable to any of the eight standard discharge positions. Housing and bearing supports shall be constructed of welded steel members to prevent vibration and rigidly support the shaft and bearings. The fan wheel shall be of the forward curved type, constructed of heavy gauge steel with uniform stamped steel blades. Wheels shall be statically and dynamically balanced. The wheel cone and fan inlet cone shall be carefully matched for maximum performance and operating efficiency. Motors shall be permanently lubricated, heavy duty, ball bearing type carefully matched to the fan load and furnished at the specified voltage, phase and enclosure. The fan shaft shall be ground and polished solid steel mounted in heavy duty, permanently sealed, pillow block ball bearings. Bearings shall be selected for a minimum L50 life in excess of 200,000 hours at maximum cataloged operating speed. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to the wheel and motor shafts. The motor pulley shall be adjustable for final system balancing. Fan performance shall be based on tests conducted in accordance with AMCA Standard 210 test code for air moving devices. Fans shall be licensed to bear the AMCA Certified Ratings Seal for air performance. Utility fans shall be as manufactured by GREENHECK (Model SFB) or approved equal; type and capacity as shown on the drawings.

2.

K.

Car Park Ventilation Systems: 1. Systems Functions: a. Exhaust gases produced by vehicles and pockets of stagnant air are effectively removed.

ITCC in Riyadh Residential Complex J10-13300

15860-8

Ventilation & Exhaust System

b. c. 2.

Assistance needs to be given to the fire fighters in the event of fire by clearing smoke from the car park during and after the fire. Provide clear smoke-free access for fire fighters to tackle the seat of the fire and to protect means of escape from the car park.

Standards: a. BS 7346-7:2006 - Components for Smoke and Heat Control Systems, Code of Practice on functional recommendations and calculation methods for smoke and heat control systems for covered car parks. BS 5588 Series BS EN 9001 EN 12101-3:2002 EN 12101-3:2003: Certifies that the cyclone induction unit will operate at high temperature of 300 0C for 60 minutes. NFPA CIBSE Guide Volume A : 2006 Environmental Design

b. c. d. e. f. g. 3.

General: Provide car park ventilation system including design, CFD (Computational Fluid Dynamics) analysis and report; fabrication, supply and installation of cyclone induction fans, extract and/or inlet fans, ductwork (for extract) and dampers, control and sensors systems and wiring, CO and heat/smoke detectors; and other ancillaries to complete the system. Provide mechanical ventilator similar to Model CYCLONE 100 as manufactured by COLT INTERNATIONAL LTD or approved equal with the following performance data: Throw (m): Thrust (N): Airflow (m3/s): Power (kW): FLC (A): SC (A): Power Supply: 40 100 (At full speed) 2.7

4.

2.6 4.6 15 400V/3 Phase/ 50 Hz

Physical features include: a. Casing fabricated of minimum 4 mm thick hot dip galvanized mild steel with manufacturers standard corrosion-resistant epoxy coated finish; color as selected by the Engineer. Low profile for maximum headroom. Noise Levels (for Extract Systems): 55 dBA, externally (maximum) at 3 m inside the car park.

b. c.

ITCC in Riyadh Residential Complex J10-13300

15860-9

Ventilation & Exhaust System

5.

Capacity and Ratings (for Extract Fans and Ventilators): As required by Design.

000PART 3 - EXECUTION 3.1 INSTALLATION A. General: Install fans where indicated, in accordance with manufacturer's installation instructions and recognized industry practices, to ensure that fans comply with the requirements specified and serve the intended purposes. Access: Provide access and service space around and over fans as indicated, but in no case less than that recommended by manufacturer. Support: Unless otherwise indicated, provide 100 mm high concrete pad under floor-mounted centrifugal fans. Isolation: Set centrifugal fans on vibration isolators, fasten in accordance with manufacturer's installation instructions. Electrical Wiring: Install electrical devices furnished by manufacturer but not specified to be factory-mounted. Verify that electrical wiring installation conform to the manufacturer's submittal and installation requirements of the applicable Sections of Division 16. Ensure that rotation is in the direction indicated and intended for proper performance. Ductwork Connections: Refer to Section 15891 - HVAC DUCTWORK. Provide flexible connections on inlet and outlet duct connections.

B. C. D. E.

F.

3.2 FIELD QUALITY CONTROL A. Upon completion of installation of fans and after motors has been energized with normal power source, test the equipment to demonstrate compliance with the specified requirements. Where possible, field correct malfunctioning equipment, then retest to demonstrate compliance. Replace equipment which cannot be satisfactorily corrected at no extra cost to the Owner.

B. C.

3.3 ADJUSTING AND CLEANING A. Start-up, test and adjust fans in the presence of the manufacturer's authorized representative and the Engineer. END OF SECTION