IEC Contactors and Starters


XT IEC Power Control

Star-Delta (Wye-Delta) Miniature Contactors


Maximum Current UL RatingsSingle-Phase and Three-Phase 1
Horsepower Ratings Single-Phase 115V 1/2 200V 1 230V 1-1/2 Three-Phase 200V 2 230V 3 460V 5 575V 7-1/2 Maximum Changeover Time (sec.) 30 Spare Auxiliary Contacts K1M Component Description K1M main contactor K1M auxiliary contact K5M delta contactor K3M star contactor K3M auxiliary contact K1T timing relay

Catalog Number 2 XTMC9A10_ XTMCXFC22 XTMC9A01_ XTMC9A10_ XTMCXFC02 XTTR6A60S51B

21 31 53 22 32 54

Maximum IEC Ratings AC-3 1


Horsepower Ratings Three-Phase Motors 5060 Hz 220/230/240V 4 380/400/440V 5.5 500V 5.5 Maximum Changeover Time (sec.) 30 Spare Auxiliary Contacts K1M Component Description K1M main contactor K1M auxiliary contact K5M delta contactor K3M star contactor K3M auxiliary contact K1T timing relay

Catalog Number 2 XTMC9A10_ XTMCXFC22 XTMC9A01_ XTMC9A10_ XTMCXFC02 XTTR6A60S51B

21 31 53 22 32 54

Mini Overload Relay Settings (A)


Setting A: IN x 0.58 Motor protection in the Y and delta configurations. B: IN x 1 Only partial motor protection in star position C: IN x 0.58 Motor not protected in star position. Timing relay set to approximately 10 sec. Notes Depending on the coordination type required (that is, Type 1 or Type 2) it must be established whether the fuse protection and the input wiring for the main and delta contactors are to be common or separate.
1 2

Starting <15 sec 1540 sec >40 sec

Operating frequency: 30 starts/hour. See Magnet Coil Suffix table on following page. Underscore (_) indicates magnet coil suffix required.

Volume 5Motor Control and Protection

CA08100006EApril 2013

www.eaton.com

IEC Contactors and Starters


XT IEC Power Control

1.1
Suffix Code AD BD RD WD

Magnet Coil Suffix


Coil Voltage 110V 50 Hz, 120V 60 Hz 220V 50 Hz, 240V 60 Hz 230V 50 Hz 24V 50/60 Hz 24 Vdc Suffix Code A B F T TD 1 Coil Voltage 415V 50 Hz, 480V 60 Hz 550V 50 Hz, 600V 60 Hz 208V 60 Hz 190V 50 Hz, 220V 60 Hz 240V 50 Hz, 277V 60 Hz 380V 50 Hz, 440V 60 Hz Suffix Code C D E G H L Coil Voltage 400V 50 Hz 380V 60 Hz 12V 50/60 Hz 24V 50 Hz 42V 50 Hz, 48V 60 Hz 48V 50 Hz Suffix Code N P R U W Y Coil Voltage 120 Vdc 220 Vdc 12 Vdc 48 Vdc

1 1 1 1 1 1 1

Mini Overload Relays


XTOM_

Mini Overload Relays 23


Short-Circuit Protection (A) Overload Release It 0.10.16A 0.160.24A 0.240.4A 0.40.6A 0.61A 11.6A 1.62.4A 2.44A 46A 69A 912A Trip Class 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A 10A Contact Sequence Contact Configuration 1NO-1NC 1NO-1NC Type 1 Coordination, gG/gL 20 20 20 20 20 20 20 20 20 20 Type 2 Coordination, gG/gL 0.5 1 2 2 4 6 6 Circuit Breaker 15 15 15 15 15 15 15 15 15 15 CEC/NEC Fuse 3 6 6 15 20 35 45

1
Catalog Number XTOMP16AC1 XTOMP24AC1 XTOMP40AC1 XTOMP60AC1 XTOM001AC1 XTOM1P6AC1 XTOM2P4AC1 XTOM004AC1 XTOM006AC1 XTOM009AC1 XTOM012AC1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

97 95

2 4 6 98 96

1NO-1NC 1NO-1NC 1NO-1NC 1NO-1NC 1NO-1NC 1NO-1NC 1NO-1NC 1NO-1NC 1NO-1NC

Notes 1 With DC operation: Integrated diode resistor combination, coil rating 2.6W. 2 Short-circuit protection: Observe the maximum permissible fuse of the contactor with direct device mounting. See MN03402002E for more information. 3 When fitted directly to the contactor, a clearance of at least 5 mm is required between the overload relays.

Volume 5Motor Control and Protection

CA08100006EApril 2013

www.eaton.com